• For more information and instructions, refer to the user manual and the user manual for communication.
Visit our web site (www.autonics.com) to download the manuals.
• The user manual includes product specifications, functions, and operations.
• The user manual for communication includes information about Modbus RTU protocol, and Modbus mapping table.
DAQMaster is the integrated device management program to set parameters and manage monitoring data and user group,
parameter mask which are the dedicated function of KPN.
Visit our website (www.autonics.com) to download user manual and integrated device management program.
< Computer specification for using software > < DAQMaster screen >
D-2
High Performance & Accuracy Process Controller
KPN5 5 0 0 0 0 0 B. Indicator
Power supply
0 100-240 VAC 50/60 Hz C. Converter
2 DIN W96×H48 mm
Size
3 DIN W48×H96 mm
5 DIN W96×H96 mm
Item
KPN5 Temperature / Process Controller
※ 1: The 1 output type is heating or cooling output type and the 2 output type is heating & cooling output type.
The 1 output type is able to use only one output among relay, current, SSR drive voltage outputs.
OUT1 of the 2 output type is fixed as heating output and OUT2 of the 2 output type is fixed as cooling output.
If you select the SSR drive voltage or current output model, you can select the appropriate control output.
KPN
Connections
٧٧KPN5 00
Communication 1 RS485
13 Remote SV
RS485(A+) ADC
Output Circuit V mA 1-5V
RS485 2 14 4-20mA
RS485(B-)
Digital
RESISTIVE LOAD Input
AL2 OUT Relay 4 16 Non-contact,
Control
DI-2
※1:Set relay output [ RLY], current [ CUR], or Model OUT1 control output OUT2 control output
SSR drive voltage output [ SSR] at OUT1 Current, SSR drive voltage Current, SSR drive voltage
KPN5 11
control output [ OUT1] in parameter 3 group. selection output selection output
Current, SSR drive voltage
※ Standard model has shaded terminals only. KPN5 13 Relay output
selection output
is option specification.
Current, SSR drive voltage
KPN5 17 Relay output
selection output
KPN5 19 Relay output Relay output
D-3
KPN Series
Dimensions
٧٧KPN52 (unit:mm)
Terminal
cover ● Panel cut-out
Bracket 6 Min. 115
6 64.5
96 1.5
Min. 65
45 +0.6
0
44.8
48
92 +0.8
0
٧٧KPN53
6 64.5 ● Panel cut-out
48 1.5 6 Min. 65
Bracket Terminal
cover
92 +0.8
0
Min. 115
96
91.5
45 +0.6
0
٧٧KPN55
6 64.5 ● Panel cut-out
□96
1.5 6 Min. 115
Bracket Terminal
cover
92 +0.8
0
Min. 115
91.5
92+0.8
0
A (unit:mm)
B 3
K(Black) Model A B C D E F
D E
L(White) CSTC-E80N Ø23.3 Ø7 26.5 7 3.8 10.5
D-4
High Performance & Accuracy Process Controller
٧٧Communication converter
B. Indicator
SCM-WF48 (available soon) SCM-US48 SCM-38 SCM-US
(Wi-Fi to RS485/USB (USB to RS485 converter) (RS232C to RS485 converter) (USB to Serial converter)
communication C. Converter
converter)
D. Controller
E. Thyristor
unit
F. Pressure
transmitter
Input type Dot Parameter Input range (℃) Input range (℉) H. Accessories
1 TcK1 -200 to 1350 -328 to 2463
K(CA)
0.1 TcK2 -199.9 to 999.9 -199.9 to 999.9
1 TcJ1 -200 to 800 -328 to 1472
J(IC)
0.1 TcJ2 -199.9 to 800.0 -199.9 to 999.9
1 TcE1 -200 to 800 -328 to 1472
E(CR)
0.1 TcE2 -199.9 to 800.0 -199.9 to 999.9
1 TcT1 -200 to 400 -328 to 752
T(CC)
0.1 TcT2 -199.9 to 400.0 -199.9 to 752.0
B(PR) 1 TC-B 0 to 1800 32 to 3272
Thermocouple
R(PR) 1 TC-R 0 to 1750 32 to 3182
S(PR) 1 TC-S 0 to 1750 32 to 3182
N(NN) 1 TC-N -200 to 1300 -328 to 2372
KPN
C(TT)※1 1 TC-C 0 to 2300 32 to 4172
G(TT)※2 1 TC-G 0 to 2300 32 to 4172
1 TcL1 -200 to 900 -328 to 1652
L(IC)
0.1 TcL2 -199.9 to 900.0 -199.9 to 999.9
1 TcU1 -200 to 400 -328 to 752
U(CC)
0.1 TcU2 -199.9 to 400.0 -199.9 to 752.0
Platinel II 1 TC-P 0 to 1390 32 to 2534
Cu50Ω 0.1 Cu50 -199.9 to 200.0 -199.9 to 392.0
Cu100Ω 0.1 Cu10 -199.9 to 200.0 -199.9 to 392.0
1 JPt1 -200 to 650 -328 to 1202
JPt100Ω
RTD 0.1 JPt2 -199.9 to 650.0 -199.9 to 999.9
DPt50Ω 0.1 DPt5 -199.9 to 650.0 -199.9 to 999.9
1 DPt1 -200 to 650 -328 to 1202
DPt100Ω
0.1 DPt2 -199.9 to 650.0 -199.9 to 999.9
Nickel120Ω 1 Ni12 -80 to 200 -112 to 392
0-10 V A-V1
0-5 V A-V2
1-5 V A-V3 -1999 to 9999
Analog
0-100 mV aMV1 (display range depends on the decimal point position )
0-20 mA aMA1
4-20 mA aMA2
D-5
KPN Series
Specifications
Option Transmission 4-20 mA (Load max. 600 Ω, output accuracy: ±0.3% F.S.±1digit)
output Communication RS485 communication output (Modbus RTU method)
CT 0.0-50.0 A(primary heater current value measuring range) ※CT ratio is 1/1000
Option Remote SV 1-5 VDC or 4-20 mA(current input: using external resistance 250 Ω)
input
ㆍContact input: Max. 2 kΩ in ON, Min. 90 kΩ in ON
Digital input
ㆍNon-contact input: Residual voltage max. 1.0 V in ON, leakage current max. 0.1 mA in OFF
D-6
High Performance & Accuracy Process Controller
SV settings
You can set the temperature to control with the , , keys.
Set range is within SV low-limit value [ L-SV] to SV high-limit value [ H-SV].
※ Ex) In case of changing set temperature from 210 ℃ to 250 ℃
① ② ③ ④
Press any key among the Press the key to move digit. Press the or key to raise Press the MODE key to save
, , in RUN mode to (100→101→102→103→100) or lower the setting value. the setting value. If there is
enter into SV setting mode. (1 → 5) no additional key operations
Last digit (100 digit) on SV in 3 sec., the changed SV is
display part flashes. automatically saved.
D-7
KPN Series
Parameter groups
RUN mode
When PW is valid.
MV high-limit (H-MV)
D-8
High Performance & Accuracy Process Controller
A. Recorder
B. Indicator
MODE 3 sec.
C. Converter
D. Controller
H-MV C-MV
Heating MV monitoring Cooling MV monitoring
E. Thyristor
unit
G. Temp.
transmitter
Input type(IN-T) Alarm output 1 operation mode(AL-1) Multi SV (MtSV)
MODE 1.5 sec. MODE MODE 1.5 sec. MODE MODE 1.5 sec. MODE
H. Accessories
Sensor temperature unit (UNIT) Alarm output 1 option (AL!T) Digital input key (DI-K)
Analog low-limit input (L-RG) Alarm output 1 hysteresis (A!HY) DI-1 input terminal function (DI-1)
Analog high-limit input (H-RG) Alarm output 1 N.O./N.C. (A!N) DI-2 input terminal function (DI-2)
Scale value decimal point (DOT) Alarm output 1 ON delay time (A!ON) Remote SV (ReSV)
Low-limit scale value (L-SC) Alarm output 1 OFF delay time (A!OF) Remote SV low-limit correction (RInB)
High-limit scale value (H-SC) Alarm output 2 operation mode (AL-2) Remote SV high-limit gradient
correction (RSPN)
Display unit (dUNT) Alarm output 2 option (AL@T)
Bar graph (BAR)
Input correction (IN-B) Alarm output 2 hysteresis (A@HY)
Manual control, initial MV (ItMV)
Input digital filter (MAvF) Alarm output 2 N.O./N.C. (A@N)
Manual control, preset MV (PrMV) KPN
SV low-limit value (L-SV) Alarm output 2 ON delay time (A@ON)
Sensor error, MV (ErMV)
SV high-limit value (H-SV) Alarm output 2 OFF delay time (A@OF)
Control stop, MV (StMV)
Control output operation mode (O-FT) Alarm output 3 operation mode (AL-2)
Control stop, alarm output (StAL)
Control type (C-MD) Alarm output 3 option (AL#T)
User level (USER)
Auto-tuning mode (ATT) Alarm output 3 hysteresis (A#HY)
SV group lock (LcSV)
OUT1 control output (OUT1) Alarm output 3 N.O./N.C. (A#N)
Parameter group 1 lock (LcP1)
OUT1 current output range (O!MA) Alarm output 3 ON delay time (A#ON)
Parameter group 2 lock (LcP2)
OUT2 control output (OUT2) Alarm output 3 OFF delay time (A#OF)
Parameter group 3 lock (LcP3)
OUT2 current output range (O@MA) LBA monitoring time (LBaT)
Parameter group 4 lock (LcP4)
Heating control time (H-T) LBA detection band (LBaB)
Parameter group 5 lock (LcP5)
Cooling control time (C-T) Analog trans. output value (AoM1)
MODE
Password (PWD)
PV trans. output low-limit (FsL1)
MODE
PV trans. output high-limit (FsH1)
MODE
D-9
KPN Series
Parameter 1 group
※1: S : Press any key among , ,
MODE 3 sec.
RUN mode ※After entering setting mode, press key anytime for 3 sec. to return to Run mode.
MODE
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name.
S ※1 ※If you press the key after changing the setting value of the parameter the setting value will be stored.
PASS ※ Shaded parameters are for standard-level users, the others are for high-level users.
When password is (You can set the user level in parameter 5 group)
invalid, SV display part ※ This parameter might not be displayed depending on other parameter settings.
displays password code
Enter password
MODE S
When PW
PASS 0001
is invalid MODE
When PV is valid
Parameter 1 group Parameter 2 group Parameter 3 group
PAR1 PAR2 PAR3
MODE
Control output
RUN/STOP
S
MODE
R-S RUN STOP
MODE
Multi SV numbers
S
SV-N SV-0 SV-1 SV-2 SV-3
MODE
※ Displays the set SV0 to SV3 at multi SV[ MtSV].
Heater current monitoring
S
• Set range : 00.0 to 50.0 A(display range)
CT-A )0
MODE • Set range: deviation alarm (-F.S. to F.S.),
absolute value alarm (within display range), unit (℃/℉)
※ Displayed only when alarm output 1 operation mode [ AL-1] is set as deviation/
Alarm output 1 low-limit
S absolute value low-limit alarm or deviation high/low-limit reserve alarm.
AL!L 1550 ※ Displayed only when alarm output 1 operation mode [ AL-1] is set as heater
MODE break alarm [ HBA], set heater break SV.
※ Not displayed when alarm output 1 operation mode [ AL-1] is no alarm
output [ OFF], sensor break alarm [SBA], or loop break alarm [ LBA].
Alarm output 1 high-limit
S ※ Displayed only when alarm output 1 operation mode [ AL-1] is set as devia-
AL!H 1550 tion/absolute value high-limit alarm or deviation high/low-limit reserve alarm.
MODE
※ Not displayed when alarm output 1 operation mode [ AL-1] is no alarm
output [ OFF], sensor break alarm [ SBA], loop break alarm [ LBA], or heater
Alarm output 2 low-limit break alarm [ HBA].
S
AL@L 1550
MODE
D-10
High Performance & Accuracy Process Controller
MODE
AT OFF ON G. Temp.
transmitter
MODE
Cooling,
proportional band
S • Set range : 000.1 to 999.9℃ / ℉, %
C-P 01)0 ※ Displayed only when control output operation mode [ O-FT]
MODE
is cooling [ COOL] or heating&cooling [ H-C] control.
Heating, integral time
S • Set range : 0001 to 9999 sec.
H-1 0000 ※ Displayed only when control output operation mode [ O-FT]
MODE is heating [ HEAT] or heating&cooling [ H-C] control.
※ Displayed only when
Cooling, integral time control type [ C-MD] is
S • Set range : 0001 to 9999 sec.
C-1 0000 ※ Displayed only when control output operation mode [ O-FT]
PID control.
MODE
is cooling [ COOL] or heating&cooling [ H-C] control. KPN
D-11
KPN Series
MV low-limit
S • Set range :
L-MV 00)0 ► Standard control : 000.0 to (H-MV-0.1%)
MODE
► Heating/Cooling control : -100.0 to 000.0%
MV high-limit
S • Set range :
H-MV 10)0 ► Standard control : (L-MV+0.1) to 100.0%
MODE
► Heating/Cooling control : 000.0 to 100.0%
※ Displays only when control
RAMP-Up change rate type [C-MD] is ONOF or OnON.
S
LAMU 0000 • Set range : 000 to 999digit (000.0 to 999.9)
MODE
RAMP unit
S
rUNT MIN HOUR SEC • Set range : SEC / MIN / HOUR
Parameter 3 group
Input type ※1
S
MODE
IN-T KCaH KCaL •••••• NI12
MODE
Temperature unit
S ※ Displayed only when input type [ IN-T] is
UNIT '?C ?F temperature sensor input.
MODE
Decimal point
S
DOT )0 • Set range : 0 / 0.0 / 0.00 / 0.000
MODE
※ Displayed only when
Low-limit scale value input type [ IN-T] is
S
analog input.
L-SC 00)0 • Set range : -1999 to 9999
MODE
Display unit
S
dUNT ?/O OFF ?C ?F
D-12
High Performance & Accuracy Process Controller
Input correction
S A. Recorder
IN-B 000 • Set range : -999 to 0999digit [-199.9 to 999.9]
MODE
B. Indicator
Input digital filter
S
MAvF 00)1 • Set range : 000.1 to 120.0 sec. C. Converter
MODE
D. Controller
SV low-limit
S
L-SV -200 • Set range : input low-limit [ L-SC] to H-SV-1digit ℃ / ℉ / %
E. Thyristor
MODE unit
F. Pressure
SV high-limit transmitter
S
H-SV 1350 • Set range : L-SC+1digit to input high-limit [ H-SV] ℃ / ℉ / %
MODE G. Temp.
transmitter
Control output
operation mode HEAT COOL ※ 1 output model
S H. Accessories
O-FT
MODE
H-C HEAT COOL ※ 2 output model
Auto-tuning mode
S
AtT TUN1 TUN2 ※ Displayed only when control type [ C-MD] is PID control.
MODE
OUT1 current
output range
S
O!MA 4-20 0-20 ※ Displays only when OUT1 is current output [ CURR].
MODE
OUT2 current
output range
S
O@MA 4-20 0-20 ※ Displays only when OUT2 is current output [ CURR].
MODE
D-13
KPN Series
Parameter 4 group
※1: S : Press any key among , ,
※After entering setting mode, press key anytime for 3 sec. to return to Run mode.
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name.
※If you press the key after changing the setting value of the parameter the setting value will be stored.
※ Shaded parameters are for standard-level users, the others are for high-level users.
(You can set the user level in parameter 5 group)
※ This parameter might not be displayed depending on other parameter settings.
Alarm output 1
operation mode ※1
S
MODE
AL-1 DVCC ]]DV •••••• OFF
MODE
Alarm 1 N.O./N.C.
S
A!N NO NC
MODE
Alarm output 2
operation mode
S
AL-2 ]]DV ]DV[ •••••• DVCC
MODE
Alarm 2 N.O./N.C.
S
A@N NO NC
MODE
D-14
High Performance & Accuracy Process Controller
Alarm output 3
operation mode
S A. Recorder
AL-3 ]]DV ]DV[ •••••• DVCC
MODE
B. Indicator
Alarm output 3 option
S
AL#T AL-A AL-B •••••• AL-F C. Converter
MODE
※ Displayed except when alarm output 3 operation mode[ AL-3] is OFF.
Alarm output 3 hysteresis
S D. Controller
• Set range : 001 to 100digit (000.1 to 100.0)
A#HY 001
MODE
※Displayed except when alarm output 3 operation mode [ AL-2] is set as deviation/
absolute value high-limit, low-limit, high/low limit alarm or reserve alarm. E. Thyristor
unit
Alarm 3 N.O./N.C.
S
A#N NO NC F. Pressure
transmitter
MODE
Com. address
S
ADRS 01 • Set range : 01 to 127
MODE
Com. speed
S
BPS 96 192 •••••• 48
MODE
Com. write
S
COMW EnA DIsA
MODE
D-15
KPN Series
Parameter 5 group
※1: S : Press any key among , ,
※After entering setting mode, press key anytime for 3 sec. to return to Run mode.
※After entering setting mode, press key anytime for 1.5 sec. to go to the concerned group name.
※If you press the key after changing the setting value of the parameter the setting value will be stored.
※ Shaded parameters are for standard-level users, the others are for high-level users.
(You can set the user level in parameter 5 group)
※ This parameter might not be displayed depending on other parameter settings.
Multi SV ※1
S
MODE
MtSV 1 2 4
MODE
DI-1 input
terminal function
S
DI-1 STOP AlRE •••••• OFF
MODE
DI-2 input
terminal function
S
DI-2 AlRE MAN •••••• STOP
MODE
Remote SV
S
ㄲRESV OFF ON
MODE
Remote SV
low-limit correction
S ※ Displayed only for remote SV model (KPN5 30).
ㄲR1NB 0
MODE
Remote SV high-limit
gradient correction
S
RSPN !00
MODE
Bar graph
S
BAR OUT1 OUT2 ALL
MODE
Manual control,
initial MV
S
ItMV AUTO PrMV
MODE
Manual control,
preset MV
S
PrMV 00)0
MODE
Sensor error, MV
S
ErMV 00)0 • Set range :
MODE ► Standard control : 000.0 to 100.0%
► Heating / Cooling control : -100.0 to 100.0%
Control stop, MV
S
StMV 00)0
MODE
D-16
High Performance & Accuracy Process Controller
A. Recorder
Control stop,
alarm output
S
StAL CONT OFF B. Indicator
MODE
C. Converter
User level
S
USER STND HIGH
D. Controller
MODE
MODE
H. Accessories
Password setting
S
PWD 0000 • Set range : 0000 (password function Off), 0002 to 9999
D-17
KPN Series
Factory default
※ Shaded parameters are factory defaults for the heating & cooling model.
D-18
High Performance & Accuracy Process Controller
Functions A. Recorder
F. Pressure
If deviation between PV and SV as low- transmitter
Deviation low-limit limit is higher than set value of deviation
]]DV PV SV SV PV
alarm temperature, the alarm output will be
90℃ 100℃ 100℃ 110℃ G. Temp.
ON. transmitter
Low deviation : Set as 10℃ Low deviation : Set as -10℃
KPN
Alarm option
AL-A Standard alarm If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
AL-B Alarm latch If it is an alarm condition, alarm output is ON and maintains ON status.
First alarm condition is ignored and from second alarm condition, standard alarm operates. When
AL-C Standby sequence 1 power is supplied and it is an alarm condition, this first alarm condition is ignored and from the
second alarm condition, standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is
Alarm latch and
AL-D supplied and it is an alarm condition, this first alarm condition is ignored and from the second alarm
standby sequence 1
condition, alarm latch operates.
First alarm condition is ignored and from second alarm condition, standard alarm operates. When
AL-E Standby sequence 2 re-applied standby sequence and if it is alarm condition, alarm output does not turn ON. After
clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence 1. If it operates not only by power
Alarm latch and standby ON/OFF, but also alarm setting value, or alarm option changing. When re-applied standby
AL-F
sequence 2 sequence and if it is alarm condition, alarm output does not turn ON.
After clearing alarm condition, alarm latch operates.
※ Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set temperature,
alarm temperature[ AL1, AL2] or alarm operation [ AL-1, AL-2] ), switching STOP mode to RUN mode.
D-19
KPN Series
0% PV
Heating (reverse) SV Description
Control output OFF Auto-tuning stops
(MV)
100% ON Auto-tuning starts
D-20
High Performance & Accuracy Process Controller
autonics.com) to download the DAQMaster program and ● When the load (Heater etc) is not operated
the user manual. Please check operation of the out indicator located in C. Converter
front panel of the unit. If the indicator does not operate,
RUN mode please check the parameter of all programmed mode.
If the indicator is operating, please check the output D. Controller
(Relay, SSR drive voltage, DC4-20 mA current) after
PARU AT ••• PARS
separating output line from the unit. E. Thyristor
unit
● When it displays OPEN during operation
AL!L AL!H SV-0 hHYS
This is a warning that external sensor is cut off (open). F. Pressure
transmitter
cHYS IN-B A!HY A@HY Please turn off power and check the state of sensor.
If sensor is not cut off (open), disconnect sensor line
G. Temp.
The above is setting user parameter group in the from terminal block and +, - together. When you turn transmitter
DAQMaster with alarm output 1 low-limit value [ AL!!L], on power it can check room temperature.
alarm output 1 high-limit value [ AL!H], SV-0 set value If this unit cannot indicate room temperature, this unit H. Accessories
[ SV-0] parameters of parameter 1 group, heating itself is faulty. Please remove this unit from equipment
hysteresis [ hHYS], cooling hysteresis [ cHYS] parameters and service or replace.
of parameter 2 group, (When the input mode is thermocouple, it is available to
input correction [ IN-B], parameter of parameter 3 group, indicate room temperature.)
alarm output 1 hysteresis [ A!HY], alarm output 2
hysteresis [ A@HY] parameters of parameter 4 group. ● In case of indicating "Error" in display
This Error message is indicated in case of damaging
inner chip program data by outer strong noise.
Bar graph In this case, please send the unit to our after service
MV of control output (OUT1, OUT2) is displayed as the bar center after removing the unit from system.
graph in real-time. According to bar graph setting [ BA R] in Noise protection is designed in this unit, but it does not
parameter 5 group, it displays bar graph by control output stand up strong noise continuously.
or does not display it. If bigger noise than specified(Max. 2 kV) flows in the
unit, it can be damaged.
OUT1 (red LED)
50 100 KPN
OUT2 (green LED)
Caution for using
One LED is 10% (total 10 LEDs: 100%). If control output • The connection of this unit should be separated from
MV is 0.1 to 10%, one LED turns ON. If MV is 90.1 to the power line and high voltage line in order to prevent
100%, 10 LEDs turn ON. inductive noise.
The 1 output type (heating or cooling control) model has • Install a power switch or a circuit breaker to supply or
one OUT1 bar graph (red). cut off the power.
The 2 output type (heating & cooling control) model has • Switch or circuit breaker should be installed nearby
two bar graphs; OUT1 bar graph (red), OUT2 bar graph users for convenient control.
(green). OUT1 is for heating MV and OUT2 is for cooling
MV. • This unit is designed for temperature controlling only.
Do not apply this unit as a voltage meter or a current
meter.
Remote SV setting • In case of using RTD sensor, 3-wire type must be
This function is to set SV by inputting analog (DC4-20 used. If you need to extend the line, use 3-wire with the
mA, 1-5 VDC) signal to no. 13 and 14 terminals. (Set that same thickness as the line. It might cause temperature
remote SV [ ReSV] is ON in parameter 5 group) difference if the resistance of line is different.
Input analog signal is changed to between SV low-limit • In case of making power line and input signal line
value [ L-SV] to SV high-limit value [ H-SV]. closely, line filter for noise protection should be installed
at power line and input signal line should be shielded.
※ When using remote SV, you cannot select SV setting by
front keys and multi SV setting by digital input. • Do not use this unit near the high frequency instruments
(high frequency welding machine & sewing machine,
large capacity SCR controller).
• Installation environment
Parameter initialization
① It shall be used indoors.
It initializes all parameters to factory default values. Press ② Altitude max. 2,000 m
the front 1+4+3 keys for 5 sec. at the same time and ③ Pollution degree 2
[ INIT] parameter is displayed. Select ‘YES’ to initialize all ④ Installation category II
parameters.
• It may cause malfunction if above instructions are not
If the password is set, you must enter the password. After followed.
initialing the parameters, the password parameter is also
initialized.
D-21