Professional Documents
Culture Documents
Gas-freeing with IGG blowers is used when all tanks are to be gas-freed
before the ship enters dry dock.
The graph below illustrates the effect on the atmosphere of the gas-freeing operation. During gas-freeing,
the oxygen level can rise to 21% without the risk of creating a potentially flammable mixture.
Reference must be made to the section on oxygen deficiency and toxicity of hydrocarbon vapours
16
IT
8
I M
L EL
MAB
M
6
A
FL
CRITI P ER
CAL D UP FLAMMABLE OR
ILU TI
O N LI
4
NE EXPLOSIVE REGION
COMMENCE LO WE
R FLAM
2
GAS FREEING MA BL
E LIMIT
1
(LFL)
0 2 4 6 8 10 12 14 16 18 20
PERCENT OXYGEN(O2) GAS FREE
All tank must have an oxygen content of 8% by volume or less with a positive gas pressure at all times.
The tanks can be gas-freed when it has been established that a flammable atmosphere will not be created
in any tank as a result of introducing fresh air, i.e. the tank has first been purged with inert gas.
The quickest and best results are obtained when a maximum of two tanks are inerted at the same time.
3. Gas-free until the tank has an oxygen content of 21% by volume and a reading of less than 1% LFL is
obtained on the combustible gas indicator.
4. A responsible person wearing appropriate breathing apparatus may enter the gas-free tank and take
further oxygen content measurements.
When it has been established that the atmosphere throughout the tank containes 21% oxygen, further
personnel may be allowed to commence inspection or repair-work within the tank.
5. The conditions given in Chap. 1.6, Safety Procedures, must be observed and a fresh air supply to the
tank must be maintained at all times when personnel are working in the tank.
CAUTION
If hydro-carbon gas is detected in ballast tanks, then inerting to ballast tanks at
any time.
The graph below illustrate the effect on the tank atmosphere as inert gas introduced.
The air is displaced and the oxygen content is reduced to approximately 5%.
Reference must be made to the section on oxygen deficiency and toxicity of hydrocarbon vapours
16
IT
8
IM
L EL
AB
M
AM
6
FL
R
CRI T PE
ICAL UP FLAMMABLE OR
D ILU
4
TI ON EXPLOSIVE REGION
LI NE
LOW
2
ER FL
A MM A
B LE LI
1
M IT (LFL)
0 2 4 6 8 10 12 14 16 18 20
COMMENCE PERCENT OXYGEN(O2)
BELOW 8 %
COMMENCE
INERTING
1. All ballast tanks are connected to the inert gas generator and all isolating valves in the deck inert gas
pipework are locked open.
3. All valves isolating the mast risers from the inert gas generators are shut.
4. The arrangements required by the Fire Protection, Detection and Extinguished Equipment Regulations,
are used to isolate the cargo main from the inert gas main.
7. The oxygen content of the inert gas and its pressure in the inert gas main should be recorded.
IMPORTANT INFORMATION
Inerting water ballast tank is, only if hydrocarbon gases are detected indicating leakage
between cargo tanks and double hull spaces.
During the inerting double hull spaces(ballast tanks) the press. of the inert gas in the ullage
space of the tanks and in the inert gas deck main must be maintained above 200 mmWG.
If the pressure falls to a negative value there is danger of fresh air ingress into the tanks.
Most hydrocarbon gases from crude oil, hydrogen sulphide and inert gas are heavier than air.
With requirements for connections for inert gas supply to ballast tanks, inerting of ballast
tanks will probably be a normal procedure.
NOTE.
Breather valves for the ballast tank.
Suitable pipe reducers to be provided and installed on the vent pipe od ballst tank
(After removing the vent head) if necessary.