These were the original spacing of
temporary filler beams that were used to 1'-101/4 2'-0 2'-0 3'-0 2'-0 2'-0 2'-71/2 2'-0 2'-0 2'-0 3'-0 2'-0 2'-0 2'-0 2'-03/4 2'-0 2'-0 2'-0 1'-31/2
move the heavy equipment across
platform.

1'-101/4 4'-0 3'-0 4'-0 2'-71/2 4'-0 2'-0 3'-0 4'-0 4'-03/4 4'-0 3'-31/2

Can this work?


We have reused the spacing to make use of the existing holes in the girder.
We are reusing the beams that are highlighted in green and omitted beams highlighted in red.
Please review the spacing considering the 4'-0" MAX grating span and confirm this spacing is acceptable.
14'-3 39'-10 17'-11

PLATFORM FRAMING PLAN As per Approver response we are


REFER: FH-S-002 following these spacing, & skipping
beams which are marked in red line.