Professional Documents
Culture Documents
Table F 12. Single-circuit current ratings and associated volt drops for twin and multicore cables insulated
with impregnated paper (BS 6480) lead-sheathed or aluminium-sheathed, armoured or non-armoured, with or
without serving.
1 2 4
3
5
mm² A A A A
- 207 -
JS 21: 1992
Table F 12(cont'd)
1 2 4
3
mm² mV mV mV
* Total voltage drop between the consumer's main switchboard and any other point in the installation must
not exceed 2.5% of the nominal voltage (see 7.3 and F 1).
+ Stranded or solid conductors.
- 208 -
JS 21: 1992
Rating factors
Ambient
temperature (C) 25 35 40 45 50 55 60 65 70 75
Rating
factor 1.05 0.95 0.89 0.82 0.75 0.68 0.61 0.53 0.43 0.3
For groups of cables unenclosed, the single-circuit ratings apply provided that:
(a) The horizontal clearance between cables is not less than six times the overall diameter of an
individual cable, except that the horizontal clearance need not in any case exceed 150 mm.,
(b) The vertical clearance between cables is not less than 150 mm., and
(c) If the number of cables exceed four, they are installed in a horizontal plane.
In all other cases unless a more precise evaluation of current rating has been made based on experimental
work or, calculated data, the following factors are applicable:
Number of
cables 2 3 4 5 6 8 10 12 14 16~ 18~ 20~
Rating
factor 0.80 0.70 0.65 0.60 0.57 0.52 0.48 0.45 0.43 0.41 0.39 0.38
- 209 -
JS 21: 1992
Heavy duty (450/750 V) mineral, exposed to touch or PVC-covered
(COPPER)
Table F 13. Current ratings and associated volt drops for heavy duty mineral-insulated cables (copper
conductors and sheath) (BS 6207 Part 1), exposed to touch are having an overall covering of PVC.
1 2 3 4 5
mm² A A A A
- 210 -
JS 21: 1992
Table F 13(cont'd)
1 42 36
1.5 28 24
2.5 17 14
4 10 9.1
6 7 6.0
10 4.2 3.6
16 2.6 2.3
25 1.65 1.45
35 1.20 1.05
50 0.91 0.80
70 0.64 0.56
95 0.49 0.43
120 0.41 0.36
150 0.34 0.30
185 0.29 0.26
240 0.25 0.22
*Total voltage drop between the consumer's main switchboard and any other point in the installation must
not exceed 2.5% of the nominal voltage (see 7.3 and F.1).
Rating factors
Number of
circuits* 2 3 4 5 6 8 10 12 14 16+ 18+
20+
Rating
factor 0.8 0.69 0.63 0.59 0.56 0.51 0.48 0.44 0.42 0.41 0.39
0.38
*for single-core cables or number of cables for twin and multi-core cables
+Not applicable to single-core three-phase.
- 211 -
JS 21: 1992
Light duty (300/500 V) mineral, exposed to touch or PVC-covered
(COPPER)
Table F 14. Current ratings and associated volt drops for heavy duty mineral-insulated cables (copper
conductors and sheath) (BS 6207 Part 1), exposed to touch are having an overall covering of PVC.
4
1 2 3 5
mm² A A A A
1.0 18.5 17 15 10
1.5 23 21 19.5 13
2.5 31 29 26 17.5
4 40 38 - -
* Total voltage drop between the consumer's main switchboard and any other point in the installation must
not exceed 2.5% of the nominal voltage (see 7.3 and F.1).
- 212 -
JS 21: 1992
Table F 14(cont'd)
1 42 36
1.5 28 24
2.5 17 14
4 10 9.1
6 7 6.0
10 4.2 3.6
16 2.6 2.3
25 1.65 1.45
35 1.20 1.05
50 0.91 0.80
70 0.64 0.56
95 0.49 0.43
120 0.41 0.36
150 0.34 0.30
185 0.29 0.26
240 0.25 0.22
*Total voltage drop between the consumer's main switchboard and any other point in the installation must
not exceed 2.5% of the nominal voltage (see 7.3 and F.1).
Rating factors
Number of
circuits* 2 3 4 5 6 8 10 12 14 16+ 18+
20+
Rating
factor 0.8 0.69 0.63 0.59 0.56 0.51 0.48 0.44 0.42 0.41 0.39
0.38
*for single-core cables or number of cables for twin and multi-core cables
+Not applicable to single-core three-phase.
- 213 -
JS 21: 1992
Heavy duty (450/750 V) mineral, sheath bare, not exposed to touch
(COPPER)
Table F 15. Current ratings and associated volt drops for heavy duty, mineral insulated cables (copper
conductors and sheath) having the sheath bare and not exposed to touch and not in contact with
combustible materials.(BS 6207, Part 1)
1 2
3 4
mm² A A A
1.0 24 20 14
1.5 31 26 17.5
2.5 42 35 24
4 55 46 32
6 70 58 -
10 96 78 -
16 127 103 -
25 166 134 -
35 203 - -
50 251 - -
70 307 - -
95 369 - -
120 424 - -
150 485 - -
185 550 - -
240 643 - -
- 214 -
JS 21: 1992
Table F 15(cont'd)
1 47 40
1.5 31 27
2.5 19 16
4 12 10
6 7.8 6.8
10 4.7 4.1
16 3.0 2.6
25 1.85 1.65
35 1.35 1.20
50 1.00 0.88
70 0.71 0.62
95 0.54 0.47
120 0.44 0.38
150 0.36 0.32
185 0.31 0.27
240 0.26 0.22
*Total voltage drop between the consumer's main switchboard and any other point in the installation must
not exceed 2.5% of the nominal voltage (see 7.3 and F.1).
Rating factors
Ambient
temp.(C) 25 30 40 50 60 70 80 90 100 110 120 130 140
Rating factor* 1.04 1.0 0.96 0.92 0.84 0.8 0.61 0.46 - - - - -
Rating factor@ 1.12 1.09 1.06 1.02 0.98 0.94 0.90 0.86 0.81 0.77 0.66 0.53 0.36
- 215 -
JS 21: 1992
Light duty (300/500 V) mineral, sheath bare, not exposed to touch
- 216 -
JS 21: 1992
(COPPER)
Table F 16. Current ratings and associated volt drops for light duty, mineral insulated cables (copper conductors and sheath) having the sheath bare
and not exposed to touch and not in contact with combustible materials.(BS 6207, Part 1)
1
2 3 4 5 6
mm² A A A A A
1 25 21 18 18 13
1.5 32 26 22 23 15
2.5 43 36 30 31 22
4 56 47 40 42 -
- 217 -
JS 21: 1992
Table F 16(cont'd)
1 45 39
1.5 30 26
2.5 18 15
4 11 9.6
* Total voltage drop between the consumer's main switchboard and any other point in the installation must not exceed 2.5% of the nominal voltage
(see 7.3 and F.1).
Rating factors
- 218 -
JS 21: 1992
Mineral, as earth-concentric wiring
(COPPER)
Table F 17. Current ratings and associated volt drops for mineral-insulated cables (copper conductor and sheath). (BS 6207, Part 1) used as
earth-concentric wiring.
~1.0 18 22
~1.5 21 26
~2.5 27 33
~4.0 34 42
1.0 21 26
1.5 26 32
2.5 33 40
4.0 41 50
49 60
6.0
- 219 -
JS 21: 1992
Table F 17(cont'd)
1 2 3
mm² mV mV
~1.0 29 31
~1.5 21 22
~2.5 14 15
~4.0 10 10
1.0 25 27
1.5 18 19
2.5 12 13
4.0 7.8 8.5
5.9 6.3
6.0
Note: For three-core mineral insulated cables carrying balanced three phase a.c. in earth concentric system, the current ratings and values of volt
drop stated for three-core cable in tables F 13 to F 16 as appropriate, are applicable.
* Total voltage drop between the consumer's main switchboard and any other point in the installation must not exceed 2.5% of the nominal voltage
(see 7.3 and F.1).
~Light-duty cable
Heavy-duty cable
- 220 -
JS 21: 1992
Rating factors
Number of
circuits* 2 3 4 5 6 8 10 12 14 16+ 18+ 20+
Rating
factor 0.8 0.69 0.63 0.59 0.56 0.51 0.48 0.44 0.42 0.41 0.39 0.38
*for single-core cables or number of cables for twin and multi-core cables
Sheath bare, not exposed to touch and in contact with combustible material.
Ambient
temp.(C) 25 30 40 50 60 70 80 90 100 110 120 130 140
Rating
factor~ 1.04 1.0 0.96 0.92 0.84 0.8 0.61 0.46 - - - - -
Rating
factor@ 1.12 1.09 1.06 1.02 0.98 0.94 0.90 0.86 0.81 0.77 0.66 0.53 0.36
- 221 -
JS 21: 1992
Bare circuit copper conductor (risers)
Table F 18. Single-circuit current ratings and associated volt drops for bare or lightly-covered solid
copper conductor of circular cross-section, installed in vertical trunking with spacing of 75 mm between
conductors.
10 79 270 270
12.5 120 370 370
16 200 510 510
20 315 700 690
25 490 940 920
- 222 -
JS 21: 1992
Table F 18(cont'd)
* Total voltage drop between the consumer's main switchboard and any other point in the installation must not exceed 2.5% of the nominal voltage
(see 7.3 and F.1).
Note: 1) Table F 18 does not apply to bus-bar and connections on switchboards; ratings for these are dealt with in BS 159.
2) For the rating factors for conductors connected to rubber or p.v.c. insulated cables, see note 9 of 7.12.
(a) Current rating factor: 0.9
- 223 -
JS 21: 1992
Bare rectangular copper conductor (risers)
(COPPER)
Table F 19. Single-circuit current ratings and associated volt drops for bare or lightly-covered solid
copper conductor of rectangular cross-section, installed in vertical trunking, with spacing of 75 mm
between conductors when disposed in parallel, or with a spacing of 30 mm between conductors when
disposed edge-to-edge.
2
1 3 4 5
mm mm² A A A
- 224 -
JS 21: 1992
Table F 19(cont'd)
1 2
3 4 5 6 7 8 9 10 11
mm mm² mV mV mV mV mV mV mV mV mV
16x2.5 40 1.08 1.08 1.02 1.08 0.97 0.94 0.90 0.94 0.86
16x4.0 64 0.67 0.67 0.73 0.68 0.69 0.58 0.65 0.59 0.62
25x4.0 100 0.44 0.44 0.53 0.44 0.50 0.38 0.48 0.38 0.45
25x6.3 157 0.27 0.28 0.42 0.28 0.38 0.24 0.38 0.24 0.35
40x6.3 250 0.17 0.18 0.31 0.18 0.30 0.15 0.29 0.15 0.28
63x6.3 400 0.11 0.11 0.23 0.12 0.28 0.10 0.22 0.11 0.23
100x6.3 630 0.069 0.075 0.17 0.084 0.22 0.065 0.16 0.07 0.20
* Total voltage drop between the consumer's main switchboard and any other point in the installation must not exceed 2.5% of the nominal voltage.
Note: (1) Table F 19 does not apply to bus-bar and connections on switchboards; ratings for these are dealt with in BS 159.
(2) For the rating factors for conductors connected to rubber or p.v.c. insulated cables, see note 9 of 7.12.
(a) Current rating factor: 0.9
(b) Volt drop rating factor:
(1) 0.97 for d.c. conductors and a.c. conductors with p.f. = 1.0
(2) 0.98 for a.c. conductors with p.f. = 0.7 (mean value).
- 225 -
JS 21: 1992
Vulcanised rubber flexible cables
Table F 20. Current ratings and associated volt drops for vulcanised rubber-insulated
flexible cables, other than flexible cords (BS 6007).
3
1 2
mm² A A
4 30 26
6 39 34
10 51 47
16 73 63
25 97 83
35 120 102
50 150 124
70 180 158
95 220 192
120 250 222
150 290 255
185 330 291
240 380 343
300 435 394
400 520 -
500 590 -
630 680 -
- 226 -
JS 21: 1992
Table F 20(cont'd)
1 2 3 4
mm² mV mV mV
4 12 12 10
6 7.8 7.8 6.7
10 4.6 4.6 4.0
16 2.9 2.9 2.5
25 1.80 1.85 1.55
35 1.20 1.24 1.15
50 0.85 0.88 0.84
70 0.60 0.64 0.58
95 0.45 0.50 0.44
120 0.35 0.41 0.36
150 0.29 0.34 0.30
185 0.23 0.30 0.26
240 0.18 0.25 0.21
300 0.14 0.23 0.185
400 0.11 0.21 -
500 0.086 0.19 -
630 0.067 0.18 -
* Total voltage drop between the consumer's main switchboard and any other point in the installation must
not exceed 2.5% of the nominal voltage (see 7.3 and F.1).
Note: The tabulated ratings are not applicable to flexible cables wound on drums. The current rating of a
cable on a drum depends upon the type of drum and may be less than one-half of the
corresponding rating stated in the table.
Ambient temperature(C) 25 35 40 45 50 55
Rating factor 1.04 0.91 0.82 0.71 0.57 0.41
- 227 -
JS 21: 1992
`High-temperature' flexible cables
Table F 21. Current ratings and associated volt drops for flexible cables insulated with
butyl rubber or e.p. rubber or silicone rubber (BS 6007).
mm² A A
4 41 36
6 53 47
10 73 64
16 99 86
25 131 114
35 145 140
50 185 170
70 225 216
95 270 262
120 305 303
150 355 348
185 405 397
240 465 467
300 530 537
400 630 -
500 720 -
630 830 -
- 228 -
JS 21: 1992
Table F 21(cont'd)
4 13 13 11
6 8.4 8.4 7.3
10 5.0 5.0 4.3
16 3.1 3.1 2.7
25 2.0 2.00 1.70
35 1.42 1.34 1.20
50 0.99 0.95 0.91
70 0.70 0.68 0.63
95 0.53 0.53 0.48
120 0.41 0.43 0.39
150 0.33 0.36 0.32
185 0.26 0.32 0.27
240 0.21 0.27 0.22
300 0.165 0.24 0.195
400 0.125 0.21 -
500 0.098 0.20 -
630 0.073 0.19 -
* Total voltage drop between the consumer's main switchboard and any other point in the installation must
not exceed 2.5% of the nominal voltage (see 7.3 or F.1).
Note. The tabulated ratings are not applicable to flexible cables wound on drums. The current rating of a
cable on a drum depends upon the type of drum and may be less than one-half of the
corresponding rating stated in the table.
Ambient temperature(C) (35 to 95) 100 105 110 115 120 125 130 135 140
Rating factor 1.0 0.94 0.88 0.82 0.77 0.71 0.64 0.56 0.48 0.39
- 229 -