Professional Documents
Culture Documents
W
D
rights of their respective owners. operated. Before disconnecting the equipment, ensure that the W: 9.5 mm (0.37 in)
DC 48 V, 0.8 A, General Purpose
current-transformer circuits are short-circuited. L: 7.1 mm (0.28 in) to 7.7 mm (0.30 in)
DC 240 V, 0.1 A, General Purpose
NOTE The limit values stated under “Technical Data” in the SIPROTEC 5 AC 240 V, 5 A, General Purpose L
Hardware manual may not be exceeded. This must also be AC 120 V, 1/6 hp
Assembly Dimensions, Installation, Terminal and Connection Diagrams considered during testing and commissioning. AC 250 V, 1/2 hp
and Technical Data are part of the SIPROTEC 5 Hardware Manual. B300 Permissible tightening torque at the 2.7 Nm (23.9 lb.in.)
If you require further information, or if particular problems occur that are not handled in R300 terminal screw
The manuals are available in the SIPROTEC Download Area on the
Internet (http://www.siemens.com/siprotec). sufficient depth in the instructions of the respective product, you can request help
Fast Relay (Type F) AC 120 V, 5 A, General Purpose Maximum allowed speed of the used 640 RPM
through your local Siemens Office or representative.
AC 250 V, 5 A, General Purpose tool
Notes on Safety AC 250 V, 0.5 hp Location on device To be visible as follows:
This manual contains notes that must be adhered to for your own personal safety and WARNING B300
to avoid damage to property. Laser radiation! Danger of eye injury R300
However, it does not constitute a complete description of all safety measures required This device may contain a class 1 laser. High-Speed Relay with Semi- B150
for installation, service, and maintenance of the equipment (module, device) in conductor Acceleration (Type HS) Q300
question. Details are to be taken from the manuals and those are mandatory. Do not look directly into the beam.
Power Relay (for Direct Control of DC 300 V, 4.5 A - 30 s ON, 15 min OFF
Motor Switches) DC 250 V, 1 Hp Motor - 30 s ON,
WARNING
15 min OFF
CAUTION DC 110 V, 3/4 Hp Motor - 30 s ON,
Danger of severe personal injury or substantial damage to
property Danger of damage due to static electrical charges 15 min OFF
Hazardous voltages may occur in devices and modules during DC 60 V, 10 A, 1/2 Hp Motor - 30 s ON,
The printed circuit boards of numerical relays contain CMOS circuits.
operation depending on the design and application. 15 min OFF
These shall not be withdrawn or inserted under live conditions! The
DC 48 V, 10 A, 1/3 Hp Motor - 30 s ON,
Always observe the instructions given in “Qualified Electrical modules must be so handled that any possibility of damage due to
15 min OFF
Engineering Personnel” below. static electrical charges is excluded.
DC 24 V, 10 A, 1/6 Hp Motor - 30 s ON,
During any necessary handling of individual modules the 15 min OFF
Qualified Electrical Engineering Personnel recommendations relating to the handling of electrostatically
Only qualified electrical engineering personnel may commission and operate the endangered components (EEC) must be observed.
CAUTION
equipment (module, device) described in this document. Qualified electrical In installed conditions, the modules are in no danger.
engineering personnel in the sense of this document are people who can demonstrate Danger of fire or chemical burn hazard
technical qualifications as electrical technicians. These persons may commission, Statement of Conformity The battery used in this device may present a fire or chemical burn
isolate, ground and label devices, systems and circuits according to the standards of hazard if mistreated.
safety engineering. Low-voltage Directive 2014/35/EU
EMC Directive 2014/30/EU Do not recharge, disassemble, heat above 100 °C (212 °F) or
Use as Prescribed Voltage Terminals, Binary Inputs and Outputs
incinerate.
The equipment (device, module) may only be used for such applications as set out in This conformity is based on the compliance with the following Wire cross-section 1x AWG 20-14 (0.5 mm2 to 2.5 mm2) solid
harmonized standards: Dispose the used battery promptly. or stranded with UL-listed ferrule
the catalogs and the technical description, and only in combination with third-party
equipment recommended and approved by Siemens. EN 60255-26 and EN 60255-27 Keep away from children! Use copper conductors only, at least certified
for a temperature of +105 °C
Problem-free and safe operation of the product depends on the following:
Other Standards Ferrule with plastic sleeve L = 12 mm (0.47 in)
• Proper transport IEEE Std C 37.90
Stripping length (when used without 12 mm (0.47 in); only copper wires may be
• Proper storage, setup, and installation The technical data of the product is approved in accordance with UL.
For more information about the UL database, see www.ul.com ferrule) used.
• Proper operation and maintenance Select Online Certifications Directory and enter E194016 as UL File Number. Permissible tightening torque at the 1.0 Nm (8.85 lb.in.)
terminal screw
Maximum allowed speed of the used 640 RPM
IND. CONT. EQ. tool
69CA Location on device To be visible as follows:
NOTE
Battery disposal
The batteries must only be replaced with the same type or another type
recommended by the manufacturer. Improper replacement involves
explosion hazard. For disposing the batteries it is necessary to observe
the local national/international directives.