TCS2P125 (TC-V2)
TABLE OF CONTENTS
Section Page
SECTOIN 1 : INTRODUCTION
1.1 Safety Precautions ........................................................................................................................... 3
1.2 Products Overview ........................................................................................................................... 3
SECTOIN 4 : OPERATION
4.1 General............................................................................................................................................. 7
4.2 Auto Mode ........................................................................................................................................ 7
4.3 Test Mode ........................................................................................................................................ 7
4.4 Programming Mode.......................................................................................................................... 7
4.5 AC Voltage Display adjustment ....................................................................................................... 7
4.6 Specification Summary .................................................................................................................... 7
4.7 System Setting Reference Table ..................................................................................................... 8
______________________________________________________________________________________
2
TCS2P125 (TC-V2)
SECTION 1 : INTRODUCTION
HIGH VOLTAGES CAN KILL. ● Monitor normal source for full phase over and
under voltages.
● Monitor emergency source for single phase over
1.2 Products Overview
and under voltages.
The TCS2P125 automatic transfer switch consist of
● Normal & emergency source voltage and
two parts the TS2P125 switch and the TC-V2
frequency parameter display.
electronic control unit:
● TDEN, TDNE, TDEC and TDOFF real time
1.2.1 TS125 Features countdown display.
● Permit testing the transfer switch from the control
The contacts on the Kutai TS2P125 transfer switch
panel.
are class PC, this means that it is capable of making
and withstanding short circuits but is not intended ● Permit system testing the transfer switch with or
for breaking short circuit current. without load from the front panel.
● Built-in 1 to 4 weeks exerciser timer.
● Rated operating Voltage:540 VAC.
● Permit customer plant exerciser test with / without
● Rated operating Current:125 Amps
load on a preset period.
● Number of poles:2P
● Safely store customer / factory settings in
● Coil operating voltage:220VAC ±20% permanent memory.
● Compact size, light weight and low power ● Shows status and failure alarm LED’s on the front
consumption. panel.
● Electrically operated and mechanically held. ● No need for PC connection and programming
● Manufactured using UL 94V-0 plastics. software. All settings can be made on site.
● Adjustable time delay in OFF position when ● Controller can be installed next to switch or
transferring. separately on an enclosure panel.
TS2P125 TC-V2
______________________________________________________________________________________
3
TCS2P125 (TC-V2)
Display
Window
Function
Selector Manual
Handle
ATS
Emergency
Status
Normal
______________________________________________________________________________________
4
TCS2P125 (TC-V2)
______________________________________________________________________________________
5
TCS2P125 (TC-V2)
TDNE provides a time delay when transferring from When the exerciser is activated the exerciser LED
Normal to Emergency. Timing begins when the (EX) on the right side of display flashes and turns on
Emergency Source (generator) becomes available. during the exercise period.
TDNE:Adjustable from 0 to 99 seconds.
3.8 Over / Under Voltage Sensing
3.3 TDEN Settings The TC-V2 constantly monitors normal & emergency
TDEN provides a time delay when transferring from power. When power falls outside the programmed
Emergency to Normal. This permits stabilization of voltages this LED turns RED from GREEN and
the Normal Power before transferring back to flashing to show OV / UV problems.
normal. Timing begins when the Normal Power
returns and becomes available and steady. Adjustable Over voltage range:110VAC ~ 530VAC
Over voltage reset:When voltage falls below 10VAC
TDNE:Adjustable from 0 to 99 seconds.
of the OV setting.
3.4 TDEC Settings Adjustable Under voltage range:80VAC ~ 470VAC
TDEC timer keeps the generator running without Under voltage reset:When voltage exceeds 10VAC
load (Engine Cool-down) after the ATS transfer of the UV setting.
back to Normal Power. Timing begins when the
transfer back to normal is completed. 3.9 Transfer Failure
TDEC:Engine Cool-down - from 0 to 99 sec. When a transfer is made the TS125 communicates
it’s position to the TC-V2 controller by using two
3.5 TDES Setting small internal micro-switches, if this signal is not
received, it will try switching 3 more times every 2
TDES is the time delay for Engine Start when the seconds or until the connection is made. A flashing
Normal Source voltage is in over or under-voltage light indicator and a “FAIL” signal displayed an
(OV or UV). If power return to normal while timing, incomplete transfer and that the ATS mechanism or
the TDES timer resets and starts again. wiring is defective.
TDES:Adjustable from 0 to 30 seconds.
If the ATS fails, the TC-V2 controller stops all ATS
3.6 TD-OFF Setting functions and starts’ flashing until the failure is
corrected and the control is reset.
Time Delay on OFF this timer keeps the switch in
the center neutral OFF position (completely To reset the transfer fail alarm:
disengaged) before transferring to the other side.
1. Manually move the ATS to the correct position.
You can preset the switch in Neutral or OFF from 0
to 18 seconds (Normally 2 to 3 sec). 2. Press any button (Auto, Program or Test) on the
front panel to reset the alarm.
TD-OFF:Adjustable from 1 to 20 seconds.
______________________________________________________________________________________
6
TCS2P125 (TC-V2)
______________________________________________________________________________________
7
TCS2P125 (TC-V2)
FACTORY
ITEM DESCRIPTION SETTING
SETTING
1 Is this ATS operator in 1Ø or 3Ø 01) 1Ø 02) 3Ø 02
Normal power VL12 voltage display
2 -99~ 99 V 00
adjustment setting
Normal power VL23 voltage display
3 -99~ 99 V 00
adjustment setting
Normal power VL31 voltage display
4 -99~ 99 V 00
adjustment setting
______________________________________________________________________________________
8
TCS2P125 (TC-V2)
5.1 General
The TC-V2 controller is modular and is designed for installation next to switch or on the front door panel. A
longer harness is required for door installation.
STEP-1 STEP-2
STEP-3 STEP-4
______________________________________________________________________________________
9
TCS2P125 (TC-V2)
STEP-1 STEP-2
STEP-3 STEP-4
STEP-5 STEP-6
______________________________________________________________________________________
10
TCS2P125 (TC-V2)
CS1 CS2
NORMAL N1 E1 EMERGENCY
CS1 CS2
SOURCE N2 E2 SOURCE
220V COIL
NLS ELS
CN1-1
CN1-9
CN1-10
CN1-6
CN1-11
CN1-2
CN1-3
CN1-4
CN1-12
BROWN
WHITE
BLACK
BLUE
PINK
RED
ORANGE
YELLOW
RED/WHITE
CN1 Connector
CN2-1
CN2-9
CN2-10
CN2-6
CN2-11
CN2-2
CN2-3
CN2-4
CN2-12
Remote
Start
TC-V2 Controller
CN2 Connector
______________________________________________________________________________________
11
TCS2P125 (TC-V2)
CS1 CS2
NORMAL N1 E1 EMERGENCY
CS1 CS2
SOURCE N2 E2 SOURCE
220V COIL
NLS ELS
CN1-1
CN1-9
CN1-10
CN1-6
CN1-11
CN1-2
CN1-3
CN1-4
CN1-12
BROWN
WHITE
BLACK
BLUE
PINK
RED
ORANGE
YELLOW
RED/WHITE
CN1 Connector
TSP-XX
CN2-1
CN2-9
CN2-10
CN2-6
CN2-11
CN2-2
CN2-3
CN2-4
CN2-12
Remote
Start
TC-V2 Controller
CN2 Connector
TSP
-XX
______________________________________________________________________________________
12