Project:

ETAP Page: 1
12.6.0H
Location: Date: 12-13-2018
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: BUDI1 Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: GI NUSA DUA

Prefault voltage = 150.000 kV = 100.00 % of nominal bus kV ( 150.000 kV)


= 100.00 % of base kV ( 150.000 kV)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

GI NUSA DUA Total 0.00 8.395 0.00 105.78 107.60 7.367 7.367 6.35E-001 4.54E+000 1.15E+000 6.43E+000

BUS GIS BNDRA GI NUSA DUA 3.28 0.819 2.24 106.10 108.02 0.521 0.128 5.60E+000 4.67E+001 6.65E+001 3.69E+002
NUSA DUA
NUSA GI NUSA DUA 25.43 6.343 33.21 102.21 99.44 6.127 7.239 9.22E-001 6.00E+000 1.17E+000 6.54E+000
DUA-PSANGGARAN
BUS NUSA DUA 1 GI NUSA DUA 20.65 0.381 68.12 68.33 99.87 0.223 0.000 8.43E+000 1.01E+002
BUS NUSA DUA 2 GI NUSA DUA 23.62 0.436 69.09 69.42 99.87 0.255 0.000 7.17E+000 8.79E+001
BUS NUSA DUA 3 GI NUSA DUA 22.62 0.418 68.76 69.05 99.87 0.244 0.000 7.56E+000 9.18E+001

GIS BANDARA BUS GIS BNDRA 3.81 0.819 2.64 106.16 108.05 0.521 0.128 5.20E+000 4.52E+001 6.55E+001 3.67E+002
NUSA DUA
GIS PESANGGARAN NUSA 26.61 6.343 35.03 102.11 98.77 6.127 7.239 5.17E-001 4.51E+000 1.74E-001 3.79E+000
DUA-PSANGGARAN
NUSA DUA 1 BUS NUSA DUA 1 100.00 2.861 100.00 100.00 100.00 1.448 0.000 7.97E+000 7.97E+001
NUSA DUA 2 BUS NUSA DUA 2 100.00 3.273 100.00 100.00 100.00 1.657 0.000 6.71E+000 6.71E+001
NUSA DUA 3 BUS NUSA DUA 3 100.00 3.135 100.00 100.00 100.00 1.587 0.000 7.10E+000 7.10E+001

# Indicates fault current contribution is from three-winding transformers

* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer