Pool AHU Analysis With Dehumidifier - Villa
Pool AHU Analysis With Dehumidifier - Villa
Mixing condition 2 (MC1+FA) - ON coil conditions 682 40.16 25.42 14.46 30.80 77.60
Off coil condition/capacity 682 11.10 10.50 7.68 93.13 30.45 38.6
Duct mounted type Electrical Heater details 682 13.10 11.33 7.68 81.30 1.7
RA conditions DH OFF conditions Mixing condition (MC) 1, say RA+DH of FA conditions Mixing condition 2 (MC1+FA) - ON coil conditions Of coi condition Duct mounted type Electrical Heater details Room condition to be achieved
Temperature rise in Rise in Humidity ratio
Cooling coil conditioned space due in conditioned space
capacity, KW to room sensible load due to room latent load
of 233 KW, °C of 18KW + 28KW. g/Kg
Air flow, lps Humidity Humidity Air flow, lps Humidity Humidity
Air flow, lps DB in°C DB in°C Humidity Ratio, RH % Air flow, DB in°C WB in°C Humidity Ratio, RH % (17448 RA+ 4720 DB in°C WB in°C Ratio, g/Kg of RH % Air flow, DB in°C WB in°C Ratio, g/Kg RH % (20044 + 2124 DB in°C WB in°C Ratio, g/Kg RH % Enthalpy, Air flow, DB in°C WB in°C Ratio, g/Kg of RH % Enthalpy, Capacity, KW DB, °C RH, % DB, °C RH, % Humidity
g/Kg of Dry air lps g/Kg of Dry air DH) Dry air lps of Dry air FA) of Dry air KJ/Kg lps Dry air KJ/Kg Ratio, g/Kg
22168.00 20.50 15.10 8.40 56.00 4720.00 26.52 15.30 6.24 29.03 22168.00 21.78 15.10 7.94 49.00 2124.00 20.50 15.60 8.94 59.50 22168.00 21.66 15.12 8.04 49.92 42.21 22168.00 10.20 9.90 7.46 96.60 29.51 337.84 27.00 11.20 93.68 8.85 0.73 20.05 55.50 8.19
Air Flow, lps DB in°C WB in°C Humidity Ratio, RH % Enthalpy, Cooling coil Capacity, KW
g/Kg of Dry air KJ/Kg capacity, KW
Mixing condition (MC) 1, say RA+DH off 22168.00 21.78 15.10 7.94 49.00
Mixing condition 2 (MC1+FA) - ON coil conditions 22168.00 21.66 15.12 8.04 49.92 42.21