You are on page 1of 10

IET Power Electronics

Research Article

ISSN 1755-4535
Multi-objective control of multi-functional Received on 6th May 2015
Revised on 28th August 2015
grid-connected inverter for renewable energy Accepted on 2nd September 2015
doi: 10.1049/iet-pel.2015.0317
integration and power quality service www.ietdl.org

Zheng Zeng 1 ✉, Hui Li 1, Shengqing Tang 2, Huan Yang 2, Rongxiang Zhao 2


1
State Key Laboratory of Power Transmission Equipment and System Security and New Technology, School of Electrical Engineering,
Chongqing University, Chongqing 400044, People’s Republic of China
2
College of Electrical Engineering, Zhejiang University, Hangzhou 310027, Zhejiang Province, People’s Republic of China
✉ E-mail: zengerzheng@126.com

Abstract: Multi-functional grid-connected inverters (MFGCIs) not only interface renewable energy sources into the utility,
but also provide ancillary power quality enhancement service. Therefore, extra installment of power quality conditioners
can be partially avoided in a micro-grid including MFGCIs. Because the capacity of an MFGCI employed for power quality
compensation is limited, how to balance the multiple functions and optimally utilise the limited capacity becomes a
challenging for MFGCI application, and this is studied in details in this paper. First, to set up a benchmark for balancing
the multiple functions of the MFGCI, a comprehensive power quality evaluation (CPQE) index is presented based on
the catastrophe decision theory to quantify the power quality of a micro-grid. Then, for the strategic utilisation of the
limited capacity, a multi-objective optimal compensation model is proposed in which the objectives are to optimise the
CPQE index and minimise the occupied capacity of an MFGCI for power quality compensation. Finally, the solutions of
the model are derived on the basis of Pareto approach. As a result, the MFGCI can flexibly customise the power quality
of the micro-grid according to its available capacity margin and the users’ requirement. Finally, the experimental
results performed on a 10 kVA MFGCI prototype have confirmed the validity of the proposed model.

1 Introduction However, aiming to the optimal control of a MFGCI in limited


capacity condition, there are two issues should be further
To interface solar, wind and other renewable energy sources (RESs) investigated.
into the utility, micro-grid is regarded as a good choice [1–3].
However, due to the numerous converters and local loads, the power
† First, the power quality levels of a micro-grid, before and after the
quality issues, such as phase unbalance, reactive power, waveform
compensation of MFGCI, are hardly quantified. A comprehensive
distortion, and so on, have become the challenges which affect the
power quality evaluation (CPQE) model is needed to guide the
stability and effective operation of the micro-grid [4–6]. To enhance
power quality service of an MFGCI and the strategic usage of the
the power quality of a micro-grid, some passive and/or active
limited capacity. In this paper, a catastrophe-decision-based CPQE
devices employed in distribution networks were recommended
method is proposed to quantify the power quality of a micro-grid
[7, 8]. However, the grid-connected inverters can be embedded in
and judge the performance of an MFGCI on power quality service.
the power quality enhancement function, apart from renewable
It can hugely eliminate the influence from experts’ experience
integration function. This kind of grid-connected inverter with
compared with traditional CPQE approaches based on analytic
ancillary service of power quality enhancement is usually called as
hierarchy processing [27], fuzzy logic [28], or artificial neural
multi-functional grid-connected inverter (MFGCI) [9–13]. With the
network [29].
aid of MFGCIs, extra power quality conditioners may no longer be
† Second, harmonic and reactive power issues were set with the
essential in an inverter-dominated micro-grid avoiding the additional
same weights in the previous MFGCI application studies [23–26].
investment and operational cost of power quality conditioners.
However, to optimally utilise the limited capacity of an MFGCI,
The circuit topologies and control strategies of MFGCIs for
the harmonic and reactive power issues should be assigned with
single-phase application are well documented in [9, 14, 15].
the independent weights. In such a way, it can enhance the power
Authors in [16–20] have proposed some control schemes of
quality of the micro-grid as much as possible guided by the
three-phase MFGCIs, and some MFGCIs with the functions of
CPQE-based model [11].
uniformed power quality conditioners were validated in [21, 22].
In these literatures, it is clear that the power quality enhancement
is just the auxiliary function of an MFGCI compared with RES In this paper, a multi-objective optimal compensation control
integration. The capacity of an MFGCI used for power quality strategy is proposed for MFGCI application in a micro-grid. This
enhancement is limited and related to its working condition. control strategy aims to use the minimum capacity of an MFGCI
Therefore, how to utilise the limited capacity margin of an MFGCI and optimise the defined CPQE index. The rest of this paper is
and optimise its power quality enhancement function is a very organised as follows. In Section 2, the typical micro-grid feeder
important issue. In [23, 24], a limiter with strategic control is used studied in this paper is briefly introduced. The multi-objective
to guarantee that the output current of the MFGCI is in the safe control model for the optimised power quality compensation for
level. In [25], an agent-based communication strategy is proposed MFGCI application is presented in Section 3. In Section 4, some
to coordinate the multiple MFGCIs to share the power quality experimental results performed on a 10 kVA prototype are selected
issues in a micro-grid. Without using communication channels, a to verify the validity and feasibility of the proposed
cascaded control scheme based on the limitations of conductance multi-objective-based optimal control strategy. Section 5 concludes
and susceptance is further presented in [26]. this paper.

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


& The Institution of Engineering and Technology 2016 761
2 Mathematical model and control scheme As shown in Fig. 2, the CPQE index F1 consists of the two factors,
of MFGCI namely THD and true power factor (TPF), where the TPF except for
harmonic is defined as
The configuration of a typical micro-grid feeder is depicted in Fig. 1.
The line-to-neutral root-mean-square (RMS) voltage and TPF = P/(3UI1 ) (5)
fundamental line-frequency of the utility are Un = 110 V and fn =
50 Hz, respectively. The feeder consists of a diode rectifier with where U is the line-to-neutral RMS utility voltage, I1 is the RMS
resistive load, a resistive-capacitive load, and an MFGCI. The value of the fundamental current of igabc in any phase, P stands
external parts of the feeder are equivalently regarded as a set of for the active power.
voltage sources with inner inductor Lg at the point of common According to catastrophe decision theory, the two factors forms a
coupling (PCC). The MFGCI employs a typical three-phase cusp catastrophe model, as depicted in Fig. 2, and it can be expressed
two-level converter with output filter inductor L. Furthermore, the as
dc-link of the MFGCI is considered as a dc voltage source with
voltage Udc associated with capacitor Cdc. Normally, the MFGCI f (y) = y4 + x1 y2 + x2 y (6)
for RES integration injects purely active power into the micro-grid
[30–32], but the current igabc flows through PCC may be low
where y represents the state variable, x1 and x2 are the THD and TPF
power factor (PF) and high total harmonic distortion (THD) due to
of grid-connected current igabc through the PCC, respectively.
the reactive and harmonic loads in the feeder. However, if the
The points in the equilibrium surface of the cusp catastrophe
MFGCI can also partially generate reactive and harmonic current
model satisfy f′(y) = 0. While its set of singularities can be got by
to feed the local loads in the micro-grid, the power quality at PCC
setting f’′(y) = 0. As a result, the points in the bifurcation equation
can be greatly enhanced.
of the model can be expressed as
It is supposed that the three phases of the grid are symmetrical.
According to the circuit model of the MFGCI, the dynamic 
characteristic of the grid-tied current iabc across filter inductors L f ′ (y) = 4y3 + 2x1 y + x2
(7)
can be expressed as f ′′ (y) = 12y2 + 2x1
.
Liabc = uoabc − uabc − Rd iabc (1) Eliminating the y in (7), it can be derived that

where uoabc and uabc stand for the output voltage of the MFGTI and  
ya = −x1 /6, yb = 3 x2 /8 (8)
PCC, respectively; Rd represents the equivalent parasitic resistor of
filter inductor, insulated gate nipolar transistors (IGBTs), and lines.
According to (1), the transfer function from the grid-tied current to To guarantee x1, x2, and y all within [0, 1] for decision application, x1
the output voltage of MFGTI can be written as in ya multiplies –6, and x2 in yb are reduced 8 times, as indicated in
[33]. Hence the normalised bifurcation equations can be rewritten as
G1 = I(s)/Uo (s) = 1/(Ls + Rd ) (2)
√ √
y′a = x1 , y′b = 3 x2 (9)
Similarly, the transfer function from the grid-tied current to the
voltage of PCC can be expressed as Since the model in (6) is special and just two factors can be
contained, a further consideration is needed for other analytical
G2 = I(s)/U (s) = −1/(Ls + Rd ) (3) indexes includes more than two factors. According to the
catastrophe theory, when the factors of CPQE index to be
Taking any phase for instance, the block model of the MFGTI can be considered are more than two, some other models such as
derived, with the aid of (2) and (3), as indicated in Fig. 1b, where swallowtail catastrophe, butterfly catastrophe, etc. can be
Kpwm = Udc/2 is the equivalent gain of the MFGTI. employed, as indicated in [33].
To confirm the accuracy current-tracking for RESs integration and To eliminate the influence of variables with different units, the
power quality compensation, a multiple proportional-resonant (PR) factors x1 and x2 need to be normalised. It should be noted that,
is employed, which can be expressed as normalised factors have ‘smaller-and-better’ feature. The
normalised x1 and x2 can be written as
 2Krh vch s
GPR (s) = Kp + (4) 
s 2 + 2 v s + v2 x p1 = (x1 − x1min )/(x1max − x1min ) = y1 x1 + l1
ch h (10)
h=1,3,5,7
x p2 = (x2max − x2 )/(x2max − x2min ) = y2 x2 + l2
where ω1(ωc1) and ωh(ωch) are angular frequency (cut-off angular
frequency) of fundamental and hth harmonic components; Kp and where
Krh (h = 1, 3, 5, 7) are proportional and integral gains of the PR  
controller, respectively. The open-loop and close-loop Bode y1 = 1/(x1max − x1min ) l1 = −x1min /(x1max − x1min )
, (11)
diagrams of the MFGCI with PR controller are given in Figs. 1c y2 = −1/(x2max − x2min ) l2 = x2max /(x2max − x2min )
and d, where ωc1 = ωch = 1 rad/s, Kp = 2.5 and Krh = 20. It can be
seen that appropriate zero-error current-tracking feature can be where x1max and x1min can be chosen as the THD of current through
achieved at the resonant angular frequencies, thanks to the high PCC igabc before the MFGCI compensating and zero, respectively; in
gain and zero phase-shift performance of the PR controller at such contrast, x2max and x2min can be chosen as unity and the TPF of igabc
frequencies, where the controlled plant model is G = GPRG1. before the MFGCI compensating, respectively. Because, the THD
and TPF of igabc are ideally controlled as zero and unity, after the
MFGCI carries out perfect power quality compensation. It should
3 Multi-objective optimal compensation of the be noted that the reference values for x1max and x2max are base
MFGCI values for the normalising process, and they also can be chosen as
other values. For instance, maximum THD x1max also can be 100%,
3.1 Model of the multi-objective optimal compensation and the maximum power quality PF x2max can be 1. In practice, all
the optimal compensation algorithm can be embedded in the
To quantify the cared power quality of the micro-grid, a CPQE micro-grid central controller (MGCC) as discussed in Section 6.
model is established based on the catastrophe decision theory as The multi-objective optimal compensation control strategy for
shown in Fig. 2 [33]. MFGCI application will be established step-by-step as follows.

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


762 & The Institution of Engineering and Technology 2016
Fig. 1 Configuration of studied micro-grid and MFGCI
a Micro-grid feeder with MFGCI
b Schematic of current-tracking control of MFGCI
c Open-loop Bode diagram of MFGCI
d Close-loop Bode diagram of MFGCI

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


& The Institution of Engineering and Technology 2016 763
after compensation of the MFGCI, Sh0 and Sh, can be expressed as

Sh0 = 3UIh0 = 3U (x10 I1 ) (14)

Sh = 3UIh = 3U (x1 I1 ) = 3UI1 (1 − a1 )x10 (15)

where α1 = (Ih0–Ih)/Ih0 is the compensated percentage of harmonic


current and needs to be optimally selected. To avoid injecting
surplus harmonic current into the utility and introducing extra
power quality problem, the output harmonic current of the MFGCI
should not be larger than the initialised current of local load,
namely Ih ≤ Ih0. If the MFGCI does not activate the power quality
service function, the harmonic current remained in the micro-grid
is Ih = Ih0 and α1 = 0. If the MFGCI compensates all the harmonic
current in the micro-grid, there is no harmonic current in the
micro-grid, Ih = 0 and α1 = 1. Hence the compensation coefficient
α1 is limited between 0 and 1. Apparent capacity of the MFGCI
for harmonic current compensation can be written as
Fig. 2 CPQE model based on catastrophe decision theory  
S1 = 2 − S 2 = 3UI
Sh0 h 1 x10 − x1
2 2 (16)
3.1.1 Optimal objectives: The first objective for an MFGCI is
the CPQE index. According to the catastrophe decision theory and Second, for the capacity to compensate reactive components, before
the normalised factors in (10) and (11) [33], CPQE index can be and after the MFGCI activates the power quality service, the reactive
expressed as capacity of igabc are Sq0 and Sq, respectively. As indicated in Fig. 3,
the PFs before and after compensation can be, respectively,
expressed as
 
F1 = 0.5 x p1 + 3 x p2 
  TPF0 = cos w0 = x20 = P/ P2 + Q0 2 (17)
= 0.5 y1 x1 + l1 + 3 y2 x2 + l2 (12)

TPF = cos w = x2 = P/ P2 + Q2 (18)

It should be noted that the contribution of TPF to F1 is the cube root where Q0 and Q are the reactive power flow through PCC before and
of xp2 and it is much less important than factor xp1, since the after power quality compensation, and P is the active power through
contribution of TPF is less than the same THD in F1, as shown in PCC. j0 and j are TPF angles before and after reactive current
Fig. 2. Generally, the reactive results from the loads associated compensation of the MFGCI, while x20 and x2 are the
with electric or magnetic field, and all components of the power corresponding TPFs.
system such as generators, conductors, transformers, and According to the power analysis of reactive compensation shown
switchgear would be increased in size (and cost) to carry the extra in Fig. 3, the capacity of the MFGCI used for reactive compensation
reactive current [34]. On the other hand, the harmonic results from can be expressed as
the non-linear factors of machine, transformer, electronic elements,
etc., and harmonics have a number of undesirable effects on power
DQ = Q0 − Q = P( tan w0 − tan w) (19)
system components and loads. It may cause nuisance tripping of
sensitive electronic loads and overheating of transformers, and
even can degrade meter accuracy, etc. [35]. As a result, a series of The TPF at the PCC before and after compensation satisfies as
standard requirements on harmonic and reactive has been
promulgated to confirm the safety and economic operation of the tan w = tan(cos−1 x2 ) = Q/P = (1 − a2 )Q0 /P (20)
utility. Usually, it is typically required that the TPF is more than
0.9 to 0.95 and the THD is less than 5% [36]. For example, if the where α2 = (Q0–Q)/Q0 is the compensated percentage of the reactive
TPF of a power system is 0.9, the acceptable reactive current current that should be optimally designed. Similar to the results of
should be Iq = I1sin(cos–10.9) = 0.45I1. On the contrary, for a same coefficient α1 mentioned before, the coefficient α2 is also limited
power system, if the THD is 5%, the allowable harmonic current between 0 and 1. There is α2 = 0, if there is no reactive
is Ih = 0.05I1. That is to say, a power system can accept much compensation of the MFGCI. If the MFGCI carries out full
more reactive current compared with harmonic current, hence the reactive compensation, it is α2 = 1. Thus, apparent capacity of the
THD is paid much more attention to quantify the CPQE index. MFGCI for reactive compensation can be written as
The second objective for the MFGCI is the apparent capacity
utilised for power quality enhancement, which can be written as S2 = DQ = P( tan w0 − tan w) = a2 Q0 (21)


F2 = S12 + S22 (13)

where S1 and S2 are apparent capacity of the MFGCI employed to


compensate harmonic and reactive current, respectively. The
calculation of S1 and S2 will be discussed separately as follows.
First, for the capacity to compensate harmonic components S1, the
RMS values of harmonic components of grid-connected current igabc
before and after compensation are Ih0 and Ih. Correspondingly, the
THD results of igabc in these cases are x10 and x1, respectively.
Then, the capacity of harmonic components of igabc before and Fig. 3 Power analysis before and after MFGCI compensation

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


764 & The Institution of Engineering and Technology 2016
3.1.2 Constraints conditions: As previously mentioned, Table 1 Parameters of simulated model
compensation coefficients α1 and α2 should be naturally restricted
utility line–line voltage 380 V, fundamental frequency 50 Hz, inner
among 0 and 1, that is inductor 1 mH.
PV string modules BP365 65 W, 20 series and 10 parallel, open voltage

0 ≤ a1 ≤ 1 400 V, short current 41 A, temperature 25°, solar insolation
(22) 800 W/m2.
0 ≤ a2 ≤ 1 MFGCI DC-link voltage 650 V, capacitor 6000 μF, LC filter 1 mH and
20 μF.
local diode-rectifier resistor 50 Ω, resistive and capacitive 10 Ω and
The power quality should be enhanced after the MFGCI activates loads 1000 μF.
power quality enhancement function, namely

0 ≤ x1 ≤ x10
(23)
x20 ≤ x2 ≤ 1 current iabc. Thus, no matter what the load is, the load current iLabc
always equals to igabc + iabc by using Kirchhoff’s Current Law.
In summary, the multi-objective optimal compensation model for The reference current iref,dq in rotating dq frame of the MFGCI
MFGCI can be derived, according to (10)–(23), as consists of two parts. One part igdq is used to track the power
generation of RESs. The other part icdq is utilised to optimally
  compensate the power quality issues at the PCC. The
min F1 = 0.5 x p10 + 3 x p20 transformation matrix T1 in Fig. 4 is utilised to calculate the
 reference current for power generation tracking, which can be
min F2 = S12 + S22 written as
⎧    
⎪ 0 ≤ a1 , a2 ≤ 1 (24)
ud ud

⎪ igd 1 Pref Qref
⎨0 ≤ x ≤ x , x ≤ x ≤ 1 = T1 = (26)
1
10

20 2 igq uq u2d + u2q −Qref Pref uq
s.t.

⎪ S = 3UI x2 − x2


1 1 10 1
S2 = a2 Q0 where Pref and Qref are the reference active and reactive power,
respectively. In addition, transformation matrix T2 is employed to
It should be noted that the CPQE index of PCC after compensation separate the fundamental active and reactive current from the
will be smaller than the one before compensation and not less than equivalent load current [11], which can be expressed as
zero, namely
  
ipd udid + uqiq 1 0 ud
F1 [ [0, s) = (27)
(25) ipq u2d + u2q 0 1 uq
    
√ √ uqid − udiq 0 1 ud
where s = 0.5 x p10 + 3 x p20 is the maximum CPQE of iqd
= (28)
micro-grid before the power quality compensation is activated. iqq u2d + u2q −1 0 uq

3.2 Reference current generation algorithm where ipdq and iqdq are the active and reactive parts of the
fundamental component of equivalent load current iLabc = iabc +
Aforementioned CPQE-based multi-objective optimal compensation igabc in rotating dq frame [26]. udq and idq , corresponding to
model considers the harmonic and reactive components separately, fundamental components of voltage and current in natural abc
and it requires compensating these components distinguishably. frame, are constants in rotating dq frame and can be filtered out by
Therefore, the algorithm of reference current generation should LPFs.
independently detect harmonic and reactive components of the Therefore, the harmonic components of the equivalent load
equivalent load current at PCC. In such condition, an algorithm current in synchronous rotating dq frame ihdq can be derived as
can meet the requirements of the optimal model is presented as
shown in Fig. 4, where Tabc/dq is the Park transformation and Tdq/ ihdq = idq − i pdq − iqdq (29)
abc is its inverse transformation. Besides, an extra block is
employed to detect the zero-sequence current i0 and eliminate its To calculate the compensation part of the reference current icdq of the
influence. To obtain the fundamental positive-sequence MFGCI, the detected harmonic and reactive components ihdq and iqdq
components of voltage and current, low pass filters (LPFs) are also should multiply the compensation coefficients α1 and α2 according
employed as shown in Fig. 4. It should be noted that, thanks to to the multi-objective optimal model mentioned before, which can
the ‘T’-type structure of MFGCI in Figs. 1a and 4, the reference be expressed as
current generation algorithm is independent of the active and
passive elements of local loads, because the total load current can
be obtained by the summation of utility current igabc and MFGCI icdq = a1 ihdq + a2 iqdq (30)

Fig. 4 Reference current generation algorithm of the MFGCI

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


& The Institution of Engineering and Technology 2016 765
Fig. 5 Simulated results of MFGCI for power quality service
a Utility voltage
b Output current of MFGCI
c Utility current at PCC of micro-grid
d Voltage and current of PV by MPPT
e Power loss of IGBTs and diodes
f dc current of MFGCI
g dc voltage of MFGCI
h Zoom in of dc-link voltage
i Zoom in of dc-link voltage

In summary, power generation part igdq and power quality


compensation part icdq comprise the reference current of the
MFGCI in rotating dq frame. With the help of the inverse Park
transformation, the reference current of the MFGCI in abc frame
can be achieved. As a result, the MFGCI can be properly

Table 2 Parameters of the experimental test rig

utility line-neutral RMS voltage Un = 110 V, frequency


fn = 50 Hz, inner inductor Lg = 3 mH Fig. 6 Measured steady-state and dynamic responses of the MFGCI
MFGCI dc link voltage Udc = 350 V and capacitor Cdc =
a Instantaneous current and power waveforms
4400 μF, switching frequency 10 kHz, sampling
b Performance of the PR-based current-tracking controller
frequency 20 kHz, filter inductor L = 0.5 mH
c Steady-state performances
non-linear load diode rectifier with resistor RL = 20 Ω
d Power quality service function activated
resistive-capacitive R = 10 Ω, C = 1000 μF
e Harmonic distribution of PCC current before and after compensation to full
load
compensation

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


766 & The Institution of Engineering and Technology 2016
controlled by the previously mentioned PR-based current-tracking conditions. It can be seen that the THD is below 5% and the TPF
controller as shown in Fig. 1. approximates 99.9% as long as the active power is bigger than
half of its rated capacity. Especially, the efficiency of the MFGCI
in condition of power quality service is also measured. Due to the
4 Simulated results and analysis extra current output for reactive and harmonic compensation, the
loss of the MFGCI is slightly increased. The efficiency of MFGCI
To verify the performance of MFGCI for power quality service, a with compensation is decreased compared with normal
detailed simulation study is achieved by using PLECS. Parameters grid-connected inverter without compensation.
of the simulated model are listed in Table 1. A typical boost In cases of that active/reactive power generation reference of the
converter is used to link the photovoltaic (PV) and MFGCI, and MFGCI is Pref = 1.5 kW, Qref = 0 var, Fig. 6d demonstrates the
incremental conductance method is employed for the maximum dynamic responses of the MFGCI from no compensation to full
power point tracking (MPPT). compensation of the power quality issues in the micro-grid feeder.
Fig. 5 shows the dynamic responses when MFGCI activated the The instantaneous waveforms of the voltage, current, and power at
power quality compensation function at 0.5 s. It can be found from PCC are illustrated in Fig. 6d. It can be observed that the MFGCI
Figs. 5a–c that, because of the power quality service of MFGCI, can seamlessly transfer from no compensation to full
the output current of MFGCI is distorted. However, the power compensation. Besides, the oscillation of active and reactive power
quality of interaction current between micro-grid and the utility is can be significantly eliminated, which is caused by the harmonic
enhanced. current of the non-linear load. Fig. 6e presents the harmonic
Figs. 5d–i further indicates how the power quality service distribution of the PCC current before and after the MFGCI
influences the MFGCI. From Fig. 5d, it can be seen that the carrying out full compensation. It can be seen that the 6n ± 1
auxiliary service hardly affects the MPPT control of PV string. (n = 1, 2, 3, …) orders of harmonic components mainly distort the
However, as shown in Fig. 5e, the extra harmonic and reactive PCC current due to the diode rectifier with resistive load. Before
current generation of the MFGCI will increase the power loss of full compensation of the MFGCI, TPF and THD of the PCC
IGBTs and diodes in the inverter, which will decrease the current are 0.9808 and 15.45%, respectively. After the MFGCI
efficiency of MFGCI. As demonstrated in Fig. 5f, the extra current activates its full compensation, the TPF of the PCC current is
output of the MFGCI for power quality service calls for much enhanced to 0.9999 and its THD is reduced to 5.31%.
more dc current. The power quality service also introduces the
fluctuations of dc voltage, as shown in Figs. 5g–i. When the
compensation function starts working, there is a transient process, 5.2 Multi-objective optimal compensation of the MFGCI
where the dc-link voltage slightly deviates from its reference
value, as depicted in Fig. 5h. Besides, as displayed in Fig. 5i, To achieve optimal compensation of the MFGCI, the Pareto
because of the harmonic current compensation, the voltage of solutions of the multi-objective optimal compensation model in
dc-link contains small sixth-order harmonic component. Section 3 should be derived. With the help of MATLAB, in the
case of mentioned condition x1max = 15.45% and x2max = 0.9808,
the Pareto fronts of the multi-objective optimal model can be
obtained, as shown in Fig. 7.
5 Experimental validation
It can be found from Fig. 6d that, for the micro-grid feeder in
Fig. 1, without power quality compensation (α1 = α2 = 0) of the
To verify the validity and feasibility of the proposed multi-objective
MFGCI in Fig. 4, the CPQE index of the PCC current are F1 =
optimal control strategy, a micro-grid feeder with a 10 kVA MFGCI
0.6342 in the conditions of TPF0 = 0.9808 and THD0 = 15.45%
prototype as displayed in Fig. 1 is built and tested. The key
initially; meanwhile, the apparent capacity of the MFGCI for
parameters of the system are listed in Table 2.
power quality enhancement is F2 = 0 VA. On the other hand, to
compensate all the harmonic and reactive current through the
5.1 Power generation tracking of the MFGCI PCC, the CPQE index will be F1 = 0, but the MFGCI should
employ compensation capacity 1.8185 kVA. This condition, where
To confirm the steady-state and dynamic performances of the α1 = α2 = 1 in Fig. 4, is called as full compensation in the
MFGCI without power quality service function, the waveforms of following part. It should be noted that 18.19% of the rated
dynamic responses (the MFGCI starts up and active power Pref capacity of the MFGCI will be utilised to enhance power quality.
steps from 5 to 8 kW) are illustrated in Figs. 6a and b. It can be However, this kind of full compensation condition may not be
observed that the PR controller can accurately track the reference available. Especially, when renewable energy is very sufficient and
power generation or grid-connected current, and the magnitude of most of the MFGCI capacity is used for active power generation,
the steady-state current-tracking error is approximate 1.5 A. the rest apparent capacity of the MFGCI for power quality
Fig. 6c depicts the TPF, THD of grid-connected current, and enhancement may not be enough to compensate all the harmonic
efficiency of the MFGCI in different active power generation and reactive current components through PCC. Therefore, the

Fig. 7 Pareto solutions of the multi-objective optimal compensation model of the MFGCI
a Pareto fronts
b Optimal compensation coefficients

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


& The Institution of Engineering and Technology 2016 767
Pareto fronts are very important for optimal compensation of the harmonic current as indicated by the experimental results in Fig. 6.
MFGCI. Thanks to the Pareto fronts in Fig. 7, the MFGCI can Thus, the MFGCI cannot ideally compensate all the harmonic
optimally operate and enhance the power quality of the PCC components in practice.
current according to its available capacity margin F2. Hence the In summary, due to the cut-off frequency of the controller,
power quality compensation of the MFGCI can be much more steady-state error of current-tracking, and the limited available
flexible. apparent capacity for power quality compensation, it is hard to
It also should be noted that the employed PR controller of the exactly and ideally compensate all the harmonic and reactive
MFGCI cannot perform perfect zero-error on tracking high-order current through PCC. To optimally utilise the limited capacity and
enhance the power quality as well as possible, the proposed
multi-objective optimal compensation strategy is a good choice.
To verify the effectiveness and flexibility of the proposed optimal
model and strategic compensation, the optimal compensation
results compared with the results of half compensation are given
as follows. The half compensation is defined as operation mode
with α1 = α2 = 0.5. In half compensation condition, the CPQE
index is F1 = 0.3565, and the apparent capacity is F2 = 0.7060 kVA
according to (12)–(21).

5.2.1 Optimal compensation strategy I: Optimal


compensation has the same CPQE index as half
compensation does: According to the Pareto solution of the
multi-objective optimal model in Fig. 7, the optimal coefficients
are α1 = 0.5379 and α2 = 0.05973, in the condition of F1 = 0.36
and F2 = 0.6121 kVA. That is, to achieve the same power quality
level of half compensation, the harmonic and reactive current can
be compensated in different percentages, because of the CPQE
index model in Fig. 2 and the control scheme in Fig. 4, where the
harmonic and reactive factors are separately considered. In such an
optimal way that, the apparent capacity of the MFGCI for power
quality compensation can be saved.
Experimental results of the dynamic responses from half
compensation to optimal compensation using optimal
compensation strategy I are shown in Fig. 8. The waveforms of
instantaneous voltage, current, and power at PCC are illustrated in
Fig. 8a. It is validated that the optimal strategy I focuses on
reactive compensation less, compared with the ones of half
compensation. Meanwhile, the harmonic current after optimal
compensation is similar with the results of half compensation as
previously mentioned α1 = α2 = 0.5 for half compensation and α1 =
0.5379, α2 = 0.05973 for optimal compensation I. Furthermore, the
digital results of harmonic distribution are displayed in Fig. 8b.
The TPF of the PCC current is 0.9953 and 0.9837, as well as the
THD is 8.71% and 7.69% in half compensation and optimal
compensation I, respectively. In addition, for the half
compensation and optimal compensation I, the actual CPQE
indexes are 0.3654 and 0.3904, as well as the utilised capacity for
power quality compensation is 0.8825 kVA and 0.5461 kVA,
respectively, according to (12) and (13). Compared with the
theoretical solutions mentioned before, the actual compensation
capacity employed is less due to the error of current-tracking.

5.2.2 Optimal compensation strategy II: Optimal


compensation has the same apparent capacity as half
compensation does: According to the Pareto solutions in
Fig. 7, if the optimal compensation strategy II have utilised the
same capacity as the one of half compensation F2 = 0.7060 kVA,
the optimal compensation coefficients of harmonic and reactive
components are α1 = 0.6359 and α2 = 0.07095, respectively. It
should be noted that the CPQE index of the PCC can be
effectively decreased from 0.3565 to 0.31. It can be found that,
using optimal control strategy II, the power quality at PCC can be
greatly enhanced in the cases of the MFGCI utilising the same
compensation capacity as half compensation doing.
Experimental results of the dynamic responses from half
compensation to optimal compensation using optimal
compensation strategy II are demonstrated in Fig. 8. The
waveforms of instantaneous voltage, current, and power at PCC
Fig. 8 Experimental results of the optimal compensation strategies
provided in Fig. 8c, it is revealed that the optimal strategy pays
less attention to the reactive compensation, compared with the
a Waveforms of the dynamic from half compensation to optimal compensation I
b Harmonic distribution of PCC current igabc in strategy I
results of half compensation as analysed in the CPQE model.
c Waveforms of the dynamic from half compensation to optimal compensation II Meanwhile, the harmonic current after optimal compensation is
d Harmonic distribution of PCC current igabc in strategy II little smaller than the ones of half compensation because the

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


768 & The Institution of Engineering and Technology 2016
Fig. 9 Hierarchical-based micro-grid application of the proposed optimal strategy
a Configuration of a micro-grid combines multiple MFGCIs
b Algorithm of the tertiary controller in the MGCC to coordinate MFGCIs

coefficients for harmonic compensation are 0.6359 and 0.5, the multiple MFGCIs in the micro-grid. With the guide of MGCC,
respectively. Hence employed harmonic compensation in optimal each MFGCI just partly compensates the power quality issues in
compensation II has small difference from the one in half the micro-grid according to the multi-objective optimal model in
compensation. Furthermore, the harmonic distribution is shown in the tertiary control. Thus, each MFGCI can autonomously work as
Fig. 8d. The TPF of the PCC current is 0.9953 and 0.9841, as an individual module without needing the information of other
well as the THD is 8.632% and 6.729% in half compensation and MFGCIs. In the secondary control, the power generation of
optimal compensation II, respectively. In addition, for half MFGCIs is exchanged and modified by the MGCC to ensure the
compensation and optimal compensation II, actual CPQE indexes safe and economic operation of the micro-grid as suggested in
are 0.3582 and 0.3456, as well as the utilised capacity for power [37, 38]. In the local primary controller of the MFGCI, the output
quality compensation is 0.8921 kVA and 0.6459 kVA, current tracking controller is embedded, and the MFGCI can
respectively. Compared with the optimal compensation strategy I, generate the desired active, reactive, and harmonic current to the
strategy II pays much attention to the harmonic and reactive micro-grid to fulfill the functions to interface DERs into utility and
current compensation. As a result, there is more capacity is utilised enhance the power quality of the micro-grid as expected as
and the CPQE index is much smaller than the one of strategy I. In demonstrated in [37, 38].
summary, more capacity usage of the MFGCI, better power
quality at PCC can be guaranteed. If the available capacity for
power quality enhancement is limited, the MFGCI can flexibly and 7 Conclusions
optimally work based on the multi-objective compensation in
Fig. 7 to customise the power quality to a certain level. In micro-grids, provision of power quality enhancement service by
MFGCIs is important. As the apparent power capacity of an
MFGCI is limited, it is necessary to utilise the limited capacity
6 Discussions effectively and enhance the power quality of the micro-grid as
much as possible. A multi-objective optimal compensation
To integrate the multiple MFGCIs in a micro-grid, a configuration is strategy for MFGCI application is proposed in this paper.
displayed in Fig. 9 to show how the proposed method can Besides, a CPQE approach based on catastrophe decision theory
cooperatively handle the power quality issues in a feeder with is applied to evaluate the micro-grid power quality in a
communication. It can be seen from Fig. 9 that the proposed comprehensive and quantitative way. In such a way, an MFGCI
multi-objective optimal compensation model can be solved by the can flexibly and optimally enhance the power quality of the
CPQE-based multi-objective optimal model in the MGCC, and the micro-grid without extra power quality conditioners to a certain
MGCC also download the optimal compensation coefficients α1 extent. Experimental results from a feeder of a micro-grid have
and α2 to MFGCIs’ local controllers. In general, the MGCC can confirmed the validity and feasibility of the proposed optimal
be a hierarchical controller as indicated in [37, 38], and it also compensation strategy.
should be noted that the optimal compensation of MFGCIs may be
embedded in the tertiary control to dispatch the MFGCIs to
provide optimal power quality services. 8 Acknowledgments
In the micro-grid, the MGCC detects the utility voltage uPCC and
current iPCC at PCC, and then the THD and TPF of the current can be Thanks for the financial supports from National Key Basic Research
computed. In addition, the initial information of the optimal model Program of China (‘973 Program’) (under grant no.
can be given. Therefore, the aforementioned multi-objective 2012CB215200), National High Technology Research and
optimal model in Section 3 can be solved in the tertiary control, Development Program (‘863 Program’) (under grant no.
and the obtained Pareto fronts solution is numerically saved in the 2011AA050204), National Natural Science Foundation of China
MGCC. To meet the requirement of the system operator or the (under grant no. 51377184), and Fundamental Research Funds for
owner of the micro-grid on the CPQE index F1, the desired the Central Universities (under grant nos.
compensation coefficients, α1 and α2, can be obtained and sent to 106112015CDJXY150005, CDJZR12150074).

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


& The Institution of Engineering and Technology 2016 769
9 References 20 Wang, F., Duarte, J.L., Hendrix, M.A.M.: ‘Grid-interfacing converter systems with
enhanced voltage quality for microgrid application-concept and implementation’,
IEEE Trans. Power Electron., 2011, 26, (12), pp. 3501–3513
1 Loh, P.C., Chai, Y.K., Li, D., et al.: ‘Autonomous operation of distributed storages
21 Han, B., Bae, B., Kim, H., et al.: ‘Combined operation of unified power-quality
in microgrids’, IET Power Electron., 2014, 7, (1), pp. 23–30
conditioner with distributed generation’, IEEE Trans. Power Deliv., 2006, 21,
2 Nutkani, I.U., Loh, P.C., Blaabjerg, F.: ‘Cost-based droop scheme with lower
(1), pp. 330–338
generation costs for microgrids’, IET Power Electron., 2014, 7, (5), pp. 1171–1180
22 Li, Y., Vilathgamuwa, D.M., Loh, P.C.: ‘Microgrid power quality enhancement
3 Guo, Z., Sha, D., Liao, X.: ‘Energy management by using point of common
using a three-phase four-wire grid-interfacing compensator’, IEEE Trans. Ind.
coupling frequency as an agent for islanded microgrids’, IET Power Electron.,
Appl., 2005, 41, (6), pp. 1707–1719
2014, 7, (8), pp. 2111–2122 23 Wu, T.F., Nien, H.S., Shen, C.L., et al.: ‘A single-phase inverter system for PV
4 Enslin, J.H.R., Heskes, P.J.M.: ‘Harmonic interaction between a large number of power injection and active power filtering with nonlinear inductor consideration’,
distributed power inverters and the distribution network’, IEEE Trans. Power IEEE Trans. Ind. Appl., 2005, 41, (4), pp. 1075–1083
Electron., 2004, 19, (6), pp. 1586–1593 24 Sawant, R.R., Chandorkar, M.C.: ‘Power boundaries in multifunctional converter
5 Bollen, M.H., Hassan, F.: ‘Integration of distributed generation in the power control for three-phase four-wire systems’. Proc. IEEE Region 10 Annual Int.
system’ (Wiley-IEEE Press, 2011) Conf., 2008, pp. 1–6
6 Eloy-Garcia, J., Vasquez, J.C., Guerrero, J.M.: ‘Grid simulator for power quality 25 Macken, K.J.P., Vanthournout, K., Van den Keybus, J., et al.: ‘Distributed control
assessment of micro-grids’, IET Power Electron., 2013, 6, (4), pp. 700–709 of renewable generation units with integrated active filter’, IEEE Trans. Power
7 Prodanovic, M., Green, T.C.: ‘High-quality power generation through distributed Electron., 2004, 19, (5), pp. 1353–1360
control of a power park microgrid’, IEEE Trans. Ind. Electron., 2006, 53, (5), 26 Zeng, Z., Zhao, R., Yang, H.: ‘Coordinated control of multi-functional grid-tied
pp. 1471–1482 inverters using conductance and susceptance limitation’, IET Power Electron.,
8 Rahmani, B., Bina, M.T.: ‘Reciprocal effects of the distorted wind turbine source 2014, 7, (7), pp. 1821–1831
and the shunt active power filter: full compensation of unbalance and harmonics 27 Farghal, S.A., Kandil, M.S., Elmitwally, A.: ‘Quantifying electric power quality
under ‘capacitive non-linear load’ condition’, IET Power Electron., 2013, 6, (8), via fuzzy modelling and analytic hierarchy processing’, IEE Proc. – Gener.
pp. 1668–1682 Trans. Distrib., 2002, 149, (1), pp. 44–49
9 Zeng, Z., Zhao, R., Yang, H., et al.: ‘Topologies and control strategies of 28 Morsi, W.G., El-Hawary, M.E.: ‘Power quality evaluation in smart grids
multi-functional grid-connected inverters for power quality enhancement: A considering modern distortion in electric power systems’, Electr. Power Syst.
comprehensive review’, Renew. Sustain. Energy Rev., 2013, 24, pp. 223–270 Res., 2011, 81, (5), pp. 1117–1123
10 Fan, L.L., Miao, Z.X.: ‘Mitigating SSR using DFIG-based wind generation’, IEEE 29 Salarvand, A., Mirzaeian, B., Moallem, M.: ‘Obtaining a quantitative index for
Trans. Sustain. Energy, 2012, 3, (3), pp. 349–358 power quality evaluation in competitive electricity market’, IET Gener. Trans.
11 Zeng, Z., Yang, H., Tang, S., et al.: ‘Objective-oriented power quality Distrib., 2010, 4, (7), pp. 810–823
compensation of multi-functional grid-tied inverters and its application in 30 Hemdani, A., Dagbagi, M., Naouar, W.M., et al.: ‘Indirect sliding mode power
micro-grids’, IEEE Trans. Power Electron., 2015, 30, (3), pp. 1255–1265 control for three phase grid connected power converter’, IET Power Electron.,
12 Tummuru, N.R., Mishra, M.K., Srinivas, S.: ‘Multifunctional VSC controlled 2015, 8, (6), pp. 977–985
microgrid using instantaneous symmetrical components theory’, IEEE Trans. 31 Singh, B., Shahani, D.T., Verma, A.K.: ‘Neural network controlled grid interfaced
Sustain. Energy, 2014, 5, (1), pp. 313–322 solar photovoltaic power generation’, IET Power Electron., 2014, 7, (3),
13 Zeng, Z., Yang, H., Guerrero, J.M., et al.: ‘Multi-functional distributed generation pp. 614–626
unit for power quality enhancement’, IET Power Electron., 2015, 8, (3), 32 Liu, T., Xia, C.L., Shi, T.H.: ‘Robust model predictive current control of
pp. 467–476 grid-connected converter without alternating current voltage sensors’, IET Power
14 Dai, N.Y., Zhang, W.C., Wong, M.C., et al.: ‘Analysis, control and experimental Electron., 2014, 7, (12), pp. 2934–2944
verification of a single-phase capacitive-coupling grid-connected inverter’, IET 33 Zhang, T., Ren, S., Li, S., et al.: ‘Application of the catastrophe progression method
Power Electron., 2015, 8, (5), pp. 770–782 in predicting coal and gas outburst new’, Min. Sci. Technol., 2009, 19, (4),
15 Vasquez, J.C., Mastromauro, R.A., Guerrero, J.M., et al.: ‘Voltage support pp. 430–434
provided by a droop-controlled multifunctional inverter’, IEEE Trans. Ind. 34 Grady, W.M., Santoso, S.: ‘Understanding power system harmonics’, IEEE Power
Electron., 2009, 56, (11), pp. 4510–4519 Eng. Rev., 2001, 21, (11), pp. 8–11
16 Sawant, R.R., Chandorkar, M.C.: ‘Methods for multi-functional converter control 35 Cividino, L.: ‘Power factor, harmonic distortion; causes, effects and
in three-phase four-wire systems’, IET Power Electron., 2009, 2, (1), pp. 52–66 considerations’. IEEE Int. Telecommunications Energy Conf., Washington, DC,
17 Mahdianpoor, F.M., Hooshmand, R.A., Ataei, M.: ‘A new approach to USA, 1992, pp. 506–513
multifunctional dynamic voltage restorer implementation for emergency control 36 Teodorescu, R., Liserre, M., Rodriguez, P.: ‘Grid converters for photovoltaic and
in distribution systems’, IEEE Trans. Power Deliv., 2011, 26 wind power systems’ (John Wiley & Sons, Ltd, West Sussex, United Kingdom,
18 Singh, M., Khadkikar, V., Chandra, A.: ‘Grid synchronisation with harmonics and 2011)
reactive power compensation capability of a permanent magnet synchronous 37 Guerrero, J.M., Vasquez, J.C., Matas, J., et al.: ‘Hierarchical control of
generator-based variable speed wind energy conversion system’, IET Power droop-controlled AC and DC microgrids-A general approach toward
Electron., 2011, 4, (1), pp. 122–130 standardization’, IEEE Trans. Ind. Electron., 2011, 58, (1), pp. 158–172
19 Todeschini, G., Emanuel, A.E.: ‘Wind energy conversion systems as active filters: 38 Guerrero, J.M., Chandorkar, M., Lee, T., et al.: ‘Advanced control architectures for
Design and comparison of three control methods’, IET Renew. Power Gener., intelligent microgrids—Part I: Decentralized and hierarchical control’, IEEE Trans.
2010, 4, (4), pp. 341–353 Ind. Electron., 2013, 60, (4), pp. 1254–1262

IET Power Electron., 2016, Vol. 9, Iss. 4, pp. 761–770


770 & The Institution of Engineering and Technology 2016

You might also like