Swimming pool Air Handling Unit Analysis with De-humidifier

Enthalpy, Total Cooling coil /


Humidity Ratio,
Air Flow, lps DB in°C WB in°C RH % heater capacity
g/Kg of Dry air KJ/Kg capacity, KW

Return Air(RA) conditions 662 28.00 22.07 14.31 60.00

Dehumidifier(DH) OFF conditions 662 35.68 21.20 9.87 26.98

FA conditions 296 46.00 30.00 20.45 31.80

Mixing condition 2 (MC1+FA) - ON coil conditions 682 40.16 25.42 14.46 30.80 77.60

Off coil condition/capacity 682 11.10 10.50 7.68 93.13 30.45 38.6

Supply Fan 682 11.86 10.80 7.68 88.20

Duct mounted type Electrical Heater details 682 13.10 11.33 7.68 81.30 1.7

Temperature rise in conditioned space due to room 16.42


sensible load of 13.7 KW
Rise in Humidity ratio in conditioned space due to 7.71
room latent load of 15.5KW. g/Kg

Room condition to be achieved 29.52 15.39 58.90


Project : Al Wajbah, Phase 2A
Building reference : Gym
Subject : Swimming pool Air Handling Unit Analysis with Dehumidifier

RA conditions DH OFF conditions Mixing condition (MC) 1, say RA+DH of FA conditions Mixing condition 2 (MC1+FA) - ON coil conditions Of coi condition Duct mounted type Electrical Heater details Room condition to be achieved
Temperature rise in Rise in Humidity ratio
Cooling coil conditioned space due in conditioned space
capacity, KW to room sensible load due to room latent load
of 233 KW, °C of 18KW + 28KW. g/Kg
Air flow, lps Humidity Humidity Air flow, lps Humidity Humidity
Air flow, lps DB in°C DB in°C Humidity Ratio, RH % Air flow, DB in°C WB in°C Humidity Ratio, RH % (17448 RA+ 4720 DB in°C WB in°C Ratio, g/Kg of RH % Air flow, DB in°C WB in°C Ratio, g/Kg RH % (20044 + 2124 DB in°C WB in°C Ratio, g/Kg RH % Enthalpy, Air flow, DB in°C WB in°C Ratio, g/Kg of RH % Enthalpy, Capacity, KW DB, °C RH, % DB, °C RH, % Humidity
g/Kg of Dry air lps g/Kg of Dry air DH) Dry air lps of Dry air FA) of Dry air KJ/Kg lps Dry air KJ/Kg Ratio, g/Kg

22168.00 20.50 15.10 8.40 56.00 4720.00 26.52 15.30 6.24 29.03 22168.00 21.78 15.10 7.94 49.00 2124.00 20.50 15.60 8.94 59.50 22168.00 21.66 15.12 8.04 49.92 42.21 22168.00 10.20 9.90 7.46 96.60 29.51 337.84 27.00 11.20 93.68 8.85 0.73 20.05 55.50 8.19

Swimming pool Air Handling Unit Analysis with Dehumidifier

Air Flow, lps DB in°C WB in°C Humidity Ratio, RH % Enthalpy, Cooling coil Capacity, KW
g/Kg of Dry air KJ/Kg capacity, KW

Return Air(RA) conditions 22168.00 20.50 15.10 8.40 56.00

Dehumidifier(DH) OFF conditions 4720.00 26.52 15.30 6.24 29.03

Mixing condition (MC) 1, say RA+DH off 22168.00 21.78 15.10 7.94 49.00

FA conditions 2124.00 20.50 15.60 8.94 59.50

Mixing condition 2 (MC1+FA) - ON coil conditions 22168.00 21.66 15.12 8.04 49.92 42.21

Off coi condition 22168.00 10.20 9.90 7.46 96.60 29.51

Cooling coil capacity, KW 337.8

Duct mounted type Electrical Heater details 11.20 93.68 27

Temperature rise in conditioned space due to room


sensible load of 233 KW, °C 8.85

Rise in Humidity ratio in conditioned space due to


room latent load of 18KW + 28KW. g/Kg 0.73

Room condition to be achieved 20.05 8.19 55.50