Guaranteed Technical Particulars of Circuit Breaker Ref.

No : ESD/GTP/Bkr

Project : 513 DAK BLA RESERVOIR REDVCING Page No : 1 of 7


B Fouress (P) Limited
FLOOD & COMBINE HPP

EQUIPMENT: GUARANTEED TECHNICAL PARTICULARS, OUT DOOR, PORCELAIN CLAD


SF6 CIRCUIT BREAKER
Sl no Description To be filled in By supplier

1. Type of circuit breaker SF6 Live tank


2. Manufacturer Type and designation LTB145D1/B/FSA1
3. Applicable standards IEC62271-100
4. Class Outdoor
5. Designed Ambient Temperature. 40degC
6. Rated Normal current
a. Under normal condition @ 40 O C 1250A
b. Under site condition @ 50 O C 1250A
7. Highest System voltage 145kV
8. Rated Normal Voltage 145kV
9. Rated frequency 50Hz
10. No of poles 3
11. No of Brakes per pole. 1
12. Rated operating duty. O-0.3sec-CO-3min-CO
13. First pole to clear factor. 1.5
21 Short time circuit breaking current rating
a. One second 31.5kA
b. Three second 31.5kA
14. Rated short circuit breaking current
a. Symmetrical component at rated voltage 40kA
b. % of DC component 36%
c. Asymmetrical Breaking current at rated voltage 44.88 kA
15. Maximum breaking capacity under kilometric faults and rated TRV As per IEC62271-100
characteristics.
16. Maximum breaking current under phase opposition conditions 10kA
17. Maximum single capacitor bank breaking current 400A
18. Over Voltage factor while switching off above currents <2 p.u.
19. Rated small inductive breaking current Not applicable as per IEC
20. Over voltage due to above ( Small inductive breaking current) Not applicable as per IEC
21. Rated Short circuit Making current 80kAp
Guaranteed Technical Particulars of Circuit Breaker Ref. No : ESD/GTP/Bkr

Project : 513 DAK BLA RESERVOIR REDVCING Page No : 2 of 7


B Fouress (P) Limited
FLOOD & COMBINE HPP

Sl no Description To be filled in By supplier

22. Rated Making capacity


a. At Higher rated voltage 80kAp
b. At Rated Voltage 80kAp

c. At lower rated voltage 80kAp

23. Maximum Cable charging current 160A


24. Catching current As per IEC62271-100
25. Dynamic Current Rating As per IEC62271-100
26. Rated out of phase breaking current. 10kA
27. Maximum over voltage on switching transformer on no-load and <2 p.u.
corresponding charging current
28. Data for Restrike Voltage
a. TRV Peak in kV 249kVp
b. Amplitude factor 1.4
c. Phase factor 1.5
d. Rate of rise of Restrike voltage 2kV/µs
29. Dielectric Withstand of complete breaker 145kV/275kVrms/650kVp
30. Insulation Level.
i. Rated lightning Impulse withstand voltage ( 1.2 / 50 Micro second )
a. Between live terminals and ground 650kVp
b. Between Live terminal and Across open switching devise 650kVp
ii. Rated One-minute power frequency withstands voltage Dry and Wet
a. Between live terminals and ground 275kVrms
b. Between Live terminal and Across open switching devise 275kVrms
31. RIV Level <2500µv at 1.1u/rt3
32. Minimum allowable moisture content in interrupting medium 50ppm
33. Visible Corona Discharge Voltage No visible corona as per IEC
Operating Mechanism
34. Type of Mechanism for
a. Opening Spring
b. Closing Spring
35. Weather gang operated Yes
36. Fixed trip or Trip free. Trip free
Guaranteed Technical Particulars of Circuit Breaker Ref. No : ESD/GTP/Bkr

Project : 513 DAK BLA RESERVOIR REDVCING Page No : 3 of 7


B Fouress (P) Limited
FLOOD & COMBINE HPP

Sl no Description To be filled in By supplier

37. Rated opening time


a. Maximum opening time under any condition with limiting voltage 35ms(at Rated voltage)
38. Rated closing time
a. Maximum closing time under any condition with limiting voltage <=66ms(at Rated voltage)
39. Max close open time <65ms

40. Arcing Time 25ms


41. Maximum Total break time under any duty condition for any current up to <=53ms
rated breaking current with limiting condition of voltage
42. Maximum arc duration and corresponding current under lock out pressure 25ms
43. Max temp rise for main contacts over and ambient temp of 50 Deg C 55 degC
44. Maximum Pole Discrepancy between poles
a. For Tripping <3.33ms
b. For Closing. <5ms
45. Main Contact
a. Type of Fixed / Main Contact Finger
b. Contact material Silver faced copper
46. Type of Arcing Contact Plug & Tulip
a. Contact Material Copper-Tungsten
47. Contact Pressure on main Contacts 25N
48. Length of Contact Travel 85mm
49. Rate of Contact Travel (m/s )
a. Opening 2.2~2.6
b. Closing 1.7~2.0
50. Auxiliary Contacts
a. Type of Auxiliary Contact Wiping contacts
b. Whether Contacts are Silver plated. Yes
c. No of Potential Free Contacts per pole
i. Normally Open 12
ii. Normally Close 12
d. Rated Voltage 220V
e. Rated Current Capacity 4A
i. Continuous 10A
ii. DC Breaking Current 4A ,t=20ms
Guaranteed Technical Particulars of Circuit Breaker Ref. No : ESD/GTP/Bkr

Project : 513 DAK BLA RESERVOIR REDVCING Page No : 4 of 7


B Fouress (P) Limited
FLOOD & COMBINE HPP

Sl no Description To be filled in By supplier

51. Closing Coil


a. No of Closing Coils 1
b. Rated Voltage 220VDC
c. Voltage Operating Range of Coil (Below and Above Rated voltage ) 85 to 110%

d. Power Consumption in VA 500W


e. Rated Voltage 220VDC
f. Maximum Voltage 110% of rated voltage
g. Minimum Voltage 85% of rated voltage
h. Ampere turns of the Coil As per ABB design
52. Tripping Coil.
a. No of Tripping Coils. 2
b. Rated Voltage. 220VDC
c. Voltage Operating Range of Coil (Below and Above Rated voltage). 70 to 110%

d. Power Consumption in VA. 500W


e. Rated Voltage. 220VDC
f. Maximum Voltage. 110% of rated voltage
g. Minimum Voltage. 70% of rated voltage
h. Ampere turns of the Coil, As per ABB design
53. Spring Charge Motor.
a. Rated Voltage AC 230VAC
b. Rated Voltage DC 220VDC
c. Voltage Operating Range (Below and Above Rated voltage ) 85 to 110%

d. Power Consumption in Watts 735W


e. Rated Voltage 230VAC / 220VDC
f. Maximum Voltage 110% of rated voltage
g. Minimum Voltage 85% of rated voltage
h. Time required by the motor to charge the closing spring fully <=15s
i. Automatic Operation of the Motor is Provided ( With Limit Switch ) Yes
Guaranteed Technical Particulars of Circuit Breaker Ref. No : ESD/GTP/Bkr

Project : 513 DAK BLA RESERVOIR REDVCING Page No : 5 of 7


B Fouress (P) Limited
FLOOD & COMBINE HPP

Sl no Description To be filled in By supplier

54. Minimum Dead Time for


a. Three Phase Reclosing 300ms
b. Single Phase Reclosing NA
55. No of Operations of Breaker without Maintenance
a. At rated Interrupting Capacity 20 at 31.5KA/3sec
b. At 50 % Rated interrupting Capacity Refer product manual
c. At rated Normal Current 2000
d. At 50 % Rated Normal Current Refer product manual
56. SF6 Gas Data
a. Volume of SF6 Gas per Pole. 153 litre
b. Wt of the Gas per breaker. 7kg approx
c. SF6 Gas Density
i. Normal Temperature 0.7 MPa @ 20deg C absolute
ii. Maximum Temperature
iii. Minimum Temperature
d. Guaranteed Maximum leakage rate <0.5% per annum
e. Rated Pressure of SF6 in Operating 0.7 MPa
f. Capacity of Gas Container 9kg approx. for gas cylinder
g. Spare gas provided for each breaker in separate cylinders Refer offer document for spares
h. Whether breakers are dispatched with gas filled At transport pressure & as per
transport guidelines
i. Parameters of SF6 As per IEC 60376
i. Gas pressure settings ( at 20 Deg Centigrade) 0.7MPa
ii. Normal operating Pressure 0.7MPa
iii. Min. pr. And density at which CB can operate 0.62MPa
iv. Low pressure alarm 0.62MPa
v. Lockout pressure for
a. Opening 0.6MPa
b. Closing 0.6MPa
vi. Device provided to give Alarm Contacts will be provided(device not in
ABB India scope)
vii. Details of Density Monitor 1 Density monitor will be provided per
CB
Guaranteed Technical Particulars of Circuit Breaker Ref. No : ESD/GTP/Bkr

Project : 513 DAK BLA RESERVOIR REDVCING Page No : 6 of 7


B Fouress (P) Limited
FLOOD & COMBINE HPP

Sl no Description To be filled in By supplier

57. Insulator Bushing


a. Name of the manufacturer ABB approved vendor
b. Type Brown Porcelain
c. Applicable standard As per IEC62155
d. Rated voltage 145KV
e. Highest system voltage 145KV
f. One minute power frequency withstand voltage(dry) 275KVrms
g. One minute power frequency withstand voltage(wet) 275KVrms
h. 1.2 / 50 Micro second wave impulse withstand voltage 650kvP
i. Volume of insulating medium per Pole. ~=50ltr
j. Creepage distance. 25mm/kV
k. Permissible safe cantilever loading on insulated. 1.5KN static and 3KN dynamic
l. Dimensions. As per enclosed GA drgs
m. Porcelain jointed to flanges. Yes
n. Weight. Approx. 300kg(per CB pole)
58. Power Connector for HV Terminal. Not in ABB India scope
a. No of Connectors. Not in ABB India scope
b. Size of Connectors. Not in ABB India scope
c. Material of Connector. Not in ABB India scope
59. Impact loading for foundation design 1000N horizontal & 12000N Vertical
60. Seismic level 0.5g
61. Minimum Clearance in Air
a. Between live part 1483mm
b. Between Live parts to earth 2507mm
c. Live parts to ground level 2507mm
62. Noise Level in Distance
a. 0 Mtr >116Db (abs)
b. 1 Mtr 116Db (abs)
c. 10 Mtr 91dB (abs)
d. 50 Mtr <91dB (abs)
63. Dimension and Weights
Height As per Enclosed GA drg
Width As per Enclosed GA drg
Length As per Enclosed GA drg
a. Weight of Complete breaker for Foundation design As per Enclosed GA drg
Guaranteed Technical Particulars of Circuit Breaker Ref. No : ESD/GTP/Bkr

Project : 513 DAK BLA RESERVOIR REDVCING Page No : 7 of 7


B Fouress (P) Limited
FLOOD & COMBINE HPP

b. Weight of Heaviest part of the breaker with name As per Enclosed GA drg

Mechanical stability Operation: >10,000 Times.


OPERATING MECHANISM: COLOR SHADE RAL7032