Simple Analysis of the Measurement Methods of Arc Fault


Cao Zhena, Liu Xiaopenga,Zhangzhib,Wang Qingcongb, Shi Chongb,Li Chunchic,
a
Ministry of Public Security Shenyang Fire Research Institution,Shenyang 110034, China
b
Shenyang Fire Control Bureau, Shenyang 110013, China
c
The Chinese People’s Armed Police Force Academy,Langfang 065000,China
caozhen@syfri.cn

Abstract—According to fire statistics in recent years, in terms II. MECHANISM OF ARC FAULT
of both quantity and loss, electrical fire is the first in the
reasons of fire. It is found that arc fault is one of the main
There are many factors causing fault arc, the most
reasons of electrical fire, which cause electrical fire. It has important is the following three factors:
seriously harmed the safety of public life and property. So the A. Insulation Carbonization
study on arc fault particularly on the detection method for arc
fault is becoming increasingly important. This paper firstly Even in the AC 120V line, if carbonized path exists, it
introduces the mechanism of arc fault, secondly the paper may also cause sustained arcing. Facts prove that many ways
describes the classification of arc fault, the current situation of can lead to the formation of carbonized path. The simplest
the detection method for arc fault. Finally the paper gives the method in the arc fault circuit interrupter (hereinafter
trends of the study on arc fault. On one had the research lay referred to as AFCI) standard test is to use two electrodes on
the foundation to prevent the electrical fire caused by arc fault, the insulating layer of cable, with a high voltage through the
on the other hand it could provide basis for drafting or writing electrodes, the arc can be formed directly on the surface of
relevant standard. the cable. According to arc fault circuit interrupter safety
standards UL1699, carbonized path in relevant sections, the
Keywords-Arc Fault; Arc Sight; Arc Sound above method is being used. Another method combines
moisture on insulating surface and pollutant effect, so the
I. PREFACE method is also called the “wet path” .The combined effects
of moisture and pollutant leading to leakage current in the
According to fire statistics in recent years, the frequency
insulating surface which gradually forms the carbonized path.
of electrical fire has accounted for 27% of the total number
Typical carbonized path fault arc is repetitive and
of fire, which is the leading reason for fire. Its loss has
irregular but usually come into being by the following steps:
reached 53% of total loss caused by fire. In the electrical fire,
the initial current form a carbonized layer; continuous
fire caused by electrical short circuit has accounted for over
current increase until the arc starts burning; burning arc
50%. There are two types of electrical short circuit: the first
melts metal and releases the melt; once released from the
one is direct connection between conductors, such as the
metal melt, the current will drop; current that takes
short circuit between phases, between phase and N circuit.
carbonized material as medium continuous flow in the
The point of short circuit is the metal short circuit melt down
circuit until the current amplitude once again greatly
at high temperature. It is called metal short circuit. Another
increased.
kind is the ground short circuit of energized conductor. It is
the arc short circuit (arc fault) based on the circuit of arc. B. The air ionization caused by external factors
Previously, the current of short circuit is calculated by kA. Although the intrinsic dielectric strength of air is very
The core of metal circuit produces high temperature that high (typically 3MV/m), if the air is ionized, it will
would lead to incandescence. The insulation has been largely decompose at lower energies. Two ways to ionized air is
oxidized and burnt itself. The danger of fire is extremely pre-arcing and combustion. If a severe arc fault happens on
high. However, because of high short circuit current it the power distribution bus, large amounts of ionized gas will
produces, the metal short circuit can make the breaker cut off be emitted. These ionized gas will fly a certain distance, if
the power instantly, by which the fire can be avoided. In they encounter another line, it is easy to cause air
terms of the latter one, the short circuit current is influenced decomposition and leads to arc fault on the line. The
by impedance and the arc has lasted continuously. Local combustion would make the dielectric strength of air is
temperature caused by arc can reach 3000~4000℃, which reduced to 0.11MV / m.
will easily burn surrounding material to lead to a fire. But Arcing caused by the fire is the most common hazards at
the short circuit current caused by ground fault is relevantly the scene of the fire, and combustion would lead to
low; it fails to make the breaker cut off the power. Thus, the insulation carbonization, or air ionization, or both.
danger of fire caused by arc fault is much larger than the one
of metal short circuit. Thus, we should pay attention to the C. Short Circuit
study on the detection principle and method of arc fault in Short circuit exists in two forms: ①metallic short circuit:
order to prevent electrical fire and thus effectively protect when the contact is between different potential conductors,
the safety of public life and property. the thermal effect of short-circuit current would lead to high
temperature, and metal at the contact point is molten. If the
contraction of the melting metal results in a separation
between the contactor, and the failure point would

978-1-4799-4261-9/14 $31.00 © 2014 IEEE 914


DOI 10.1109/ISDEA.2014.203
disconnect, then short circuit disappears naturally, and
electrical hazard will not happen. If the two conductors was Load
melted and welded together tightly, contact impedance is
negligible, and the short-circuit current is several hundred
times the rated current or thousands of times, it is called
metallic short-circuit. Although metallic short circuit brings
larger fire hazard, short-circuit fire is completely avoidable
by the installation of electrical short-circuit protector and
effective maintenance following the specification. ② short
arc circuit: the situation is very different if the contact type Figure 2. Ground Arc
between the conductors is arc contact. Because of the poor
contact, the contact would not be melted and arc or spark
may burst out. Due to a larger impedance at failure point, the
current is not large, then short-circuit protector will not work. Load
Because the current is not large enough, over-current
protector can not trip timely, so that the arc persists. When
an arc appear , due to the high temperature, up to thousands
of degrees, the presence of combustible material around the
arc site would make a high risk of fire.
III. CLASSIFICATIONS OF ARC FAULT
Arc is a kind of electric discharging of gas ionization and Figure 3. Wire-wire Arc
it is also one kind of plasma. From the microcosmic
perspective, the current in the arc is the outcome of When the atmospheric breakdown occurs frequently,
movement of electron and positive ion under the force of characters of arc are high temperature, low current and short
electric field. The movement of electron constructs the main duration. When the arc discharges, it produces plenty of heat,
part of current. which can burn surrounding combustible and inflammable
Based on the production principle of arc, it can be products. It may cause fire or even explosion. For example,
divided into easy arc and bad arc. The easy arc occurs in the according to Yearbook of Fire Statistics of China, the
plugging of electric appliance; and bad arc is also called arc frequency of electrical fire has occupied the leading
fault, which is mainly caused by the burn-in and damaged positions over other types of fire. Over 30% fire is caused by
electrical insulation of circuit and cable, atmospheric the burn-in circuit or unreasonable arrangement of circuit of
breakdown from pollution and damp air or loose electronic the building. It has continuously increased on average 1%
connection. According to the power of arc current, arc fault per year. Over 6.6% of person who use plug board have felt
can be divided into high-level arc and low-level arc. electric shock. FAA points out that electrical fault are the
According to the generation position of arc fault, it can be key problem of numerous business plane accidents. The
divided into serious arc and parallel arc, and parallel arc can military force also regards that electrical fault is the
be divided into ground arc and wire-wire arc, as it is shown important reason for safety problems and delay of planes.
in figure 1, 2 and 3. Arc fault is one of the main reasons that cause these
electrical accidents. Traditional fuse protectors and electrical
breakers fail to meet the requirement of arc fault detection.
This is because the breaker is designed for the detection of
Load overloading arc. However, because the current of low-level
arc is low and even lower than rated current, the breaker will
not have any reflection while high-level arc has a big current,
but it lasts for a short time. While a traditional breaker fails
to perform protection, the arc has already been distinguished.
IV. CURRENT CONDITION OF ARC FAULT DETECTION
When arc fault occurs, the pressure of power grid will
decrease and the current will increase with arc light, arc
Figure 1. Series Arc
sound, heat and electromagnetic radiation. Currently, based
on above arc fault, both domestic and international scholars
have conducted some studies about arc detection.
A. Detection Method based on Arc Light and Arc Sound
In recent years, by resorting to the light effect of arc, arc
light detection and protection system has been developed

915
abroad, such as arc fault protection system used in low- change of loading. However, in fact, the terminal loading of
pressure switch cabinet from Moeller Company from circuit often changes on many conditions. Either non-linear
Germany, arc fault protection system of ARC Guard System loading or hot-plugging of loading can cause the mistaken
of ARCON ABB and VAMP system of Finland Vaasa action of arc fault detection. R.Spyker has conducted studies
Company. The judgment of these systems is based on the arc on DC series arc and found that the content of harmonic
light and over-current caused by arc fault. These systems wave of current increases a lot in the frequency range from
provide a fast and save bus protection. This provides 10kHz to 100kHz. The frequency domain of arc current has
effective solution for limiting the arc fault. However, these illustrated the possibility of arc fault detection within the
detection devices also have their limitations. The sensors frequency domain. Thus, James A.Momoh has introduced
used by them for arc detection have certain installation Fourier synthesis into arc detection, which is to consider the
positions, which are generally applied to internal part of collected voltage and current values together in order to
switch cabinet for arc fault protection. They are not suitable obtain the Fourier synthesis of energy. This result can be
for the device with a longer circuit. used as the basis for judgment of arc fault. However,
The arc fault of switch cabinet is a very complex process considering the loading property (high-frequency
caused by various reasons. One of the key reasons is burn-in interference is introduced to DC-DC) and quality of power,
insulation. The burn-in wire is a slow process. Some burn-in they have introduced ANN (Artificial Neural Network),
wire may not cause arc fault at right. But it has the potential which introduces the result of Fourier synthesis into neutral
for arc fault and it produces arc sound. The arc sound alarm network in order to avoid misjudgment. After training,
mechanism before the occurrence of arcing avoids its accurate results can be obtained. However, traditional FFT
occurrence and erroneous judgment. Before arcing, the arc transfer requires linear system and stable signal, but the
sound change obviously and the sound signal has certain signal of arc fault is non-linear and random. Both domestic
range of frequency band. Studies and analysis show that arc and foreign scholars have introduced wavelet analysis into
light can be applied to detection of arc fault as the previous arc fault. Based on high-resistance arc fault of Korean
symptoms of arc fault. 154kV high-voltage transmission system, Korean scholars
have studied about the modification with wavelet.
B. Detection Method based on Pressure Effect of Arc Based on the voltage characters in arc fault, an electronic
When switch cabinet arc occurs, the electric energy is arc fault detector is developed. First, 220 voltage is
transformed into thermal energy that increases temperature transformed to amplification and smoothing. After filter
of surrounding air and pressure. The gradual expansion of air processes the voltage signal, it is transmitted to pulse former
medium has further impact on cabinet. Siemens has taken in which the sudden incoming information of voltage has
advantage of pressure effect of arc fault to develop a kind of become pulse. This pulse will have constant amplitude and
pressure switch system. Through collecting pressure signal width through single short trigger, and then it will be
in arc fault, in the early moment of short circuit arc, it gives transmitted to integrator for integration and to comparator.
out signal rapidly and cuts the fault circuit. It causes that the When the amplitude of integrator exceeds the setting value
time from pressure wave caused by short circuit current to of comparator, the circuit will start. After delay, it sends
separating break of breaker is <100ms. The pressure tripping signals. The upstream breaker of arc fault separates
character has used to develop the detection system for arc the break. The shortcoming of this electronic arc fault
fault. Although it has good performance, the high-pressure detector is that when the detection of voltage signal of arc is
air caused by arc fault has released by pressure release disturbed by power grid loading and other factors, the
device. Thus, there is certain difference between pressure of misjudgment will occur.
switch cabinet calculated in the model and the pressure of
real model. When the pressure is lower than required valve V. STUDY TREND OF ARC FAULT DETECTION
of detection device, this system will cause miss judgment.
A. Detection Method based on Combination of Multiple
C. Detection Method based on Current and Voltage Information and Judgments
When arc fault occurs, the current and voltage in the Studies show that the arc fault has caused slight arc
circuit will change. In arc fault, current becomes zero for a sound signal. During arcing, the amplitude of short circuit
while which is called “square shoulder”, the difference of current will take large changes with the arc light. In the
positive and negative semi-circle region of current is large, reference, the oscillator signal of Duffing has based on the
the amplitude of surrounding cycle changes a lot. In the zero judgment on arc sound, arc light and short circuit current. By
zone, the constant of voltage is very small. The change rate setting reasonable amplitude, the alarm system is founded. It
of arc voltage is larger in zero zone and it reaches the peak has further improved the reliability of arc fault detection.
when current is over zero. This arc fault detection method based on combination of
Based on the sudden increase and decrease of current in multiple information and judgments is the important trend of
arc fault, Delphi Research Institute has designed the FDC studies on arc fault detection method.
module (Series/Parallel Arc Fault Discrimination Circuit)
that provides arc detection device to arc detection of B. Detection method based on intellectual algorithm
automotive system. The disadvantage of this device is that For switch power, fluorescent lamp, dimming light and
when the switch is closed, the system requires normal so on with electrical loading during stable operation has

916
similar pressure and current characters with the one of low- [5] Wu Zhuoqi and Wangli. Overiew of Arc Fault Detection [J],
pressure series arc fault. In addition, the environmental Proceedings of 13th National Electrical Automation and Electric-
controlled System Annual Academic Meeting, 8-11 (in Chinese)
change, including climate and electronic noise, has often
[6] Malakondaiah Naidu, Thomas J Schoepf, Suresh Gopalakrishnan.
caused the change of collected signal of sensors that is close Arc Fault Detection Scheme for 42-V Automotive DC Networks
to the change of parameters of arc fault. What’s more, the Using Current Shunt[J],.IEEE Transactions on power electricals,
occurrence of arc fault has been influenced by many 2006, 21(3): 633–639
surrounding complex factors. Thus, the advanced and [7] Chul-Hwan Kim,Hyun Kim, Young-Hun Ko et al. A Novel Fault-
intellectual detection algorithm shall be introduced into Detection Technique of High-impedance Arcing Faults in
signal process of arc sound and arc light detectors. The Transmission Lines Using the Wavelet Transform[J],. IEEE
Transaction on power delivery, 2002, 17(4): 921–929
intellectual detection algorithm has tried to apply the
multidisciplinary technology, including chaos theory, [8] Donald G. Kilroy, Wayne H. Oldenbury, AC Arc Fault Detection and
Protection[J],, USA,Application, US 2007/0133134 A1, 2007
wavelet analysis and fuzzy theory to the identification of arc
[9] LAN Huili,Zhang Rencheng,Current Research and Development
sound and arc light of arc fault. It will be the key part for Trends on Faults Arc Detection Method in Switch Cabinet[J],, High
studies on arc fault detection in the future. Voltage Engineering,2008,34(3): 496–499.
C. Positioning of Arc Fault
Currently, most studies about the arc fault detection
focuses on the internal part of high- and low-voltage switch
cabinet which may cause arc fault easily. The application
scope has certain limitations. Thus, the integration with
wireless communication technology for the positioning
technology study of arc fault will be another significant
research direction of arc fault in the future.
VI. CONCLUSIONS
The electrical safety accident caused by arc fault has
accounted for a large proportion and has been increased
gradually. It poses increasing threat to the lives of people
and their assets. In order to solve and prevent electrical
accidents caused by arc fault in residential building, the
study on the arc fault protection technology has enjoyed
necessary application background and extensive social
demand. It is closely related to the safety of domestic power,
lives and property safety. Both domestic and international
studies have received excellent outcomes in the low-voltage
arc fault detection technology, development and promotion
of application products and standard of products. USA has
occupied the leading position. Thus, it is necessary to
conduct a study on the principle of arc fault, analyze and to
learn from advanced international detection technology,
industry standard and technological specification. We should
accumulate achievements in the study and development of
core technology with proprietary intellectual property rights,
designing practical low-voltage arc fault detectors,
formulating product detection specification and inspection
procedures under domestic application background and
editing technical and specification standards.
REFERENCES.
[1] UL1699-2008, Arc-Fault Circuit-Interrupters, UL Standards
[2] Dong Aihua, Yang Yi and Fu Yongli, Overiew of Low-voltage Arc
Fault Detection[J], Low-voltage Apparatus, 2009(5). (in Chinese)
[3] Cai Bin, Chen Degui,Wu Rui, et al. Current Research Condition and
Trend of Arc Fault Detection Method inside Switch Cabinet [J],
High-voltage Technology, 2008, 34(3): 496-499. (in Chinese)
[4] Yang Jianhong, Zhang Rencheng and Fang Huaiying. Application of
Duffing Vibrator Signal Detection in Arc Fault Short Circuit
Protection [J], Journal on Automation of Electrical Power System,
2006, 30(24): 69-71