You are on page 1of 12

Building and Environment 102 (2016) 116e127

Contents lists available at ScienceDirect

Building and Environment


journal homepage: www.elsevier.com/locate/buildenv

Evaluation of thermal comfort in an historical Italian opera theatre by


the calculation of the neutral comfort temperature
P. Ricciardi a, *, A. Ziletti b, C. Buratti c
a
Department of Civil Engineering and Architecture, University of Pavia, Via Ferrata, 1, 27100 Pavia, Italy
b
Alessandro Ziletti Engineering Studio, Via Fontane, 26/D, 25133, Brescia, Italy
c
Department of Engineering, University of Perugia, Via G. Duranti, 67, 06125 Perugia, Italy

a r t i c l e i n f o a b s t r a c t

Article history: Theatres are a very complex environment where thermal comfort is difficult to control. They frequently
Received 2 February 2016 operate at high occupancy level and tend to have high sensible and latent heat loads. An application of
Received in revised form the neutral comfort temperature methodology is proposed to analyze this particular kind of building.
10 March 2016
Thermal-hygrometric parameters defined in ISO 7730, Ashrae Standard 55/2004 and ISO 10551, were
Accepted 12 March 2016
Available online 15 March 2016
measured at carefully selected locations in the occupied zone within the auditorium in the Fraschini
theatre, in order to ensure a good representation of human exposure to thermal comfort. In addition, a
subjective evaluation was achieved by the distribution of a dedicated multiple response questionnaire.
Keywords:
Thermal comfort
More than 400 questionnaires were analyzed, comprehensive of information for the application of the
Theatre traditional static and adaptive model. When heating system is on (1st and 2nd survey), thermal strati-
Neutral comfort temperature fication is really relevant in the theatre (air temperature runs from 23  C in the stalls area to 30  C in the
Questionnaire upper order), while when the theatre is in naturally ventilated, the thermal stratification is not relevant.
An application of a new thermal comfort evaluation method is here proposed by means of the calculation
of the neutral comfort temperature with both the analytical and adaptive methods. . The methodology
was also applied to data acquired in 9 different open space offices, where a total amount of 846 people
were interviewed. Results showed that the method is applicable to both theatres and open plan offices
and could provide a simple tool to quickly evaluate thermal comfort conditions.
© 2016 Published by Elsevier Ltd.

1. Introduction Papakonstantinou et al. [1] only based on computational fluid dy-


namics (CFD) modelling scenarios, evaluated how two ventilation
Theatres usually have high heat loads, which are of a transient systems with the same air inlet arrangement, but different systems
nature as audiences come and go, and from lighting which changes of air extraction, affected the air speed, temperature and CO2 con-
from scenes to scenes, and also their occupancy can vary from centration profile inside the teaching auditorium. The conclusion,
completely full or nearly empty, depending on performances. not surprisingly, was that the lowest rate of air change leads to the
Furthermore, unlike other building types, the use of opening win- increase of temperature. Furthermore, it was found that CO2 con-
dows for air intake and extract ventilation is not possible, requiring centration decreases rapidly if the ventilation rate is increased, in
a different approach. Air must be distributed over a wide area, both this case by the unexpectedly large factor of five. Another study,
within the auditorium and the stage, with numerous supplies and only based on computational fluid dynamics, was conducted by
return registers. All these factors place constraints on the ventila- Stamau et al. [2], in order to evaluate thermal comfort conditions in
tion design, and if it is poor, it can led to the deterioration of indoor the indoor stadium of the Galatsi Arena, which hosted the sports of
air quality and thermal comfort. There is some useful Literature on rhythmic gymnastics and table tennis during the Olympic Games
thermal comfort performance in theatres. A study of Athens 2004. Calculated PMV and PPD values showed that thermal
conditions were very satisfactory for air temperature of 16  C with a
percentage minor of 7% of the spectators was expected to be
slightly uncomfortable.
* Corresponding author.
E-mail addresses: paola.ricciardi@unipv.it (P. Ricciardi), alessandroziletti@gmail.
A more comprehensive assessment methodology was devel-
com (A. Ziletti), cinzia.buratti@unipg.it (C. Buratti). oped by Cheong and Lau [3], and applied to indoor air quality and

http://dx.doi.org/10.1016/j.buildenv.2016.03.011
0360-1323/© 2016 Published by Elsevier Ltd.
P. Ricciardi et al. / Building and Environment 102 (2016) 116e127 117

thermal comfort in lecture theatres in Singapore. A questionnaire cubic metres. The theatre has a typical Italian horseshoe shape with
survey was carried out in the lecture theatre a few weeks prior to 5 orders balconies. In Fig. 1 the plan of the theatre is presented.
monitoring campaign. Despite the fact that all the thermal comfort The building was object during the years of different actions of
parameters were within the range limit, the occupant survey maintenance, but the most important restoration took place in
showed that more than 20% of the occupants were not satisfied 1985 and interested the whole theatre. Recently, in 2010, the
with thermal comfort. Furthermore, the authors concluded that the wooden floorboards of the parterre were completely renewed and
air conditioning system was unable to cope with the peak occu- the internal surfaces of some balconies were restored, in order to
pancy load. regenerate the “marmorino” decorations.
Another review [4] focused on thermal comfort and indoor air In Fig. 2a and b interiors of the Fraschini theatre are shown.
quality in a lecture theatre with a 4-way cassette air conditioning The theatre has an air building service having a total power of
and mixing ventilation system. This showed that increasing the 1220 kW and delivering 41,000 m3/h of air. The heating of the
discharge angle from the supply grilles on the cassette unit makes parterre is provided by jet-nozzles diffusers situated in the fifth
uniformity of thermal comfort worse, but rarely affects the indoor order of seats. The hot air is then recollected by grilles situated at
air quality. A very comprehensive evaluation was carried out by every floor. In Fig. 3 is possible to see the nozzles and their position
Kavgic et al. [5] on the thermal comfort and indoor air quality in the in the theatre.
mechanically ventilated theatre of Belgrade. The analysis based on
the results of monitoring and modelling as well as the assessment 3. Methodology
of comfort and health as perceived by occupants showed that the
environmental parameters were within the standard limits. How- Thermal comfort in the Fraschini theatre was evaluated with
ever the calculated ventilation rates showed that the theatre was analytical-objective method by means of experimental surveys and
over ventilated, which has serious consequences for energy con- questionnaires, in order to obtain information about the subjective
sumptions, and the displacement ventilation arrangement perception of the audience.
employed led to higher than expected complains of cold discom-
fort, probably due to cold draughts around the occupants feet. The 3.1. Questionnaire surveys
problem of air distribution in theatre was also recently developed
by Cheng et al. [6], who presented simulation results for the design The questionnaire given to the audience was very similar the
of a stratified air distribution system in a large space lecture theatre. one used by Buratti et al. and Nematchoua et al. [12e16], which
Results revealed that the best satisfied thermal environment was comply with ISO 10551 [17] and it is composed by three parts; in
obtained when supplied air from floor level, terrace and desk edge the first one the interviewed person fills information regarding age
mounted grilles simultaneously. A specific underfloor air distribu- and sex, in the second one evaluations of temperature and air
tion (UFAD), which is typically just used in office buildings, was speed, overall thermal comfort sensation and the presence of local
investigated for a huge theatre space with high ceiling by Kim et al. discomfort feelings. There is also a part in which people provide
[7]. Considering the performance not only for energy saving but information about their dressing and, by means of this data, it is
also for thermal quality, the UFAD system appears to offer many possible to estimate the corresponding thermal resistance. The last
advantages, however additional research is needed on key variable, part collects information about the possibility of micro-climatic
such as location and kind of diffusers, distance between diffusers, control and the satisfaction of the interviewed people about these
configuration of buildings and height in order to put the system possibilities. In this part occupants had to indicate their position on
into practise. The above scientific reviews show the great the theatre's plan (see appendix A of [15]).
complexity for obtaining adequate comfort performance, both By processing information acquired from the questionnaires, the
perceived and measured, in theatres. None of all the cited scientific following data were elaborated:
works showed a simple method to quickly evaluate thermal com-
fort conditions in this particular type of environment.  average age of the sample and number of interviewed people;
Other papers consider thermal comfort studies in climate con-  Predicted Mean Vote (PMV);
ditions focussing on other kind of buildings: DiasPereira et al. [8]  Percentage of people that consider the theatre not thermally
studied the thermal comfort in a Portuguese class-room, Con- acceptable (TUI);
ceicao et al. [9] developed an adaptive comfort model in a kinder-  Percentage of people that consider the theatre not thermally
garten in Portugal, Asit Kumar Mishra et al. [10] proposed an comfortable (TAI);
adaptive thermal comfort model for the tropical climatic regions of  Percentage of people that consider the speed of air movements
India and Manu S. et al. [11] presented a single adaptive model for not acceptable (UAMI);
office buildings across India asserting its validity for both naturally  Thermal resistance of the clothing of the audience;
ventilated and air-conditioned modes.  Percentage of people that feels discomfort caused by too big
In the present study, in order to analyze the level of thermal difference between the temperature at their head height and
comfort in a typical eighteen century Italian horseshoe shape the temperature at heir ankle height. (UVTGI).
theatre, with 5 orders balconies, a comprehensive evaluation study
was carried out in the Fraschini theatre of the city of Pavia, in both
mechanical and natural ventilated conditions. In addition the 3.2. Experimental surveys
method of the neutral comfort temperature was applied to the
theatre. The experimental measurements were conducted with the
same methodology and instruments used formerly in previous
2. The Fraschini theatre studies [12e15]. In particular it was employed a Babuc eA storage
acquisition system that fulfils the requirements of ISO 7726 [18]
Thermal comfort in the Fraschini Theatre, located in the city of and that is made by LSI Lastem. Its acquisition rate can vary from
Pavia (Italy), was experimentally investigated. The construction of 1s up to 24 h and, after downloading the data on a personal
the building ended in 1773. computer.
The plan surface is 340 square metres and its volume is 7200 The thermal-hygrometric parameters that was detected are
118 P. Ricciardi et al. / Building and Environment 102 (2016) 116e127

Fig. 1. Plan of Fraschini theatre.

those defined in ISO 7730 [19] Ashrae Standard 55/2004 [20], and parameters:
ISO 10551 [17].
Three measurement campaigns were carried out: on January,  Dry bulb air temperature (operative range 50 to þ 80  C,
March, and May 2011. Accuracy ± 0.17  C);
Fig. 4 shows the different points of acquisition of the environ-  Wet bulb air temperature (operative range 50 to þ 80  C,
mental parameters: - indicates the January surveys,  the March Accuracy ± 0.17  C);
ones, and x the May ones, respectively.  Dew point temperature (operative range 50 to þ 80  C,
In particular the probes allowed monitoring the following Accuracy ± 0.17  C);
P. Ricciardi et al. / Building and Environment 102 (2016) 116e127 119

Fig. 2. a. Interior views of Fraschini theatre. b. Interior views of Fraschini theatre.

 Average radiant temperature (operative range 50 to þ 100  C, measure the temperature and the relative humidity of the external
Accuracy ± 0.17  C); air. The mean values of the outdoor temperatures were respectively
 Average air flow speed (operative range 0 to 50 m/s, Accuracy 5.3  C, 4.0  C and 17.8  C during the monitoring periods: these
±0.05 m/s for va ¼ 0e0.5 m/s, ±0.1 m/s for va ¼ 0.5e1.5 m/s, ±4% values can be considered representative of two different seasons
for va >1.5 m/s); (winter and spring). The Data Ohm DO9847 device was also utilized
 Temperature of the floor surface (operative range 50 to assess the thermal stratification in the main hall. The measure-
to þ 80  C, Accuracy ± 0.17  C); ments were carried out over three evenings, during a theatre per-
 Temperature of the air at the height of ankle and neck (operative formance. HVAC system was functioning during two sessions, while
range 50 to þ 80  C, Accuracy ± 0.17  C). it was turned off during the last session, since it was spring time,
and the theatre was in naturally ventilated conditions. The first
It was also used a portable data logger Data Ohm DO9847 to campaign took place on 12 January 2011, and in that occasion the
120 P. Ricciardi et al. / Building and Environment 102 (2016) 116e127

Fig. 3. Diffusers position on the fifth order.

Fig. 4. Measurement points on the parterre (left) and on the I, II, III IV order balcony (right): square points were in January, round points in March, cross points in May.

data logger Babuc collected measurements in five different posi- balconies of the first order, so the questionnaires provided infor-
tions in the parterre. mation about the comfort of just these positions. In Fig. 5 it is
During this day the audience was only in the parterre and in the possible to see the Babuc storage acquisition system during the
first order balconies, so information from the questionnaires where measurement campaign in the parterre and in a balcony.
deduced just for these occupied places.
The second surveys were performed on 2nd march 2011 and
that time the Babuc was used in the parterre and in the upper or- 4. Results
ders. The audience occupied the whole theatre and the question-
naire where given in each of them. During the three days of surveys a total amount of 409 ques-
The last day of measurements was 4th May 2011. The mea- tionnaires were collected for processing: 165 questionnaires were
surements with the Babuc were taken from the parterre and from filled by male and 244 by females.
the upper orders. The audience was in the parterre and in the Most of the audience is in the range between 30 and 50 years,
but also the samples composed by people with less than 30 and
P. Ricciardi et al. / Building and Environment 102 (2016) 116e127 121

Fig. 5. BABUC storage acquisition system during the measurement campaign in the parterre (on the left) and in a balcony (on the right).

more than 50 years were consistent. The percentage of not satisfied people is lower than 15%, both for
In Fig. 6 the composition of the sample classified by day of the overall thermal sensation and the local gradient of temperature.
measurements, gender and age is represented. The results from the surveys are reported in Table 1.
During the first survey, questionnaires data, all referred to the The instrumental measurements confirmed that, when heating
parterre, revealed that thermal sensation was oriented towards hot. system is in function, thermal stratification is really relevant in the
In fact the male people reported an average PMV of 0.8 and female theatre. In fact during the first two surveys the temperature runs
people an higher value of 1.69. Less than 5% of people considered from 23  C in the parterre to 30  C in the upper order. As seen from
the theatre thermally not acceptable. For the 41% of the male the questionnaires this causes serious problems for the thermal
sample and for the 36% of the female sample the conditions were acceptability of the audience that sits in the upper places.
satisfactory. Less than 15% of the audience felt discomfort caused by When the theatre is in naturally ventilated conditions the
local temperature gradient. thermal stratification is not relevant.
During the second survey, questionnaires were also distributed The reason for this stratification that causes discomfort to the
in the upper balconies and this allowed to put in evidence the audience, has to be found on the air emission system: the jet
problems caused by thermal stratification. In fact the PMV in- nozzles situated only in the upper order doesn't allow an uniform
creases with the height of the balcony order, varying from almost temperature field to be reached in the whole theatre.
neutral values in the parterre to values of 1.6 in the forth order. This In Fig. 7 the temperature in the different places of the theatre
is directly confirmed by the TAI index, which represents the per- during the surveys is represented.
centage of people that consider the theatre not thermally satis- The local vertical temperature gradient (at 0.010 m and 1.10 m
factory, and it varies from 21% in the parterre to almost 90% in the height) was also monitored with Babuc. According to measure-
4th order. The percentage of people not satisfied by the local ments the predicted percentage of dissatisfied people by the local
temperature gradient are higher in the upper orders, where the temperature gradient is almost zero. This agrees with the ques-
values arise to 60% for males. tionnaires' results, where the percentage of people that feel this
The third survey was conducted in naturally ventilated condi- kind of discomfort were usually about 10%.
tions and the overall thermal sensation of the audience tended to
neutral-slightly cold. This is because the heating system was not on.

Fig. 6. Questionnaire classification by day of measurements, gender and age.


122 P. Ricciardi et al. / Building and Environment 102 (2016) 116e127

Table 1
Average surveys results.

1st survey 2nd survey 3rd survey

Parterre Parterre 1st order 2nd order 3rd order 4th order Parterre 1st order

M F M F M F M F M F M F M F M F

Number of people interviewed 44 59 19 46 5 13 11 17 3 11 10 8 66 84 6 7


Average age 49 44 48 50 50 46 38 36 37 35 34 37 37,98 38,49 30,50 27,86
PMVq 0,80 1,69 0,26 0,07 0,60 0,08 0,73 0,06 1,33 0,45 1,60 1,38 0,15 0,05 0,00 0.57
TAI (%) 40,91 35,59 21,05 28,26 40,00 38,46 45,45 11,76 100,00 18,18 70,00 87,50 24,24 30,95 50,00 85,71
TUI (%) 2,27 5,08 0,00 2,17 0,00 7,69 9,09 0,00 0,00 0,00 30,00 25,00 9,09 3,57 0,00 14,29
TDI (%) 13,64 23,73 0,00 15,22 40,00 23,08 36,36 5,88 66,67 18,18 40,00 50,00 16,67 14,29 16,67 14,29
UAMI (%) 13,64 20,34 5,26 4,35 20,00 38,46 18,18 5,88 66,67 9,09 60,00 50,00 18,18 13,10 16,67 14,29
UVTGI (%) 15,91 11,86 0,00 13,04 20,00 7,69 9,09 11,76 0,00 27,27 60,00 37,50 15,15 7,14 0,00 14,29

Fig. 7. Temperature distribution in the theatre during the three surveys.

5. Discussion e a new approach to adaptive temperature previous work [13] tn becomes:

The thermal comfort perceived in the theatre varies on person's tn ¼ to  PMV=0:3879 (1)
position and on building service conditions. When the heating
system was switched off, as in the third survey, the overall thermal where to is the operative temperature, defined as the uniform
sensation of the audience tended to neutral-slightly cold and the temperature of an imaginary enclosure with which man will ex-
percentage of not satisfied people is lower than 15%. When the change the same dry heat by radiation and convection as in the
heating system was on, as in the first and second survey, the per- actual environment.
centage of people that consider the theatre not thermally satis- This calculus option was applied only to the situations in which
factory varies from 21% in the stalls area to almost 90% in the IV box PMV is within the range between 1 and þ1, which could be
seats denouncing a considerable problem of thermal stratification. considered a comfort or light discomfort zone.
Using the adaptive approach the neutral comfort temperature can
be calculated with the relation:
5.1. Optimal temperature evaluation: the “neutral comfort
temperature” tn ¼ a þ b  tamt (2)

The neutral comfort temperature “tn” is defined as the optimal where a and b are coefficients that assume different values
temperature in order to guarantee the best comfort. It could be a depending on the fact that the building is in naturally ventilated
useful tool in order to quickly estimate comfort conditions by condition or the HVAC system is on. According to Literature [21],
means of only one parameter. tn was calculated with both the the coefficients have the following values: a ¼ 18.9; b ¼ 0.255,
analytical and adaptive methods. Using the analytical method, the when the building is in naturally ventilated conditions. In case of
neutral comfort temperature “tn” is the temperature that, for a environments where heating system is in function, values are:
particular set of values of the air velocity, metabolic activity, ther- a ¼ 22.6; b ¼ 0.04.
mal insulation of clothing, relative humidity, allows the PMV to tamt is the average monthly temperature; in this work the official
become 0. In order to calculate PMV a spreadsheet with a macro Italian data defined by the standard UNI 10349 [23] was applied.
based on the BASIC routine was used as presented in the ISO 7730 By means of these two methods, the neutral comfort tempera-
[15]. Therefore with the analytical method the Neutral Temperature ture for the theatre was calculated. The value obtained with the
tn is obtained applying an artifice proposed by Griffiths [17], who analytic method was of 24  C, for the periods in which the heating
indicated that when PMV ¼ 0, to ¼ tn. Therefore, as described in a system was switched on, and 25  C, for naturally ventilated
P. Ricciardi et al. / Building and Environment 102 (2016) 116e127 123

conditions. With the adaptive method, the neutral comfort tem- whole sample, while for analytic method correlations were inves-
perature was calculated as 23  C both for naturally ventilated and tigated for the male, the female and the whole sample.
air conditioned conditions. The neutral comfort temperature values In Figs. 10e12 all the correlations are outlined when the neutral
calculated with both the methods for the three surveys are repre- comfort temperature is calculated with the analytical method,
sented in Fig. 8. respectively for males, females and both genders.
The neutral temperature values in the adaptive approach are Among all the samples, as found before, females in office during
always lower than the ones obtained by the analytical method, for winter time found the best correlation coefficient (R2 ¼ 0.88).
all the surveys. It could be due to the low values of the external In Fig. 13 correlations found when the neutral comfort tem-
temperature, especially in the first surveys (te ¼ 5.3  C and te ¼ 4  C perature is calculated with the adaptive method are shown, for
respectively) and to the related adapting behaviours of the occu- females and males together in theatre and open space offices.
pants, who could prefer lower values of the neutral temperature. With the adaptive model, the higher correlation was found in
In Fig. 9 the difference between operative temperature (to) and offices in summertime (R2 ¼ 0.557) rather than the one in the
neutral comfort temperature (tn) versus PMV (PMVq) from ques- theatre (R2 ¼ 0.48). Anyway both the methods applied for the
tionnaire for male, female, and male and female together was calculation of the neutral comfort temperatures headed to signifi-
investigated. When the neutral comfort temperature is higher than cant correlations and, as expected, the interpolation lines have
operative temperature people should feel warm and therefore positive slope. This means that, as it can be imagined, more the
PMVq is expected to be positive. Vice-versa in case of tn minor to to temperature and therefore the neutral comfort temperature are
people should feel cold and PMVq is expected to be negative. higher more the people feel warm and vice versa. It was observed
It is interesting to notice that all the correlation lines have the that, since in the offices series the slopes are lower than in winter
same slope and the only difference is the constant coefficient, time, people appear to have less sensibility for the difference be-
which is higher for female (R2 ¼ 0.667) than for male (R2 ¼ 0.438). tween optimal temperature and real temperature than in summer
This result is in accordance with the fact that [24e26] females time. This particular condition happens because in wintertime it is
usually have a lower metabolism than men, therefore, at the same easier to change clothes in order to adapt to the comfort temper-
environment thermal conditions, females perceive colder than ature, while in summertime this is not always possible, since
men. clothing in offices should fulfil formal requirements and standards.

5.2. Analysis and comparison with data collected in open space 6. Conclusion
offices
During the first survey, questionnaires data, all referred to the
In order to understand the applicability of the methodology of parterre, revealed that thermal sensation was oriented towards hot.
the neutral comfort temperature used for a particular kind of This is confirmed by experimental results: temperature in the
building, such as theatres, the above described method for the parterre a bit lower than 24  C.
calculation of the neutral comfort temperature was also extended During the second survey questionnaires were also distributed
to data collected by means of a subjective and objective measure- in the upper balconies and this allowed to put in evidence the
ment campaign in open space offices [13]. The other measurements problems caused by thermal stratification. In fact the PMV in-
campaigns took places in nine different open space offices, both in creases with the height of the balcony order, varying from almost
winter and in summer seasons, and for each day surveys were neutral values in the parterre to values of 1.6 in the fourth order.
carried out in morning and afternoon time. In these campaigns a Experimental data showed that temperature was varying from
total amount of 846 people were interviewed. 22  C in the parterre to 28  C in the fifth order.
For every office the neutral comfort temperature was calculated The third survey was conducted in naturally ventilated condi-
in the same way as the one adopted for the theatre. Correlation was tions and the overall thermal sensation of the audience tended to
differently evaluated for the series of data collected in wintertime neutral-slightly cold. This is because the heating system was off.
and the ones collected in summertime. The percentage of unsatisfied people is lower than 15%, both for the
Since adaptive model does not take into account the difference overall thermal sensation and for the local gradient of temperature.
of gender, correlations for this method were performed on the Measured temperature varied from 20  C in the parterre to 22  C in

Fig. 8. Neutral comfort temperature values calculated with analytic and adaptive methods for the three surveys.
124 P. Ricciardi et al. / Building and Environment 102 (2016) 116e127

Fig. 9. PMV from questionnaires versus difference between operative temperature and neutral comfort temperature for men, female and men and female together.

Fig. 10. PMV from questionnaire versus difference between operative temperature and neutral comfort temperature (analytical method) for males: comparison between data
acquired in the theatre and open space offices.

the fifth order. The temperature air stratification problem, evident comfort temperature by means of both the analytical and adaptive
when HVAC system is on, is probably due to the air emission system methods. PMV from questionnaire (PMVq) versus the difference
where the jet nozzles are situated only in the upper order. As between operative temperature (to) and neutral comfort temper-
previously seen from Literature survey [5e7], thermal comfort ature (tn) for men, female and men and female together, were
could be ameliorated by a better distribution of jet nozzles in all the evaluated. All the correlation lines have the same slopes and the
five orders and by the installation of a new control system for en- only difference is the regression coefficient, which is higher for
ergy and comfort management [27]. female than for men. This confirms that females, having a lower
A new approach for the evaluation of the thermal comfort in the metabolism than men, usually prefer a warmer temperature than
Fraschini theatre is proposed by the determination of the neutral men.
P. Ricciardi et al. / Building and Environment 102 (2016) 116e127 125

Fig. 11. PMV from questionnaire versus difference between operative temperature and neutral comfort temperature (analytical method) for females, comparison with data acquired
in the theatre and open space offices.

Fig. 12. PMV from questionnaire versus difference between operative temperature and neutral comfort temperature (analytical method) for females and males comparison with
data acquired in the theatre and open space offices.

The neutral comfort temperature, with the analytical and temperature could be a useful parameter to evaluate thermal
adaptive methods, was also calculated using data collected by comfort in buildings. However additional research should be car-
means of a subjective and objective measurement campaign in nine ried out in order to test the reliability of the method to other types
different open space offices. As discussed quite good correlations of buildings. In particular it would be interesting to evaluate the
have been found. utility of neutral comfort temperature buildings that differ from the
The analysis carried out in the theatre Fraschini of Pavia and in case of this study for the HAVC emission system (radiators, fan coils,
open spaces offices led to the conclusion that the neutral comfort underfloor heating system et cetera) and composition of the
126 P. Ricciardi et al. / Building and Environment 102 (2016) 116e127

Fig. 13. PMV from questionnaire versus difference between operative temperature and neutral comfort temperature (adaptive method) for females and males: comparison with
data acquired in the theatre and open space offices.

volumes of the space (for example homes and hospitals are [13] P. Ricciardi, C. Buratti, Thermal comfort in open plan offices in northern Italy:
an adaptive approach, Build. Environ. 56 (2012) 314e320.
composed by small rooms). It could also be interesting to perform
[14] C. Buratti, P. Ricciardi, M. Vergoni, HVAC systems testing and check: a
investigation about neutral comfort temperature in buildings that simplified model to predict thermal comfort conditions in moderate envi-
differs for activity of occupancy from the theatre and the offices, ronments, Appl. Energy 104 (2013) 117e127.
such as locker rooms, factories and sport centres. [15] P. Ricciardi, C. Buratti, Thermal comfort in the Fraschini theatre (Pavia, Italy):
Correlation between data from questionnaires, measurements, and mathe-
matical model, Energy Build. 99 (2015) 243e252.
References [16] M.K. Nematchoua, R. Tchinda, P. Ricciardi, N. Djongyang, A field study on
thermal comfort in naturally ventilated building located in the equatorial
climatic region of Cameroon, Renew. Sustain. Energy Rev. 39 (2014) 381e393.
[1] K.A. Papakonstantinou, C.T. Kiranoudis, N.C. Markatos, Numerical simulation
[17] UNI EN ISO 10551, Ergonomia Degli Ambienti Termici e Valutazione Del-
of CO2 dispersion in an auditorium, Energy Build. 134 (2002) 245e250.
l'Influenza Dell'Ambiente Termico Mediante Scale di Giudizio Soggettivo,
[2] A.I. Stamou, I. Katsiris, A. Schaelin, Evaluation of thermal comfort conditions in
Gennaio 2002.
the Galatsi Arena of the Olympics Athens 2004 using a CFD model, Appl.
[18] ISO 7726, Ergonomics of the Thermal Environment e Instruments for
Therm. Eng. 28 (2008) 1206e1215.
Measuring Physical, 1998.
[3] K.W.D. Cheong, E. Djunaedy, Y.L. Chua, K.W. Tham, S.C. Sekhar, M.B. Wong,
[19] UNI EN ISO 7730, Ergonomics of the Thermal Environment e Analytical
N.H. Ullah, Thermal comfort study of an air conditioned lecture theatre in the
Determination and Interpretation of Thermal Comfort using Calculation of the
tropics, Build. Environ. 38 (2003) 63e73.
PMV and PPD Indices and Local Thermal Comfort Criteria, 2006.
[4] C.N. Kwang, S.J. Jae, D.O. Myung, Thermal comfort and indoor air quality in the
[20] A.S.H.R.A.E. Standard 55/2004, Thermal environment Conditions for Human
lecture room with 4-way cassette air-conditioner and mixing ventilation
Occupancy, Atlanta, Ga., USA, 2004.
system, Build. Environ. 42 (2007) 689e698.
[21] I. Griffiths, Thermal comfort studies in buildings with passive solar features.
[5] M. Kavgic, D. Mumovic, Z. Stevanovic, A. Young, Analysis of thermal comfort
Field Studies. Report to the Commission of the European Community, 1990.
and indoor air quality in a mechanically ventilated theatre, Energy Build. 40
ENS35090 UK.
(2008) 1334e1343.
[23] UNI10349, Riscaldamento e Raffrescamento degli Edifici Dati Climatici, aprile
[6] Y. Cheng, J. Niu, N. Gao, Stratified air distribution in a large lecture theatre: a
1994.
numerical method to optimize thermal comfort and maximize energy saving,
[24] P.O. Fanger, Thermal Comfort, Analysis and Application in Environmental
Energy Build. 55 (2012) 515e525.
Engineering, Danish technical press, Copenaghen, 1970.
[7] G. Kim, L. Schaefer, T.S. Lim, J.T. Kim, Thermal comfort prediction of an
[25] N. Djongyang, R. Tchinda, D. Njomo, Thermal comfort: a review paper, Renew.
underfloor air distribution system in a large indoor environment, Energy
Sustain. energy Rev. 14 (2010) 2626e2640.
Build. 64 (2013) 323e331.
[26] M. Humphreys, Field Studies of Thermal Comfort Compared and Applied,
[8] D. Pereira, D. Raimondo, S.P. Corgnati, M. Gameiro da Silva, Assessment of
Department of the Environment: Building Research Establishment, 1975.
indoor air quality and thermal comfort in Portuguese secondary classrooms:
[27] A.I. Dounis, C. Caraiscos, Advanced control system engineering for energy and
methodology and results, Build. Environ. 81 (2014) 69e80.
comfort management in a building environment e a review, Renew. Sustain.
[9] E.Z.E. Conceic~ao, J.M.M. Gomes, N.H. Ant~ ao, M. Manuela, J.R. Lúcio, Application
Energy Rev. 13 (2009) 1246e1261.
of a developed adaptive model in the evaluation of thermal comfort in
ventilated kindergarten occupied spaces, Build. Environ. 50 (2011) 190e201.
[10] A.K. Mishra, M. Ramgopal, An adaptive thermal comfort model for the tropical Nomenclature
climatic regions of India (Ko €ppen climate type A), Build. Environ. 85 (2015)
134e143.
[11] S. Manu, Y. Shukla, R. Rawal, L.E. Thomas, R. De Dear, Field studies of thermal PMV: Predictive Mean Vote
comfort across multiple climate zones for the subcontinent: India Model for PPD: Percentage of person dissatisfied
Adaptive Comfort (IMAC), Build. Environ. 98 (2016) 55e70. TUI: Percentage of people that consider the theatre not thermally acceptable
[12] C. Buratti, P. Ricciardi, Adaptive analysis of thermal comfort in university TAI: Percentage of people that consider the theatre not thermally comfortable
classrooms: correlation between experimental data and mathematical UAMI: Percentage of people that consider the speed of air movements not acceptable
models, Build. Environ. 44 (2009) 674e687.
P. Ricciardi et al. / Building and Environment 102 (2016) 116e127 127

UVTGI: Percentage of people that feels discomfort caused by too big difference be- tamt: Average monthly temperature
tween the temperature at their head height and the temperature at heir ankle
height. Subscripts
PMVq: Predictive Mean Vote calculated by questionnaire
te: External temperature
tn: Neutral comfort temperature n: neutral
tnf: Neutral comfort temperature calculated with the analytical method o: operative
tna: Neutral comfort temperature calculated with adaptive method and the q: questionnaire
monitored amt: average monthly temperature
to: Operative temperature

You might also like