You are on page 1of 5

Page 1 of 5 2014-PSEC-0380

Ignition Characteristics of Residential Series Arc Fault in 220V HIV Wire

Won-Sik Moon, Jae-Chul Kim, Ara Jo Sun-Bae Bang Won-Sik Ko


Student Member, IEEE, Member, IEEE Senior researcher Vice President
Electrical Engineering Dept. Electrical Safety Research Institute HETCO Inc.
Soongsil University 12, Ogon-ro, Wanju-gun 602-2, Ga-Yang Techno Town
369, Sangdo-ro, Dongjak-Gu, Seoul, KOREA Jeollabuk-do, 565-851, Korea 157-793, Seoul, KOREA
chriswsmoon@ssu.ac.kr, jckim@ssu.ac.kr bsb1586@kesco.or.kr kows1018@hanmail.net

Abstract -- Unintentional arc faults, caused from damaged experimental equipment using the standard suggested by
power line cords and loose connections, can start a serious fire UL1699. HIV wires were used for wire samples because these
and safety hazard in residential areas. The arc fault circuit are the most widely used materials as residential electric wires
interrupter (AFCI) is beginning to emerge as a product to
in Korea.
protect against the arc that may cause fire. In this paper, we
analyze ignition characteristics depending on the magnitude of
load current when series arc occurs. Also, we suggest the II. ARC FAULT CHARACTERISTICS
suitable arc clearing time based on characteristic analysis in
Korean residential electric environment. To do this, we have A. Types of Arc Faults
tested the carbonized path arc clearing time test using ultraviolet An arc is defined as a continuous luminous discharge of
signal detecting system according to the test method of UL 1699.
electricity across an insulating medium, usually accompanied
As wire specimen in those experiments, we used the heat
resistant indoor PVC insulated (HIV) wire which is a kind of by the partial volatilization of the electrodes [5]. There are
residential electric wire. two modes in which arcs occur and may cause fire [6]. One of
modes is formation of a carbonized path between electrodes
Index Terms—AFCI, arc clearing time, carbonized path, HIV and the other is point contact and separation of electrodes.
wire, ignition, Series Arc Fault, UV sensor There are three types of arc faults as shown in Fig. 1 [6]-[8].

I. INTRODUCTION
In some cases of electrical fire occurred in 2011, it
accounted for 21.3% as 9,351 cases out of total 43,875 cases
in Korea. Analyzed by causes of electrical fire, short circuit
by insulation deterioration was 2,287 cases (24.5%), (a) Series arc
unidentified short circuit was 2,245 (24%), loose contact was
722 cases (7.7%), and short circuit by tracking was 668 cases
(7.1%). It shows that electrical fire caused by arc faults
accounts for 73.2 percent as 6,844 cases [1]. In this way, most
of the electrical fires have been occurred by arc fault. But the (b) Line-to-line (parallel) arc
arc fault circuit interrupter (AFCI) to prevent electric fire has
not been introduced in Korea.
In the case of North American countries, Ground Fault
Circuit Interrupter (GFCI) for preventing electrical shock, as
well as AFCI for preventing fire has to be installed. It is
required at homes for preventing electrical disaster in (c) Line-to-ground arc
bathrooms and basement where are damp or wet [2]-[4]. Like
Fig. 1. Types of arc fault circuits
these countries, Korea needs to be installed arc detector and
interrupter to prevent electrical fires. Therefore, it should be
considered with the introduction in Korean industrial Fig. 1 (a) shows a line-to-line (parallel) arc. The two wires
standards or electrical installation technical standard of the are short circuit state that is from being stuck in a crack in
electricity enterprises act. door or under pressure by heavy objects. The Fig. 1 (b) is to
Korea has been ready to be introduced of AFCI. This paper show the series arc. It occurs in a single conductor that has
suggests the suitable arc clearing time in residential electric pulled apart or a loose connection to a receptacle or in a
environment. The carbonized path arc clearing time test was splice. The series arc is in series with the load and remains at
utilized for this experiment. Also the characteristics of lower levels than the load current. Since the current levels of
ignition energy were analyzed. We have developed series arc cannot greater than the rating of the circuit breaker,

978-1-4799-2288-8/14/$31.00 © 2014 IEEE


2014-PSEC-0380 Page 2 of 5

it is difficult to detect the series arcing than the parallel arcing. In the case of continuous arcing by loose contacts of
Fig. 1 (c) is Line-to-ground arc fault and another type of the electric wires, a carbonized path can be generated at the point
parallel arcs. It is formed only when a ground path is present. of arcing. If load currents flow through the generated path,
this path serves as an electric conductor and it could cause
B. Series Arc Protection Characteristics
fires through ignitable substances [9]. We had conducted 200
One of the main reasons for electric fires is arcing [4]. experiments to simulate ignition occurrence by arcing. For
Despite of such a situation, circuit breakers or earth leakage these experiments, we developed an experimental device for
circuit breakers are still used for preventing electric fires in testing carbonized path arcing based on UL 1699 standard.
Korea. These circuit breakers can keep people safe from a We also utilized UV sensor to detect the time until fires occur
short circuit accident or an electrocution accident. But it from arcing.
cannot protect at all from the fires by series arc. Since 1974
residential voltage had been boosted from 110V to 220V. For A. Experimental Configuration
this reason, Korea had mandated earth leakage circuit To measure the time from ignition after the arc related with
breakers for the purpose of preventing various electric electrical fires directly occurs, Carbonized Path Arc Clearing
accidents. Until now, the function of overcurrent protection Time Test presented in UL 1699 standard was performed [7]-
has been added for keeping residential areas safe from [11]. Experimental device is composed of two parts as shown
overload electric fires. in Fig. 3. One is for forming a carbonized path on specimen
Fig. 2 is a traditional time-current characteristic of 20A wire as shown in Fig. 3 (I). The other is for carbonized path
circuit breaker [6]. This time-current curve can be divided by arc clearing time test of series arc fault in the wire in Fig. 3
two parts. On the basis of the wire protection cure, the upper (II). The experimental device is comprised of power source,
right side is the area that a circuit breaker is able to work well wire specimen, oscilloscope, switches and incandescent lamp
when overcurrent such as overload or a short circuit accident to make sure whether arc path is generated well in Fig. 4.
happens. But the below left two sides both region 1 and 2 of Especially UV signal detection system is made to measure the
the curve is the area that a circuit breaker cannot detect the time that cotton on the wire is ignited by the series arc [11].
faults, especially series arcs because of comparably lower
currents. This area which is marked by region 1 and 2 means
series arcs and parallel arcs respectively. Most of electric fires
have happened in these kind of circumstances which are in the
below left side of the curve. Therefore, AFCIs need to be
introduced for lowering the risks of electric fires.
Furthermore, the suitable arc clearing time should be
confirmed.

10,000

1,000
Wire Protection
Curve
100

10
Fig. 3. Schematic of experimental configuration for carbonized path arc
1 clearing time test

0.1

0.01
1 2

0.001
1 10 100 1,000 10,000
current (amperes)
1 Series arcs 2 Parallel arcs

Fig. 2. Time-current characteristic of a 20 A circuit breaker and its


protection regions

III. EXPERIMENTAL CONFIGURATION AND PROCEDURE


This section describes the experiment that a fire caused by
the arc occurrence. At first, it describes experimental Fig. 4. Photograph showing the experiment setup device
configuration and then wire specimen production process
required for experiments.

978-1-4799-2288-8/14/$31.00 © 2014 IEEE


Page 3 of 5 2014-PSEC-0380

B. Experimental Specimens C. Experimental Procedure


Wire specimens for the carbonized path arc test follow the The experimental procedure suggested in this paper is
production methods suggested in UL 1699 standard and in the composed of two steps. The first step is for making
manner similar to the method explained in [3], [7], and [10]. carbonized path on the specimen. In this process, high voltage
The currents used in this experiment are 5, 10, 20 and 30 A, and low current need to be set as an experimental condition.
respectively and each current is used by making 50 wires. The The second step is the simulated fires out procedure. When
specimens are produced by the following procedures. load current flows through the carbonized path, fires can be
2
• Step 1) Cut two strands of 2.5mm HIV to the length of ignited by arcing.
8 inch (203mm), and then wind a tape at both ends of • Step 1) Fig. 6 shows a 220/15,000V, 30mA rated neon
the wires. transformer that is used as high voltage source for
• Step 2) Set both ends of the wire apart. One end of the creating a carbonized path on specimen wire.
wires removes sheath of the HIV about 1/2inch(12.7 ㎜) Practically, a carbonized path is also able to be
in order to connect power. generated in low voltage condition, but it tends to take
• Step 3) In the middle of the sample, make a scratch at a long time. That is why 7,500V which is boosted by
the coating of electric wire with a knife to generate the neon transformer is utilized to make the
carbonized path. At this time, be careful not to damage experimental process effective. The current of 30mA or
the conductor. less is set as a condition because carbonized paths can
• Step 4) At the point of the cut insulation, make double be damaged or even those paths may not be generated
wrapped with PVC insulation tape, and then complete in high current flowing situation. Fig. 7 (a) is the
the sample wrapping fiberglass tape over it again. specimen without a carbonized path, and Fig. 7 (b) is
the specimen with a carbonized path generated by the
experimental procedure.

220V
Mg - 1
2.5 mm2 60Hz
HIV cable
SPECIMEN

220/ 15000V
(a) 30m A

Fig. 6. A part of the experimental circuit to create a carbonized path on


specimen wire

(b)

Double wrapped
(a) (b)
with PVC insulation tape
Fig. 7. Two specimen wires. (a) before the carbonized path was formed, (b)
after the carbonized path was formed
(c)
• Step 2) After the carbonized path production is
confirmed at the sample, configure the experimental
device with a sample wire as shown Fig. 8. After then,
put a piece of cotton on the scratched part already
Double wrapped
wrapped by tape as shown Fig. 9(a). It sets the
with fiberglass tape condition that fire can occur when arc generates.
Measure the current and voltage according to changes
(d) the magnitude of load current using the arc generating
device. And measure the arc generating time and initial
Fig. 5. Procedure of experimental specimens, 75℃, 2.5 ㎟ HIV wire
ignition time using UV detection system as shown Fig.
9 (b).

978-1-4799-2288-8/14/$31.00 © 2014 IEEE


2014-PSEC-0380 Page 4 of 5

the ignition time of a cotton piece by faults arcing. This UV


sensor is a device to sense ultraviolet radiation emitted during
arcing. The arcing time and ignition time by arcing can be
measured well, because this device is characterized by high
level of accuracy. UV radiation is showed like ignition time
signal of Fig.10 through UV sensor controller. Ignition time is
defined as the time from an arc starting point to an ignition
starting point. In this condition, an ignition starting point
means the very first point of continuous ultraviolet sensor
output. Before the ignition is started on a piece of cotton,
Fig. 8. A part of the experimental circuit for carbonized path arc clearing output signal does not show up. After the ignition starts, the
time test for series arc fault continuous output signal shows.
B. Ignition Arc Energy
We analyzed the arc energy that contributes to ignition
from arc occurrence on the wires. Fig. 11 shows the
instantaneous power during the time from initial arc starting
to ignition starting. The amount of energy released during
half-cycle varies with each current magnitude. But it is
(a) (b) revealed that those are about the same of average total arc
Fig. 9. Experimental procedure for arc clearing time test of series arc fault energy as being about 150 J released during ignition time
shown in Fig. 12.
IV. IGNITION ANALYSIS OF SERIES ARC FAULT
P(t) Ignition Time

A. Output Signals
When arc occurs, arc voltage is generated at both ends of 30A

the specimen. Also shoulder electric potential appears in the ●●●


7.8
input current, and current level is reduced. Fig. 10 shows T (ms)

input voltage, input current, arc voltage and UV sensor output Ignition Time

measured by oscilloscope.
●●●
20A

4.5
Pre-fault Post-fault
T (ms)

Ignition Time

10A
●●●
2.5

T (ms)
Ignition Time
5A
1.4 ●●●

T (ms)

Fig. 11. Instantaneous power for the time to ignition

Arc staring Ignition staring

Fig. 10. Output Signals of series arc fault for ignition time measurement

This experiment had been conducted by utilizing a similar


way to UL 1699 standard [3]. Input voltage was supplied as
220V. Respectively 5A, 10A, 20A and 30A were set as the
input current that flows through a purely resistive load. The
specimen wires for this experiment were used as 75 ℃
2.5mm2 HIV wires, because these are the most widely used as
residential electric wires in Korea. This experiment was Fig. 12. Average total arc energy for the time to ignition
performed as 50 times per each of the currents.
Especially, an ultraviolet sensor was applied to measure

978-1-4799-2288-8/14/$31.00 © 2014 IEEE


Page 5 of 5 2014-PSEC-0380

C. Ignition Probability order to prevent electrical fires and introduce the AFCIs. In
Table I presents the standard for arc clearing time Korea, the introduction of AFCIs is just around the corner.
specified in UL 1699 [3]. In order to apply the standard in UL However, it seems to be difficult to introduce AFCIs and
1699 to the Korean industrial standards, it is important to commercialize them in short time. That's because there is no
compare the arc clearing time in UL standard and the ignition standard about arc interruption. Besides, Voltage reference
probability shown in Fig 13. and types of wires are all different with North America. It
means it is definitely hard to apply the UL 1699 standard in
TABLE I
ARC CLEARING TIME SPECIFIED IN UL 1699 STANDARD FOR 120V AFCIS domestic electric environment.
This paper analyzed ignition characteristics and
Load Current probabilities related with series arcs using HIV wires at 220V.
5 10 15 22.5 30
of UL 1699 [A]
The arc clearing time provided by UL 1699 standard was
Arc Clearing Time
1 0.4 0.28 0.16 0.11 analyzed based on domestic condition and compared with the
of UL 1699, [s]
newly suggested clearing time. As supporting a conclusion,
Fig. 13 shows the cumulative ignition probability obtained the ignition probability graph helps to suggest the suitable arc
by ignition time for the currents of 5A, 10A, 20A, and 30A on clearing standard on the condition of HIV wires and 220V.
the HIV wires at 220V. Fig. 13(I) is the area that is suggested The new method utilizing UV sensor system helps to measure
by UL 1699 as the arc clearing time. This result supports the ignition time with high level accuracy. If more samples can be
conclusion that just applying the UL standard is not used in the same procedures, much more accurate arc clearing
appropriate in domestic electrical environment because of a time would be drawn as a conclusion. This approach expects
high probability of ignition by more than 50%. to help setting a new arc clearing time in domestic
environment over the long range aim.

ACKNOWLEDGMENT
This work was supported by the New and Renewable
Energy program (No. 2011T100200064) of the Korea
Institute of Energy Technology Evaluation and Planning
(KETEP) grant funded by the Korea government Ministry of
Knowledge Economy.

REFERENCES
[1] A Statistical Analysis on the Electrical Accidents in 2011, Korea
Electrical Safety Corporation, 2012.
[2] George D. Gregory, Kon Wong, and Robert F. Dvorak, "More About
Arc-Fault Circuit Interrupters," IEEE Transactions on Industry
Application, Vol. 40, No. 4, pp. 1006-1011, 2004.
[3] D. Kolker, S. Campolo, N. Disalvo, "A study of Time/Current
Characteristics of the Ignition Processes in Cellulosic Material Caused
Fig. 13 Cumulative probability of ignition for HIV wire at 220V by Electrical Arcing for Application in 240V Arc-Fault Circuit
Interrupters", IEEE Holm Conference Proceedings on Electrical
It is expected to be utilized to establish the standard of the Contacts, Pittsburgh, PA. pp. 105-114, Sept. 2007.
arc interruption time on the AFCI. Using this cumulative [4] J. C. Engel, "Combination AFCIs: What the will and will not do," in
Electrical Safety Workshop (ESW), 2012 IEEE IAS, 2012, pp. 1-18.
probability graph, the suitable arc clearing time on 220V HIV [5] IEEE Standard Dictionary of Electrical and Electronics Terms, IEEE
wires is shown in Table II. Considering the margin that AFCI Std. 100-1996
can operate, the 15% of ignition probability was set as a basis. [6] George D. Gregory, Gary W. Scott, “The Arc-Fault Circuit Interrupter:
An Emerging Product,” IEEE Transactions on Industry Application,
In addition, Fig. 13 (II) represents the arc clearing region vol. 34, no.5, pp.928-933, September/October 1998.
suggested in this paper. [7] Underwriters Laboratories Inc. UL 1699, “Arc-Fault Circuit
Interrupters,” May, 2003
TABLE III [8] Sun-Bae Bang, “Analysis Method for Series Arc Fault Current using
DERIVED ARC CLEARING TIME FOR HIV WIRE AT 220V Approximation Coefficients of Discrete Wavelet Transform,” Ph.D.
Load Current Ignition probability Arc clearing time dissertation, Kangwon National University, 2009
[9] J.J. Shea, "Conditions for series arcing phenomena in PVC wiring,"
[A] [%] [s] IEEE Trans. Compon. Packag. Technol. Vol.30, no.3, pp.532-539,
5 15 0.35 Sep. 2007.
10 15 0.2 [10] J.J. Shea, "Comparing 240 Vrms to 120 Vrms Series Arcing Faults in
20 15 0.15 Residential Wire," 54th IEEE Holm Conference Proceedings on
30 15 0.05 Electrical Contacts, Orlando, Florida. pp. 218 - 224, 27-29 Oct. 2008.
[11] Won-Sik Ko, Won-Sik Moon, Sun-Bae Bang, Jae-Chul Kim,
“Analysis of Ignition Time/Current Characteristics and Energy when
V. CONCLUSION Series Arc-Fault Occurs at Rated 220V,” Trans. KIEE, Vol.62, No.8,
pp.1184-1191, 2013
In North America, they established UL 1699 standard in

978-1-4799-2288-8/14/$31.00 © 2014 IEEE

You might also like