Product Bulletin
34.3:4150K
4150K/4160K Controllers and Transmitters October 2007
Specifications
Available Configurations Proportional Band Adjustment
See table 1 For Proportional and Proportional-Plus-Reset
Controllers:
0.2 to 1.0 bar (3 to 15 psig) Output: Full output
Input Signal pressure change adjustable from 3 to 100% of the
sensing element range.
Type: J Gauge pressure, J vacuum, 0.4 to 2.0 bar (6 to 30 psig) Output: Full output
J compound pressure, or J differential pressure pressure change adjustable from 6 to 100% of the
of a liquid or gas sensing element range.
Limits: See table 2 or 3
Differential Gap Adjustment
Output Signal For Differential Gap Controllers: Full output
pressure change adjustable from 15% to 100% of
Proportional or Proportional-Plus-Reset sensing element range
Controllers and Transmitters: J 0.2 to 1.0 bar
(3 to 15 psig) or J 0.4 to 2.0 bar (6 to 30 psig) Reset Adjustment
pneumatic pressure signal
Differential Gap Controllers: J 0 and 1.4 bar For Proportional-Plus-Reset Controllers:
(0 and 20 psig) or J 0 and 2.4 bar (0 and 35 psig) Adjustable from 0.01 to 74 minutes per repeat
pneumatic pressure signal (100 to 0.01 repeats per minute)
Action: Control action is field reversible between
J direct (increasing sensed pressure produces Zero Adjustment (Transmitters Only)
increasing output signal) and J reverse Continuously adjustable to position span of less
(increasing sensed pressure produces decreasing than 100% anywhere within the sensing element
output signal). The suffix R is added to the type range
number of a construction specified for reverse
action.
Span Adjustment (Transmitters Only)
Full output pressure change adjustable from 6 to
Supply Pressure Requirements(1) 100% of process sensing element range
See table 4
Performance
Repeatability: 0.5% of sensing element range
Supply Pressure Medium Dead Band (Except Differential Gap
Controllers(3)): 0.1% of output span
Air or Natural Gas(2) Typical Frequency Response at 100%
Proportional Band:
Output to Actuator: 0.7 Hz and 110 degree phase
Steady-State Air Consumption shift with 1850 cm3 (113 inches3) volume actuator
See figure 2 at mid-stroke
Output to Positioner Bellows: 9 Hz and 130
degree phase shift with 0.2 to 1.0 bar (3 to 15
Supply and Output Connections psig) output to 33 cm3 ( 2 inches3 ) bellows
- Continued -
2
Product Bulletin
34.3:4150K
October 2007 4150K/4160K Controllers and Transmitters
Specifications (continued)
Typical Ambient Temperature Operating (50_F) change in temperature between −40 and
Influence 71_C (−40 and 160_F) for a transmitter set at
100% span
Proportional Control only: Output pressure
changes ±3.0% of sensing element rating for Hazardous Area Classification
each 28_C (50_F) change in temperature
between −40 and 71_C (−40 and 160_F) for a Complies with the requirements of ATEX Group II
controller set at 100% proportional band Category 2 Gas and Dust
2
2 PROPORTIONAL BAND PROPORTIONAL
SUPPLY AIR FLOW, SCFH
PROPORTIONAL BAND
SETTING OF 0 OR 10
PROPORTIONAL
BAND SETTING OF 0
OR 10
NOTES
1 TO CONVERT PSIG TO BAR, MULTIPLY BY 0.06895.
2 SCFH—STANDARD CUBIC FEET PER HOUR (60_F AND 14.7 PSIA).
TO CONVERT TO NORMAL M3/HR—NORMAL CUBIC METERS PER HOUR (0_C AND
1.01325 BAR, ABSOLUTE), MULTIPLY BY 0.0268
A7242 / IL
3
Product Bulletin
34.3:4150K
4150K/4160K Controllers and Transmitters October 2007
4
Product Bulletin
34.3:4150K
October 2007 4150K/4160K Controllers and Transmitters
Table 4. Supply Pressure Data
MAXIMUM ALLOWABLE
NORMAL OPERATING SUPPLY PRESSURE TO
OUTPUT SIGNAL
SUPPLY PRESSURE(1) PREVENT INTERNAL PART
DAMAGE
Bar Psig Bar Psig Bar Psig
0.2 to 1.0 or 0 and 1.4 3 to 15 or 0 and 20 1.4 20 3.4 50
0.4 to 2.0 or 0 and 2.4 6 to 30 or 0 and 35 2.4 35 3.4 50
1. If this pressure is exceeded, control may be impaired.
5
Product Bulletin
34.3:4150K
4150K/4160K Controllers and Transmitters October 2007
Proportional-Only Controllers
Construction Features
The controller output pressure change feeds back to Rugged Service Capability
the proportional bellows, countering the pressure
change in the nozzle and equalizing the relay The case and cover are made of weather resistant,
diaphragm pressure differential. The relay valve die-cast aluminum. Stainless steel tubing and fitting
maintains a new loading pressure according to the materials provide the capability for operation in
change in sensed pressure. ammonia and similar corrosive service conditions.
Optional materials for relay diaphragms and other
soft parts permit operation at ambient temperatures
If the proportional valve is wide open (maximum dial
up to 93_C (200_F).
setting), all of the controller output pressure change
feeds back to the proportional bellows. The more the
proportional valve is closed, the more the controller
output pressure change bleeds out through the Low-Pressure Precision
proportional valve exhaust and the less there is to Bellows sensing constructions provide accuracy in
feed back to the proportional bellows. A fully open low-pressure, vacuum, or compound ranges. Two
proportional valve results in a proportional band of sensing bellows are used where an important
100 percent; closing the proportional valve reduces variable is the difference between two sensed
the proportional band. pressures.
6
Product Bulletin
34.3:4150K
October 2007 4150K/4160K Controllers and Transmitters
INLET END OF
CONSTANT SUPPLY PRESSURE
RELAY VALVE
SMALL DIAPHRAGM
LARGE DIAPHRAGM
EXHAUST
FIXED ORIFICE
EXHAUST END OF RELAY VALVE
PROPORTIONAL BELLOWS
FIXED
PIVOT
NOZZLE
VENTED
Figure 3. Operational Schematic of Direct-Acting Bourdon Tube Controller on Pipeline Pressure Service
EXHAUST
RESET
BELLOWS
ORIFICE
RELIEF VALVE
DIAPHRAGM
RESET
VALVE
TO FINAL
CONTROL
ELEMENT
PROPORTIONAL
BELLOWS
SENSED
PRESSURE PROPORTIONAL VALVE
7
Product Bulletin
34.3:4150K
4150K/4160K Controllers and Transmitters October 2007
PRESSURE ADJUSTMENT
PRESSURE SPRING-OUT DESIGN MINIMIZES
BLOCK RELAY CLEANING BACKLASH FOR MORE
AND TUBING ORIFICE WIRE POSITIVE SETTINGS
SENSING BELLOWS
HIGH-PRESSURE SENSING BELLOWS
W5458-1 / IL W3546-1 / IL
8
Product Bulletin
34.3:4150K
October 2007 4150K/4160K Controllers and Transmitters
HIGH-VISIBILITY
DIAL ON RESET VALVE
PROPORTIONAL
BELLOWS
RESET
BELLOWS
W7414 / IL W7417 / IL
W5458-1 / IL
W3550-1 / IL
9
Product Bulletin
34.3:4150K
4150K/4160K Controllers and Transmitters October 2007
Table 7. Optional Process Pressure Gauges pressure, if a Wizard II controller experiences supply
Sensing Element Gauge Range(1) pressure failure or other malfunction.
0 to 30 psig(2)
0 to 60 psig
0 to 160 psig
Bourdon tube Positive pressure
0 to 300 psig(2) Continuous Indication of Process Pressure
0 to 600 psig
0 to 1000 psig Replacing the supply pressure gauge on a controller
Bellows Positive pressure 0 to 30 psig(2) or transmitter by a process pressure gauge permits
1. Consult your Emerson Process Managementt sales office for gauges in other indicating process pressure in one of the ranges
units.
2. Also available in stainless steel trim. shown in table 7. To obtain a supply pressure
indication, install a gauge on the supply regulator.
The process pressure gauge must be specially
ordered and comes with brass trim standard in all
Easy Conversion From Proportional To On-Off ranges and stainless steel trim optional in some
Control ranges. Adding a process pressure gauge in the field
also requires a special control pressure block. A
The Type 4150KS controller provides on-off rather process pressure gauge can not be added to
than proportional control. This construction has the controllers or transmitters that use a differential
same parts as the comparable Type 4150K bellows for sensing process pressure.
controller. However, the proportional bellows is
connected so that feedback pressure pushes the Bourdon Tube Protection
beam and flapper in the same direction as caused
by the sensed pressure change. This reinforcement All Bourdon tube constructions are available with
completely opens the relay valve either to full supply one or both of the following protective devices:
pressure or to full exhaust, allowing no in-between
throttling.
D Barrier Protector for Corrosive or Clogging
Process Fluids—A sealed and fluid-filled barrier
To change from a proportional to on-off controller, or (described in a separate bulletin) may be installed
vice versa, just reverse the tubing connection at the between the process and the Bourdon tube. The
bellows frame on top of the beam and flapper as barrier fluid transmits sensed pressure on a
shown in figure 7. one-to-one basis into the Bourdon tube.
10
Product Bulletin
34.3:4150K
October 2007 4150K/4160K Controllers and Transmitters
BEAM AND
FLAPPER TUBING TO CONTROLLER
PROPORTIONAL LOADING
TUBING ALTERNATE LOADING
VALVE PRESSURE
TO RELAY PRESSURE GAUGE
GAUGE
670 SERIES OR
REVERSING TYPE 671
BLOCK MANUAL LOADER
WITH THREE-WAY
CHANGEOVER
TUBING CONNECTION IN LOADING PRESSURE VALVE
THIS LOCATION CONVERTS OUTPUT FROM
PROPORTIONAL TO CONTROLLER ALTERNATE
DIFFERENTIAL-GAP LOADING
CONTROLLER PRESSURE
PROPORTIONAL SOURCE
BELLOWS TO ACTUATOR AND VALVE
A2111-2 / IL
TUBING CONNECTION IN
THIS LOCATION CONVERTS
WIZARD II
PROPORTIONAL TO
CONTROLLER
DIFFERENTIAL-GAP
CONTROLLER
TYPE 657
VENTED BELLOWS ACTUATOR
REVERSING
1H4421-A BLOCK
1A4417-A
1H4422-A
REVERSE ACTING 4150K SERIES
1H4418-A 67 SERIES
A2870 / IL PROPORTIONAL CONTROLLERS FILTER
REGULATOR
Figure 7. Conversion from Direct to Reverse Action
or Proportional to On-Off Control
2. Composition, pressure, and temperature of Always specify the complete type number (including
measured variable(s). the R suffix for reverse action) of the Wizard II
controller or transmitter, supply pressure regulator,
and other desired equipment. On controllers with
3. Type number, orientation, and other applicable anti-reset windup, specify whether the differential
descriptions of control or indicating device(s). relief valve is to relieve with falling or rising output.
11
Product Bulletin
34.3:4150K
4150K/4160K Controllers and Transmitters October 2007
181
(7.12)
23.1
(0.91)
241.3
(9.50)
6.35 65.8
(0.25) DIA 50.8
(2.59) (2.00)
SCREWS 218.9
(8.62)
50.8
(2.00)
23.1 23.1
(0.97) (0.97) 14.3 R
(0.56)
Note
Neither Emerson, Emerson Process
Management, nor any of their affiliated
entities assumes responsibility for the
selection, use, and maintenance of any
product. Responsibility for the
selection, use, and maintenance of any
product remains with the purchaser
and end-user
Wizard and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of
Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.
All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.
We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use and
maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
www.Fisher.com
12
EFisher Controls International LLC 1989, 2007; All Rights Reserved Printed in USA