You are on page 1of 37

6518/6519

3/2, 5/2, 5/2 bistable and


5/3 way pneumatic solenoid valve

Type 6518

• Single or block mounting


• Suitable for outdoor and chemical atmospheres
Type 6519

• Suitable for low temperatures


• Explosion-proof versions
• Threaded or NAMUR flange connections
Type 6518/6519 can be combined with...

Type 2508 Type 2513 Type 2510/11 Type 2012 Type 2030
Cable plug Cable plug Cable plug ASI Single seat valve Diaphragm valve
(ATEX Cat. 3 GD)

The Type 6518 is a servo-assisted 3/2 way


Content 6518/6519 Page
valve and the Type 6519 is a 5/2 or 5/3 way
valve. Together, they form a product line. The
6518/6519 Standard temperature range
valves can be used individually or in blocks. The
valves work without a continuous air consump- 6518/6519 Standard 2
tion and are used for the pneumatic control of Ex m 3
double or single-acting actuators. A solenoid
Ex i 4
valve Type 6014 is used as a pilot. The use of
high quality materials makes it possible to use 6519 NAMUR Standard 5
these valves in the open air and under chemi- Ex m 6
cal atmospheres. The product line contains
Ex i 7
units with Ex-Approvals and NAMUR flange
interface. Manifold assembly with MP07 pneumatic modules 8
Accessories 10
Dimensions 12

6519 with extended temperature range


6519 Standard 20
Ex m 22
Ex i 24
6519 NAMUR Standard 26
Ex m 28
Ex i 30
Accessories 32
Dimensions 34

www.burkert.com S. 1/37
6518/6519

Type 6518/6519 Standard (with tag connector acc.to DIN EN 175301-803 Form A, without cable plug)
Technical data
Orifice Type 6518 DN8 mm
Type 6519 DN8 and 9 mm
Body material
Type 6518
Pilot and main valve Polyamide, reinforced glass-fibre
Type 6519
Pilot valve Polyamide, reinforced
Main valve Polyamide (5/2 way), aluminium (5/3 way)
Type 6518
Threaded socket material Brass (stainless steel on request)
Standard Type 6519 Seal material Type 6518 NBR and PUR
Standard Type 6519 NBR and PUR (5/2 way), NBR (5/3 way)
Medium Neutral Medium, e.g. lubricated or non-lubricated com-
pressed air
Compressed air quality ISO 8573-1:2010, Class 7.4.4*
Type 6518 and the Type 6519 together form a product Medium temperature - 10 °C to + 50 °C
line. Both types can be mounted on a pneumatic module. Ambient temperature - 25 °C to + 55 °C
The valve width of 32 mm allows high flow rates. A sole- Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, multi-station manifold (on request NPT ¼)
noid valve Type 6014 is used as a pilot. The valves can Service port 2, 4 Thread G ¼ (on request NPT ¼)
be used individually or in blocks. Operating voltages 24 V DC
24/ 110/ 230 V/ 50 - 60 Hz
Power consumption Voltage tolerance + 10 %
Inrush Hold (hot coil) Duty cycle 100 % continuous operation
AC [VA] AC [VA/W] DC [W] Electrical connection Tag connector acc. to DIN EN 175301-803 (previously
DIN 43650) Form A for cable plug Type 2508
11 6/2 2 Type of protection IP65 with cable plug
Response times1) Installation As required, preferably with actuator upright
Opening 20 [ms] * To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than
Closing 40 [ms] the temperature of the medium.
1)
Measured at valve outlet at 6 bar and + 20 °C acc. to ISO 12238.
Opening: Pressure rise 0 to 90 %,
Closing: Pressure drop 100 to 10 %

Ordering chart with manual override (without manual override on request)


connection

Frequency

Article no.
Weight [g]

power [W]
Threaded
and body

QNn value

Pressure

Voltage/
Nominal
function

material

range2)
Orifice
Circuit

[l/min]

[V/Hz]
[inch]
[mm]

[bar]
Seal

port

air1)

Type 6518 Standard – Brass threaded socket, also threads 1 and 3 of multi-station manifold; without cable plug
C 2(A) 8.0 NBR and G¼ 1300 2 - 8 370 2 024/DC 132457 
12 PUR 024/50 - 60 132458 
1(P) 3(R) (Polyamide)
110/50 - 60 132459 
3/2 way servo-controlled solenoid valve,
normally closed, with manual override 230/50 - 60 132460 
D 2(B) 8.0 NBR and G¼ 1300 2 - 8 370 2 024/DC 132461 
10
PUR 024/50 - 60 132462 
1(P) 3(R) (Polyamide)
110/50 - 60 132463 
3/2 way servo-controlled, solenoid valve,
normally open, with manual override 230/50 - 60 132464 
Type 6519 Standard – Brass threaded socket, also threads 1, 3 and 5 of multi-station manifold; without cable plug
H 4 2 8.0 NBR and G¼ 1300 2 - 8 450 2 024/DC 132465 
14 PUR
12 024/50 - 60 132466 
5 1 3 (Polyamide)
5/2 way servo-controlled solenoid valve, 110/50 - 60 132467 
with manual override 230/50 - 60 132468 
L 4 2 9.0 NBR G¼ 1300 3 - 10 720 2 024/DC 132469 
14 12
(Aluminium) 024/50 - 60 132470 
5 13
110/50 - 60 132471 
5/3 way solenoid valve, in middle position
all ports locked, with manual override 230/50 - 60 132472 
N 4 2 9.0 NBR G¼ 1300 3 - 10 720 2 024/DC 132473 
14 12
(Aluminium) 024/50 - 60 132474 
5 13
110/50 - 60 132475 
5/3 way valve, in middle position ports 2
and 4 open, with manual override 230/50 - 60 132476 

1) Flow rate: QNn value air [l/min]: Measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar pressure difference
2) Pressure values [bar]: ‌Overpressure with respect to atmospheric pressure
S. 2/37
6518/6519

Type 6518/6519 Ex m (with moulded cable, 3 m long, junction box on request)

The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.

Technical data
Orifice Type 6518 DN8 mm
Type 6519 DN8 and 9 mm
Body material
Type 6518 - Pilot & main valve Polyamide, reinforced glass-fibre
Type 6519 - Pilot valve Polyamide, reinforced glass-fibre
Main valve Polyamide (5/2 way), aluminium (5/3 way)
Threaded socket material Brass (stainless steel on request)
Seal material Type 6518 NBR and PUR
Type 6519 NBR and PUR (5/2 way), NBR (5/3 way)
Medium Neutral medium, e.g. lubricated or non-lubricated
compressed air
Compressed air quality ISO 8573-1:2010, Class 7.4.4*
Medium temperature - 10 °C to + 50 °C
Type 6519 Ex m Ambient temperature - 25 °C to + 50 °C
Type 6518 Ex m
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, multi-station manifold (on request NPT ¼)
Service port 2, 4 Thread G ¼ (on request NPT ¼)
The approval Ex m is achieved by the mounting of an Operating voltages 24/ 110/ 230 V/UC
approved push-over coil. The cable connection and the Voltage tolerance + 10 %
cable are non-detachable and sealed together with the Duty cycle 100 % continuous operation
valve. The valves can be used individually or in blocks. Electrical connection 3 m cable, moulded
junction box (without fuse)
Type of protection IP65
Response times1) Approvals
Opening 20 [ms] Coil PTB 14 ATEX 2023 X / IECEx PTB 14.0049 X
Closing 50 [ms] II 2G Ex mb IIC T5 Gb
II 2D Ex mb IIIC T 100 °C Db
1)
Measured at valve outlet at 6 bar and + 20 °C acc. to ISO 12238. Junction box EPS16 ATEX 1046 X / IECEx EPS 16.0021 X
Öffnen: Pressure rise 0 to 90 % II 2G EX eb mb IIC T5 Gb
Closing: Pressure drop 100 to 10 % II 2D EX mb tb IIIC T100 °C Db
Installation As required, preferably with actuator upright
* T
 o prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the
temperature of the medium.

Ordering chart with manual override (without manual override on request)


connection

Frequency

Article no.
Weight [g]

power [W]
Threaded
and body

QNn value

Pressure

Voltage/
Nominal
function

material

range2)
Orifice
Circuit

[l/min]

[V/Hz]
[inch]

Luft1)
[mm]

[bar]
Seal

port

Type 6518 Ex m – Brass threaded socket, also threads 1 and 3 of multi-station manifold; with moulded cable, 3 m long3)
C 2(A) 8.0 NBR G¼ 1300 2 - 8 600 3 024/UC 278195 
12
and 110/UC 278200 
1(P) 3(R) PUR
230/UC 278201 
3/2 way servo-controlled solenoid valve, (Polyamide)
normally closed, with manual override
D 2(B) 8.0 NBR G¼ 1300 2 - 8 600 3 024/UC 278205 
10
and 110/UC x
1(P) 3(R) PUR
230/UC x
3/2 way servo-controlled, solenoid valve, (Polyamide)
normally open, with manual override
Type 6519 Ex m – Brass threaded socket, also threads 1, 3 and 5 of multi-station manifold; with moulded cable, 3 m long4)
H 4 2 8.0 NBR G¼ 1300 2 - 8 700 3 024/UC 278209 
14
and 110/UC 278212 
12
5 1 3 PUR
230/UC 278213 
5/2 way servo-controlled solenoid valve, (Polyamide)
with manual override
L 4 2 9.0 NBR G¼ 1300 3 - 10 1.100 3 024/UC 278221 
14 12
(Aluminium) 110/UC x
5 13 230/UC x
5/3 way solenoid valve, in middle position
all ports locked, with manual override
N 4 2 9.0 NBR G¼ 1300 3 - 10 1.100 3 024/UC 278222 
14 12
(Aluminium) 110/UC x
5 13 230/UC x
5/3 way valve, in middle position ports 2
and 4 open, with manual override
1)
Flow rate: QNn value air [l/min]: Measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar pressure difference
2)
Pressure values [bar]: ‌Overpressure with respect to atmospheric pressure
3)
Versions with junction box on request
4)
Circuit function H (5/2 way) as impulsee version on request
S. 3/37
x = on request
6518/6519

Type 6518/6519 Ex i (with Tag connector acc. to DIN EN 175301-803 Form A, without cable plug)

The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.

Technical data
Orifice Type 6518 DN8 mm
Type 6519 DN8 and 9 mm
Body material
Pilot valve Stainless steel 1.4305 or brass
Main valve Polyamide, reinforced glass-fibre
Threaded socket material Brass (stainless steel on request)
Seal material FPM, NBR and PUR
Medium Neutral medium, e.g. lubricated or non-lubricated
compressed air
Compressed air quality ISO 8573-1:2010, Class 7.4.4*
Medium temperature - 10 °C to + 50 °C
Type 6518 Ambient temperature - 25 °C to + 55 °C
Ex i Type 6519
Pneumatic connection
Ex i Supply port connection 1, 3, 5 Thread G ¼, multi-station manifold (on request PT1/4)
Service port 2, 4 Thread G ¼ (on request NPT ¼)
The intrinsically-safe Type 6518 Ex i and 6519 Ex i valves
Duty cycle 100 % continuous operation
consist of an intrinsically-safe pilot control and a pneumatic
Electrical connection Tag connector acc. to DIN EN 175301-803 (previ-
amplifier. The diaphragm-controlled valve seats work with
ously DIN 43650) Form A for cable plug Type 2508
very low friction, ensuring reliable switching of the valve,
(not in delivery, see accessories), check for correct
even after long shutdown periods.
polarity
Response times1) Type of protection IP65 with cable plug
Opening 75 [ms] Installation As required, preferably with actuator upright
Closing 115 [ms] * To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than
Measured at valve outlet at 6 bar and + 20 °C acc. to ISO 12238.
1) the temperature of the medium.
Opening: Pressure rise 0 to 90 %
Closing: Pressure drop 100 to 10 %
Electrical data - Coil AC10 Ex i
Approvals PTB 01 ATEX 2101 / PTB IECEx 10.0019
Note II 2G Ex ia IIC T6 Gb
These units may only be used in explosive atmospheres in II 2G Ex ia IIIC T80 °C Db
the manner approved by the Federal Institute of Physics and Function values for
Technology (PTB), i.e., the permissible maximum electrical Switching function valve1) at + 20 °C at + 55 °C
values must be complied with. Suitable barriers and isolating
Minimum switching current 29 mA 29 mA
modules are available for this.
Nominal resistance coil 310 Ω 360 Ω
Minimum terminal voltage 9.0 V 10.4 V
Conformity specifications
Ui 35 V
Ii 0.9 A
The valve is intended for operation on 24 V DC outputs via the Pi 1.1 W
intermediate switching of a corresponding intrinsically-safe 1)
With high resistance coil on request
operating resource (isolating module or barrier).
If required, request the “Recommended Barrier and Isolating
Module” data sheet.

Ordering chart for valves without manual override (with manual override and high resistance coil on request)
range2) [bar]
connection

air control
pilot valve

Article no.
Weight [g]

connector
terial and

Threaded

QNn value
Seal ma-

Pressure

Material
function

material
Orifice
Circuit

[l/min]
[inch]

Body
Luft1)
[mm]

body

port

Type 6518 Ex i without cable plug


C 2(A) St. St. 145111 
12 NBR St. St.
Brass, nickel
and 1.4305 144486 
1(P) 3(R) 8.0 G¼ 1300 2 - 8 580 plated
PUR
3/2 way servo-controlled solenoid Brass, nickel
(Polyamide) Brass 147253 
valve, normally closed plated
Type 6519 Ex i without cable plug
4 2 St. St.
H 144484 
14 NBR St. St.
12
and 1.4305 Brass, nickel
5 1 3 8.0 G¼ 1300 2 - 8 670 144485 
PUR plated
5/2 way servo-controlled solenoid
(Polyamide) Brass, nickel
valve Brass 147252 
plated
1)
Flow rate: QNn value air [l/min]: Measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar pressure difference
2)
Pressure values [bar]: Overpressure with respect to atmospheric pressure
S. 4/37
6518/6519

Type 6519 NAMUR Standard (with Tag connector acc. to DIN EN 175301-803 Form A, without cable plug)

Technical data
Orifice Type 6519 DN6 mm
Body material
Type 6519 Pilot and main valve Polyamide, reinforced glass-fibre
Threaded socket material Brass (stainless steel on request)
Seal material Type 6519 NBR and PUR
Medium Neutral medium, e.g. lubricated or non-lubricated
compressed air
Compressed air quality ISO 8573-1:2010, Class 7.4.4*
Medium temperature - 10 °C to + 50 °C
Ambient temperature - 25 °C to + 55 °C
Pneumatic connection
Type 6519 NA- Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
MUR Standard
Service port 2, 4 NAMUR Flange
Operating voltages 24 V DC
24/ 110/ 230 V/ 50 - 60 Hz
The valve bodies of Type 6519 NAMUR are identi- Voltage tolerance + 10 %
cal with the Ex m variants. The difference is in the Duty cycle 100 % continuous operation
coils, which are laid out and approved in different Electrical connection Tag connector acc. to DIN EN 175301-803 (previ-
ways. By changing the coil on the valve body, it is ously DIN 43650) Form A for cable plug Type 2508
possible to easily convert from Non-Ex operation to Type of protection IP65 with cable plug
Ex operation (or vice versa). The coils are designed Installation As required, preferably with actuator upright
to be push-over and can be locked in 4 × 90° * To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the
displaced positions and be positioned any where temperature of the medium.
in-between.
Power consumption Response times1)
Inrush Hold (hot coil)
Opening 20 [ms]
AC [VA] AC [VA/W] DC [W]
Closing 40 [ms]
11 6/2 2
1)
Measured at valve outlet at 6 bar and + 20 °C acc. to ISO 12238.
Opening: Pressure rise 0 to 90 %,
Closing: Pressure drop 100 to 10 %

Ordering chart with manual override (without manual override on request)


connection

Frequency

Article no.
Weight [g]

power [W]
Electrical
Threaded
and body

QNn value
sockets1)

Pressure

Voltage/
Material
function

material

nominal
range3)
Orifice
Circuit

[l/min]

[V/Hz]
[inch]

Luft2)
[mm]

[bar]
Seal

port

W 024/DC 131425 
4 2
14
NBR
12 and Stainless 024/50 - 60 131426 
6.0 G¼ 900 2 - 8 460 2
3 15 PUR steel 110/50 - 60 131427 
or
230/50 - 60 131428 
4 2 024/DC 131421 
14
W 12 NBR 024/50 - 60 131422 
5 1 3 Brass,
and 110/50 - 60 131423 
6.0 nickel G¼ 900 2 - 8 460 2
PUR
plated
5/2 or 3/2 way solenoid valve,
with removable disk and manual 230/50 - 60 131424 
override

1)
When the connecting sockets are made of stainless steel, then the mounting screws are also made of stainless steel
2)
Flow rate: QNn value air [l/min]: Measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar pressure difference
3)
Pressure values [bar]: ‌Overpressure with respect to atmospheric pressure

All valves can be operated in circuit function C as well as in circuit function H. By replacing the adapter
plate that comes with the valves, the change between the two circuit functions can be set up.

S. 5/37
6518/6519

Type 6519 NAMUR Ex m (with moulded cable) or Ex me (with junction box)


The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.
Technical data
Orifice DN6 mm
Body material
Pilot and main valve Polyamide, reinforced glass-fibre
Threaded socket material Brass (stainless steel on request)
Seal material NBR and PUR
Medium Neutral medium, e.g. lubricated or non-lubricated compressed air
Compressed air quality ISO 8573-1:2010, Class 7.4.4*
Medium temperature - 10 °C to + 50 °C
Ambient temperature - 25 °C to + 50 °C
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 NAMUR Flange
Type 6519 NAMUR Ex m
Operating voltages 24/ 110/ 230 V/UC
Voltage tolerance + 10 %
Type 6519 NAMUR Ex m NAMUR valve for process Duty cycle 100 % continuous operation
plants switches reliably, even when fully restricted. The Electrical connection 3 m cable, moulded
valve made out of premium polyamide can be operated junction box (without fuse)
either as a 5/2 or a 3/2 way version through different Type of protection IP65
mounting plates. The solenoid valve Type 6014 with a Approvals
coil approved for use in hazardous areas is connected Coil PTB 14 ATEX 2023 X / IECEx PTB 14.0049 X
as a pilot. The NAMUR flange interface allows easy as- II 2G Ex mb IIC T5 Gb
sembly on different pneumatic actuators on the spot. II 2D Ex mb IIIC T 100 °C Db
Junction box EPS16 ATEX 1046 X / IECEx EPS 16.0021 X
The valve bodies are identical with the Type 6519 II 2G EX eb mb IIC T5 Gb
II 2D EX mb tb IIIC T100 °C Db
NAMUR standard version. The difference between the
valves is in the coils, which are laid out and approved in Installation As required, preferably with actuator upright
different ways. By changing the coil on the valve body, * To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the
it is possible to easily convert from Non-Ex operation to temperature of the medium.
Ex operation (or vice versa). Coil versions with moulded Response times1)
cable are designed to be push-over and can be locked
Opening 20 [ms]
in 4 × 90° displaced positions and be positioned any
Closing 40 [ms]
where in-between.
1)
Measured at valve outlet at 6 bar and + 20 °C acc. to ISO 12238.
Opening: Pressure rise 0 to 90 %,
Closing: Pressure drop 100 to 10 %

Ordering chart with manual override (without manual override on request)


Threaded port
Seal material
Orifice [mm]

connection

Frequency

Article no.
Weight [g]

power [W]
Electrical
and body

QNn value
sockets1)

Pressure

Voltage/
Nominal
Material
function

range3)
Circuit

[l/min]

[V/Hz]
[inch]

Luft2)

[bar]

W 4 2 Version acc. to Ex m, with moulded 3 m-cable


14 024/UC 278231 
12
Stainless
3 15 G¼ 900 2 - 8 650 3 110/UC 278234 
steel
NBR 230/UC 278237 
6.0 and
or PUR 024/UC 278228 
Brass,
nickel G¼ 900 2 - 8 650 3 110/UC 278235 
plated
230/UC 278239 
Version acc. to Ex me, with junction box without fuse
W 024/UC
4 2 Stainless 289407 
14 G¼ 900 2 - 8 690 3
12
steel 230/UC 289415 
5 1 3 NBR
6.0 and 024/UC 289406 
Brass,
PUR 110/UC 289412 
5/2 or 3/2 way solenoid valve, nickel G¼ 900 2 - 8 690 3
with removable disk and manual plated
230/UC 289414 
override

1)
When the connecting sockets are made of stainless steel, then the mounting screws are also made of stainless steel x on request
2)
Flow rate: QNn value air [l/min]: Measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar pressure difference
3)
Pressure values [bar]: ‌Overpressure with respect to atmospheric pressure

All valves can be operated in circuit function C as well as in circuit function H. By replacing the adapter plate that comes with the valves, the change between the
two circuit functions can be set up.
S. 6/37
6518/6519

Type 6519 NAMUR Ex i (with Tag connector acc. to DIN EN 175301-803 Form A, without cable plug)
The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.
Technical data
Orifice DN6 mm
Body material
Pilot valve Stainless steel 1.4305 or brass
Main valve Polyamide, reinforced glass-fibre
Threaded socket material Brass (stainless steel on request)
Seal material FPM, NBR and PUR
Medium Neutral medium, e.g. lubricated or non-lubricated
compressed air
Compressed air quality ISO 8573-1:2010, Class 7.4.4*
Medium temperature - 10 °C to + 50 °C
Ambient temperature - 25 °C to + 55 °C
Pneumatic connection
Type 6519 NAMUR Ex i Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 NAMUR Flange
Duty cycle 100 % continuous operation
The Type 6519 NAMUR Ex i valve is used for the pneumatic
Electrical connection Tag connector acc. to DIN EN 175301-803 (previously
DIN 43650) Form A for cable plug Type 2508 (not in de-
control of double or single-acting actuators with a NAMUR
adapter plate flange. The circuit function can easily be livery, see accessories), check for correct polarity
changed using an adapter plate. In the 3/2 way function, Type of protection IP65 with cable plug
feedback of the exhaust air takes place in the spring area Installation As required, preferably with actuator upright
of the armature drive. The diaphragm-controlled valve seats * To
 prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than
work with very low friction, ensuring reliable switching of the the temperature of the medium.
valve even after long shutdown periods and at ambient tem- 1)
Measured at valve outlet at 6 bar and + 20 °C acc. to ISO 12238.
Response times1) [ms]
peratures below 0 °C. The valves work without a continuous Opening: Pressure rise 0 to 90 %
air consumption. Opening 75 Closing: Pressure drop 100 to 10 %
Closing 115
Note
The units may only be used in explosive atmospheres in the Electrical data
manner approved by the Federal Institute of Physics and Approvals PTB 01 ATEX 2101 / PTB IECEx 10.0019
Technology (PTB), i.e., the permissible maximum electrical II 2G Ex ia IIC T6 Gb
values must be complied with. Suitable barriers and isolat- II 2G Ex ia IIIC T80 °C Db
ing modules are available for this. Function values for
Switching function valve1) at + 20 °C at + 55 °C
Minimum switching current 29 mA 29 mA
Nominal resistance coil 310 Ω 360 Ω
Minimum terminal voltage 9.0 V 10.4 V
The valve is intended for operation on 24 V DC outputs via
Conformity specifications
Ui 35 V
the intermediate switching of a corresponding intrinsically- Ii 0.9 A
safe operating resource (isolating module or barrier). Pi 1.1 W
If required, request the “Recommended Barrier and Isolating 1)
With high resistance coil on request
Module” data sheet.

Ordering chart for valves without manual override (with manual override and high resistance coil on request)
without cable plug
range2) [bar]

Material air
connection

pilot valve

Article no.
Weight [g]

connector
Threaded
and body

QNn value

Pressure
function

material

material

control
Orifice
Circuit

[l/min]
[inch]

Body
Luft1)
[mm]

Seal

port

4 2
W 14 St. St. 144482 
12 St. St.
3 15
1.4305
NBR Brass, nickel
or 144483 
and plated
6.0 G¼ 900 2 - 8 670
PUR
4 2
W 14 (Polyamide)
12 Brass, nickel
Brass 147244 
5 1 3 plated
5/2 or 3/2 way solenoid valve,
with removable disk

1) Flow rate: QNn value air [l/min]: Measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar pressure difference
2) Pressure values [bar]: ‌Overpressure with respect to atmospheric pressure

All valves can be operated in circuit function C as well as in circuit function H. By replacing the adapter plate that comes with the valves, the change
between the two circuit functions can be set up. All valves have mounting plates and tag connectors acc. to DIN EN 175301-803 Form A
(previously DIN 43650) and are supplied without cable plug
S. 7/37
6518/6519

Pneumatic modules Type MP07


Single modules or pre-mounted blocks are available.

Example of a complete valve block

Connector module,
Pneumatic basic Pneumatic intermediate supply module: supply channel pushed
left
module, 3 valves through for additional pressure supply
or
Connector module, right: supply channel closed off, thereby several
operational pressures possible in a single block

Pneumatic
basic module,
2 valves
Connector module,
right

Supply ports
3(R)
1(P)

Covering plate for 3/2 5(S)


way valves (to cover up
unused ports)

Note when ordering complete valve blocks:


Please list the modules in the block assembly from right to left, as shown in the ordering example.
Valves with NAMUR Flange. Ex i coil or Ex versions with junction boxes are not suitable for block mounting.

Ordering example for Type 6518 with Type MP07


Article
Unit
No.

no.

1 Connector module right, G ½ 635331 


1 Pneumatic basic module, 2 valves 635319 
1 Pneumatic basic module, 3 valves 635343 
1 Connector module left, G ½ 635324 
5 Valves 132457 

Ordering chart for Type MP07 pneumatic modules


Version

Article
no.

Connector module right G ½ 635331 


Intermediate supply module 637505 
Pneumatic basic module, 2 valves universal (for 3/2-, 5/2- and 5/3 way) 635319 
Pneumatic basic module, 3 valves universal (for 3/2-, 5/2- and 5/3 way) 635343 
Connector module left G ½ 635324 
Covering plate for 5/2- and 5/3 way (to cover unused valve positions) 635335 
Covering plate for 3/2 way (to cover unused connections) 635337 

S. 8/37
6518/6519

Type MP07 pneumatic modules, continued

Dimensions for Type MP07 pneumatic modules [mm]


Manifold assembly either wall-mounted or standard mounting DIN rail 50022 or 50023

101,5
59 + (n x 33) 65

5/3, 5/3 - Impuls


55 5/2
42
35

ø 5,5
15

3 3

182
1 1
102,5
115

124,8
120

249
108

24
58

100
92

82
57,5
48

5 5

G 1/2
G 1/8 6
10

33 NPT 1/2
NPT 1/8 8
G 1/4 55
NPT 1/4

46
n x 33 52
87 + (n x 33) 90
110 + (n x 33)

n=no. of valves, maximum 12

Valve assembly on pneumatic modules Type MP07 using the supplied M4 screws

S. 9/37
6518/6519

18

Accessories

18
Cable plug 2508 acc. to DIN EN 175301-803 Form A
46 Fixing screw
The delivery of a cable plug includes the flat seal and the fixing screw. For other cable plug
versions acc. to DIN EN 175301-803 Form A (previously DIN 43650) with

27,5
18
integrated circuitry, see datasheet Type 2508.
Flat seal

18

1,5
Dimensions Type 2508 [mm] M3
28

18 46

18
27,5
18

1,5

M3
46 28
27,5

Ordering chart
18
1,5

M3
28 2508
Cable plug
Beschaltung Voltage Article no.
For standard version 6518/19
18

Fixing screw in steel (galvanised and chrome-plated)


without circuitry 0 - 250 V 008376 
with LED 12 - 24 V 008360 
with LED and varistor 12 - 24 V 008367 
with LED and varistor 200 - 240 V 008369 
For Ex i version 6519
Fixing screw in stainless steel 1.4404 and blue compression gland nut
without circuitry 0 - 250 V 438574 
for further versions see datasheet 2508

Cable plug Type 2513 acc. to DIN EN 175301-803, Form A


Meets the requirements of ATEX category 3 GD

BN

[in mm]
Article
length
Cable

[mm]

no.
BU 12000 260893 
5000 260892 
GNYE 3000 260891 
300 260890 

Ordering chart for further accessories

Accessories Features Article no.


Cap nut Cap nut in stainless steel for 649554 
additional protection of the exhaust air
channel from the penetration of damp
Blanking plug G ⅛" 780141 
G ¼" 780142 
G ½" 780144 
Silencer G ⅛" 005305 
G ¼" 005064 
G ½" 005062 
Labelling plate 64 pieces 635416 

Semi-delay fuse for 6519 NAMUR Ex m

Voltage [V] Max. current [mA] Article no.


24 V 315 mA 153733 
110 V 50 mA 153716 
230 V 32 mA 153715 
S. 10/37
6518/6519

Accessories (continued)

Ex-Cable glands
(polyamide version included in delivery / surcharge applied for brass nickel plated version
Ex Approvals

Certification
Description

Identifica-

Article no

Drawing
Photo

tion
TL 29 - 37 mm
Brass.
L 6 mm
nickel- PTB 04 ATEX 1112 X, II 2 G Ex e IIC Gb,
773278   D 20
plated, IECEx PTB 13.0027X II 2 D Ex tb IIIC Db IP68,
6 - 13 mm SW 24 mm
E 27 mm

TL 36 - 45 mm
L 10 mm
Polyamide, PTB 13 ATEX 1015 X, II 2 G Ex e IIC Gb,
773277  D 20
7 - 13 mm IECEx PTB 13.0034X II 2 D Ex tb IIIC Db IP68
SW 24 mm
E 28 mm

Special tool to turn the junction box (not included in delivery)

Article no.
Descrip-
Photo

tion

Set SC02-AC10
Special wrench
293488 
Service Manual

S. 11/37
6518/6519

Dimensions [mm]

Standard versions

Type 6518
3/2 way valve, circuit function C and D

32
SW 14 45

G1/8 20.5
11.2

G1/4 / NPT1/4
8 - 4.3 deep
G1/4 / NPT1/4
138.7

7.9 - 4.2 deep

4.3
69.6
4.3

13.5

12

28.5
25.5
25.5

8
3 43 24

3 - 3 tief
24 53

32

Type 6519
5/2 way valve, circuit function H

32
SW 14 45
G1/8 20.5
11.2

G1/4 / NPT1/4
G1/4 / NPT1/4

7.9 - 4.2 deep


176.8

4.3

28.5
8 - 4.3 deep
4.3

107.7
36
24

48
26.5
39.6

3 - 3 deep

3 43 24
24 53

32

* Mounting length with 2 magnetic coils 249 mm

S. 12/37
6518/6519

Dimensions [mm]

Standard versions

Type 6519
5/3 way valve, circuit function L and N

Standard version

32
SW 14 45
G1/8 20.5
11.2

G1/4 / NPT1/4
3 - 3 deep
G1/4 / NPT1/4

26 24

4.3

28.5
11 - 3 deep

43
36
250.2

112
24

70

48
4.5

26.5
50
44

32

5/2-Way- Pneumatic valve WWH-Impulse (WWZ)


5/3-Way- Pneumatic valve WWL and WWN

S. 13/37
6518/6519

Dimensions [mm]

Ex m/me versions

Type 6518
3/2 way valve, circuit function C and D

with moulded cable (3 m long) (Ex m)

Length acc. to D
A
ordering information C
SW 14
G1/8 B

6.2
10.9

mi

G1/4 / NPT1/4
n.
R2

8 - 4.3 deep
5
G1/4 / NPT1/4
138.7

7.9 - 4.2 deep

4.3
4.3

69.6
13.5

12

28.5
25 5
25.5

3 - 3 deep
8
3 43 24
24 53

32

Coil size A B C D E F
5 32 20.5 46 68.8 99.8 174.7
with junction box (Ex me) 6 40 23.5 52 74.8 102.8 177.7

A F
SW 14 E
68 G1/8 M20x1.5 B
SW 27
29.7

R84
radius
10.9

Turning
41.3
84.3
G1/4 / NPT1/4

8 - 4.3 deep
138.7

7.9 - 4.2 deep

4.3
69.6
4.3

13.5

12
25.5

25.5

3
24 43
32 53

S. 14/37
6518/6519

Dimensions [mm]

Ex m/me versions

Type 6519
5/2 way valve, circuit function H

with moulded cable (3 m long) (Ex m)

A length acc. to D
SW 14 ordering information C
G1/8 B

6.2
10.9

G1/4 / NPT1/4
mi
n.
G1/4 / NPT1/4

R2
5
7.9 - 4.2 deep
176.85

4.3

28.5
107.75
4.3
8 - 4.3 deep
36
24

48
26.5
39.6

3 - 3 deep
43 24
24 53
32

5/2 way valve, circuit function L and N

A Length acc. to D
SW14 ordering information C
G1/8 B
6.2
G1/4 / NPT 1/4 10.9

G1/4 / NPT 1/4

mi
3 - 3 deep

n.
R2
5
26 24
4.3
11 - 3 deep

28.5

43
250.2

112
36
70

48
24

4.5

26.5

50
44

32

S. 15/37
6518/6519

Dimensions [mm]

Ex i versions

Type 6518
3/2 way valve, circuit function C Ex i- Zulassung

40
SW 14 51
G1/8 23,5
11,2

G1/4 / NPT1/4
8 - 4,3 tief
145,7

G1/4 / NPT1/4

4,3
7,9 - 4,2 tief

69,6
4,3

13,5

12

28,5
25,5
25,5

8
3 43 24

3 - 3 tief
24 53

32

Type 6519
5/2 way valve, circuit function H
Ex i Approval
40
SW 14 51

G1/8 23.5
11.2

G1/4 / NPT1/4
G1/4 / NPT1/4

7.9 - 4.2 deep


183.8

4.3

28.5
8 - 4.3 deep
4.3

107.7
36
24

48
26.5
39.6

3 - 3 tief

3 43 24

24 53

32

S. 16/37
6518/6519

Dimensions [mm]
NAMUR Standard version

Type 6519
Standard version
3/2 way valve, circuit function C or 5/2 way valve, circuit function H

32
45
SW 14
20.5
G1/8
11.2

G1/4 / NPT1/4
176.8

5.3
107.7
48

24

51.6
51.6

32 3.95

37 32

53

S. 17/37
6518/6519

Dimensions [mm]

NAMUR Ex m/me version

Type 6519
3/2 way valve, circuit function C or 5/2 way valve, circuit function H

with moulded cable (3 m long) (Ex m)

A D
Length acc. to
SW 14 C ordering information
G1/8 B

6.2
10.9

G1/4 / NPT1/4

25
.R
min
176.8

5.3
107.7
48

24

51.6
51.6

32 3.95
37 32
53

Coil size A B C D E F
5 32 20.5 46 68.8 99.8 174.7
6 40 23.5 52 74.8 102.8 177.7
with junction box (Ex me)

F
E
20.5 M20x1.5
29.7

R84
Turnin
g radiu
s
41.3
G1/4 / NPT1/4

84.3
176.8

5.3
107.7
48

24

51.6
51.6

SW27
68 32 3.95
37 32
53

S. 18/37
6518/6519

Dimensions [mm]

NAMUR Ex i version

Type 6519
3/2 way valve, circuit function C or 5/2 way valve, circuit function H

Ex i Approval

40

SW 14 51

G1/8 23.5
11.2

G1/4 / NPT1/4

Aluminium
183.6

5.3
107.7
48

24

51.6
51.6

32 3.95

37 32

53

S. 19/37
6519
for extended
temperature range
Type 6519 for extended standard temperature range

Technical data Aluminium Stainless steel


Orifice 9 9
Body material
Pilot valve Stainless steel Stainless steel
Main valve Aluminium ematal coated Stainless steel 1.4571
Threaded socket material in aluminium in stainless steel
Seal material FPM, NBR PU, NBR, FPM
Medium Neutral medium, eg lubricated or non-lubricated compressed air
Compressed air quality ISO 8573-1:2010, Class 7.2.4*
Medium temperature - 30 °C to + 80 °C - 30 °C to + 80 °C
Ambient temperature - 40 °C to + 80 °C - 30 °C to + 80 °C
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 Thread G ¼ (on request NPT ¼)
Operating voltages 24 V DC
24/ 110/ 230 V/ 50 - 60 Hz
Voltage tolerance + 10 %
Electr. power consumption 2W
Duty cycle 100 % continuous operation
Electrical connection Tag connector acc. to DIN EN 175301-803 (previously DIN
43650) Form A for cable plug Type 2508
Type of protection IP65 with cable plug
Installation As required, preferably with actuator upright

Response times 5/2 5/2-bi 5/3 3/2 5/2 5/2-bi


Opening [ms] 16 18 16 13 12 14
Closing [ms] 27 18 22 47 74 14
* To
 prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the tem-
perature of the medium.

Ordering chart for valves in aluminium with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.
connection

Frequency

Article no.
Weight [g]

power [W]
QNn-value
Threaded
and body

Pressure

Voltage/
Nominal
function

material
Orifice
Circuit

[l/min]

[V/Hz]
range
[inch]
[mm]

[bar]
Seal

port

air

5/2 WWH 9.0 FPM, NBR G ¼" 1800 2.5 - 10 680 2 024/DC 231386 
4 2 024/50 - 60 231387 
14
12 110/50 - 60 231388 
5 1 3 230/50 - 60 231389 
5/2-bistable WWZ 9.0 FPM, NBR G ¼" 2100 2.5 - 10 990 2 024/DC 231390 
4 2 024/50 - 60 231391 
14 12 110/50 - 60 231392 
5 1 3 230/50 - 60 231393 
5/3 WWL 9.0 FPM, NBR G ¼" 1500 2.5 - 10 1060 2 024/DC 231394 
4 2 024/50 - 60 231395 
14 12
110/50 - 60 231396 
5 13
230/50 - 60 231397 
5/3 WWN 9.0 FPM, NBR G ¼" 1500 2.5 - 10 1060 2 024/DC 231399 
4 2
14 12 024/50 - 60 231400 
110/50 - 60 231401 
5 13
230/50 - 60 231402 

S. 20/37
6519
for extended
temperature range
Ordering chart for valves in stainless steel with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.

connection

Frequency

Article no.
Weight [g]

power [W]
QNn-value
Threaded

Pressure

Voltage/
Nominal
function

material
Orifice
Circuit

[l/min]

[V/Hz]
range
[inch]
[mm]

body

[bar]
Seal

port

air
5/2 WWH 8.0 PU, NBR G ¼" 1980 3 - 10 1370 2 024/DC 231403 
4 2 024/50 - 60 231404 
14
12
110/50 - 60 231405 
5 1 3 230/50 - 60 231406 
5/2-bistable WWZ 8.0 PU, NBR G ¼" 1920 3 - 10 1680 2 024/DC 231407 
4 2 024/50 - 60 231408 
14 12
110/50 - 60 231409 
5 1 3
230/50 - 60 231410 
5/3 WWL 8.0 PU, NBR G ¼" 1770 3 - 10 1680 2 024/DC 231411 
4 2 024/50 - 60 231412 
14 12
110/50 - 60 231413 
5 13 230/50 - 60 231414 
5/3 WWN 8.0 PU, NBR G ¼" 1770 3 - 10 1680 2 024/DC 231415 
4 2
14 12
024/50 - 60 231416 
110/50 - 60 231417 
5 13
230/50 - 60 231418 

S. 21/37
6519
for extended
temperature range
Type 6519 for extended Ex m temperature range
The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.

Technical data Aluminium Stainless steel


Orifice 9 9
Body material
Pilot valve Stainless steel Stainless steel
Main valve Aluminium ematal coated Stainless steel 1.4571
Threaded socket material in aluminium in stainless steel
Seal material FPM, NBR PU, NBR, FPM
Medium Neutral medium, e.g. lubricated or non-lubricated com-
pressed air
Compressed air quality ISO 8573-1:2010, Class 7.2.4*
Medium temperature - 30 °C to + 80 °C - 30 °C to + 80 °C
Ambient temperature - 40 °C to + 60 °C - 30 °C to + 60 °C
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 Thread G ¼ (on request NPT ¼)
Operating voltages 24 V DC
24/ 110/ 230 V/ 50 - 60 Hz
Voltage tolerance + 10 %
Electr. power consumption 3W
Duty cycle 100 % continuous operation
Electrical connection 3 m cable, moulded
junction box (without fuse) on request
Type of protection IP65
Approvals
Coil PTB 14 ATEX 2023 X / IECEx PTB 14.0049 X
II 2G Ex mb IIC T5 Gb
II 2D Ex mb IIIC T 100 °C Db
Junction box EPS16 ATEX 1046 X / IECEx EPS 16.0021 X
II 2G EX eb mb IIC T5 Gb
II 2D EX mb tb IIIC T100 °C Db
Installation As required, preferably with actuator upright

Response times 5/2 5/2-bi 5/3 3/2 5/2 5/2-bi


Opening [ms] 16 18 16 13 12 14
Closing [ms] 27 18 22 47 74 14
* To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the tem-
perature of the medium.

Ordering chart for valves in aluminium with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.
connection
Seal mate-

Frequency

Article no.
Weight [g]

power [W]
QNn-value
Threaded

Pressure
rial body

Voltage/
Nominal
function

Orifice
Circuit

[l/min]

[V/Hz]
range
[inch]
[mm]

[bar]
port

air

Type 6519 Ex m - with moulded cable, 3 m long1)


5/2 WWH 9.0 FPM, NBR G ¼" 1800 2.5 - 10 680 3 024/UC 278217 
4 2
14 110/UC x
12
5 1 3 230/UC 278220 
5/2-bistable WWZ 9.0 FPM, NBR G ¼" 2100 2.5 - 10 990 3 024/UC 278247 
4 2
14 12 110/UC x

5 1 3
230/UC x
5/3 WWL 9.0 FPM, NBR G ¼" 1500 2.5 - 10 1060 3 024/UC x
4 2
14 12 110/UC x

5 13 230/UC x
5/3 WWN 9.0 FPM, NBR G ¼" 1500 2.5 - 10 1060 3 024/UC 278223  
4 2
14 12 110/UC x

5 13 230/UC x
1)
Junction box version on request x = on request

S. 22/37
6519
for extended
temperature range
Ordering chart for valves in stainless steel with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.

connection

Frequency

Article no.
Weight [g]

power [W]
QNn-value
Threaded

Pressure

Voltage/
Nominal
function

material
Orifice
Circuit

[l/min]

[V/Hz]
range
[inch]
[mm]

body

[bar]
Seal

port

air
Type 6519 Ex m - with moulded cable, 3 m long1)
5/2 WWH 4 2 8.0 PU, NBR G ¼" 1980 3 - 10 1370 3 024/UC x
14
12
110/UC x
5 1 3
230/UC 278219 
5/2-bistable WWZ 8.0 PU, NBR G ¼" 1920 3 - 10 1680 3 024/UC 278246 
4 2
14 12 110/UC x

5 1 3 230/UC x
5/3 WWL 8.0 PU, NBR G ¼" 1770 3 - 10 1680 3 024/UC x
4 2
14 12 110/UC x

5 13 230/UC x
5/3 WWN 8.0 PU, NBR G ¼" 1770 3 - 10 1680 3 024/UC x
4 2
14 12 110/UC x

5 13 230/UC x
1)
Junction box version on request x = on request

S. 23/37
6519
for extended
temperature range
Type 6519 for extended Ex i temperature range
The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.

Technical data Aluminium Stainless steel


Orifice Type 6519 9 9
Body material
Pilot valve Stainless steel Stainless steel
Main valve Aluminium ematal coated Stainless steel 1.4571
Threaded socket material in aluminium in stainless steel
Seal material FPM, NBR PU, NBR, FPM
Medium Neutral medium, e.g. lubricated or non-lubricated compressed air
Compressed air quality ISO 8573-1:2010, Class 7.2.4*
Medium temperature - 30 °C to + 80 °C - 30 °C to + 80 °C
Ambient temperature - 40 °C to + 75 °C - 30 °C to + 75 °C
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 Thread G ¼ (on request NPT ¼)
Voltage tolerance + 10 %
Electrical connection Tag connector acc. to DIN EN 175301-803 (previously DIN
43650) Form A for cable plug Type 2508 (not in delivery, see ac-
cessories), check for correct polarity
Type of protection IP65 with cable plug
Installation As required, preferably with actuator upright

Response times 5/2 5/2-bi 5/3 3/2 5/2 5/2-bi


Opening [ms] 16 18 16 13 12 14
Closing [ms] 27 18 22 47 74 14
* To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the tem-
perature of the medium.

Electrical data - coil AC10 Ex i


Approvals PTB 01 ATEX 2101 / PTB IECEx 10.0019
II 2G Ex ia IIC T6 Gb
II 2G Ex ia IIIC T80 °C Db
Function values for
Switching function valve1) at + 20 °C at + 55 °C
Minimum switching current 29 mA 29 mA
Nominal resistance coil 310 Ω 360 Ω
Minimum terminal voltage 9.0 V 10.4 V
Conformity specifications
Ui 35 V
Ii 0.9 A
Pi 1.1 W
1)
With high resistance coil on request

Note

+ ≥ lmin
+

SPS 24V DC barrier ≥ Umin

These units may only be used in explosive atmospheres in the manner approved by the Federal Institute of Physics and Technology (PTB), i.e.,
the permissible maximum electrical values must be complied with. Suitable barriers and isolating modules are available for this.
The valve is intended for operation on 24 V DC outputs via the intermediate switching of a corresponding intrinsically-safe operating resource
(isolating module or barrier).

S. 24/37
6519
for extended
temperature range
Ordering chart for valves in aluminium with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.

Threaded port
Seal material

current [mA]
Orifice [mm]

connection

voltage [V]
resistance

Article no.
coil [Ohm]
Weight [g]
air [l/min]

switching
QNn-value

Minimum

Minimum
Pressure

Nominal

terminal
function
Circuit

range
[inch]
body

[bar]
5/2 WWH 9.0 FPM, NBR G ¼" 1800 2.5 - 10 825 29 310 9 231452 
4 2
14
12 23 481 11 231453 
5 1 3

5/2-bistable WWZ 9.0 FPM, NBR G ¼" 2100 2.5 - 10 1280 29 310 9 231454 
4 2
14 12 23 481 11 231455 
5 1 3
5/3 WWL 9.0 FPM, NBR G ¼" 1500 2.5 - 10 1350 29 310 9 231456 
4 2
14 12 23 481 11 231457 
5 13
5/3 WWN 9.0 FPM, NBR G ¼" 1500 2.5 - 10 1350 29 310 9 231458 
4 2
14 12 23 481 11 231459 
5 13

Ordering chart for valves in stainless steel with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.
Seal material

current [mA]
Orifice [mm]

connection

range [bar]

voltage [V]
resistance

Article no.
coil [Ohm]
Weight [g]
air [l/min]

switching
QNn-value
Threaded

Minimum

Minimum
Pressure

Nominal

terminal
function
Circuit

[inch]
body

port

5/2 WWH 8.0 PU, NBR G ¼" 1980 3 - 10 1520 29 310 9 231460 
4 2
14
12 23 481 11 231461 
5 1 3

5/2-bistable WWZ 8.0 PU, NBR G ¼" 1920 3 - 10 1970 29 310 9 231463 
4 2
14 12
23 481 11 231464 
5 1 3

5/3 WWL 8.0 PU, NBR G ¼" 1770 3 - 10 1970 29 310 9 231465 
4 2
14 12
23 481 11 231466 
5 13

5/3 WWN 8.0 PU, NBR G ¼" 1770 3 - 10 1970 29 310 9 231467 
4 2
14 12
23 481 11 231468 
5 13

S. 25/37
6519
for extended
temperature range
Type 6519 for extended NAMUR standard temperature range

Technical data Aluminium Stainless steel


Orifice 6 6
Body material
Pilot valve Stainless steel Stainless steel
Main valve Aluminium ematal coated Stainless steel 1.4571
Threaded socket material in aluminium in stainless steel
Seal material FPM, NBR PU, NBR, FPM
Medium Neutral medium, e.g. lubricated or non-lubricated com-
pressed air
Compressed air quality ISO 8573-1:2010, Class 7.2.4*
Medium temperature - 30 °C to + 80 °C - 30 °C to + 80 °C
Ambient temperature - 40 °C to + 80 °C - 30 °C to + 80 °C
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 NAMUR Flange
Operating voltages 24 V DC
24/ 110/ 230 V/ 50 - 60 Hz
Voltage tolerance + 10 %
Electr. power consumption 2W
Duty cycle 100 % continuous operation
Electrical connection Tag connector acc. to DIN EN 175301-803 (previously DIN
43650) Form A for cable plug Type 2508
Type of protection IP65 with cable plug
Installation As required, preferably with actuator upright

Response times 5/2 5/2-bi 5/3 3/2 5/2 5/2-bi


Opening [ms] 16 18 16 13 12 14
Closing [ms] 27 18 22 47 74 14
* To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the tem-
perature of the medium.

Ordering chart for valves in aluminium with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.
connection

Frequency

Article no.
Weight [g]

power [W]
QNn-value
Threaded

Pressure

Voltage/
Nominal
function

material
Orifice
Circuit

[l/min]

[V/Hz]
range
[inch]
[mm]

body

[bar]
Seal

port

air

3/2 WWC 6.0 FPM, NBR G ¼" 780 3 - 10 540 2 024/DC 231469 
2(A)
024/50 - 60 231470 
12
110/50 - 60 231471 
1(P) 3(R)
230/50 - 60 231472 
5/2 WWH 4 2 6.0 FPM, NBR G ¼" 800 3 - 10 540 2 024/DC 231473 
14 024/50 - 60
12
231474 
5 1 3 110/50 - 60 231475 
230/50 - 60 231476 
5/2-bistable WWZ 6.0 FPM, NBR G ¼" 900 3 - 10 540 2 024/DC 231477 
4 2
14 12 024/50 - 60 231478 
110/50 - 60 231479 
5 1 3
230/50 - 60 231480 

S. 26/37
6519
for extended
temperature range
Ordering chart for valves in stainless steel with manual override (without manual override on request)

All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.

connection

Frequency

Article no.
Weight [g]

power [W]
air [l/min]
QNn-value
Threaded

Pressure

Voltage/
Nominal
function

material
Orifice
Circuit

[V/Hz]
range
[inch]
[mm]

body

[bar]
Seal

port
3/2 WWC 6.0 PU, NBR G ¼" 1280 3 - 10 540 2 024/DC 231481 
2(A)
12 024/50 - 60 231482 
1(P) 3(R)
110/50 - 60 231483 
230/50 - 60 231484 
5/2 WWH 6.0 PU, NBR G ¼" 1060 3 - 10 540 2 024/DC 231485 
4 2
14 024/50 - 60 231486 
12
110/50 - 60 231487 
5 1 3
230/50 - 60 231488 
5/2-bistable WWZ 6.0 PU, NBR G ¼" 1050 3 - 10 540 2 024/DC 231489 
4 2 024/50 - 60 231490 
14 12
110/50 - 60 231491 
5 1 3 230/50 - 60 231492 

S. 27/37
6519
for extended
temperature range
Type 6519 for extended NAMUR Ex m temperature range
The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.

Technical data Aluminium Stainless steel


Orifice 6 6
Body material
Pilot valve Stainless steel Stainless steel
Main valve Aluminium ematal coated Stainless steel 1.4571
Threaded socket material in aluminium in stainless steel
Seal material FPM, NBR PU, NBR, FPM
Medium Neutral medium, e.g. lubricated or non-lubricated compressed air
Compressed air quality ISO 8573-1:2010, Class 7.2.4*
Medium temperature - 30 °C to + 80 °C - 30 °C to + 80 °C
Ambient temperature - 40 °C to + 60 °C - 30 °C to + 60 °C
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 NAMUR Flange
Operating voltages 24 V DC
24/ 110/ 230 V/ 50 - 60 Hz
Voltage tolerance + 10 %
Electr. power consumption 3W
Duty cycle 100 % continuous operation
Electrical connection 3 m cable, moulded
junction box (without fuse) on request
Type of protection IP65
Approvals
Coil PTB 14 ATEX 2023 X / IECEx PTB 14.0049 X
II 2G Ex mb IIC T5 Gb
II 2D Ex mb IIIC T 100 °C Db
Junction box EPS16 ATEX 1046 X / IECEx EPS 16.0021 X
II 2G EX eb mb IIC T5 Gb
II 2D EX mb tb IIIC T100 °C Db
Installation As required, preferably with actuator upright

Response times 5/2 5/2-bi 5/3 3/2 5/2 5/2-bi


Opening [ms] 16 18 16 13 12 14
Closing [ms] 27 18 22 47 74 14
* To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the tem-
perature of the medium.

Ordering chart for valves in aluminium with manual override (without manual override on request)
All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.
connection

range [bar]

Frequency

Article no.
Weight [g]

power [W]
air [l/min]
QNn-value
Threaded

Pressure

Voltage/
Nominal
function

material
Orifice
Circuit

[V/Hz]
[inch]
[mm]

body
Seal

port

Type 6519 Ex m - with moulded cable, 3 m long1)


3/2 WWC 6.0 FPM, NBR G ¼" 780 3 - 10 540 3 024/UC x
2(A)
12 110/UC x
1(P) 3(R) 230/UC x
5/2 WWH 6.0 FPM, NBR G ¼" 800 3 - 10 540 3 024/UC 278207  
4 2
14 110/UC x
12
5 1 3 230/UC x
5/2-bistable WWZ 6.0 FPM, NBR G ¼" 900 3 - 10 540 3 024/UC 278242 
4 2
14 12 110/UC x

5 1 3 230/UC x
1)
Junction box version on request x = on request

S. 28/37
6519
for extended
temperature range
Ordering chart for valves in stainless steel with manual override (without manual override on request)
All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.

connection

Frequency

Article no.
Weight [g]

power [W]
QNn-value
Threaded

Pressure

Voltage/
Nominal
function

material
Orifice
Circuit

[l/min]

[V/Hz]
range
[inch]
[mm]

body

[bar]
Seal

port

air
Type 6519 Ex m - with moulded cable, 3 m long1)
3/2 WWC 6.0 PU, NBR G ¼" 1280 3 - 10 960 3 024/UC x
2(A)
12 110/UC x
1(P) 3(R) 230/UC x
5/2 WWH 4 2
6.0 PU, NBR G ¼" 1060 3 - 10 960 3 024/UC x
14 110/UC x
12
5 1 3 230/UC x
5/2-bistable WWZ 6.0 PU, NBR G ¼" 1050 3 - 10 1260 3 024/UC x
4 2
14 12
110/UC x

5 1 3
230/UC x
1)
Junction box version on request x = on request

S. 29/37
6519
for extended
temperature range
Type 6519 for extended NAMUR Ex i temperature range
The maximum fluid temperature may never exceed the permissible temperature class (T4 135 °C, T5 100 °C, T6 85 °C) minus 5K.

Technical data Aluminium Stainless steel


Orifice Type 6519 6 6
Body material
Pilot valve Stainless steel Stainless steel
Main valve Aluminium ematal coated Stainless steel 1.4571
Threaded socket material in aluminium in stainless steel
Seal material FPM, NBR PU, NBR, FPM
Medium Neutral medium, e.g. lubricated or non-lubricated compressed air
Compressed air quality ISO 8573-1:2010, Class 7.2.4*
Medium temperature - 30 °C to + 80 °C - 30 °C to + 80 °C
Ambient temperature - 40 °C to + 75 °C - 30 °C to + 75 °C
Pneumatic connection
Supply port connection 1, 3, 5 Thread G ¼, (on request NPT ¼)
Service port 2, 4 NAMUR Flange
Voltage tolerance + 10 %
Electrical connection Tag connector acc. to DIN EN 175301-803 (previously DIN
43650) Form A for cable plug Type 2508 (not in delivery,
see accessories), check for correct polarity
Type of protection IP65 with cable plug
Installation As required, preferably with actuator upright

Response times 5/2 5/2-bi 5/3 3/2 5/2 5/2-bi


Opening [ms] 16 18 16 13 12 14
Closing [ms] 27 18 22 47 74 14
* To prevent freezing of the expanded compressed air, the pressure dew point must be at least 10 K lower than the tem-
perature of the medium.

Electrical data - coil AC10 Ex i


Approvals PTB 01 ATEX 2101 / PTB IECEx 10.0019
II 2G Ex ia IIC T6 Gb
II 2G Ex ia IIIC T80 °C Db
Function values for at + 20 °C at + 55 °C
Switching function valve*
Minimum switching current 29 mA 29 mA
Nominal resistance coil 310 Ohm 360 Ohm
Minimum terminal voltage 9.0 V 10.4 V
Conformity specifications
Ui 35 V
li 0.9 A
Pi 1.1 W

Note
+ ≥ lmin
+

SPS 24V DC barrier ≥ Umin

These units may only be used in explosive atmospheres in the manner approved by the Federal Institute of Physics and Technology (PTB), i.e.,
the p
­ ermissible maximum electrical values must be complied with. Suitable barriers and isolating modules are available for this.
The valve is intended for operation on 24 V DC outputs via the intermediate switching of a corresponding intrinsically-safe operating resource (isolating
module or barrier).

S. 30/37
6519
for extended
temperature range
Ordering chart for valves in aluminium with manual override (without manual override on request)
All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.

QNn-value air

current [mA]
Orifice [mm]

connection

range [bar]

resistance

Article no.
coil [Ohm]
Weight [g]

voltage[V]
switching
Threaded

Minimum

Minimum
Pressure

Nominal

terminal
function

material
Circuit

[l/min]
[inch]
body
Seal

port
3/2 WWC 6.0 FPM, NBR G ¼" 780 3 - 10 690 29 310 9 231520 
2(A)
12
23 481 11 231521 
1(P) 3(R)

5/2 WWH 6.0 FPM, NBR G ¼" 800 3 - 10 690 29 310 9 231522 
4 2
14
12 23 481 11 231523 
5 1 3

5/2 bistable WWZ 6.0 FPM, NBR G ¼" 900 3 - 10 1140 29 310 9 231524 
4 2
14 12
23 481 11 231525 
5 1 3

Ordering chart for valves in stainless steel with manual override (without manual override on request)
All products come with a standard stainless steel cap nut. This cap nut protects the exhaust channel from penetrating humidity.
QNn-value air

current [mA]
Seal materi-
Orifice [mm]

connection

resistance

Article no.
coil [Ohm]
Weight [g]

voltage[V]
switching
Threaded

Minimum

Minimum
Pressure

Nominal

terminal
function

al body
Circuit

[l/min]

range
[inch]

[bar]
port

3/2 WWC 6.0 PU, NBR G ¼" 1280 3 - 10 1100 29 310 9 231526 
2(A)
12
23 481 11 231527 
1(P) 3(R)

5/2 WWH 6.0 PU, NBR G ¼" 1060 3 - 10 1100 29 310 9 231528 
4 2
14
12
5 1 3 23 481 11 231529 

5/2 bistable WWZ 6.0 PU, NBR G ¼" 1050 3 - 10 1550 29 310 9 231530 
4 2
14 12

5 1 3 23 481 11 231531 

S. 31/37
6519
for extended
temperature range 18

Accessories

18
Cable plug 2508 acc. to DIN EN 175301-803 Form A
Fixing screw
Included in delivery is a connector with flat seal and fixing screw.46
For other cable plug v­ ersions acc. to DIN EN 175301-803 Form A (previously DIN 43650)

27,5
18
with integrated circuitry, see datasheet Type 2508.
Flat seal

18

1,5
Dimensions Type 2508 [mm] M3
28

18 46

18
27,5
18

1,5

M3
46 28
27,5

18
1,5

M3
Ordering
28 chart for cable plug 2508

Circuit Voltage Article no.


18

For standard version 6519 fixing screw in steel


(galvanised and chrome-plated)
without circuitry 0 - 250 V 008376 
with LED 12 - 24 V 008360 
with LED and varistor 12 - 24 V 008367 
with LED and varistor 200 - 240 V 008369 
For Ex i version 6519
Fixing screw in stainless steel 1.4404 and blue compression gland nut
without circuitry 0 - 250 V 438574 
for further versions see datasheet 2508

Cable plug Type 2513 acc. to DIN EN 175301-803, Form A


Meets the requirements of ATEX category 3 GD

BN

[in mm]
Article
length
Cable

[mm]

no.
BU 12000 260893 
5000 260892 
GNYE 3000 260891 
300 260890 

Ordering chart for further accessories

Accessories Features Article no.


Cap nut Cap nut in stainless steel for additional 649554 
protection of the exhaust channel from
penetrating humidity,

Blanking plug G¼ 780142 


Silencer G¼ 005064 
Labelling plate 64 pieces 635416 

Semi-delay fuse for 6519 NAMUR Ex m

Voltage [V] Max. current [mA] Article no.


24 V 315 mA 153733 
110 V 50 mA 153716 
230 V 32 mA 153715 
S. 32/37
6519
for extended
temperature range
Accessories (continued)

Ex-Cable glands
(polyamide version included in delivery / surcharge applied for brass nickel plated version
Ex Approvals

Certification
Description

Identifica-

Article no

Drawing
Photo

tion
TL 29 - 37 mm
Brass.
L 6 mm
nickel- PTB 04 ATEX 1112 X, II 2 G Ex e IIC Gb,
773278   D 20
plated, IECEx PTB 13.0027X II 2 D Ex tb IIIC Db IP68,
6 - 13 mm SW 24 mm
E 27 mm

TL 36 - 45 mm
L 10 mm
Polyamide, PTB 13 ATEX 1015 X, II 2 G Ex e IIC Gb,
773277  D 20
7 - 13 mm IECEx PTB 13.0034X II 2 D Ex tb IIIC Db IP68
SW 24 mm
E 28 mm

Special tool to turn the junction box (not included in delivery)

Article no.
Descrip-
Photo

tion

Set SC02-AC10
Special wrench
293488 
Service Manual

S. 33/37
6519
for extended
temperature range
Dimensions [mm]
WWH

E
Threaded port version D
12
WWH

G1/4

H
5.5

48
B
24
24

66
4.3

A
A
24 32 G1/4

30 50

WWH - Impulse. WWL. WWN

E
Threaded port version D
12
WWH – Impulse, WWL,
WWN

G1/4
G1/4

5.5
66

B
H

48
24
24
H

4.3
5.5

A
48
B

A
A

G1/4

24 32
30 50

Version Variants A B D E H
Standard, Ex m Ex i Standard, Ex m Ex i Standard, Ex m Ex i
WWH Stainless 53.5 107 35 40.7 45 51 177.8 186.6
steel
WWH Aluminium 43.5 97 35 40.7 45 51 167.8 176.6
WWH – Impulse, WWL, WWN Stainless 53.5 107 35 40.7 45 51 248.6 266.2
steel
WWH – Impulse, WWL, WWN Aluminium 53.5 107 35 40.7 45 51 148.6 266.2

S. 34/37
6519
for extended
temperature range
Dimensions [mm]

WWC
NAMUR version
WWC E
D
12

WWC

D E
12 D

G1/4

44
24

HB
2

A
40

C
G1/4

44
24

B
25 25
32
44.35 40
A

40

C
25 32
WWH
44.35 E 40
D
12
NAMUR version Variant: stainless Variant: aluminium
WWH WWH steel
D E
12

44.35
G1/4

G1/4
H

G1/4

G1/4
44

44
H
24

C
C
44

44
A
24

12.5
C
C

25 32 10
A

44.35 40 14.5
12.5
25 32 10
44.35 40 14.5

Version Variants A B C D E H
Standard, Ex m Ex i Standard, Ex m Ex i Standard, Ex m Ex i
WWC Stainless 35 94 25 35 40.7 45 51 165 173.8
steel
WWC Aluminium 25 84 15 35 40.7 45 51 155 163.8
WWH Stainless 35 94 47 35 40.7 45 51 165 173.8
steel
WWH Aluminium 25 84 37 35 40.7 45 51 155 163.8
WWH – Impulse, WWL, WWN Stainless 35 94 47 35 40.7 45 51 236 253.6
steel
WWH – Impulse, WWL, WWN Aluminium 35 94 47 35 40.7 45 51 236 253.6

S. 35/37
6519
for extended
temperature range
Dimensions [mm]
WWH - Impulse. WWL. WWN

NAMUR version Variant: stainless Variant: aluminium


WWH – Impulse, D E steel
WWL, WWN 12
H

G1/4
G1/4
G1/4

10 12.5
44
B

H
25

44

44
24

B
40

C
C
32
C

14.5
A

64.8

44.35
G1/4

G1/4

Version Variants A B C D E H
Standard, Ex m Ex i Standard, Ex m Ex i Standard, Ex m Ex i
WWC Stainless 35 94 25 35 40.7 45 51 165 173.8
steel
44

44

WWC Aluminium 25 84 15 35 40.7 45 51 155 163.8


WWH Stainless 35 94 47 35 40.7 45 51 165 173.8
C
C

steel
WWH Aluminium 25 84 37 35 40.7 45 51 155 163.8
12.5
WWH
10
– Impulse, WWL, WWN Stainless 35 94 47 35 40.7 45 51 236 253.6
steel
14.5
WWH – Impulse, WWL, WWN Aluminium 35 94 47 35 40.7 45 51 236 253.6

S. 36/37
6519
for extended
temperature range
Dimensions - Atex Approvals [mm]

Cable coil

D
Length acc. to
ordering information C

B A
6.2

m
in
R2
5

Junction box

68 F
27
E

M20x1.5 B

29.7
R84
dius
Turn ing ra
84.3

A 41.3

Coil size A B C D E F
5 32 20.5 46 68.8 99.8 174.7
6 40 23.5 52 74.8 102.8 177.7

To find your nearest Bürkert facility, click on the orange box www.burkert.com

In case of special application conditions, We reserve the right to make technical changes without notice.
please consult for advice. © Christian Bürkert GmbH & Co. KG 1801/15_EU-en_00891764

S. 37/37

You might also like