Professional Documents
Culture Documents
Loose Connection
Xin Zhou, Senior IEEE Member Thomas J. Schoepf, Senior IEEE Member
Innovation Center Innovation Center
Eaton Corporation Eaton Corporation
Pittsburgh, PA Milwaukee, WI
USA USA
xinzhou@eaton.com thomasjschoepf@eaton.com
Abstract - Overheated electrical joints due to loose 100 A up to 5000 A. The tightening torque of the busbars
connection are often precursors of electric fires, arc faults, bolts (responsible for the contact force), the amplitude of the
and arc flash in electrical systems. load current (indicating the electrical stress level), and the
This paper is about the formation mechanism and behavior sizing of the joint (proper design for the level of stress) were
characteristics of loose connection induced overheated found to have a major impact on the time it takes to form an
electrical joints. Specific experiments were conducted on overheated contact.
busbar joints and systems with currents ranging from 100 A
up to 5000 A. The lead time of the overheated contact
formation is significantly impacted by the tightening torque 2. Experimental Setup
of busbar bolts, the amplitude of current, and the proper
sizing of electrical joints. The investigations were conducted on two different types of
bolted connections to cover a wide current range:
Key words: Loose connection, overheated contact, electrical
• 250-A-Panelboard-Busbar (Fig. 1), and
fire, arc fault, arc flash, electrical system
• 3000-A-Medium-Voltage-Switchgear-Busbar
(Fig. 3).
1. Introduction
Loose connections in electrical systems may be precursors T1 thermocouples is clamped
to arc faults and electrical fires. They may not only cause Thermocouples between the bolt washer and
equipment damage, but also lead to personal injuries and the short busbar
AC Power Supply
even the loss of life. Numerous investigations have been Short busbar
conducted with respect to overheated electrical connections
I
due to loose connection, corrosion, current cycling, and V Bolt
Acoustic Sensor
thermal cycling [1]-[15]. Overheated electrical joints not
only occur in residential applications [1]-[6], [14], but also T4 T3 T2 T1
in commercial and industrial applications [3], [8]-[10], [15].
Most common practice in industry to prevent overheated Loose
electrical joints from escalating into arcing faults, arc flash Long busbar connection
or electrical fire is preventive maintenance through Data Recorder
regular(e.g. annual) thermal scanning and re-torque of the
connection bolts. Thermocouples were also used to monitor
temperature in the vicinity of electrical joints [10]. Figure 1: Test setup of loose connection thermal test using a
Technologies have been previously investigated to detect 250-A-panelboard
loose electrical connections using acoustic sensing and
reflectometry [16]-[19]. The often-encountered perception
that a loose connection immediately turns into an overheated
contact interface doesn’t prove correct in every case. In A loose connection was established by reducing the
fact, a loose connection in the context of the investigated tightening torque of the bolt below the specified value close
busbar joints can still provide good electrical contact for a or equal to zero (see next section for details). The
period of time before its contact temperature starts to rise. temperature at different locations in the vicinity of the
In this paper, the formation mechanism and characteristics connection under test was measured with thermocouples
of loose connection induced overheated contact interfaces (Figures 1, 2). An acoustic sensor, such as described
will be discussed in detail employing acoustic signal and previously in [16] was placed onto the busbar to pick-up the
temperature measurement. Specific experiments were acoustic signal induced by the overheated contact interface
conducted on busbar joints with currents ranging from from the loose connection. In the event of overheating, i.e.
Acoustic Sensor
Data Recorder
Thermocouples
120 70
current
60
(a)
100
80 50
Temperature (C)
temperature 1
Current (A)
60
40 Thermocouple
temperature 2
temperature 3 30
40
Loosened
temperature 4 20
20 bolts
10
0
0
-1 0 1 2 3 4 5 6 7 8 9
Time (hrs)
The temperature gradient around the panelboard busbar joint Figure 3: Temperature rise tests with aloose connection at
was measured with four thermocouples at different locations one end of a medium voltage switchgear busbar: (a) busbar
on busbar (Figure 1). All sensors were clamped between connection to the switchgear with acoustic sensor mounted
bolt washers and the busbar. As shown in Figure 1, Sensor on the busbar; (b) close-up view of the loose connection at
1 was placed at the location of the loose joint. Sensors 2, 3 one end of the busbar
and 4 were mounted two inches, eight inches and eleven
inches away from the loose joint, respectively. The acoustic
sensor was mounted on a busbar connected by a cable to one In the case of the medium voltage busbar connection, only
end of the 3-phase long busbar (see Figure 1). one thermocouple was mounted on the cable connecting
Authorized licensed use limited to: CURTIN UNIVERSITY. Downloaded on January 07,2022 at 01:11:36 UTC from IEEE Xplore. Restrictions apply.
plate in the vicinity of the loose joint. The acoustic sensor from the bolt,measured minimum temperature rise, as
was mounted directly onto the tested busbar (see Figure3). expected.
Step-increase of temperature
3. Results and Discussions 120 at loose joint 70
The results are presented in the following sections with 100 Current 60
respect to the major parameters impacting the formation of
80 50
Temperature (C)
an overheated contact.
Current (A)
40
60 Temperature 1
Temperature 2 30
3.1. Tightening Torque 40 Temperature 3
20
The electrical joint showed negligible temperature increase 20
Temperature 4
12 Current
60
100
Temperature 1
10 50
80
Temperature (C)
Current (A)
8 Temperature 2 40
60
Temperature 3 30
6 40
Temperature 4 20
4 20
30 in-lb 24 in-lb 18 in-lb 12 in-lb 6 in-lb 10
Bolt Torque 0
0
-1 0 1 2 3 4 5 6 7 8 9
Figure 4: Average temperature rise (ΔT) during the first 8- Time (hrs)
hour thermal test for different tightening torques
Figure 6:Current and temperature profiles of the panelboard
loose connection on day 19
The first significant temperature rise (ΔT=25 °C) was
noticed right at the joint (temperature sensor 1, Figure 5) on
the 6th day of the 43-day test. No acoustic signal was During day 21, a sudden dramatic decrease of the joint
generated at that time. This indicates deteriozation at the temperature could be observed. This may be due to
contact interface due to oxidation, which led to higher softening of the contact spot caused by the high temperature.
contact interface temperature further accelerating the It produced a larger contact area and consequently led to
oxidation process. Such a temperature riseoccuredfour much lower constriction resistance (see Figure 8). This
times before acoustic signal was generated by anoverheated cycle of significant rise of joint temperature followed by a
contact interface.The thermocouple T4, eleven inches away large decrease of temperature occurred 2 times during the
43-day testing period. During the second cycle, no acoustic
Authorized licensed use limited to: CURTIN UNIVERSITY. Downloaded on January 07,2022 at 01:11:36 UTC from IEEE Xplore. Restrictions apply.
signal was generated, and the temperature T1 at the loose
joint was below 50 °C. This means that no melting of the
contact spot occured. However, the softening of the
oxidized contact spot led to the collapsing of the contact Acoustic signal
resistance due to large contact surface area or formation of
another contact spot.
Current
Voltage
Acoustic signal
Current
Voltage
Figure 9: Acoustic signal detected on day 21indicating
melting contact spot
80
(in-lb)
Current (A)
Temperature 2 40
60
Authorized licensed use limited to: CURTIN UNIVERSITY. Downloaded on January 07,2022 at 01:11:36 UTC from IEEE Xplore. Restrictions apply.
36 °Cwhen acoustic signal ocurred and was still rising. current reaches a few thousand amps. Figure 10 depicts the
This is much lower than that of a fully tightened busbar joint constriction force as a function of current. This means that
at rated torque and current. A comparison between the the constriction force might be able to push the busbar joint
medium voltage busbar thermal tests and the low voltage apart against the contact force, increasing the constriction
panelboard thermal tests isshown in Table III. It must be resistance, and in turn raising the constriction temperature
emphazised that even though the bolts were completely resulting in the formation of a molten metal bridge.
loosened (0 in-lb) at the medium voltage busbar thermal
Table III also lists the time durations leading to detection of
test, there was still contact force exerted due to the weight of
overheated contact interface by the acoustic sensor, the
the electrical cables. At these high current levels, the
temperature T1 at the busbar joint at the time of detection,.
contact spots may not have been completely oxidized within
At 5000 A, the busbar surface temperature at the busbar
such ashort period of time. The reduction of contact force
joint was only 36 °Cat the time of detection. The formation
and the increased constrcition force at the contact interface
of overheated contact interface occured before the busbar
most likely led in the end to a molten bridge at the contact
joint reached its equilibrium temperature. This
interface.
demonstrates that improper sizing of busbars and cables, or
too high over-current stress will lead to rapid formation of
overheated contact spots. Whereas at 3000 A, the busbar
3.3. Constriction force
surface temperature at the joint was measured 56 °Cat the
As the current passing through the electrical joint increases, time of detection. This is about 7 °Chigher than that
the constriction force across the contact spot increases. The withfully tightened bolts (30 in-lb).
constrcition force can be expressed by the following
equation [7]:
4. Summary and Conclusions
μ ⋅ I2
Fconstriction =
4 ⋅π
( )
⋅ ln r H ⋅ π / Fc , Specific experiments on different types of bolted busbar
jointswere conducted to investigate the formation
where μ is the permeability of free space (μ=4·π·10-7H/m), mechanism and characteristics of loose connection induced
H is the contact material hardness [N/m2], F is the contact overheated electrical contacts. The formation of overheated
force [N] and I is the current (A). contact interfacescould experimentally simulated and
confirmed by detecting their acoustic signal propagating
through busbars.
30
Test results show that the formation of overheated contact
25 interface is significantly impacted by:
Constriction Force (N)
Authorized licensed use limited to: CURTIN UNIVERSITY. Downloaded on January 07,2022 at 01:11:36 UTC from IEEE Xplore. Restrictions apply.
Table III: Effect of current and torque on the formation process of loose connections
Test Current Device Tested Status of Loose Time led to detection Temperature at electrical joint when
(A) Connection detection occurred
Authorized licensed use limited to: CURTIN UNIVERSITY. Downloaded on January 07,2022 at 01:11:36 UTC from IEEE Xplore. Restrictions apply.
Xin Zhou (M’96-SM’03) received the Ph.D. degrees Thomas J. Schoepf received the Dipl.-Ing. (MS) and
in Mechanical Engineering from the University of Dr. techn. (Ph.D.) degrees in electrical engineering
Minnesota, Minneapolis, in 1995. From 1995 to from the Vienna University of Technology, Austria, in
1996, he was with Phoenix Solutions Company as a 1991 and 1994 resp. From 1992 to 1994, he was with
plasma technology specialist responsible for the Institute of Switching Devices and High Voltage
developing and designing plasma torch systems for Technology at the Vienna University of Technology.
waste remediation. He is currently a principle In 1995 he joined Siemens AG, Electromechanical
engineer at the Innovation Center of Eaton Components, Berlin, Germany, which later became
Corporation. His research projects include arcing Tyco Electronics EC. He was Manager of Material
phenomena, next generation product development in power control and Engineering before he moved on to Delphi Research Labs, Michigan,
distribution, optical emission spectroscopy and plasma enhanced material U.S.A. in July 2000. He held the position Chief Scientist and led the
processing. He is the recipients of both 2008 and 2010 Eaton Innovation Connection Systems Group. He was R&D Laboratory Manager at Delphi
Award. He has 34 patents issued or pending and published over 30 Journal Mechatronic Systems, Langenlonsheim, Germany from 2005 to 2006. In
and conference papers. He is a senior member of IEEE and has served as a Oct. 2006 he accepted his current position as senior manager engineering
member of various committees of IEEE Holm Conference. He is a technology with Eaton Corp. leading the Power Systems and Architectures
recipient of the IEEE-CHMT Graduate Fellowship Award for Research on Department of Eaton’s Innovation Center in Milwaukee, USA. He was the
Electric Contacts for 1991-1992. He is also the recipient of both the 1993 chairman of the committee "Contact Behavior and Switching" of the
and the 2003 IEEE Erle Shobert Prize Paper Award. German Association for Electrical, Electronic and Information
Technologies (VDE) from 1998 through 2007, and he represented Germany
as a member of the Advisory Group for International Conferences on
Electrical Contacts until he was nominated Honorary Member in June
2008.
Authorized licensed use limited to: CURTIN UNIVERSITY. Downloaded on January 07,2022 at 01:11:36 UTC from IEEE Xplore. Restrictions apply.