You are on page 1of 5

Understand How Valves & Fittings

Affect Head Loss


by Ray Hardee (Engineered Software, Inc.)

This series discusses valves and fittings and evaluates how these devices affect the
operation of piping systems. Part 1 (Pumps & Systems, May 2015) covered head loss,
K value and L/D coefficient. You can read part 1 here.

CV Coefficient
The CV value is an indication of the capacity of a valve or fitting and is often used to
describe the performance of control valves. The CV coefficient is often used to
describe the hydraulic characteristics of elements in a pipeline. The definition of CV is
the number of U.S. gallons per minute (gpm) of 60 F water flowing through a valve or
fitting results in a 1 pound per square inch (psi) pressure drop across the device.

For example, if a device has a CV value of 200, then when 200 gpm flows through the
device, a 1 psi pressure drop would occur. Equation 6 describes the CV value.

Where
CV = Flow coefficient (unitless)
Q = Flow rate (gpm)
P = Pressure (psi)
SG = Specific gravity of the fluid (unitless)

The equation can be rearranged to allow for the solution of the flow rate for a given
pressure drop and the pressure drop for a given flow rate.
Equation 6 gives the result of using CV in differential pressure instead of head. If a
manufacturer provides information in CV, users must convert it to differential pressure,
then convert the results to head loss. Equation 7 can be used to eliminate the need to
convert from pressure to head. It allows for the conversion of a CV value to a K value.

Where
K = Resistance coefficient (unitless)
CV = Flow coefficient (unitless)
d = internal diameter (inches)

Calculating the Head Loss Using K Value


Regardless of the method used to arrive at a K value for a valve or fitting, Equation 8
is used to calculate the head loss resulting from valves and fittings.

When multiple valves and fittings in a pipeline have the same diameter, the K values
for each valve or fitting can be added. The sum of the K values can be used to
calculate the head loss for all the valves and fittings.

To demonstrate, calculate the head loss for the valves and fittings in a pipeline when
600 gpm of water is flowing through the following valves and fittings: a sharp-edged
transition from a tank to pipeline, a full-seated globe valve and a strainer with a CV
value of 450. These full-seated devices are in a 6-inch pipe with a turbulent friction
factor of 0.015 inches. The K values are listed in Table 1. The resulting head loss with
600 gpm going through the pipeline is shown in Equation 9.
Table 1. Calculation of
K value for different methods describing valves and fittings (Graphics courtesy of the author)

Cross Section of Valves & Fittings


Reference 1 has cross sections of types of valves and fittings and the corresponding K
values or L/D coefficients. There are too many types of valves and fittings to present
in this article, but some attributes can be generalized. For example, a full-seat ball
valve with its straight-through design has a much lower L/D value than a globe valve
through which the fluid must make four changes of direction and flow around the
valve disk within the flow path. The type of valve employed is based on many factors.
Leak tightness is an important factor, but when two types of valves meet the same
requirements, it is recommended to use the one with the lower head loss.

Another example of fittings with varied loss coefficients are elbows. A short radius
90-degree elbow has an L/D coefficient of 20, but a long radius 90-degree elbow has a
L/D coefficient of 14. This may not seem like a significant loss, but it adds up. So do
the associated costs. The pump must supply the energy that is lost across the valves
and fitting.

Cost of Pipeline Operation


To demonstrate the pumping cost associated with valves and fittings, calculate the
operating costs for different types of valves and fittings. Equation 10 can determine
the pumping cost.
Where
OC = Operating cost ($/time)
Q = Flow rate (gpm)
H = Head (feet of fluid)
ρ = Density (lb/ft3)
η = Efficiency, M motor, P pump, V variable speed drive (VSD) (percent)
O = Operating hours in evaluation (hours)
$/kWh = Electrical power cost ($/kWh)

In this example, the pump efficiency is 70 percent, and the motor efficiency is 90
percent. No VSD is installed, the evaluation period is 8,000 hours, and the cost of
power is $0.10/kilowatt-hour (kWh). This example evaluates 4-inch valves and
fittings with a flow rate of 400 gpm. The results are presented in Table 2.

Table 2. The
relationship between K values, head loss and annual operating cost for valves and fittings. The example is for 4-inch
valves and fittings passing 400 gpm.

Every item placed in a piping system has an operating cost. This should be considered
every time a user specifies a valve time or adds elbows.
Conclusion
The often overlooked performance of the multitude of valves and fittings adds up.
They have a compounded effect on performance in a fluid operation and need to be
taken into consideration for efficiency planning and optimization.

Next month's column will investigate how the control elements operate and the role
that these devices play in piping systems and their associated cost.

References

1. Flow of fluids through valves, fittings, and pipe. (1957). Chicago: Crane
2. Flow of Fluids through Valves, Fittings and Pipe Technical Paper 410. © 2013 Crane Co. Stamford CT
06902.

ABOUT THE AUTHOR


Ray Hardee is a principal founder of Engineered Software, creators of PIPE-FLO and PUMP-
FLO software. At Engineered Software, he helped develop two training courses and teaches
these courses in the U.S. and internationally. He is a member of the ASME ES-2 Energy
Assessment for Pumping Systems standards committee and the ISO Technical Committee
115/Working Group 07 "Pumping System Energy Assessment." Hardee was a contributing
member of the HI/Europump Pump Life Cycle Cost and HI/PSM Optimizing Piping System
publications. He may be reached at ray.hardee@eng-software.com.

You might also like