Buildings
for extreme
environments
ARID
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Buildings
Arid
for extreme
environments
The rights of publication or translation are reserved.
ISBN 978-1-906846-43-5
This document is based on the best knowledge available at the time of publication.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
However no responsibility of any kind for any injury, death, loss, damage or delay
however caused resulting from the use of these recommendations can be accepted
by the Chartered Institution of Building Services Engineers, the authors or others
involved in its publication. In adopting these recommendations for use each
adopter by doing so agrees to accept full responsibility for any personal injury,
death, loss, damage or delay arising out of or in connection with their use by or
on behalf of such adopter irrespective of the cause or reason therefore and agrees
to defend, indemnify and hold harmless the Chartered Institution of Building
Services Engineers, the authors and others involved in their publication from
any and all liability arising out of or in connection with such use as aforesaid and
irrespective of any negligence on the part of those indemnified.
Printed in Great Britain by The Lavenham Press, Lavenham, Suffolk CO10 9RN
zone driven, which could be applied to different parts of the world as appropriate.
This document on arid zones is the first of a three-part series that will reflect
different climate zones; the others representing polar and tropical climates.
5 Sustainability ..........................................................................................99
5.1 Introduction ..............................................................................................99
5.2 Measuring sustainability—benchmarking systems in arid climates 99
5.3 Integrated design ....................................................................................100
5.4 Sustainability considerations in arid climates ..........................................101
References ........................................................................................................109
Index ..............................................................................................................114
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Buildings for extreme environments: Arid
This section outlines the basic weather, solar ‘Climate is the characteristic condition of the
and design notes required to provide designers of atmosphere near the earth’s surface at a certain
engineering services with the basic information to place on earth. Climate is the long-term weather
engineer building services to satisfactory standards of that area (over at least 30 years). This includes
in an arid extreme climate condition. It cannot the region’s general pattern of weather conditions,
replace sound engineering judgement, which is the seasons and weather extremes such as hurricanes,
basis of all good design. It directs the designer to the droughts or rainy periods/floods. Two of the most
appropriate sections of CIBSE and other equivalent important factors determining an area’s climate are
guides and sources of information. Three extreme air temperature and precipitation. Solar radiation
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
climates will be covered in the Buildings for extreme and humidity also play an important role. World
environments series (see Table 1). This publication biomes are controlled by climate. The climate
looks at buildings for arid climates. of a region will determine what plants will grow
there and what animals will inhabit it. All three
Institutions around the world recognise that components—climate, plants and animals—are
professional building services design engineers interwoven to create the fabric of a biome.’ (Strahler
engage with considerable amounts of work outside and Strahler, 1984)
their native country. This document has been
developed in recognition of this. The sources for Figure 1 shows the world map of Köppen-Geiger
the geographical descriptions are based on the climate classification.
Köppen-Geiger climate classification system, which
is considered to be the most widely used. The rapid development of countries around the
world has required building services engineers from
CIBSE will update and re-issue this document as all over the globe to apply their specialist knowledge
further information becomes available. CIBSE will to areas with extreme climatic conditions and
accumulate this information and welcomes advice changing social patterns and technologies.
from users and any constructive criticism.
It is difficult to define the countries that make up the
1.1 General climate zones and there is no political implication
There are different systems for classifying climate; attached to the choice of countries covered by this
Köppen-Geiger is recognised as the most widely used. document. The locations covered are those for which
information has been readily available and covered
The type of climate affects whether the area is desert, by the climate zone system used.
grassland or rainforest. It determines the plants that
grow and what animals inhabit it. The climate of a There are limitations to the data, which must be
region also controls or determines the biome. World appreciated by those who use it. The reliability of
biomas is controlled by climate. the meteorological data is limited by the relatively
Table 1: Extreme climates
Climate zone Descriptor Typical latitude Geographic Source: Arup
descriptor
1: Cold climates Ice cap, tundra, sub-Arctic 50°N and above Arctic, Greenland,
50°S and above North Canada,
North Asia
Antarctica
2: Arid Steppe, desert 15°N–25°N Africa (part), Middle
15°N–25°S East
Central Australia,
America (part)
3: Tropical Savannah, rainforest 15°N–15°S Africa, India
(part), South Asia,
Indonesia, South
America
(See section 1.3 for an explanation
of these abbreviations)
Source: koeppen-geiger.vu-
wien.ac.at (Kottek et al., 2006)
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
short period over which the data have been This affects the atmosphere and air mass (climate)
accumulated. This varies from location to location. and causes hot and cold air mass regions, which
If meteorological data is of critical importance to circulate around the earth.
a design, the designer should carry out his or her
own detailed research; however the data provided Trade winds in the northern hemisphere blow from
in this publication should be adequate for most the northeast; in the southern hemisphere they
preliminary design work. CIBSE and ASHRAE tend to blow from the southwest. These winds then
both provide meteorological data for various meet at the equator where the air rises and cools,
countries for design purposes. developing into clouds and rain. As this is near to
the equator, tropical conditions are generated.
It is not possible to cover all the countries listed The so-called westerlies coming from the southwest
with example data and calculations. Therefore, as in the northern hemisphere, and from the northwest
arid climates are hot, humid, desert-type terrain, the in the southern hemisphere, create storms from west
Middle East (Dubai) will be used as an example (see to east across the middle latitudes. These blow away
section 1.6). from the 30º latitude zone; they cover large areas
and at this latitude the surface winds tend to be
1.2 Scope of data light. As this air blows away, it is replaced by slowly
1.2.1 Climate facts descending air, and any moisture contained within
the air evaporates. These conditions can be seen
The hotter spots around the earth are at a direct in the tropical deserts of the African Sahara and
angle of between 23ºN and 23ºS latitude to the sun, Mexico’s Sonoran.
where the most intense rays/radiation reach the
earth’s atmosphere and strike its surface. 1.2.2 Seasons
The earth rotates around the sun with its axis at a
The sun’s rays hit other parts of the earth at a more slight tilt (23.5º). When its tilt is towards the sun, it
obtuse angle and are therefore less intense. The is summer in the northern hemisphere and winter
climate is colder towards the earth’s poles because in the southern hemisphere; thus when the earth
the angle to the sun is smaller and the radiation moves around the sun and its tilt is away from the
is less intense, reducing its effect on the earth sun, it is winter in the northern hemisphere and
and atmosphere. summer in the southern hemisphere.
This affects the sun’s radiation on the earth, which t Group D: Continental (moist mid-latitude,
causes the earth’s seasons. The rays emitted from the cold winters): These climates tend to have
sun hit the earth at different angles. Rays hitting the warm summers but cold winters. The average
earth’s surface at 90º have the highest levels of energy, summer temperature of the warmest month will
and these places have the highest temperatures. exceed 10 ºC, the coldest will be below −3 ºC
Areas where the Sun’s rays hit the earth at different t Group E: Polar climates (cold): ‘Cold climates’
angles tend to be cooler. describes this climate type perfectly. These
climates are cold in winter with no real summer
1.3
season. The average temperature of the warmest
month is below 10 ºC.
Wladimir Köppen was a climatologist of Russian-
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
t BWh: dry arid (low latitude) The third letters h and k indicate temperature.
t BWk: dry arid (mid latitude). t h is used to represent low latitude climate,
where the average annual temperature is above
C and D climates use the letters a, b, c, and d;
18 ºC
these indicate different monthly temperature
characteristics: t k is used to represent middle latitude climate,
where the average annual temperature is below
t Cfa: humid (subtropical) 18 ºC.
t Cfb: marine (mild winter) The common practice today, mainly in the US, is
t Cfc: marine (cool winter) to use h to represent the coolest month where the
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
depict desert areas that are located along coastal t Eritrea: dry desert strip along red sea coast;
continents (west coasts) that are at tropical or near cooler and wetter in the central highlands (up
tropical locations. They are generally cooler due to 61 cm of rainfall annually, heaviest June
to the effect of cold ocean currents nearby and are to September; semiarid in western hills and
prone to fog and low clouds. However, they are still lowlands.
among the driest areas in terms of the amount of t Haiti: tropical; semiarid where mountains in
precipitation they receive. east cut-off trade winds.
BWn examples: t Iran: mostly arid or semiarid, subtropical along
Caspian coast.
t Lima, Peru
t Jordan: mostly arid desert; rainy season in west
t Walvis Bay, Nambia. (November to April).
BSn examples: Foggy, coastal steppes. t Kazakhstan: cold winters and hot summers;
arid and semiarid.
A fourth letter is sometimes added to demonstrate
t Kuwait: dry desert; intensely hot summers;
that the winter or summer is wetter than the other
short, cool winters.
half of the year.
t Mali: subtropical to arid; hot and dry
1.5 Climate analyses (February to June); rainy, humid, and mild
1.5.1 Climate data (arid environment) (June to November); cool and dry (November
to February).
The following list shows various countries with
their Köppen climate classification. t Mauritania: desert; constantly hot, dry, dusty.
t Mexico: varies from tropical to desert.
t Afghanistan: arid to semiarid; cold winters and
hot summers. t Mongolia: desert; continental (large daily and
seasonal temperature ranges).
t Algeria: arid to semiarid; mild, wet winters
with hot summers along coast; drier with cold t Namibia: desert; hot, dry; rainfall sparse and
winters and hot summers on high plateau and erratic.
experience sirocco, a hot, dust/sand-laden wind t Niger: desert; mostly hot, dry, dusty; tropical
especially common in summer. in extreme south.
t Angola: semiarid in south and along coast to t Oman: dry desert; hot, humid along coast;
Luanda; north has cool, dry season (May to hot, dry interior, strong southwest summer
October) and hot, rainy season (November to monsoon (May to September) in far south.
April). t Pakistan: mostly hot, dry desert; temperate in
t Australia: generally arid and semiarid; northwest; arctic in north.
temperate in south and east; tropical in north. t Peru: varies from tropical in the east to dry
t Azerbaijan: semiarid steppe. desert in west; temperate in Andes.
t Bahrain: arid; mild, pleasant winters; very hot, t Qatar: arid; mild, pleasant winters; very hot,
humid summers. humid summers.
1.6.2 Climate
The UAE geographically lays on the line of the
Tropic of Cancer, causing warm and sunny weather Figure 5: Sources of available weather data
in Dubai. Average daytime temperatures inland CQCM: Minhad Military Airport OIBA: Abu Musa Islands
are 25 ºC, and nights are slightly cooler in winter D1117: Jumeriah (inactive station) WMO40890: Abu Musa Islands
months. Coastal temperatures average 12–15 ºC; OMDB: Dubai International Airport OMAL : Ain International Airport
OMSJ: Sharjah International Airport OMAA: Abu Dhabi International
desert and mountainous regions have an average of
OMRK: Ras Al Khaimah Airport
5 ºC. Due to its coastal location, humidity levels can International Airport
average 50% to 60%. Map data courtesy © 2011 Google, LeadDog Consulting
30 space down.
Month the cool period and reduce the apparent effect of the
hot period; optimum passive design should harness
Figure 6: Dubai air temperature ranges
these climatic conditions to minimise the reliance
The average temperatures at different times of the on air conditioning.
day and different seasons are shown in Figure 6. The
following conclusions can be made from this data. 1.6.5 Solar radiation
The air temperatures during the day in the summer The climate across the Middle East is dominated
months are very high, and it is extremely unlikely that by high solar intensity throughout the day. A key
buildings can be used passively during these times. design feature is to achieve low-energy buildings
and comfortable internal and external spaces with
The air temperatures during the night in summer shading to block solar radiation. The orientation of
are still high, and it is extremely unlikely that the building and location and size of windows can
benefit can be gained in the form of night-time be used to provide a degree of self-shading.
purge cooling during these months.
The average air temperatures during the day in It should be noted that in the summer mornings
winter are comfortable, so there is the potential for and evenings the sun is in the northern part of
useable external spaces. the sky (illustrated in Figure 8). This means that
the quantity of glazing will need to be limited and
The air temperatures at night are cooler in winter shading will be required on all facade orientations.
months, and could be used to provide free cooling This will affect both the thermal performance and
to the building (subject to air quality). visual comfort.
Figure 7: Dubai mean wet-bulb temperature, °C
40
NW NE
50
60
WNW ENE
18 70 JUN
231 231
17 7
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
424 424
16 80 8
544 544
15 9
636 14 10 636
W18 13 11 MAR
0 715 12 715 0
788 851 788
17 7
215 215
16 8
348 348
15 9
437 437
14 10
WSW 507 13 12 11 507 ESE
17 557 578 557 JUN
54 54
16 8
259 259
15 9
380 14 10 380
451 13 12 11 451
SW 493 493 SE
507
SSW SSE
S
1.6.6 Wind During the summer, the wind tends to come from
The wind climate around a building should have the northwest. These winds are hot and should
an important effect on the form and orientation of a be prevented from entering the building by the
building because the wind can be used to ventilate orientation of the building or by shutting the
internal and external spaces. Figures nine to twelve building openings.
show the average wind direction and strength for
The wind speeds during the night and mornings
different seasons and at different times of the day.
are low in strength and are expected to come from a
The benefits afforded by wind are strongly dependent range of directions from east around to southwest.
on the temperature of the air. It may be desirable at
some times of the year to prevent wind from entering During the night, it is possible to use purge
the building if the air temperature is high. ventilation cooling for a portion of the year. Due
to the low wind strength, if night purge cooling is
The following conclusions can be made from the supplied using natural ventilation, ventilation rates
data available. will be dominated by buoyancy forces rather than
driven by the wind.
During the normal day hours, the strongest winds
are in the winter and spring and tend to come from a It should be noted that wind is inherently a transient
westerly direction. These winds are cool to warm and phenomenon and will be constantly changing with
can be used for passive cooling of the external spaces. time. Therefore, although the wind roses show the
To exploit the benefits of these winds, the openings likely average wind directions, in reality the wind
in buildings should be orientated in this direction. direction and strength will continually change.
Figure 9: Spring wind roses m/s Figure 10: Summer wind roses m/s
Morning Daytime Morning Daytime
(10am–6pm) (6am–10am) (10am–6pm) (6am–10am)
Figure 11: Autumn wind roses m/s Figure 12: Winter wind roses m/s
Morning Daytime Evening Night-time
(10am–6pm) (6am–10am) (10am–6pm) (6am–10am)
Finally, the wind climate local to buildings is Figure 13 shows the humidity and external air
strongly dependent on the surrounding terrain temperature for three months. The following
and surrounding buildings. Where the design is information can be concluded from this.
dependent upon the wind patterns and profiles, site-
specific surveys are recommended. In such cases, In summer, the air temperatures are high, but also
consideration must be given to the impact of future the humidity levels are often high, although not
neighbouring developments. coincident. During these times, evaporative cooling
will work well during the day but not at night
1.6.7 Humidity when the humidity level increases and mechanical
The humidity of the air is important when considering systems will be required to achieve satisfactory
human comfort and the efficiency of cooling systems internal conditions.
In the mid seasons there are a range of humidity will be very unpleasant for a person who is outside.
values, but generally when the air temperature is It is not possible to passively achieve comfortable
high, the relative humidity is low, which means that external conditions during these times.
evaporative cooling could be beneficial.
In the mid seasons the wet-bulb temperature is still
In winter the air temperature is lower and, similar high. It is generally recommended by both CIBSE
to the mid seasons, a range of relative humidity and ASHRAE that evaporative cooling is not
values occur. undertaken for wet-bulb temperatures above 21 °C.
During these times, external spaces are likely to be
Due to its proximity to the sea, Dubai has a suitable for people moving between internal spaces
relatively humid climate when compared with more but not for people to spend considerable time in
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
inland locations. This will be a limiting factor in the during the day.
implementation of evaporative cooling and means
that the diurnal range is reduced when compared In winter the wet-bulb temperature is generally low,
with a more inland location. indicating pleasant external spaces and the potential
for natural or evaporation assisted ventilation.
The wet-bulb temperature can be used as a measure
of comfort because it relates to the ability of a 1.6.8 Precipitation (rainfall)
person to sweat in order to keep cool. The wet-bulb
temperatures are shown in Figure 14, from which The rainfall intensity for this region is sparse. Dubai has
the following conclusions can be made. short and irregular rainfall as is typical for the Middle
East. Most of the rainfall in Dubai occurs between
In the summer, the wet-bulb temperature is very high December and March, as can be seen from Figure 15.
at all times of day. A wet-bulb temperature of 26 °C Design intensity typically is 75 mm per hour.
0·025 0·025
Absolute humidity / kg water/kg dry air
0·020 0·020
20%
0·015 0·015
0·010 0·010
10%
0·005 0·005
0·000 0·000
-10 0 10 20 30 40 50
Dry bulb temperature / °C
Figure 14: Dubai annual mean wet-bulb temperatures °C In addition, the microclimate strategies will reduce
the heat island effect and lead to reduced energy
Figure 15: Monthly rainfall (cm)
consumption for cooling.
3·22
2·58 The microclimate of outdoor spaces is defined by
Rainfall / cm
them heating up. On summer evenings, comfort Additionally, internal spaces can be improved by
will be improved, as the surfaces will not radiate setting back glazing behind shaded balconies.
heat. Figure 16 illustrates the different building
configurations to protect spaces between buildings, 1.7.2 Air movement
depending on climate. Air movement is an important factor in
The orientation of the streets can be configured to improving comfort in external areas during
improve the amount of shading the streets receive the cooler months of the year. While the air
due to buildings. Because the sun tracks relatively temperature is lower than skin temperature (33–
high in the sky from east to west, the east and west 34 °C), air movement will improve the loss of heat
flanks of buildings offer the most shading. This leads from the skin and enhance comfort. Additionally,
to an ideal street orientation running from north to air movement over the skin will increase the rate of
south, thus maximising shading. evaporation and improve cooling of the body due to
sweat, thus increasing comfort.
When considering shading at the scale of buildings,
exposed horizontal faces must be taken into account. The wind can be used to increase air movement
Direct sunlight can penetrate underneath shading passively (so there is no need to input any energy).
structures in the morning and afternoon when the The majority of the wind comes from the north/
sun is at a low angle in the sky—the extent of shade northwest and can be channelled along orientated
required will be defined by the surrounding massing streets. Planning the site with building height rising
and the requirements of each space. It should be from these wind directions will allow the buildings
noted that solar intensity tends to increase from low to bring wind down onto the site, as illustrated in
sun angles to higher ones. Figure 17.
Figure 17: Wind channelling by using building
The facades of buildings should be configured height to increase air movement at low level
to reduce solar heat gain and cooling energy
consumption. This is particularly crucial for
the windows, which should be small and can be
shaded well by deep reveals and external structures.
This needs to be balanced with daylight and
view requirements.
Traditionally, localised devices are used to improve required. These issues are considered in detail in
conditions in their vicinity. Wind catching towers SLL Lighting Guide LG10: Daylighting and window
(see Figures 18 and 19) have been used in the Middle design (SLL, 1999). The required climatic data are
East to provide natural ventilation to buildings. discussed in detail in CIBSE Guide J: Weather, solar
They work by presenting a bluff body to the wind. and illuminance data (CIBSE, 2002).
The wind causes a positive pressure on the windward
side and a negative pressure on the leeward side. In photometry, illuminance is the total luminous flux
Fresh air will enter any windward opening and be incident on a surface, per unit area. It is a measure of
drawn up through from any leeward opening. how much the incident light illuminates the surface.
Similarly, luminous emittance is the luminous flux
1.8 Illumination per unit area emitted from a surface. Luminous
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
+ –
Although the solar corona is a source of extreme 4. Visible range of light spans 380–780 nm. As
UV and X-ray radiation, these rays make up only a the name suggests, this range is visible to the
very small amount of the power output of the sun naked eye.
(see Figure 21) and will not be discussed further. 5. Infrared range spans 700–106 nm (1 mm). It
The spectrum of nearly all solar electromagnetic is responsible for an important part of the
radiation striking the earth’s atmosphere spans electromagnetic radiation that reaches the
a range of 100 nm to about 1 mm. This band of earth. It is divided into three types on the basis
significant radiation power can be divided into five of wavelength:
regions in increasing order of wavelengths.
a. Infrared-A: 700–1400 nm
1. Ultraviolet C (UVC) range, which spans a range b. Infrared-B: 1400–3000 nm
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
a plane perpendicular to the rays, at a distance of combining the perception of bright white light
one astronomical unit (AU), roughly the mean (sunlight in the strict sense) and warming. The
distance from the sun to the earth. The ‘solar warming on the body, the ground and other objects
constant’ includes all types of solar radiation, not depends on the absorption of the electromagnetic
just the visible light. Its average value was thought radiation in the form of heat.
to be approximately, 1.366 kW/m² varying slightly
with solar activity, but recent recalibrations of The amount of radiation intercepted by a planetary
the relevant satellite observations indicate that a body varies inversely with the square of the distance
value closer to 1.361 kW/m² is more realistic. This between the star and the planet. The earth’s orbit
radiation is about 50% infrared, 40% visible and 10% and obliquity change with time (over thousands of
UV at the top of the atmosphere. years), sometimes forming a nearly perfect circle
and at other times stretching out to an orbital
1.8.5 Total solar irradiance (TSI) and spectral solar eccentricity of 5% (currently 1.67%). The total
irradiance (SSI) on Earth insolation remains almost constant due to Kepler’s
Total solar irradiance (TSI)—the amount second law:
of solar radiation received at the top of the
earth’s atmosphere—was measured by satellite
2A
to be roughly 1.366 kW per m², but NASA dt = dθ (1.3)
describes TSI as ‘1361 W/m² as compared to r2
~1366 W/m² from earlier observations’, based on
regular readings from NASA’s Solar Radiation and where A is the ‘areal velocity’ invariant, i.e. the
Climate Experiments (SORCE) satellite, active since integration over the orbital period (also invariant)
2003. This is a NASA-sponsored satellite mission is a constant.
that provides measurements of incoming X-ray,
UV, visible, near-infrared and total solar radiation. T 2A 2π
These measurements specifically address long-term ∫ 0 r2
= ∫
0
= constant (1.4)
climate change, natural variability and enhanced
climate prediction, and atmospheric ozone and If we assume the solar radiation power as a constant
UVB radiation. These measurements are critical to over time and the solar irradiation given by the
studies of the sun, its effect on the earth system and inverse-square law, we also obtain the average
its influence on humankind. The Laboratory for insolation as a constant.
Atmospheric and Space Physics (LASP) has further
information on this topic. The seasonal and latitudinal distribution and
intensity of solar radiation received at the earth’s
1.8.6 Surface illumination surface also varies. For example, at latitudes of 65°
The spectrum of surface illumination depends on the change in solar energy in summer and winter
solar elevation due to atmospheric effects, with the can vary by more than 25% as a result of the earth’s
blue spectral component from atmospheric scatter orbital variation. Because changes in winter and
dominating during twilight before and after sunrise summer tend to offset each other, the change in the
respectively, and red dominating during sunrise annual average insolation at any given location is
near zero, but the redistribution of energy between humidity and solar conditions.
summer and winter does strongly affect the intensity
of seasonal cycles. Such changes associated with the Changes in the 2009 edition of ASHRAE Handbook:
redistribution of solar energy are considered a likely Fundamentals (ASHRAE, 2009) from the 2005
cause for the coming and going of recent ice ages. edition include the use of different percentiles for
monthly design dry-bulb and mean coincident wet-
1.9 Climatic design information bulb temperatures and monthly design wet-bulb
Climate design information is generally sourced and mean coincident dry-bulb temperatures.
from recognised weather data files and used for
Additions to the 2009 edition (ASHRAE, 2009)
design, sizing, distribution, installation and
were monthly average temperature and standard
marketing of heating, ventilating, air conditioning
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Lat: 25.25N Long: 55.33E Elev: 10 StdP: 101.2 Time Zone: 4.00 (ARN) Period: 86-10 WBAN: 99999
Annual Heating and Humidification Design Conditions
Annual Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
(d) (e) (f) (g) (h) (i) (j) (k) (l) (m) (n) (o) (p)
(5) Tavg 28.0 19.2 20.7 23.2 27.1 31.3 33.5 35.4 35.8 33.3 29.9 25.5 21.3 (5)
(6) Sd 2.02 2.73 3.16 3.25 2.67 2.12 2.12 1.74 1.60 1.77 2.01 2.11 (6)
(7) Temperatures, HDD10.0 0 0 0 0 0 0 0 0 0 0 0 0 0 (7)
(8) Degree-Days HDD18.3 21 13 6 1 0 0 0 0 0 0 0 0 2 (8)
(9) and CDD10.0 6588 284 299 408 513 661 704 788 800 698 616 464 352 (9)
(10)
Degree-Hours CDD18.3 3568 39 72 151 263 403 454 529 542 448 358 214 95 (10)
(11) CDH23.3 49383 131 356 1106 2972 5851 7132 8696 8905 6888 4807 2055 487 (11)
(12) CDH26.7 30779 12 87 384 1425 3591 4759 6216 6425 4506 2602 708 63 (12)
(17) DB 28.2 32.1 35.9 39.2 42.5 43.8 44.6 44.2 41.8 38.8 34.1 30.0 (17)
0.4%
(18)
Monthly Design
MCWB 17.3 17.8 18.2 19.8 20.9 21.8 24.0 23.8 23.0 20.7 19.2 18.5 (18)
(19) Dry Bulb DB 26.2 29.1 32.9 36.9 40.2 41.3 42.8 42.8 40.0 36.9 32.4 28.2 (19)
2%
(20) and MCWB 17.5 17.6 18.3 19.6 21.2 22.8 24.5 24.3 23.2 21.5 20.7 19.3 (20)
(21) Mean Coincident DB 24.8 27.1 30.7 35.0 38.8 39.9 41.1 41.1 38.8 35.5 31.2 27.1 (21)
Wet Bulb 5%
(22) MCWB 17.5 17.5 18.3 19.7 21.6 23.3 25.2 24.9 23.9 22.5 21.3 19.4 (22)
Temperatures
(23) DB 23.2 25.2 28.7 33.1 37.1 38.4 39.8 39.9 37.2 34.2 30.1 26.0 (23)
10%
(24) MCWB 17.0 17.8 18.2 19.8 22.0 24.4 25.5 25.5 24.8 23.3 21.6 19.1 (24)
(25) WB 20.6 21.3 22.5 24.6 27.9 30.1 31.1 31.0 30.2 28.7 25.6 22.5 (25)
0.4%
(26)
Monthly Design
MCDB 24.2 25.1 27.4 30.9 33.1 34.7 35.8 35.5 34.3 33.0 30.0 26.2 (26)
(27) Wet Bulb WB 19.6 20.5 21.6 23.5 26.8 29.2 30.4 30.3 29.6 27.7 24.4 21.5 (27)
2%
(28) and MCDB 23.6 24.4 26.4 29.9 32.4 34.0 35.2 35.0 33.9 31.9 29.2 25.8 (28)
(29) Mean Coincident WB 18.8 19.7 20.9 22.7 26.0 28.7 29.8 29.8 29.1 26.9 23.6 20.7 (29)
Dry Bulb 5%
(30) MCDB 23.0 23.9 25.8 29.1 32.2 33.7 34.8 34.7 33.5 31.5 28.5 25.2 (30)
Temperatures
(31) WB 18.0 19.0 20.3 22.0 25.1 28.0 29.3 29.2 28.5 26.3 22.8 19.9 (31)
10%
(32) MCDB 22.3 23.5 25.1 28.3 32.0 33.5 34.7 34.7 33.2 31.1 28.0 24.6 (32)
(33) MDBR 8.5 8.7 9.2 10.5 11.6 10.9 9.5 9.6 9.9 10.1 9.5 8.8 (33)
(34) Mean Daily MCDBR 10.2 11.1 12.1 13.0 13.3 12.6 11.1 11.0 11.2 11.2 10.4 10.1 (34)
5% DB
(35) Temperature MCWBR 4.9 5.1 5.8 6.3 6.5 6.9 6.4 6.3 6.7 6.5 5.1 4.9 (35)
(36) Range MCDBR 8.7 8.7 9.4 10.8 11.7 10.6 9.1 9.4 9.5 9.7 9.7 9.1 (36)
5% WB
(37) MCWBR 4.8 4.8 5.2 5.8 6.3 5.9 5.6 5.7 5.5 5.5 5.0 5.0 (37)
(38) taub 0.463 0.508 0.547 0.558 0.596 0.675 0.792 0.684 0.585 0.499 0.463 0.451 (38)
Clear Sky
(39) taud 2.185 2.029 1.902 1.828 1.708 1.551 1.427 1.611 1.820 2.046 2.186 2.232 (39)
Solar
(40) Irradiance Ebn,noon 779 771 763 765 734 673 598 664 722 767 772 773 (40)
(41) Edh,noon 131 164 195 214 241 280 317 263 209 158 130 121 (41)
(a) Temperatures, degree-days and degree-hours nominal percentile, depending on the month and
the seasonal distribution of the parameter at that
t Average temperature, °C. This parameter is a location. Generally, for the hottest or most humid
prime indicator of climate and is also useful to months of the year, the monthly percentile value
calculate heating and cooling degree-days to exceeds the design condition for the same element
any base. corresponding to the same nominal percentile. For
t Standard deviation of average daily example, Table 2 shows that the annual 0.4% design
temperature, °C. This is useful to calculate dry-bulb temperature at Dubai, is 34.9 °C; the 0.4%
heating and cooling degree-days to any base. Its monthly dry-bulb temperature exceeds 34.4 °C
use is explained in the section on estimation of from March to October, with values ranging from
degree-days, or see ASHRAE (2009). 35.9 °C, 42.2 °C and 38.2 °C, respectively. Two new
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
t Heating and cooling degree-days (bases 10 percentiles were added to the data sheets 5.0 and
and 18.3 °C). These parameters are useful in 10.0% values to give a greater range in the frequency
energy estimating methods. They are also of occurrence, in particular providing less extreme
used to classify locations into climate zones in options to select for design calculations.
ASHRAE Standard 169-2006: Weather Data for
A general, very approximate rule of thumb is that
Building Design Standards.
the n% annual cooling design condition is roughly
t Cooling degree-hours (bases 23.3 °C and 26.7 °C). equivalent to the 5n% monthly cooling condition for
These are used in various standards, such as the hottest month; i.e. the 0.4% annual design dry-
ANSI/ASHRAE Standard 90.2-2007: Energy- bulb temperature is roughly equivalent to the 2%
Efficient Design of Low-Rise Residential Buildings. monthly design dry-bulb temperature for the hottest
(b) Monthly design dry-bulb, wet-bulb and month; the 1% annual value is roughly equivalent to
mean coincident temperatures the 5% monthly value for the hottest month, and the
2% annual value is roughly equivalent to the 10%
These values are derived from the same analysis monthly value for the hottest month.
that results in the annual design conditions. The
monthly summaries are useful when seasonal
variations in solar geometry and intensity, building These values are useful in calculating daily dry- and
or facility occupancy, or building use patterns wet-bulb temperature profiles, as mentioned in the
require consideration. In particular, these values can section on generating design-day data. Three kinds
be used when determining air conditioning loads of profile are defined, as follows.
during periods of maximum solar radiation. The
values listed in the tables include: t Mean daily temperature range for month
indicated, °C (defined as mean of difference
t dry-bulb temperature corresponding to 0.4%, between daily maximum and minimum dry-
2.0%, 5.0% and 10.0% cumulative frequency bulb temperatures).
of occurrence for indicated month, °C; mean
t Mean daily dry- and wet-bulb temperature
coincident wet-bulb temperature, °C
ranges coincident with the 5% monthly design
t wet-bulb temperature corresponding to 0.4%, dry-bulb temperature. This is the difference
2.0%, 5.0% and 10.0% cumulative frequency between daily maximum and minimum dry- or
of occurrence for indicated month, °C; mean wet-bulb temperatures, respectively, averaged
coincident dry-bulb temperature, °C. over all days where the maximum daily dry-
For a 30-day month, the 0.4%, 2.0%, 5.0% and 10.0% bulb temperature exceeds the 5% monthly
values of occurrence represent the value that occurs design dry-bulb temperature.
or is exceeded for a total of 3, 14, 36 or 72 hours, t Mean daily dry- and wet-bulb temperature
respectively, per month on average over the period ranges coincident with the 5% monthly design
of record. Monthly percentile values of dry- or wet- wet-bulb temperature. This is the difference
bulb temperature may be higher or lower than the between daily maximum and minimum dry- or
annual design conditions corresponding to the same wet-bulb temperatures, respectively, averaged
over all days where the maximum daily wet-bulb t Integrated Surface Dataset (ISD) data for
temperature exceeds the 5% monthly design wet- stations from around the world provided by
bulb temperature. NCDC for the period 1982 to 2006 (Lott,
Baldwin and Jones 2001; NCDC 2003) (see
1.9.1.7 Clear-sky solar irradiance Figure 22).
Clear-sky irradiance parameters are useful in t Hourly weather records for the period
calculating solar-related air conditioning loads (provided by ASHRAE as required).
for any time of any day of the year. Parameters are
provided for the 21st day of each month. The 21st In most cases, the period of record used in the
of the month is usually a convenient day for solar calculations spanned 25 years—a compromise
calculations because 21 June and 21 December between trying to derive design conditions from
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
represent the solstices (longest and shortest days) the longest possible period of record and using
and 21 March and 21 September, are close to the the most recent data to capture climatic or land
equinox, (days and nights have the same length). use trends from the past two decades. The actual
Parameters listed in the tables are: number of years used in the calculations for a given
station depends on the amount of missing data, and,
t clear-sky optical depths for beam and diffuse as discussed in the next section, may be as few as
irradiances, which are used to calculate beam eight years. The first and last years of the period of
and diffuse irradiance as explained in the record used to calculate design conditions are listed
section on calculating clear-sky solar radiation in the top section of the tables of climatic design
t clear-sky beam normal and diffuse horizontal conditions, as shown in Table 2 for Dubai.
irradiances at solar noon.
Clear-sky solar irradiance parameters listed in the
These two values can be calculated from the clear-sky tables constitute a simple parameterisation of a
optical depths but are listed here for convenience. sophisticated broadband clear-sky radiation model
called REST2 (Gueymard, 2008; Thevenard, 2009).
1.9.1.8 Data sources The REST2 model requires detailed knowledge of
Two primary sources of observational data sets were various atmospheric constituents such as aerosols,
used in calculating design values. water vapour, ozone, etc. To extend applicability
Figure 22: Location of worldwide weather stations
Reproduced by permission of ASHRAE © ASHRAE (ASHRAE Handbook: Fundamentals, Chapter 14, Fig. 1 (2013))
of the model to the whole world, multiple data way but are usually viewed as the values for which
sets, mainly derived from space observations, were the corresponding weather element is less than
used to obtain these inputs. Water vapour data the design condition for 88 hours and 35 hours,
were derived from the NVAP satellite/radiosonde respectively. Simple design conditions were obtained
assimilated dataset for 1988–1999 (Randel et al., by binning hourly data into frequency vectors, then
1996), corrected for elevation (Thevenard, 2009). deriving from the binned data the design condition
Total ozone amount was derived from observations having the probability of being exceeded a certain
of the Total Ozone Mapping Spectrometer (TOMS) percentage of the time. Mean coincident values were
instrument aboard the Nimbus 7 satellite. More obtained by double-binning the hourly data into
information is available from the Goddard Earth joint frequency matrices, then calculating the mean
Sciences Distribution Information and Service coincident value corresponding to the simple design
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Center (GES DISC), NASA. A fixed NO2 amount of condition. Coincident temperature ranges were
0.4 matm·cm was used throughout the world. Far- also obtained by double-binning daily temperature
field ground albedo was obtained from the Surface ranges (daily maximum minus minimum) versus
and Atmospheric Radiation Budget (SARB) based maximum daily temperature. The mean coincident
on Clouds and the Earths Radiant Energy System daily range was then calculated by averaging all
(CERES) data for 2000–2005 by NASA’s Langley bins above the simple design condition of interest.
Research Centre. Aerosol turbidity data received The weather data sets used for the calculations
special attention because they are the primary often contain missing values (either isolated
inputs that condition the accuracy of the direct and records or because some stations report data only
diffuse irradiance predictions under clear skies. every third hour). Gaps up to 6 h were filled by
Space-borne data sets were used and were calibrated linear interpolation to provide as complete a time
against a large number of ground-based sites. Six series as possible. Dry-bulb temperature, dew-
years (2000–2005) of simulated monthly-average point temperature, station pressure and humidity
aerosol optical depth at 550 nm were prepared with ratio were interpolated. However, wind speed and
the MATCH model (Rasch, Mahowald and Eaton, direction were not interpolated because of their
1997) by the Science Directorate/Climate Science more stochastic and unpredictable nature. Some
Branch at NASA Langley Research Center, which stations in the ISD data set also provided data that
also supplied aerosol single-scattering albedo were not recorded at the beginning of the hour.
estimates. Aerosol optical depth data from MATCH When data at the exact hour were missing, they were
were combined with retrievals from two MODIS replaced by data up to 0.5 h before or after, when
instruments (http://modis-atmos.gsfc.nasa.gov), and available. Finally, psychrometric quantities, such as
compared for ground-truthing with a large number wet-bulb temperature or enthalpy, are not contained
of ground-based sites, mostly from the AERONET in the weather data sets. They were calculated from
network (http://aeronet.gsfc.nasa.gov). Other details dry-bulb temperature; dew-point temperature and
can be found in Thevenard (2009). station pressure using the psychrometric equations
(ASHRAE, 2009).
1.9.1.9 Calculation of design conditions
Values of ambient dry-bulb, dew-point and wet- Measures were taken to ensure that the number and
bulb temperature and wind speed corresponding distribution of missing data, both by month and by
to the various annual percentiles represent the hour of the day, did not introduce significant biases
value that is exceeded on average by the indicated into the analysis. Annual cumulative frequency
percentage of the total number of hours in a year distributions were constructed from the relative
(8760). The 0.4%, 1.0%, 2.0% and 5.0% values are frequency distributions compiled for each month.
exceeded on average 35, 88 hours, 175 hours and Each individual month’s data were included if they met
438 hours per year, respectively, for the period of the following screening criteria for completeness and
record. The design values occur more frequently unbiased distribution of missing data after data filling.
than the corresponding nominal percentile in some
years and less frequently in others. The 99.0% and t The number of hourly dry-bulb temperature
99.6% (cold-season) values are defined in the same values for the month, after filling by
interpolation, had to be at least 85% of the total potential errors. These checks included contour plots,
hours for the month. consistency checks among the various parameters
t The difference between the number of day and and comparison to the 2005 edition of the ASHRAE
night-time dry-bulb temperature observations handbook (ASHRAE, 2005); about 32 stations from
had to be less than 60. the 2005 edition have no equivalent within a 12-
mile distance in the 2009 edition, these stations may
Although the nominal period of record selected for
have been dropped because of quality problems, or
this analysis was 25 years (1982 to 2006 for most
simply because they did not have enough data within
stations), some variation and gaps in observed
the 1982–2006 period of record used for the present
data meant that some months’ data were unusable
edition (ASHRAE, 2009). Further details of the
because of incompleteness. Some months were also
analysis procedures are available in Thevenard (2009).
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
!
Annual enthalpy design conditions give the annual
design conditions enthalpy for the cooling season; this is used for
The month with the highest mean dry-bulb calculating cooling loads caused by infiltration and/
temperature is used, for example, to determine the or ventilation into buildings. Enthalpy represents
time of year where the maximum sensible cooling the total heat content of air (the sum of its sensible
load occurs, not taking into account solar loads. and latent energies). Cooling loads can be calculated
The mean daily dry-bulb temperature range for the knowing the conditions of both the outdoor ambient
hottest month is the mean difference between the and the building’s interior air.
daily maximum and minimum temperatures during
1.9.1.13 Extreme annual design conditions
the hottest month and is calculated from the extremes
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
of the hourly temperature observations. The true Extreme annual design wind speeds are used
maximum and minimum temperatures for any day in designing smoke management systems. The
generally occur between hourly readings. Thus, extreme maximum wet-bulb temperature provides
the mean maximum and minimum temperatures the highest wet-bulb temperature observed over
calculated in this way are about 0.5 °C less extreme the entire period of record and is the most extreme
than the mean daily extreme temperatures observed condition observed during the data record for
with maximum and minimum thermometers. This evaporative processes such as cooling towers. For
results in the true daily temperature range generally most locations, the extreme maximum wet-bulb
being about 1°C greater than that calculated from value is significantly higher than the 0.4% wet-bulb
hourly data. The mean daily dry-bulb temperature (see above) and should be used only for design of
range is used in cooling load calculations. The critical applications where an occasional short-
0.4%, 1.0% and 2.0% dry-bulb temperatures and duration capacity shortfall is not acceptable. The
mean coincident wet-bulb temperatures often mean and standard deviation of the extreme annual
represent conditions on hot, mostly sunny days. maximum and minimum dry-bulb temperatures
These are often used in sizing cooling equipment are used to calculate the probability of occurrence
such as chillers or air conditioning units. Design of very extreme conditions. These can be required
conditions based on wet-bulb temperature represent for design of equipment to ensure continuous
extremes of the total sensible plus latent heat of operation and serviceability, regardless of whether
outdoor air. This information is useful for design the heating or cooling loads are being met. These
of cooling towers, evaporative coolers and fresh- values were calculated from extremes of hourly
air ventilation systems. The mean wind speed and temperature observations. The true maximum and
direction coincident with the 0.4% design dry- minimum temperatures for any day generally occur
bulb temperature is used for estimating peak loads between hourly readings. Thus, the mean maximum
accounting for infiltration. Design conditions based and minimum temperatures calculated in this way
on dew-point temperatures are directly related are about 0.5 °C less extreme than the mean daily
to extremes of humidity ratio, which represent extreme temperatures observed with maximum and
peak moisture loads from the weather. Extreme minimum thermometers. The 5-, 10-, 20- and 50-
dew-point conditions may occur on days with year return periods for maximum and minimum
moderate dry-bulb temperatures, resulting in extreme dry-bulb temperature are also listed. Return
high relative humidity. These values are especially period (or recurrence interval) is defined as the
useful for humidity control applications such as reciprocal of the annual probability of occurrence.
desiccant cooling and dehumidification, cooling- For example, the 50-year return period maximum
based dehumidification and fresh-air ventilation dry-bulb temperature has a probability of occurring
systems. The values are also used as a checkpoint or being exceeded of 2.0% (i.e., 1/50) each year. This
when analysing the behaviour of cooling systems statistic does not indicate how often the condition
at part load conditions, particularly when such will occur in terms of the number of hours each year
systems are used for humidity control as a secondary (as in the design conditions based on percentiles) but
function. Humidity ratio values are calculated from describes the probability of the condition occurring
the corresponding dew-point temperature and at all in any year. The following method can be used
the standard pressure at the location’s elevation. to estimate the return period (recurrence interval) of
Table 3: Approximate astronomical data for the 21st day of each month
Month Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Day of year 21 52 80 111 141 172 202 233 264 294 325 355
E W/m2 1410 1397 1378 1354 1334 1323 1324 1336 1357 1380 1400 1411
Equation of time (ET), min 1.2 3.7 6.9 15.5 13.8 2.2
Declination , degrees 11.6 20.1 23.4 20.4 11.8
Source: ASHRAE. LST = local standard time, decimal hours; ET = equation of time in minutes, from Table 3 or equation 1.9;
LSM = longitude of local standard time meridian, °E of Greenwich (negative in western hemisphere); LON = longitude of site, °E of Greenwich
Tropic of
Cancer
23·5° N. latitude Declination
angle
154·4 GM 144·5 GM
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
The
Equatorial sun
plane Tropic of
Capricorn
June 21 23·5° S. latitude December 21
Orbital plane
(plane of the
September 21 ecliptic)
θ
Earth-sun line
N
Vertical Tilted
Solar W surface surface
altitude
β
Σ = tilt angle
Θ
H
Solar θV O
azimuth γ
φ Horizontal surface
ψ
Normal to
E
vertical
S P surface
convention, it is counted positive for afternoon the rotation of the earth, and expressed in degrees as:
hours and negative for morning hours.
H = 15 (AST – 12) (1.15)
Solar altitude and azimuth angles, in turn, depend
on the local latitude L (°N, negative in the southern
hemisphere); the solar declination which is a where AST is the apparent solar time (equation 1.11).
function of the date (see Table 3 or Equation 1.10; and H is zero at solar noon, positive in the afternoon,
the hour angle H, defined as the angular displacement and negative in the morning.
of the sun east or west of the local meridian due to
sin
= cos L cos
cos H + sin L sin where:
(1.16)
t Eb = beam normal irradiance (measured
perpendicularly to rays of the sun)
Note that at solar noon, H = 0 and the sun reaches
t Ed = diffuse horizontal irradiance (measured
its maximum:
on horizontal surface)
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
1.9.6 Transposition to receiving surfaces of various Finally, the angle between the line normal to the
orientations irradiated surface and the earth-sun line is called the
angle of incidence . It is important in fenestration,
Calculations developed in the previous section are
load calculations and solar technology because
chiefly concerned with estimating clear-sky solar
it affects the intensity of the direct component of
irradiance either normal to the rays of the sun (direct
solar radiation striking the surface and the surface’s
beam) or on a horizontal surface (diffuse). However,
ability to absorb, transmit or reflect the sun’s rays.
in many circumstances, calculation of clear-sky
Its value is given by:
solar irradiance is required on surfaces of arbitrary
orientations. Receiving surfaces can be vertical (e.g.
walls and windows) or tilted (e.g. skylights or active cos = cos cos sin
+ sin cos
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Orientation N NE E SE S SW W NW
Surface azimuth 180º 0 45º 90º 135º
( +
( )
$*
The beam component is obtained from a Ground-reflected irradiance for surfaces of all
straightforward geometric relationship: orientations is given by:
#
where Y is calculated for a vertical surface having the Table 6 gives a normalised daily temperature profile
same azimuth as the receiving surface considered. in fractions of daily temperature range. Recent
Note that equations 1.31–1.34 are appropriate for research projects RP-1363 (Hedrick, 2009) and
clear-sky conditions, but should not be used for RP-1453 (Thevenard, 2009) have shown that this
cloudy skies. profile is representative of both dry-bulb and wet-
!
$
1 (−Z 2 )
f (Z ) = exp (1.38)
When hourly dry-bulb and wet-bulb temperatures 2π 2
are known, additional moist air properties (e.g. dew-
point temperature, humidity ratio, enthalpy) can be
derived using the psychrometric chart, equations F (Z) =
f (z) dz (1.39)
Both f and F are readily available as built- Although these results are consistent with general
in functions in many scientific calculators or warming of the world climate system, there are other
spreadsheet programs, so their manual calculation effects that undoubtedly contribute such as increased
is rarely warranted. urbanisation around many of the observing sites
(airports, typically). There was no attempt in the
Cooling degree days CDDb to base Tb are calculated analysis to determine the reasons for the changes.
by the same equation: Regardless of the reasons for increases, the general
approach of developing design conditions based on
analysis of the recent record (25 years, in this case)
CDDb = N sd [Zb F (Zb) + f (Zb)] (1.40)
was specifically adopted for updating the values
(ASHRAE 2009) as a balance between accounting
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
except that Zb is now expressed as for long-term trends and the sampling variation
caused by year-to-year variation.
T − Tb
Zb = (1.41)
sd Although this does not necessarily provide
the optimum predictive value for representing
conditions over the next one or two decades, it
1.9.9.3 Annual degree-days at least has the effect of incorporating changes
Annual degree-days are simply the sum of monthly in climate and local conditions as they occur, as
degree-days over the 12 months of the year. For most updates are conducted regularly using recent data.
stations, the monthly degree-days calculated with Meteorological services worldwide are considering
this method are within 5 °C-day of the observed the many aspects of this complex issue in the
values. calculation of climate ‘normals’ (averages, extremes
and other statistical summary information of
For examples refer to ASHRAE (2009), section climate elements typically calculated for a 30-year
14.12. period at the end of each decade). Livezey et al.
(2007) and WMO (2007) provide detailed analyses
1.9.10 Effects of climate change and recommendations in this regard. Extrapolating
The evidence is unequivocal that the climate design conditions to the next few decades based on
system is warming globally (IPCC, 2007). The most observed trends should only be done with attention
frequently observed effects relate to increases in to the particular climate element and the regional
average, and to some degree extreme, temperatures. and temporal characteristics of observed trends
This is partly illustrated by the results of an analysis (Livezey et al., 2007).
of design conditions conducted as part of developing
the updated values for ASHRAE data (Thevenard,
2009). For 1274 observing sites worldwide with
suitably complete data from 1977 to 2006, selected
design conditions were compared between the
periods of 1977–1986 and 1997–2006. The results,
averaged over all locations, are as follows.
2 Basic design data designing. These are summarised here and discussed
in more detail later.
2.1 Comfort
The factors affecting comfort, which include 1. Conduction: this is due to air temperature and
temperature, noise level, intensity of illumination, accounts for around 30% of perceived comfort.
clothing and the quality of air are discussed in Traditionally, HVAC engineers focus on this.
chapter 1 of CIBSE Guide A (CIBSE, 2006) and these 2. Convection: this is due to air movement
factors generally apply to arid climates such as in the and humidity and the cooling effect from
Middle East. However, there are certain aspects of evaporation of perspiration from the body. This
thermal comfort that should be highlighted. accounts for around 25% of perceived comfort
and is provided by moving air through a room,
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
A person is capable of maintaining constant body either by mechanical means, or through natural
temperature in a wide range of environmental ventilation. Generally, mechanical engineers try
conditions by involuntary mechanisms, such as to avoid air movement above around 0.5 m/s as
shivering and sweating, and by adjusting clothing cold supply air will be felt as an uncomfortable
and changing the level of activity. Individuals may draught rather than a pleasant breeze.
differ in their comfort requirements according to the
3. Radiation: at 45% of perceived comfort,
degree of acclimatisation, activity level and clothing.
radiation is the primary driver, yet it is
It has been shown that as a consequence of generally overlooked in air conditioned
acclimatisation to ‘high’ temperatures fewer people buildings as air conditioning conditions the air,
can be comfortable in optimum conditions. However, whereas radiative comfort needs the structure
it may be argued that in very warm climates, cooling to be conditioned.
to any degree is welcome. Design techniques for natural ventilation are detailed
in CIBSE AM10: Natural ventilation in non-domestic
Higher temperatures can be acceptable, and may be
buildings (CIBSE, 2005a) and are not discussed here.
beneficial, in spaces where occupancy is transient.
This is often useful in providing a buffer zone Whether or not natural ventilation can even be used
between ‘warm’ outside conditions and general ‘cool’ depends on location, as not all hot, arid climates are
inside conditions allowing gradual acclimatisation the same. Natural ventilation techniques, such as
by reducing temperature differences and thereby night purging, will generally work when there is a
avoiding physiological effects such as ‘thermal large diurnal swing with cool nights, even if the days
shock’. In this case the temperature differential get hot, provided thermal mass is used wisely and
between outside and inside should be limited to internal loads are not too high.
approximately 15 °C where a buffer zone is provided
and to 10 °C in other situations. When temperatures While natural ventilation might be an acceptable
in working environments exceed 30 °C there is likely solution in villages, dense cities may not allow it,
to be a reduction in mental skills. as heat is trapped in the city. Even ideal thermal
conditions are no match for sandstorms or noise,
In terms of thermal comfort, there are three however. Table 9 summarises when natural
mechanisms that engineers need to consider when ventilation could be considered.
Table 9: Natural
Natural Other Examples
ventilation options for
ventilation? considerations different conditions
Cool night/mild day Yes Dust and noise Winter in Gulf
Cool night/hot day Yes Night purge Iran, Mediterranean
Thermal mass cities, American deserts
Fans
Low internal loads
Dust and noise
Warm night/hot day No Dense cities, e.g.
Damascus
60
50
0·2 40
30 55
0·1 20
10 50
0 0
5 10 15 20 25 30
°C
45
40 50 60 70 80 90 50 60 70 80 90
Indoor design temperature / °F Outside relative humidity / %
and radiant cooling) and as a result many buildings, the extent that smoking is likely to occur, i.e. ‘no
in practice, are maintained at close to 21 °C or lower, smoking’, ‘some smoking’ and ‘heavy smoking’. In
resulting in thermal shock. some regions of the Middle East, there is a drive
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Table 10 gives a range of internal design conditions 3. Occupancy schedules to reflect changes in
for hot arid climates such as the Middle East. population according to time of day.
Internal relative humidity can also vary with outside The control system that responds to varying
conditions. Table 10 indicates suggested values. conditions must be capable of providing at least the
Relative humidity affects the body sweat rate, which minimum ventilation requirement when the space
is an important mechanism for body heat loss, is occupied.
particularly in warm humid environments, and in
2.1.8 Outdoor comfort
a reduced space relative humidity can lead, under
these circumstances, to improved comfort. Note While building services engineers normally focus on
that in central desert areas, low humidity can also the inside of a building, the environment outside the
cause problems. building is also experienced by most building users.
The mechanical engineers (or building physicists)
2.1.7 Outside air rates are best placed to advise on the treatment of these
In chapter l of CIBSE Guide A (CIBSE, 2006), spaces in terms of comfort, so limited information
fresh-air ventilation rates are classified according to is included here.
Table 11: Fresh air ventilation rates for air conditioned buildings
While hot, arid environments can reach very high When calculating summer loads, it should be
temperatures outdoors, this does not mean they remembered that the time at which the peak
necessarily have to be uncomfortable. The following cooling load occurs in an individual space will
factors should be considered when designing vary with orientation. Consequently, the maximum
outdoor spaces to be comfortable. simultaneous demand imposed upon the central
plant is not generally the sum of the peak loads
t Radiation: protection of direct sun is crucial, occurring in the individual spaces or zones of a
but less obvious is radiation from surrounding building but almost certainly a lower figure.
surfaces that have heated up in the sun.
Even on the design-day, it is found in practice that
t Air movement and evaporation: wind should systems do not work at their maximum, because the
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
be directed, or mechanically augmented, internal load is always lower than the theoretical
as required. Misting systems may also be peak—the simultaneous sum of the heat gains in the
appropriate depending on water availability various treated areas in a building will be less than
and humidity. the sum of their maximum individual gains: some
t Air temperature: in some applications, of the people will be absent, for varies reasons; a
mechanical cooling of outdoor spaces may proportion of the lights will be switched off or need
be appropriate, in which case efforts need to replacing; and business machines do not generally
be made to contain cooled air and to provide operate simultaneously. A diversity factor therefore
cooling through zero-carbon means. needs applying to these elements to enable this
inevitable load variation to be taken into account
2.2 Basic design information at the design stage so the system is not unduly
oversized. (Clearly, the diversity applied should be
2.2.1 Energy considerations adjusted to suit the design and usage of the building.)
Environmental concerns and the rising cost of fuel Although in hot climates full load conditions tend
mean there is an increased focus on minimising to occur more often than in temperate zones, the
energy usage during the natural occupational life of majority of cooling coils still operate at part load
a building. In many of the world’s hot, arid areas, for most of their life. If systems are designed to
the number of large developments in recent years meet the most extreme circumstances, they and
has grown exponentially. New construction has their associated controls will be greatly oversized
resulted in millions of refrigeration kWs of new air for ‘normal’ conditions. Oversized air conditioning
conditioning equipment being installed or planned. systems do not do a good job of reducing humidity,
In some of these countries, more than 50% of the so the result can be a cool but humid environment.
electric demand in the summer months comes Also, predictably, oversized systems waste energy.
from air conditioning loads. When air conditioning
design considerations are being made for a large Multiple chiller configurations are a common
new facility, the availability of power is often taken method of effectively meeting both peak and part
for granted. More than just the local availability of load conditions in large installations. They allow
power, the decisions made for air conditioning have facilities engineers to stage their operation to match
an impact on the main power generation plant. the cooling load while keeping the chillers operating
efficiently. They also provide redundancy for routine
The thermal performance of the building envelope maintenance and equipment failure.
is one of the main drivers in determining what
the cooling load and resultant energy use will be. Multiple chiller installations can be symmetrical
Hence it is important to consider the building (all chillers sized equally) or asymmetrical (one or
envelope design with primary significance. more chillers sized at a different capacity). The key
(Insulation, for example, plays an important part to deciding the best arrangement is dependent on
in reducing the heat exchange between the inside the minimum anticipated cooling load. For many
and outside environment as well as the formation typical applications, sizing one chiller at one-third
of condensation.) peak load and the other at two-thirds peak load
enables the system to meet most cooling conditions but some of these rely on water—not always a
at relatively high chiller part load efficiencies. Even practical solution in areas where clean water is not
if the load falls below the capacity of a single chiller, in abundance. A preferred option is perhaps self-
it is still likely to be operating above 30%, which is dusting solar panels, cleaned by an electric charge
within a chiller’s acceptable region of efficiency. provided by the panels themselves; these are based
on technology specifically developed for dry and
Because there is a large temperature difference dusty environments. There have also been some
between the incoming and outgoing ventilation recent developments in dust-resistant coatings that
airstreams in hot climates, abundant waste energy are applied to the surface of the panels to actively
can be recovered through exhaust energy recovery repel dust.
systems. This can play a significant role in decreasing
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
the cooling load. Another form of solar energy that has vast potential
in sunny regions is concentrated solar power (CSP).
In sunny climates, excessive brightness contrast This system uses a series of parabolic mirrors to
between externally lit surfaces and building capture and focus the sun’s energy to create steam
interiors causes visual discomfort. This is altered by to drive a turbine that powers an electric generator
switching on internal lights permanently, leading to (or perhaps an absorption chiller). CSP is a proven
unnecessary energy consumption. A well-considered and reliable technology but, as opposed to solar
daylighting approach in buildings will not only panel installations, is only presently used for large,
reduce the incidence of glare and discomfort but also centralised sources of power for utilities. In terms
reduce the need for electric lighting if it is part of an of cost competitiveness, it cannot yet match the low
integrated daylight strategy with lighting controls production cost of fossil-fuel power plants. However,
and external shading devices. as solar energy technology improves, CSP plants will
become more economically advantageous.
2.2.2 Solar energy
Onsite renewable energy is gaining popularity 2.2.3 Mosques
worldwide. However, there are difficulties associated Mosques are places of great importance and
with implementing it in developing countries function. They constitute the heart of any Islamic
because the technology is not sufficiently advanced community, where people perform their daily and
for it to be more cost effective than conventional weekly prayers. They are an important sector of
energy sources, making it difficult to convince buildings in the Muslim world.
private underwriters to make the initial capital
investment. The atmospheric conditions in arid In hot climate zones, mosques need to be air
areas are quite different from other regions: the air conditioned: worshippers need to feel comfortable
is generally much dustier. This means that many of and relaxed in order to attain a feeling of tranquillity
the lessons learnt from, and technologies fine-tuned and peace. A design temperature of 24 °C is suggested
for operation in Europe, are not wholly transferable. for prayer areas, but other rooms within the mosque,
at the discretion of the designer, may justify a slightly
At present, solar hot water systems are the most lower design temperature.
efficient means of using the power of the sun—most
buildings have a consistent need for hot water and Mosques are characterised by their intermittent
incorporating a solar water system will significantly operating schedule, determined by prayer time,
reduce electricity usage. which varies continuously according to the local
solar time. Therefore, analysis based on a specific
Maintenance is a major consideration when time is not possible. Occupancy is usually five
contemplating solar energy. The places with the times intermittently throughout the day all year
highest concentration of sunlight (the most ideal round, each averaging a fraction of an hour to an
locations for solar panels) are desert regions, but hour. Exceptions to this are weekly Friday prayers,
these are very dusty and sand needs to be removed when worshippers tend to stay longer, and Taraweeh
from the panels frequently to prevent a decrease prayers during the nights of the holy month of
in efficiency. Self-cleaning systems are available, Ramadan. The occupancy rate in prayer rooms
should be determined at 0.75 m2/person. Maximum accommodation for workers of contracting and
worshipper numbers should be used in the air construction companies. The design lifetime for
conditioning design calculations. these temporary buildings is usually only 10 years.
If the accommodation is for a different application,
Infiltration is difficult to measure due to the requiring a more permanent camp, this figure rises
frequency of doors opening during prayer time, but to 60 years.
as long as there has been careful treatment of cracks
and leaks around windows and doors, a minimum Local regulations generally exist that dictate the
rate should suffice for design purposes. provision for such housing, but standards vary
from country to country, some stipulating as little
The orientation of a mosque is determined by the
as 3 m2/person minimum requirement. For design
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
internal garbage chute system, the garbage is fed into temperature is raised. The amount the chilled water
a removable ‘bulk-bin’ located in the garbage room. temperature can be increased is limited only by the
need to satisfy the cooling load.
In temperate climates the control of offensive odours
can be dealt with by either natural ventilation Cooling systems in hot climates very often work all
through the chute or by installing a foul air exhaust year, but infrequently at peak capacity; variable flow
fan at the top of the chute, above roof level. Air systems (Figure 27) should therefore be favoured
make-up would be through louvres in the garbage because they supply only the required cooling
room door. However, in hot climates this method capacity to each load, promoting the efficient use
alone is insufficient. of refrigeration plant. Conversely, constant flow
systems (Figure 28) when operating at part load
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Odour-causing bacteria from rotting food grow conditions generate a low T, effectively robbing
inside the garbage. As they accumulate, they become the chiller of its useful capacity, consuming a higher
putrid and hot weather intensifies the decomposition energy rate per kW of cooling. Constant primary
process. Not only does this create offensive odours, with variable secondary systems (Figure 29) are
but at higher temperatures this material also finds a compromise. These are more energy efficient
it easier to transfer to a gaseous state or break than constant flow systems, but only because of
down into small enough particles to be carried by the electrical power saving brought about by the
air movement and higher energy warm air. These secondary variable speed pumps.
particles are held in the air and can be inhaled.
Consequently, in climatic zones where the outside 2.2.7 Plant and equipment selection
ambient frequently exceeds 21 °C, garbage storage The air conditioning load is estimated to provide
areas could become a health hazard. In arid regions, the basis for selecting the cooling equipment. The
enclosed garbage rooms should be mechanically equipment selection, however, must be based on
cooled to at least 20 °C. design working conditions, which, particularly for
outdoor units, can be extreme in arid regions.
2.2.6 Chilled water temperatures
The flow temperature of chilled water is a function Most European selection data is based on Eurovent
of the system design; serious consideration should criteria. Eurovent certification confirms the
be given to determining the right condition for use performance ratings of air conditioning and
in any particular arid environment, bearing in mind refrigeration products according to European
that chillers are only able to control the temperature standards. For manufacturers, the Eurovent
at which chilled water is sent out, while the cooling certification programmes offer the ground for
load determines the temperature at which it is fair competition on equal terms and based on
returned and, ultimately, the T. comparable data. However, this does not necessarily
reflect actual design conditions, especially where
Typical ‘wet coil’ chilled water design flow and return these are outside the normally accepted parameters
temperatures in temperate climates are 7 °C and for relatively temperate climates.
12 °C respectively (standard Eurovent conditions),
Consequently, using tabulated data given in
but this should vary depending on the dew-point
manufacturers’ catalogues could result in
to be maintained. In high-humidity arid areas (e.g.
inappropriate plant and equipment selection. For
close to the coast), design temperatures of 6 °C flow
example, Eurovent standard rating conditions are:
and 12 °C return might be more appropriate, to
increase latent dropout. t fan coil units: entering air 27 °C db, 19 °C wb,
entering water temperature 7 °C with a 5 °C
Design water temperatures as low as 5 °C flow and
temperature rise
11 °C return may be encountered (or even lower
for district cooling primary water), but keeping the t air/water liquid chilling packages: evaporator
chilled water temperature as high as practicable 12 °C on, 7 °C off, condenser temperature 35 °C
provides major energy savings: approximately t air-cooled rooftops: indoor air 27 °C db, 19 °C wb,
4% of energy input per °C that the chilled water outdoor air 35 °C wb, 24 °C db.
2-port
control
valve
Return
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Cooling
load
Chiller Chiller Chiller Low
velocity
header
3-port
control
valve
Return
Constant speed
primary pump
Cooling
load
Chiller Chiller Chiller Low
velocity
header
2-port
control
valve
Return
Pressure differential
Constant speed sensor
primary pump
Capacity ratings based on these criteria are unlikely at an appropriate stage in the design process.
to meet the needs of the project.
Locally sourced plant and equipment sometimes
Most established cooling equipment manufacturers have their tabulated performance data based on
provide tables that give correction factors to adjust regional conditions. For example, capacity ratings
the catalogues’ tabulated data in line with differing for outdoor machines may be based on an external
design values. Nevertheless, these factors should ambient of 46 °C, being more appropriate for some
only be used for initial equipment selection. arid areas. They may also offer outputs based on
Computer-generated actual capacities should be 60 Hz electrical supply, which is the norm for
requested from the manufacturer, supplier or agent some countries. In locations where district cooling
systems are common, capacity ratings for cooling Infiltration also varies with the difference between
water temperatures of, say, 5.5 °C entering and indoor and outdoor temperatures, and hence air
14.5 °C leaving may be contained in the equipment densities, which create a vertical pressure gradient
provider’s standard brochure. known as ‘stack effect’. This stack pressure
(or chimney effect) is caused by the different
Most equipment ratings are based on sea-level atmospheric pressures at the top and bottom of
altitude. However, for any specific place an increase the building as a result of differing temperatures
in altitude is accompanied by a drop in both pressure creating a disparity in the weight of the indoor and
and temperature, and a fall in barometric pressure has outdoor air columns. In cold climates, this causes
a principal influence on psychrometric properties, air infiltration at the bottom of the building and
exfiltration at the top. However, for air conditioned
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
For the altitude of any particular place, reference Clearly, air infiltration from stack effect is greatly
should always be made to local meteorological influenced by the height of the building and the
data. Or where this is unavailable, CIBSE Guide presence of open stairways and vertical transport.
A (CIBSE, 2006), or its accompanying CD-ROM, (The door infiltration rate in low buildings would
should be consulted (these tabulate the elevation of be relatively unaffected by reverse stack effect.)
particular locations throughout the world).
Air infiltration through external door openings
?"! !
!
is an important factor when the doors are used
frequently. Commercial buildings, for example,
Air infiltration is the unintentional leakage of air are likely to have a high door-opening frequency,
through a building due to imperfections in its fabric. either at certain times of the day or, in some cases,
The forces that drive natural infiltration are wind throughout the hours of occupation. Air takes the
and temperature, but these forces create different path of least resistance, which means a considerable
rates of infiltration in a hot climate compared with area for infiltration (or exfiltration in the right
a temperate one. circumstances) with a traditional swinging door.
One measure that can be employed to decrease this
Wind forces outdoor air through gaps and openings infiltration, and hence reduce the building energy
on the windward side of a building where the usage, is to use revolving doors.
surface pressure is high and out through apertures
on the leeward side where the surface pressure is Internally cooled air is denser than the warm outside
low. Consequently, in hot, still air, found in most ambient air, resulting in a pressure differential that
arid countries, infiltration will be less than in a moves conditioned air through open doors and
more temperate climate. To address this deviation, cracks in seals. Revolving doors stop conditioned
the empirical air infiltration allowances shown in air from moving freely: they are never truly ‘open’
CIBSE Guide B (CIBSE, 2005b) Table 1.5, should, because seals remain in contact with the walls of the
given a good standard of envelope construction, be door at all times; the only air that is displaced is in
modified downwards for arid climatic conditions. the chamber of the person going through the door.
– +
Infiltration below Exfiltration below
the neutral plane the neutral plane
associated energy savings, and heat gain. It should g-value can have very different light transmissions.
not be assumed that reducing envelope heat loads
takes priority. Depending on the building, the glass If daylight is a consideration in a building, the energy
and the climate, turning off lights can save more savings available from that need to be balanced
energy than reducing heat gains through windows. against energy savings from using darker glass.
The designer should calculate window size to achieve
the optimum balance between daylight and thermal The climate also has an impact on glass selection, as
performance in terms of total energy consumption. maintaining lux levels within the above thresholds is
a function of diffuse illumination. If too much light
2.3.1.4 Window shading is allowed in, glare can result. In hazy conditions,
Shading reduces glare and, in the case of externally this can occur even on the shaded side of a building.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
mounted systems, reduces heat gain. Locations with clearer skies can get away with
clearer glass, with glare from direct sun controlled
In terms of glare, shading needs to keep the sun out
by shading.
of people’s eyes and off their computer screens. This
is generally best achieved with operable shading
The suggest maximum visual light transmission
devices, which can either be external or internal.
(VLT) values are as follows, although simulation
While external devices also block solar gain, they
should be carried out based on local conditions to
can get expensive, depending on the complexity
make the best decision:
and wind loads they need to withstand. Motorised
devices in sandy climates are also problematic due
t low diffuse light levels (e.g. clear sky): 80% VLT
to high maintenance requirements.
t high diffuse light (e.g. hazy sky, reflective open
Several internal shading options exist that are
ground): 50% VLT.
the same regardless of climate, so they are not
covered here. 2.3.1.6 Roof lights
In terms of reducing solar gain, external shading is Roof lights are very effective at bringing light
best, although its effectiveness is reduced in hazy deep into buildings, but in arid climates, which
environments due to the high proportion of diffuse are typically hot and sunny, their heat gains tend
solar radiation. Shading also reduces the amount of to outweigh the benefits because their thermal
sky that can be seen from the window, so daylight performance is generally not as good as windows,
penetration is also reduced. Again, energy savings and solar radiation is higher due to the angle of
from using daylight need to be balanced against the sun. It may also be the case that the building
solar gains. The cost of installing external shading operators will leave the lights on anyway, thus
also needs careful consideration. making the roof lights obsolete. Therefore, they are
Finally, it should not be forgotten that building in not recommended.
low latitudes, such as those in or near the tropics, get
sun on all sides, so a northern hemisphere building Roof lights are also not recommended for providing
may need shading on the north. Summer midday connectivity to outside in hot and sunny climates as
sun is less of a concern in terms of solar gain, as the there is rarely anything to see other than clear blue
high sun angles mean that most radiation will be (or hazy white) sky.
reflected by the glass due to Fresnel’s equations of
reflection. @! &X
&
The visual light transmission of glass has an inverse If the interior environment is being designed to
relationship to its thermal performance, so the ambient temperatures, similar to those in temperate
higher the thermal performance, the lower the climates, there are no specific design issues to
light transmission. This is not a linear relationship, consider and the general recommendations of the
however, and glasses with the same U-value and SLL Code for Lighting (SLL, 2012) will apply.
t impact of higher humidity levels 2.4.2 Building services noise to external areas
It is important to consider noise emissions from
t impact of air-borne dust and sand. external plant that could break back into the building
or affect occupants of neighbouring buildings.
2.3.3 Emergency lighting
Guidance should be sought from the relevant local
If the interior environment is being designed authority or municipality on their specific noise
to ambient temperatures, similar to those in emission requirements. These requirements will
temperate climates, there are no specific design relate to all noise-generating items of plant such as
issues to consider. heat rejection equipment, air handling units and
ventilation intakes/discharges.
2.3.4 Lighting controls
The location of plant relative to noise-sensitive
There are no special requirements for lighting receptors (e.g. windows) should be considered,
controls in arid environments. Standard control as should the potential for intervening acoustic
strategies, such as daylight sensing, presence and screening. Designers should be aware that screens
movement sensing and clearly labelled manual close to plant may need to incorporate openings or
control, all work as well in arid climates as elsewhere. louvres to allow air movement around the equipment,
so should assess the effects of these apertures on the
2.4 Noise and vibration acoustic attenuation effect of the screening. Chiller
Building services plant, whether located inside or compounds will need to be kept well away from
outside the building, generates noise and vibration noise-sensitive openable windows
that generally needs controlling to prevent
For residential receptors, building services noise
disturbance to the building occupants or those of
should be at least 5 dB lower (10 dB if tonal) than
adjacent buildings. This is particularly the case
the otherwise prevailing background noise LA90
in hot climates with the prolific use of air-cooled
levels, when measured at a distance of 1 m outside
chillers, air handling units, fan coil units (FCUs)
the nearest noise-sensitive openable window. For
and other types of mechanical cooling/ventilation
non-residential receptors 10 dB below the normal
systems.
internal criteria for building services noise is
Local regulations and standards should be generally acceptable internally. For external amenity
established and assessed. In some less developed areas, building services noise should not exceed
areas the standards may not be strict, or indeed 50–55 dBLAeq,T.
suitable, so the designer must consider this. Planning conditions, building control requirements
and statutory legislation may be more onerous and
Noise control measures could be as simple as making should be complied with in addition to the above.
careful selections of type and model of plant to
enable noise emission requirements to be achieved. Atmospheric noise emissions from the building
For example, low noise fan and chiller selection can services plant should be measured by the acoustic
negate unnecessary attenuation, whilst FCUs should consultant to demonstrate compliance with the
be sized to operate at suitably low fan speeds. daytime and night-time acoustic criteria.
Table 12: Criteria for mechanical and electrical (M&E) plant noise transfer to rooms for residential purposes
Note: Velocities in ductwork prior to grilles/diffusers/louvres must be reduced gradually down to the values shown. Where
main branches are located close to terminal, the velocities in these branches may need to be reduced to a value closer to
the guidelines for ductwork to grilles/diffusers.
as adequate vibration isolation. It is therefore t Bends and bifurcations – 90° bends should
recommended that all active pipework should be either be radiused type, or be fitted with equally
isolated on resilient mountings/hangers up to the short-cord turning vanes.
structural penetration adjacent to the service shaft, t All branches should be fitted with boots or
the first 100 pipe diameters or the first 10 m of pipe coned as a standard practice.
run, whichever is the greatest. Thereafter, oversized
t Transitions should be as gradual as possible
brackets with neoprene inserts would be advisable.
within the physical limitations, preferably with
2.4.7 Lift installations one pair of sides remaining parallel.
Lift ride quality and performance characteristics t The aspect ratio in all main and branch duct
should be set and measured in accordance with BS runs for rectangular and flat oval ductwork
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
ISO 18738: 2003 Lifts (elevators): Measurement of lift should ideally not exceed 3:1.
ride quality (BSI, 2003). t Volume control devices near duct terminations
should only be used to provide fine trimming
2.4.8 Ductwork
of the airflow. If dampers are likely to be used
The general parameters for ductwork or pipework beyond fine trimming purposes, ‘damper
design, fabrication and installation are laid down in silencers’ may be required.
the relevant codes of practice (HVCA and CIBSE).
t Duct velocities should be limited to those
The following good acoustic practices should
stated in Tables 15 and 16.
alleviate the most commonly occurring problems
with duct services.
to site that will, once in situ, perform as required and 3.2.1 Location of capital plant
can be managed and maintained. They should also
Because most buildings in arid climates are air
be durable and not require frequent replacement:
conditioned, at an early stage the designer must
they should be able to withstand the forces of
inform the architect and structural engineer of any
nature. Even if the final location of the equipment
specific requirements in relation to major plant
is in a controlled internal environment, it should
items and their particular needs (refrigeration
be recognised that the installation may take place
and heat rejection, for example). This will include
in uncontrolled conditions; also, the journey to the
spatial needs and sufficiency of structural integrity
final location could have been arduous.
to support heavy machines such as chillers and large
The architectural form of a building can itself pre- mass flow air handling units. For example, floor
eliminate some of the local climatic challenges. slabs, other than the ground floor, are not generally
For example, if well designed, courtyards can give designed to support weights imposed by such plant.
a degree of protection from sand and wind-borne
dust. Fully exposed spaces, however, require barriers Building layout constraints may impose restrictions
to provide protection from overhead dust and side- on where apparatus can be sited. Sizeable cooling
swirls. In this instance, protection is a function of plant can, however, be situated in a number of
length and height of the barrier and distance from different locations: they can go on, in or remote
face of building (generally determined from local from the building to which they serve. A convenient
empirical data). place to put chillers and large primary air plant
is on the roof of the building, keeping it out of
Orientating the building towards the prevailing site but readily accommodating its air input and
wind, using wind catchers and appropriately heat rejection needs. If this is to be the case, the
designed openings, shade and shadow, fountain and architect/structural engineer will need to confirm
water surfaces, cross-ventilation, heat-resistant and the roof is capable of bearing the dynamic loads
thick walls and other passive and natural techniques imposed during operation. Fortuitously, in hot
are all free and accessible. climates roofs are generally constructed of high
thermal mass dense material, in order to increase
Social and environmental issues, in addition to the unsteady-state heat gain response factors (time
materials, manufacturing and transportation lag and decrement), giving them good load-bearing
costs, need to be considered. The logistics of characteristics. Of course, open roof space shown
importing equipment into a country also requires on architectural concept plans is not necessarily
consideration of non-technical factors such as all available to the building services engineers—
shipping regulations, transportation concerns, the there may be competing space requirements from
role of governments and intermediaries and the other equipment such as satellite dishes, building
application of local trade laws. These factors are maintenance tracks and jibs.
subject to risks such as programming issues and
opportunities for fraud. Consequently, the designer If it is unfeasible to place the chilling machines on
should consider using locally sourced materials that or in the building, standard practice is to create a
may, on balance, be a preferable option. chiller compound, which generally incorporates the
pump house within its boundary. This method, of network. Chassis fan coil units, for example,
course, suffers from the inherent disadvantage of mounted in the false ceiling void are particularly
having to pipe the chilled water to the building(s), popular because of the relatively small amount of
and in hot climates there could, depending upon time required for design, their availability, low
the distance involved, be a considerable heat gain capital cost and comparative ease of installation and
to the chilled water system, which would need maintenance. Coordination with other engineering
to be considered when sizing the main plant and services to be accommodated in the ceiling void
pipework. Subterranean pipework has the benefit is, of course, paramount (there may be several
of not suffering solar gains, but in an arid climate distribution systems vying for the same restricted
the earth temperature will be relatively high, so the space).
problem is not totally negated by this method of
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Figure 31: Basic energy breakdown for a nominal building Figure 32: Basic energy breakdown for a nominal building
with poor U-values with good U-values
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
U-value (walls and roof) = 1·0 W/m2·K U-value (walls and roof) = 0·5 W/m2·K
U-value (windows) = 5·9 W/m2·K U-value (windows) = 1·9 W/m2·K
U-value (walls and roof) = 1.0 W/m²K U-value (walls and roof) = 0.50 W/m²K
U-value (windows) = 5.9 W/m²K U-value (windows) = 1.9 W/m²K
]! X &
%
^]|[_ } ]! X &
%
^]|[_ }
Glazing ratio = 50% Glazing ratio = 50%
Internal gains = 10 W/m² Internal gains = 10 W/m²
Lighting gains = 10 W/m² Lighting gains = 10 W/m²
Occupancy density = 15 m² per person Occupancy density = 15 m² per person
Outside air (OA) = 8.5 litres per person Outside air (OA) = 8.5 litres per person
{
%
% !%!
^[\~_
"#
& %
# "
{
%
% !%!
^COP), including fans and pumps
Figure 33: Breakdown of cooling loads by source Figure 34: Breakdown of cooling loads by source
for a nominal building with poor U-values for a nominal building with good U-values
and ‘poor’ U-values in a hot climate. terms of solar gain (see Figures 33 and 34), designers
may find a client’s money is best spent somewhere
HVAC energy is clearly the most significant in this
other than solar shading. Nonetheless, Table 17
simple example, but looking at the breakdown of
summarises some key shading options.
this energy in Figures 33 and 34 shows that facade
gains (conduction and solar) are not necessarily the
!
# !
most important.
The movement of air in and out of a building through
3.3.2 Form and orientation gaps in the building envelope is called infiltration
and exfiltration, respectively. In arid climates, this
In smaller buildings especially, and in countries increases the sensible cooling load in a building,
without effective minimum standards for insulation and the latent load is also increased where humidity
of buildings, building form and orientation is is high.
important in optimising heat gains and thus energy
consumption. As a rule of thumb, windows should There are three main causes of infiltration in hot
be concentrated on the north and south (with climates: wind loads, reverse stack effect and poorly
appropriate shading, see Table 17) to avoid high- balanced extraction systems.
intensity, low-angle sun.
When there are gaps in the building envelope,
Where natural ventilation is possible, care should such as around and through windows and doors or
be taken to allow building form to promote effective between cladding panels, the wind simply pushes
ventilation, with room depth-to-ceiling height outside air into the windward side of a building
ratios as below proving effective: and sucks it out of the leeward side. To counter this,
minimum leakage criteria are recommended, for
t single sided ventilation: 2.5 example: 5–10 m3·h–1/m2 at 50 Pa.
t cross ventilation: 5.
Infiltration also occurs due to the reverse stack
effect in tall buildings. Here, the building can
Refer to AM10: Natural ventilation in non-domestic
be considered as a tall column of cool, dense air
buildings (CIBSE, 2005a).
surrounded by hot outside air. Being denser, the
It is noted that where insulation levels are high, cool air drops and leaks out of a building from the
including the glass, and where internal loads are below the neutral pressure plane (around two thirds
also high, orientation actually makes very little of the way up the building). Hot air is then sucked
difference to overall energy consumption. in from outside to replace it.
3.3.3 Building fabric Finally, if air extraction systems are not properly
balanced during commissioning, infiltration can be
Buildings should be well insulated in hot and forced on a building.
dry arid climates. Where there is a good diurnal
range, the use of thermal mass is recommended; To counter the effects of infiltration, architectural
this can reduce both peak energy loads and annual designers (and particularly building contractors)
energy consumption. should provide good sealing throughout the
building envelope. For tall buildings, breaking Table 18: Factors affecting thermal performance
the vertical path of air within the building, with
stairwells and elevator shafts, for example, should Characteristics Low-rise Medium/
be considered; this will reduce the size and weight high-rise
of the column of cool air trying to get out. Doors at Orientation North/south Less important
the top of tall buildings, such as at roof level, deserve Site layout Close together to Views dominate
shade neighbours
special attention because they can be one of the main
Internal plan Courtyard Wet services near
sources of infiltration. Revolving doors and airlocks
core
should be considered. Where possible, air leakage
External spaces Courtyard Balconies and
tests of buildings are recommended. podiums
External walls Heavyweight Insulated panels
3.3.6 Plant location and shading
Roof Heavyweight
HVAC plant works more efficiently if located in a External openings/ Small, near ceiling 30% glazing ratio,
relatively cool environment. Plant rooms should windows VLT <50%
therefore be shaded as a minimum, if not conditioned. Shading Comfort and Comfort
Landscaping around outdoor air intakes can also be energy
used to slightly cool the air prior to entering the
!
Prevent at high
main cooling apparatus. level
Internal walls Heavyweight
3.3.7 Factors affecting thermal performance External circulation Shaded Shaded
Table 18 summarises some key issues to consider. Special precautions Dust, insects Dust, insects
this mass means that heat loads can be absorbed t roofs (non-metallic): 0.042 m2·K/W
through radiation, providing a good deal of comfort. t roofs (aluminium): 0.051 m2·K/W.
It is important, however, not to saturate the thermal
mass with heat, or let it get hot from the outside, Values for inside surface resistance are the same as
because the radiative cooling effect is then lost (or those given in chapter 3 of Guide A (CIBSE, 2006).
worse, replaced with radiative heating).
In practice, this change in the value of the outside
Thus the second mechanism of thermal mass is time surface resistance may be neglected and the U-values
lag, or how long it takes heat to travel from outside given in chapter 3 of Guide A (CIBSE, 2006) can be
to inside through the mass. If this is long enough used without modification.
(say eight hours or more), then heat from outside
3.5 Thermal properties of building
will not have time to penetrate into the building
structures
before night comes and cools it again. Exposed mass
on the inside then provides radiative cooling to In the selection of materials for buildings in hot,
the occupants. This can be experienced with stone dry climatic regions, the overriding engineering
buildings in hot climates that are cool inside, even principle is to reduce heat transmission from outside
in the height of summer. into the building.
may be extremely hot but the nights are significantly Hot, arid areas therefore have the potential for high
cooler, which prevents excessive build-up of heat. air moisture content, creating the known hot and
This storage and release ability of high thermal mass humid climate patterns typically found near the
structures does not happen, however, in locations coast and major bodies of water. With imperfect
where the night-time temperature varies little from building construction found in many of these
the day, as is typical in more humid climates. regions, buildings are more prone to uncontrolled
moisture issues through high rates of air infiltration
Whereas in England and Wales, for example, the and liquid water leakage.
maximum permitted limits for thermal properties of
building structures are regulated and contained in 3.7.2 Potential moisture-related problems
Approved Document L of the Building Regulations If uncontrolled, moisture in the air can generate
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
(2010), many developing countries have no such problems within the built environment. One of
code. Of those that do, the thermal transmittance the main components of people’s thermal comfort
requirement of the building envelope is unlikely to is the relative humidity of air i.e. moisture content,
be as stringent as those set out in Part L. For example, because it relates to the ability to perspire; hence,
the maximum permitted value of heat transmission unrestrained moisture can create discomfort.
coefficients in some Gulf countries are only: roof, However, it can also affect indoor air quality and
0.44 W/m2·K; wall, 0.57 W/m2·K. cause structural damage to buildings.
The designer should contact the local regulatory 3.7.3 Indoor air quality
body to gain first-hand knowledge of their current
Sustained high humidity levels create an optimum
statutory requirements.
environment for microbial growth. Bacteria and
3.6 Dynamic thermal performance of fungi find ideal fields for growth in building
a structure components, creating poor indoor air quality (and
One of the simplest methods of assessing the also deterioration of the building fabric). Bacteria,
dynamic, or non-steady-state, performance of a fungi and dust mites are responsible for odours,
structure is the admittance procedure. In addition allergens and even toxins. Exposure to allergens and
to the thermal transmittance coefficient (U-value), toxins can cause health problems such as asthma
this takes into account the ability of walls and roofs and lung diseases.
to reflect solar radiation and the delay of heat flow Certain conditions sustained over time are needed
through the structure. for mould, fungi and bacteria to grow and flourish.
The performance parameters are: t A source of food (majority of construction
1. thermal transmittance (U-value) materials).
2. solar heat factor (the proportion of incident t Temperatures between 5 ºC and 40 ºC.
solar radiation transmitted through the t A sustained high moisture content (70%
structure) relative humidity (RH) or higher).
3. time lag (response of the structure to t Mould and mildew spores.
temperature change)
These conditions are readily found in buildings,
4. thermal admittance (rate of heat flow between
and there are few opportunities to design them out:
the structures internal surface and space
construction materials, an acceptable temperature
temperature).
range and spores are intrinsic in the built environment.
3.7 Moisture control and Building services designers can, however, influence
condensation problems the internal relative humidity and thus diminish the
possibility of microbial growth.
3.7.1 Forms of moisture
Water vapour is a natural component of air, even in Fortuitously, a well-designed environment for
arid climates—air’s capacity to carry water increases human comfort is too dry for mould and fungi to
in straight relation to its dry-bulb temperature. propagate. Therefore, by maintaining internal
spaces below 65% RH, uncontrolled moisture issues proportionally to the different vapour pressure on
are reduced along with the potential for discomfort each side of the material and the resistance of that
through poor indoor air quality (and the risk of material (or composite of materials) to water vapour
structural corrosion). flow (permeance). To minimise this moisture transfer
by vapour pressure diffusion, vapour barriers are
3.7.4 Sources of moisture recommended for walls, roofs and floor assemblies.
Ingress of moisture into buildings takes the The most effective location for a vapour barrier is
form of water vapour or liquid water. Both these at the warm side of the structure. To help keep the
states can transform—vapour to liquid through external high water-vapour content air from the
condensation on cold surfaces; liquid to vapour cooler interior surfaces, low permeance materials
through evaporation—allowing the moisture to should be used for the building’s outer skin.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
The general design philosophy for building to rise to over 50 °C dry-bulb during the day,
services installation in an arid environment can be with surface temperatures rising to 60–70 °C
summarised as follows. through solar radiation, but can fall to −10 °C
dry-bulb during the night.
1. Establish a sound basis of design, taking t Coastal areas and offshore islands, have a highly
full and proper account of geographical, saline atmosphere often accompanied by high
local climatic, commercial, legal and social salt content in the ground. Often the ground
conditions and requirements. water level is only just below the surface and
varies with the tide, although the coast may be
2. Take care, both in system design and
several kilometres away. The high humidity,
equipment/material selection, to anticipate
saline atmosphere and effects of sandstorms
problems that may arise because of high
and fine dust will attack exposed surfaces and
temperature and humidity, exposure to
damage the internal parts of motors, fans and,
dust, sand and intense solar radiation, salty
in particular, control equipment if it is not
atmosphere, brackish water supplies and
suitably protected.
irregularity of supplies.
t Buried tanks or pipelines should be suitably
3. Avoid unnecessary or unwanted design protected against the corrosive effects of the
complications or sophistications. Also avoid ground, which may contain high levels of
over-design (unjustifiable safety margins, suspended solids and chloride as heavy metals
over-engineering through specifications and and faecal matter.
detailing). Keep it simple. Do not experiment
t In certain areas, sandstorms can occur at
or use unproven techniques without
frequent intervals. In these and other areas
undertaking a proper due diligence.
sudden storms can cause flash flooding. Tall
4. Take full advantage of local experience, structures, such as chimneys, should be
expertise and resources including local fully designed for the wind loadings likely to be
trained engineers and technicians capable encountered in practice and consideration
of applying Western technology in building given to providing lightning protection.
services. t If the areas also coincide with earthquake
zones, and ground tremors of magnitudes up
5. If the design includes specialist plant, such
to very severe are relatively commonplace,
as chillers, sewage treatment plant and
the overall resilience necessary for the system
incinerators, allow for the manufacturer,
should be confirmed during the design phase.
specialist engineer or representative to
Essential services equipment should comply
supervise, set to work and commission as
with structural requirements, which may
necessary.
necessitate earthquake provision. This means
6. The use of packaged equipment that involves they may require allowance for excessive
a minimum amount of specialised site movements (e.g. by means of articulated
installation work should be encouraged. bellows and joints).
The construction techniques for buildings are quite the ability of local maintenance staff using readily
well understood and usually fall into one of two replaceable spare parts carried by the building
main types. owner, local stockists or replacements from overseas.
An effective system of maintenance procedures
1. Lightweight structure for minimum must be established. Comprehensive maintenance
collapse damage with easy clearance of site manuals must be left with responsible personnel
and re-erection. and be written in the language used locally as well
2. Massive structure to withstand any reasonable as in English. Effective testing procedures must be
or foreseeable shock levels. established, involving regular test running of plant
Although many of the problems outlined above and equipment. The results of these tests must be
can be overcome by taking precautions on site, this properly recorded.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Enclosures should protect the equipment and the will constitute an electrolyte. If the arid region is
material will determine the quality and durability coastal, the atmosphere will be saline saturated,
of the installation. UV radiation is a great concern in which will lead to oxidation and hence corrosion.
arid regions and the equipment degradation may vary In some cases, cathodic protection can be applied,
on the basis of temperature, exposure and prevailing however any metallic equipment exposed should be
humidity. As thermoplastics and thermosetting properly treated to withstand the corrosive nature
chemical compounds are more susceptible to UV of the atmosphere. Suitable space heating should
degradation, it is advisable to offer composite be provided to prevent any excessive condensation
material or suitably treated metallic solutions for in electrical switchgear and equipment to prevent
high exposure applications. Sun screens are also flash-over threats.
advisable for equipment that will be exposed for a
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
developing areas, the conditions of utility services thickness of the sand layers in the arid areas inhibits
are also changing rapidly; early engagement is groundwater recharge and can decrease underground
recommended. Conditions that apply at the start of water levels to a point that they are only accessible
a design process can alter dramatically during the through boreholes or hand-dug wells. These can be
design and construction of a project. The designer at large depths (100 m is not unusual). The water
must, therefore, frequently check and re-check is sometimes saline due to lack of recharge from
information that has been provided during the rainfall. Water is found nearer the surface in areas of
whole design and construction period. It is advisable calcrete, silcrete and ferricrete formations. Drilling
to ensure that the information on which the design boreholes involves endless problems of striking
is based is unambiguously recorded and agreed by blanks or saline sources.
all parties concerned Alternatively, desalination could be considered,
4.2.1 Public utility services which could enable the use of saline water resources.
Desalination is a water treatment process that
The design engineer should be cognisant of the
separates salts from saline water to produce potable
public utility services providers’ requirements
water. The desalination process uses large amounts
for the design and construction phase of projects.
of energy to produce pure water from a saltwater
Each utility provider has its own processes and
source. Saltwater is fed into the process, and the
procedures. Successful liaison with utility providers
result is an output stream of pure water and another
and authorities having jurisdiction (AHJ) is a
stream of water with high salt concentration.
key attribute for any project. In light of this, the
design engineer may consider employing a ‘local’ Desalination techniques are mainly classified into
consultant to assist in authority liaison. Particular two types.
issues to consider are:
1. Processes based on physical change in the state
t enforcing codes e.g. what codes, standards and
of the water.
specifications are used
2. Processes using a membrane that employ the
t procedures for applying for services including
concept of filtration.
meters and civil engineering works
t availability of services 4.2.3 District systems
t reliability of services A district cooling system distributes thermal energy
t supply parameters e.g. voltage and frequency from a central source to residential, commercial and/
for electricity, pressure and flow rate for water or industrial consumers for use in space cooling.
t tolerances of local supplies. The energy is distributed by chilled water lines.
Thus, energy comes from a distribution medium
4.2.2 Standalone systems rather than being generated on site at each facility.
In some areas, it may not be possible or prudent to District cooling systems are capitally expensive and
connect to public utility services, and standalone are therefore best used in arid climates where the
systems will be used. The main utility services are thermal load density is high and the annual load
now considered. factor is high.
District cooling systems consist of three primary 4.2.3.1 District cooling energy centre and reticulation
components. This section does not attempt to inform the designer
how to design and size district cooling plant as this
1. Main district cooling plant.
is normally undertaken by the specialist provider,
2. Distribution piping network (reticulation). but to provide an overview of how such plant may be
arranged, sized and integrated into a building where
3. Consumer system.
district cooling is the primary cooling source. The
District cooling is typically provided for large district cooling energy centre generally comprises
developments, particularly in the Middle East, the main water-cooled chillers and pump room at
North America and other arid climates as part of ground level and the tank rooms at either ground
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
the main infrastructure. District cooling enables level or below ground. The cooling towers are
cooling plant to be centralised in one or a number located directly above, open to atmosphere. The
of energy centres depending on the cooling capacity substation element is often provided as part of the
required. The advantage of using district cooling is energy centre building or it can be located adjacent.
primarily the efficient use of water-cooled chillers The design life for the plant and equipment should
with cooling towers in one location providing be a minimum of 25 years, which can be difficult to
economic and environmental benefits where the achieve in the more harsh arid climates.
plant is easily and readily maintained. In large mega
projects where a number of towers may be part District cooling chiller plant is usually of the water-
of the overall plan, finding space for the number cooled centrifugal type, located in series. Each
of air-cooled chillers required to overcome the chiller should be provided with a minimum of
cooling load is often difficult. Providing on-site, two compressors. For each chiller, there will be an
water-cooled chillers uses valuable floor space and associated cooling tower, condenser water pump and
maintenance of the associated cooling towers is not primary pump, piped in an arrangement to ensure the
always undertaken in accordance with industry best necessary level of resilience. The number of secondary
practice requirements. pumps should consider system resilience, turndown,
capacity and rating to optimise performance.
Locating central chillers in a district cooling energy
The use of constant flow systems should be limited
centre is therefore advantageous and offers added
to relatively small central chilled water plants.
benefits such as the ability to introduce energy storage
Variable speed pumping saves energy and should be
systems to improve the plant efficiency. They can
considered for distribution system pumping.
also take advantage of diversity between differently
performing buildings. Site-wide condensate In arid climates in particular, thermal storage should
recovery systems should also be considered, as be considered to reduce chiller requirements and
water for cooling tower make-up can be expensive lower operating costs. By moving part of the cooling
and scarce in the more extreme arid environments. load, chillers can be sized closer to the average
Greywater recovery may also be considered. load than the peak load. Both ice and chilled water
storage should be considered, although chilled water
The initial capital investment for a district cooling
storage requires four to six times the volume of ice
system is usually the major economic driving
storage for the same capacity.
force. District cooling is typically provided by the
district cooling provider, although some medium- A typical district cooling energy centre layout is
scale sites do utilise the district cooling concept by shown in Figures 35 and 36.
providing their own centralised plant to a number
of buildings. District cooling providers tend to be Sizing of the district cooling plant typically
independent private companies that build the plant involves calculating the cooling load for each plot
and infrastructure at their own cost and then recover on the development and then calculating the overall
this outlay by charging each plot on the development diversified load based on the development mix and
a chilled water connection charge, an annual capacity usage. A rule of thumb diversified cooling load is
charge and a monthly usage charge. typically 70% of the total cooling for each plot. The
Chiller
Chiller
Chiller
Chiller
Chiller
Tank
Mono rail
Water treatment
Chiller
Chiller
Chiller
Chiller
Workshop
Corridor
UPS Toilet
Tank
Electrical room Electrical room
Control room
Store
designer of the district cooling plant is responsible steps. First, optimise the design conditions while
for creating, updating and maintaining an up-to- taking into account the local design weather data
date load schedule similar to that presented for and project specific details. Second, optimise the
the areas to be served by this plant. A design load control logic to take full advantage of the capital
analysis should be provided at part load and full load equipment in the chiller plant. Changing from
conditions with detailed predicted monthly profiles. very basic to advanced controls can make a 5–8%
improvement in performance without changing the
How a district cooling system operates at design capital equipment.
conditions is not always a good indicator of its
overall annual performance, particularly in a From the district cooling energy centre, the
seasonal arid climate. Controls, logic and design reticulation network is typically distributed around
conditions can be used to optimise chiller, cooling- the development in a ring main arrangement with
tower and condenser-pump system performance sectional isolation valves to prevent downtime in
throughout the year. Optimising the chiller-tower the event of a mains failure. Sectional isolation
condenser-pump system can be managed in two valves are normally located between each plot. The
maximum water velocity in any part of the system the consumer’s secondary side of the system. It is
(including plant) should be precisely selected important that this hydraulic separation is provided
ensuring the best and the most efficient parameters. for distinct demarcation between primary and
The calculation is typically prepared based on 90% secondary and also to prevent leaks from individual
of the diversified peak cooling load at 3 m/s. All buildings impacting on the chilled water network
piping reticulation sizing should be undertaken for an entire development.
using a dynamic software for district distribution.
The maximum pressure loss in the system should be Typical ETS room requirements are as follows.
selected to suit the chilled water flow performance. t There should only be one ETS room per
All piping should also be stress analysed for the building and one chilled water connection
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
The building chilled water design, including cooling It is important, particularly for high-rise projects,
load calculations, should be submitted to the district to check the pressure rating of the entirety of the
cooling provider for review and authorisation. secondary side system, including heat exchangers.
Approval is typically required before the chilled
The chilled water connection charge and the
water works can be commenced on site. In the Middle
monthly charge for cooling are generally expensive
East, for example, a NOC (No Objection Certificate)
in arid climates. It is therefore important that the
is required before commencement of works.
designer accurately calculates the building cooling
4.2.3.4 Design considerations load and does not over-design the chilled water
District cooling is unlike standard air-cooled chilled system. Safety margins should be removed from the
water systems and there are certain differences that contracted cooling load otherwise the building owner
the designer must be aware of. The chilled will pay for it. District cooling providers must meet
water temperature differential for a conventional the contracted load. Safety margins can be added to
system ranges from 5 °C to 7 °C (6–7 °C flow, 12– air handling units (AHUs) etc for future degradation
13 °C return). Due to the cost of distribution system but should not be carried over the PHEXs.
piping, district cooling systems are usually operated Such careful and accurate design, using dynamic
at lower supply water temperatures to allow a larger thermal modelling for example, can provide the
temperature differential to be achieved. This reduces client with significant cost savings. Some district
the chilled water flow per kilowatt of delivered cooling providers also charge individual consumers
capacity. An economic evaluation of piping and if they repeatedly return low chilled water return
pumping costs versus chiller power requirements can temperatures back to the network.
establish the most suitable supply water temperature.
4.3 HVAC
Typical district cooling chilled water temperatures
are distinctly different to standard chilled water 4.3.1 General
systems and generally operate on a 9 °C temperature Designing HVAC systems in arid climates poses many
differential. Typical supply (flow) and return chilled challenges for the designer, particularly if there are large
water temperatures on the primary side are 4.5 °C differentials between summer and winter conditions.
In arid climates where high summertime dry- and wet- In arid climates with high summertime wet-bulb
bulb temperatures are prevalent, the challenges are conditions, and therefore a large portion of latent
further compounded, and the designer should consider: cooling, the treatment of fresh air at source is an
important design consideration. Fresh air, air
t treatment of fresh air at source with the use handling units (FA-AHUs) are recommended to
of fresh air, air handling plant. Terminal supply the outdoor air to the building cooling
units, such as fan coil units, may not be able systems. Cooling coils can be of the direct expansion
to cool the fresh air load independently if it (DX) refrigerant type or the chilled water type,
is not treated at source due to the high latent although they can have stages and need a reasonably
component constant airflow and may not be suitable for a
t pressurisation of buildings to offset infiltration demand control application. Control of the off-coil
t the use of energy recovery to minimise the condition should be considered, particularly with
amount of cooling required for the building the use of DX systems. The number of DX units
fresh air system (in certain arid climates, such and stages should therefore form part of the design
as the Middle East, the fresh air load can add an process discussions. A second cooling coil should
additional 50% to the building cooling load) be considered when coil sizes exceed 250 kW to
improve controllability.
t software to be used for cooling load calculations
t production of system psychrometrics to
The fresh air rate should be provided on an
establish system operation at each key
occupancy basis (litres per second per person) to
condition
meet local standards and requirements or to provide
t the use of reheat and/or humidification a minimum of one air change per hour, whichever is
after dehumidification to provide supply air the greater. In arid climates with high summertime
temperature control for certain applications dry- and wet-bulb conditions, it is recommended
t type of terminal cooling or building system to that buildings, wherever possible, be pressurised
be used to overcome the building cooling loads. to offset infiltration. Such a design approach
reduces the building cooling load in arid climates, requires close environmental tolerance such as data
particularly in large volume spaces. Consideration centres or museums. Depending on the regional
can then be given to discounting the infiltration infrastructure, utilities and availability of resources,
rate in the building coaling load calculations. the heating medium will invariably vary from all
Typically, the pressurisation system should provide electric, to liquefied petroleum gas (LPG) boiler
a minimum of 120% of the extract rate. plant to natural gas or diesel oil boiler plant. The
designer should research the region and select the
Where there is a large latent cooling component, most efficient and appropriate system.
the fresh air cooling load can be high. Recirculation
extract systems should therefore be considered For specific applications, the utilisation of reheat
where possible to reduce the system cooling load. should be considered at both, or either, the central
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Energy recovery techniques, such as thermal fresh air plant and the building cooling system. The
wheels, heat pipes or plate heat exchangers can then use of reheat is an important consideration after
be used and are recommended wherever possible. If dehumidification to ensure a controlled supply
cross contamination of air streams is not an issue, air condition and therefore room temperature
thermal wheels are particularly advantageous due to and humidity level. In some arid regions with low
their high efficiencies and are particularly popular wintertime conditions, reheat via the HVAC system
in arid regions such as the Middle East. Where may provide sufficient space heating and offset the
cross contamination might be an issue, a thermal requirement for a separate building heating system.
wheel with purge facility can be considered. In Reheat is not required for all applications as it is an
more critical applications, plate heat exchangers expensive and energy intensive means of providing
may be more appropriate. control and each region and building must be
individually assessed. Reheat may also be provided
The use of recognised and approved software in process or special applications, e.g. computer
differs from region to region. In some Middle rooms or operating theatres.
Eastern countries for example, dynamic thermal
modelling software may not be recognised by As with reheat, humidification should also be
the local authority with jurisdiction and more considered at the central fresh air plant. The use
steady-state type calculations must be utilised. of humidification is particularly important in
Notwithstanding, the designer should still consider arid climates where wintertime conditions are
the use of dynamic software for calculating the particularly dry. Humidification should also be
building cooling load and steady-state calculations considered in process or special applications, e.g.
for calculating individual room loads. This helps to computer rooms or operating theatres.
ensure the building central plant is not oversized
and the correct diversities are applied. The building cooling systems may vary from fan
coil units, to variable air volume (VAV) air handling
Production of system psychrometrics is an important plant to chilled beams or ceilings. DX cooling
part of the design process, particularly in arid systems are often used up to 100 kW cooling
climates where the external design conditions may capacity. Variable refrigerant flow (VRF) systems
differ substantially between summer and winter are becoming popular—they are more efficient
months. High external ambient conditions can also than air-cooled chillers and offer the advantage of
complicate the psychrometric process e.g. 50 °C dry- reverse cycle heating.
bulb, 50% RH, which is not identified on a standard
psychrometric chart. Not only will a psychrometric Air-cooled central chiller plant is recommended
analysis enable accurate sizing of the plant and up to loads of 2 MW and water-cooled considered
components, but it will also allow the correct unit thereafter. Although more efficient, water-cooled
selection and configuration to be identified. chillers can not be considered in some regions
due to problems with availability and suitability of
Heating in arid areas is generally confined to certain the water supply, unless it is for district systems.
geographical/climatic areas – often in mountainous Closed circuit radiator dry cooled water chillers are
regions. It may also be required where the project also available.
such as a canopy. This should allow a suitable to, say, 1.5 m/s would not decrease the louvre’s
combination of light, and reduction in solar gain efficiency to a level that would make it unviable;
and solar glare. (Care should be taken to allow however, due consideration of the increased
enough space for airflow, air intake and exhaust air pressure drop needs to be taken into account—
requirements.) at 1 m/s this will be in the order of 30 Pa, but at
1.5 m/s this figure doubles to 60 Pa and may create
Air filters are an essential component of every air
noise issues.
handling unit. Their primary function is to prevent
the clogging of heat exchangers and to minimise Intake louvres should be located sufficiently above
staining on walls and ceilings around supply the roof to minimise the pickup of roof dust and
grilles. Different types of filters have evolved, each should not be directed towards residential or other
to suit a particular application. These different quiet areas unless provision is made for baffling or
applications demand different levels of efficiency, attenuating unit-transmitted noise.
and Eurovent provides a filter grading plan (EU
rating) to help classify filters. Arid environments, To attain comfort conditions in arid areas that
however, present a unique challenge to the filtration are also humid, such as coastal areas, the primary
of contaminates. air unit must lower the humidity in addition to
air temperature. If the system fails to reduce the
Because arid countries suffer from high levels of humidity adequately, the air may be cool but will
contamination from wind-blown sand, traditional feel uncomfortably damp.
filters alone do not have sufficient dust-holding
capacity to be cost effective. Therefore a ‘roughing One technology that addresses this humidity
filter’ in the form of a sand-trap louvre should problem, and is ideally suited to hot, humid
be used as the first line of defence for all outdoor climatic conditions, is the dehumidifying heat pipe,
air inlets, to avoid excessive dust-loading of the a passive device that enables dehumidification and
conventional filters. still efficiently cools the air. Strictly speaking, the
heat pipe is an energy transfer device and alters the
Sand-trap louvres are used in desert-like conditions psychrometrics; it does not generate cooling. It is
because they are designed for the removal of sand good for raising the supply air temperature after
while allowing airflow into the building; they the cooling coil to avoid a saturated condition.
also perform the function of a traditional weather
louvre in preventing the ingress of rain. This type A heat pipe dehumidification system is a set of
of louvre has a high degree of separation of sand, two coils, one placed before the cooling coil (pre-
even at levels of high dust concentration. cooling) and the other after the cooling coil (reheat);
closed tubes filled with refrigerant connect the two.
This type of louvre consists of vertical channels The tubing is tilted so that the liquid refrigerant
with no straight path between them; sand is settles in the pre-cooling coil. As the outside air
captured from the air and either falls out of the passes through the heat pipe pre-cooling coil, it is
front of the louvre or is dispelled through the self- cooled by the liquid refrigerant. The air then passes
emptying sand drain holes at its base, making it through the cooling coil and is further cooled past
self-cleaning and maintenance free. The typical its dew-point, extracting the latent energy through
condensation. The air then passes through the heat 4.3.2.2 Ductwork
pipe reheat coil and is heated by the refrigerant to The designer sholud ensure the ductwork
a comfortable supply temperature (see Figure 38). manufacturing company selected has sufficient
expertise, organisational ability, drawing office
In the heat pipe, the cold refrigerant in the production capacity and site erection capability, as
pre-cooling coil is heated past its boiling point this is not always the case in certain arid regions.
by the outside air and therefore evaporates. The
refrigerant vapour rises up to the reheat coil. The In determining ductwork specifications, particularly
cold post-cooling coil air passes through the reheat the types of joints and seams to obtain air tightness,
coil, causing the refrigerant vapour to condense, consideration must be given to the experience
and the liquid refrigerant flows back to the pre- of the erection operatives. If ductwork has to be
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
cooling coil. Heat transfer occurs as a result of the manufactured abroad and shipped to site, it is
alternating evaporation and condensation of the desirable to minimise shipping costs, either by
refrigerant. having it designed and manufactured in the sizes
suitable for stacking one piece inside another, or by
Because the heat pipe provides initial air cooling, arranging for it to be shipped in a ‘knocked-down’
the cooling coil can drop the post-cooling coil form. Where the weight of sheet metal to be used
temperature lower than if the pre-cooling were for ductwork is around 40 tonnes or more, it may be
not present. This pre-cooling allows an increased economic to establish a site fabrication workshop.
amount of moisture to be removed by condensation Generally, the guidance in Table 20 applies to
because less sensible cooling is required to reach ductwork in arid regions.
the supply air dew-point, resulting in a lowering
of the supply air humidity level. During off-peak All fresh air and supply ductwork should be
conditions, the heat pipe pre-cooling coil decreases thermally insulated, as should return air systems.
the load on the cooling coil necessary to provide a Supply air grille and diffuser plenum boxes should
given level of dehumidification, thereby reducing also be thermally insulated to help minimise the
energy consumption. risk of condensation.
Self-emptying 42 °C db 36 °C db 12 °C db 18 °C db
sand drain hole 28 °C wb 27·1 °C wb 11·8 °C wb 14·1 °C wb
of the local water should be obtained and specialist 4.3.4 Practical tips
advice sought regarding choice of materials and 4.3.4.1 Ventilation air
methods of water treatment.
Table 11 provides recommendations on minimum
ventilation rates, both where the density of
Dezincification problems may be encountered in
occupation is known and for specific types of
some areas and copper fittings should be selected
building and applications.
accordingly. Flux for soldering and brazing fittings
should be carefully selected to eliminate the external The cooling load due to introduction of fresh air into
corrosion effects in areas with high humidity. the air conditioning system is very closely related to
the difference in wet-bulb temperature between the
Caution should be exercised in the use of plastic space and outdoor air. In arid environments where
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
materials. Proper thought must be given to the the outdoor summer wet-bulb temperature is high,
suitability of plastic pipe jointing solvents, and to careful selection of space internal design conditions,
other chemical adhesives or bonding materials, particularly wet-bulb temperature, and accurate
in high temperature and/or high moisture assessment of the minimum acceptable fresh air
content environments. quantity can significantly affect comfort, system
design and refrigerating capacity.
Insulating materials must be resistant to ambient
air at high temperatures and often at high moisture 4.3.4.2 Air conditioning load calculations
content. Where pipe or water equipment surfaces Design data for determining air conditioning
are below the dew-point temperature of the air, cooling loads and estimating plant capacity are
the use of an efficient vapour barrier is essential. given in CIBSE Guide B (2005b).
Valve bodies, control valve actuators, condensate
collection pans, coil return bends, pipe flanges and In arid locations, care must be taken to calculate
drain lines generally need to be insulated to avoid solar gains accurately and to assess system gains (i.e.
condensation problems. External insulation should heat from fans and pumps and gains to ductwork
be able to withstand prolonged periods of solar and piping systems).
radiation, and should be insect and vermin proof. 4.3.4.3 Solar radiation
The specification for insulation work should take
Determination of the air-conditioning cooling load
into account the operatives’ available to carry out
due to solar radiation is essential in arid locations,
the work.
particularly in desert or semi-desert (arid) areas
where the sky is clear and ground reflections may
The specification for pipeline components, such
be high.
as valves, strainers, piping brackets and expansion
bellows, should take into account atmospheric Since tropical architecture normally makes adequate
conditions that may lead to external corrosion and provision for external structural shading, the solar
operating problems. The recommendations above gain through glazing is often less, in total, than in
regarding water treatment also apply. many metropolitan UK applications. Although
glazing may be shaded from direct radiation, the
"!
@ ground reflected component can be very much
Equipment must be selected with due regard to higher than that found in temperate zones, while
the conditions under which it will be installed the direct solar intensity on a horizontal roof can be
and required to operate; these include the 20–25% higher in arid regions, or at altitude, than
effects of high temperatures and humidity, most standard tabulated values.
exposure to dust, sand and intense solar radiation. Solar gains may be significantly underestimated
Heat gain to piping systems located outside the unless an adequate assessment is made of the
building or in unconditioned spaces may be necessary corrections for sky clarity, ground
unusually high and these factors should be taken reflection or altitude of the building location.
into account and equipment ratings and duties
adjusted accordingly. The importance of determining proper values
to the system by fan and pump power, by gains to may be many degrees above the general ambient
distribution ductwork and piping located external dry-bulb temperature due to prolonged exposure
to the building or outside the conditioned space, to solar radiation. These hot surfaces may produce
and due to duct air leakage. In arid locations, the a significant increase in the air temperature at air
cumulative effect of these various system gains can intakes or air-cooled condensers. This must be
be a major item—sometimes as much as 15–20% taken into account in design calculations. HVAC
of the total load. Therefore, a reasonably accurate equipment ratings and duties should be adjusted
assessment of their value should be made. accordingly.
""% H
4.4 Refrigeration
Fans and pumps contribute to the heat loads in air
condition systems and have influence on the cooling 4.4.1 General
equipment dimensions. Various graphical methods The majority of refrigeration plants installed in the
of determining heat gains to air distribution ducts Middle East operate in a harsh environment where
are available. routine maintenance is frequently forgotten, and
4.3.4.6 Air duct leakage there are few skilled refrigeration engineers.
CO2 (R-744) is regarded as a ‘natural refrigerant’—it Consideration must be given to the effects of
is non-flammable and non-toxic. However, as CO2 continuous operation of electrical components at
refrigeration systems operate at high pressure, there high ambient temperatures e.g. motors, switchgear
are engineering challenges in both containment and contractors, relays, wiring, motor overload trips and
safety. Overall, CO2 refrigerant systems provide a fuses. Control panels should be located indoors in
comparable alternative when considering capital well-ventilated areas where possible (see section 4.7).
cost, environmental and safety related issues.
4.4.5 Water
4.4.3 Maximum working temperature
In certain areas, two qualities of water are available:
The maximum working pressure will depend on the
potable and ‘reclaimed’. Depending on the project
highest temperature expected to occur in the plant.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
This pressure may be affected by solar radiation, Before considering the use of brackish water for
ambient dry-bulb and wet-bulb temperatures, condensers, cooling towers, jacket cooling etc, a full
presence of non-condensables or condenser fouling analysis of samples local to the site should be carried
etc. The detrimental effects of regular sandstorms out. It is recommended that designers discuss the
must be thoroughly considered in the location, intended use of treated water within the project with
orientation and protection of plant. the AHJ.
Pressure drops in the refrigerant lines reduce the ‘Hard’ potable water used in evaporative condensers
system’s efficiency, so it is important to consider all and cooling towers will require a high ‘bleed-off ’
factors when determining maximum working pressure. rate to maintain the solids content within acceptable
limits. The practice of reducing bleed rates below
4.4.4 Ambient temperatures those recommended in order to save on water costs
The use of solar shields is recommended for all should be avoided.
refrigeration plant located outdoors. Overhead
canopies designed to provide shading must not Where used with high condensing temperatures,
obstruct the airflow through condensers or cause water that is high in solids content will hasten scale
short-circuiting of the airflow. formation on tubes and fins. Rapid blocking of spray
header jets will also occur.
The high daytime dry-bulb temperatures are
frequently accompanied by high humidity, so air- A suitable water treatment unit may resolve the
cooled and evaporative condensers must be oversized. problem, provided maintenance of the equipment
Condensers and compressors must be selected for the and topping up with chemicals takes place regularly.
high ambient temperatures experienced in the region.
Evaporative condensers and cooling towers must be
Liquid receivers should be located in a well- carefully designed and maintained to minimise the
ventilated internal plant room area. If an outdoor risk of Legionnaires’ disease. These will form part
location cannot be avoided, the receiver must be of a water system and should be considered in the
provided with solar shading. project’s Legionella pneumophila management plan.
Thermal insulation on vessels, pipework and Information on Legionella pneumophila mitigation
ducting must be of adequate thickness with special strategies can be obtained from reliable sources
attention paid to maintaining a good vapour seal including:
throughout. The high humidity will quickly
t Legionnaires’ disease: The control of legionella
cause extensive damage to insulation if moisture
bacteria in water systems (HSE, 2013)
penetrates a damaged vapour seal. Mechanical
protection of insulation through the use of painted t CIBSE TM13: Minimising the risk of
metal sheathing is recommended. Legionnaires’ disease (CIBSE, 2013).
the roof or discharge over a floor drain. Condensate there should be an air break. Where the condensate
disposal from indoor comfort cooling units, however, discharges to a drainage system, it should discharge
needs a greater design input, particularly in hot indirectly to a trapped and vented receptor, such as a
climates where the number and disposition in any tundish, through an air break or gap. The pipework
significantly sized building can produce challenges to gradient should be 1:50, but this can be difficult to
draining the condensate from multiple terminal units. accommodate in larger runs. In these situations a
fall of 1:80 would not be unreasonable. A formula for
Simplistically, the apparatus for condensate removal calculating the rate at which condensate is produced
is divided into four main elements: the drain tray, can be found in CIBSE TM43: Fan coil units (CIBSE,
the trap, the network of pipework and the point of 2008).
final discharge.
In situations where the condensate cannot be drained
The drain tray collects condensate from the cooling by gravity into the main condensate network, it may
coil of the unit. It also has a secondary function of be necessary to use a condensate lifting pump. These
catching water from any small leaks from valves and normally operate only when water is available to be
joints. It should be externally insulated to prevent pumped. This type of system should be discouraged,
moisture condensing on the outside surface, known however: a condensate pumping set is a mechanical
as ‘sweating’. Usually, the cooling unit manufacturer device, and mechanical devices are susceptible to
will offer a drain tray that incorporates the failure. If there is no option but to use this method
requirements outlined. However, not all provide of condensate disposal, consideration should be
an extended drain tray to catch any leaks from given to linking it into the building management
contractor-fitted control valves, an option well system to activate an alert to the facilities manager
worth the additional investment. in the event of a pump failure.
Condensate traps are necessary wherever there is a Pipework material for condensate drain lines can
fan associated with a cooling coil, be it an air handling be either insulated copper or plastic, but these two
unit or a simple fan coil. The purpose of the trap is different materials should not be mixed.
to allow accumulating condensate to drain off while There is a small risk of Legionella pneumophila
preventing air entering a draw-through unit or occurring if condensate is not properly removed,
escaping from a blow-through unit. The purpose of therefore the condensate disposal system should
the trap is to use a column of condensate to prevent be easily cleaned to minimise that risk. Refer to
air movement into or out of the equipment casing CIBSE TM13 (CIBSE, 2013) for further guidance
while still allowing the condensate to drain away. on minimising the risk of Legionnaires’ disease.
Each unit on a shared system of condensate Any electrical control panels, or motors mounted
removal should have its own trap. If they are not outdoors or indoors where there is a possibility of
independently trapped and one of the units shuts condensation, must be equipped with heaters to
down, the others will blow air into or draw air from prevent condensation occurring inside at night.
the inactive system (depending on whether the units Variation of temperature in desert areas is very high
are of the draw-through or blow-through type). and surfaces often fall below dew-point temperatures
at night, causing heavy condensation. Heaters in With low night-time temperatures, considerable
panels should be controlled by a thermostat, and condensation can form inside oil tanks, particularly
heaters in motors should be automatically switched when the level of oil is low. Ensure that provision is
off when the motor is started. made for draining and removing sludge.
4.4.7 Ambient conditions Fans must be selected bearing in mind the elevation
of the installation and the ambient temperature
High ambient air temperatures in the Middle East
variations.
dictate almost continuous use of air water or refrigerant
cooled plant. The refrigeration plant should operate Natural draught from chimneys is a function of
at design temperatures with the specified output and the difference in density between the hot gases in
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
at a maximum temperature with a reduced output. the chimney and the equivalent column of cooler
This will reduce the risk of the plant tripping out on ambient air. This must be worked out for each
high pressure at extreme temperatures. chimney from the following formula:
4.4.8 Testing
In industrial applications, the refrigeration plant D = (pa − pg) g (4.1)
equipment used will be custom built. Therefore,
it is wise to test a unit under design conditions where:
before it leaves the manufacturer’s works. Failure
to do so can cause considerable problems on site t D = draught/m chimney (Pa/m)
and make the diagnosis of malfunction impossible.
t pa = density of ambient air (kg/m3)
The system resilience should be tested as part of a
complete commissioning plan. t pg = density of flue gasses (mean) (kg/m3)
t g = gravitational acceleration (m/s2).
4.5 Heat generation and fuels
4.5.3 Salinity of soil
4.5.1 Source, type and consistency of fuel
The installation of fuel storage tanks below ground
While most oil and gaseous fuels are similar to those
should follow one of two options. The selected option
used in the UK (LPG and natural gas), there are some
will influence the location of the tank in relation to
differences. Solid fuel and waste product burning
the building.
(e.g. Bagasse) pose other problems and it is essential
that details of the fuel to be used be obtained to enable 1. Tank installed within a sealed concrete
the correct combustion equipment to be provided. enclosure.
Details should include: calorific value, density, 2. Tank installed within a sealed concrete
viscosity characteristics, carbon, hydrogen and enclosure and filled with clean sharp sand.
sulphur content, grading and acidity Buried tanks and mains must be protected against
corrosion by the careful application of external
4.5.2 Ambient temperature effects protective coatings, such as bitumen-based paints
Oil storage tanks and mains will absorb radiant or similar materials, before back filling with clean,
heat. Gas oil tanks could reach high temperatures. sharp sand.
Vents should be fitted with flame traps and the
4.5.4 Water table
tanks painted with an aluminium or other reflective
finish. Similarly, above-ground oil mains should be The location of the water table will impact on the
insulated and painted in reflective paint. design of the tank location. The designer must
establish the location of the local water table as part
Low night-time ambient temperatures may dictate of the design process. Where the tank is to be located
tank/line heating even for light grades. Such heating in close proximity to the water table, the tank must
must be controlled accurately and shut off before the be anchored to adequate concrete structures to
high daytime temperatures are reached. avoid flotation.
The source of water on a project will contribute to In areas with a high water table or areas that are
determining the water treatment required. Mains subject to flooding, it is prudent to avoid having
water will be of appropriate quality for typical boiler services in floor ducts. It may be necessary, therefore
supply. Boiler feed water should be demineralised to to consider the plant room layout, to accommodate
avoid scaling. such services as fuel systems to equipment, boiler
blow down and feed water systems and electrical
Brackish or well water will require treatment (ion
services, above ground.
exchange treatments), such as full demineralisation,
to ensure the water is of an appropriate quality. A full 4.6 Water and sanitation
analysis of available water and its seasonal and long-
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
In all toilet facilities, ensure that spray taps and 4.6.4 Drainage of foul and surface water
floor drains are provided and located according to Although infrastructure is being installed in most
local custom. areas to provide a connection for foul water and a
separate connection for surface water, there may be
4.6.2 Internal sanitation
projects where an alternative drainage strategy is
As part of establishing the project’s basis of design, required. The following methods of waste disposal
the designer should consider these points. must be considered in consultation with AHJ:
1. Sewer system configuration: in some countries 1. septic tank: foul water only
the sewage systems are designed so that soil 2. aqua-privy: foul drainage only
water containing excreta is kept separate from
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
pipes are particularly prone to this problem. provided the water is not too corrosive.
In certain areas, the discharge of surface water As part of a water minimisation strategy, the use of
to boreholes is being considered to replenish water meters is recommended. An overall metering
ground water aquifers. Subject to the AHJ granting strategy should be determined early in the project.
permission to discharge surface water into the Although meters may be connected to the building
ground water system, the borehole should be of management system, the meters themselves must be
adequate depth and diameter to allow the water to located in accessible locations either at the point of
permeate. A perforated lining should be provided entry to the building or, in the case of split tenancies,
to stabilise the borehole walls, and the annular gap on each individual supply. It must be ascertained
between the lining and the borehole should be filled whether water meters are to be provided by the
with large granular material. water authority or by the landlord/tenant; they can
also be used for leak detection i.e. if consumption
To avoid penetration of silt, a silt trap should be
exceeds historical trends.
provided before entry to the borehole. Corrosive or
contaminated affluent must not be allowed into the Where it is necessary to drill a borehole or well, the
groundwater system. An adequate seal at the top of following items should be considered.
the borehole in the form of removable cover should
always be provided. t The local environmental agency should be
approached for permission or approval to
Boreholes or soakaways for surface water sink a new well. When approval is obtained,
disposal should be sited away from buildings. The a wells engineer will be required to advise on
water should not be able to percolate beneath load groundwater aquifer location and potential
bearing surfaces. and, if available, an isosalinity map giving the
concentration of total dissolved solids will
Ground permeability and soil reports should be
be needed. Water from a shallow well may be
checked carefully. In certain soil types, such as
suitable for irrigation, but the analysis should
limestone, the soil can be absorbed into suspension,
be checked with an irrigation specialist to
which can cause collapse. If cast iron pipes and
ensure that the water is suitable for the plants
fittings are buried below ground, protective
being considered.
wrapping in the form of adhesive tape or welded PVC
sheeting should be provided. Ideally, the internal t For potable water supplies, a deep well should
and external surfaces should also be protected with be considered to reduce treatment costs. A
a coating of ethyl vinyl alcohol copolymer. ‘pilot-well’ should be constructed and a yield
test carried out. After an initial pumping
4.6.5 Water supplies period of 24/48 hours, a water sample should be
The water supply for a building or complex can be obtained for analysis.
provided by: t The well should be suitably sealed with an
appropriate (HDPE/uPVC) lining to avoid
t water authority main penetration by contaminated water from a
t shallow or deep well shallow aquifer. At the base of the lining, a
suitable stainless steel or uPVC well screen TDS concentration can be discharged to waste in the
should be provided, sized to give sufficient form of brine.
flow capacity into the well. The well must have
a sealed cover containing the well assembly, The need for pre-treatment should always be
which must be located in a suitable position checked before connecting a flow line to a membrane
to avoid the well head being submerged by filtration plant.
contaminated surface water. If the quality of the raw water is uncertain, heavy
t Borehole pumps should be either well head or dosing with chlorine should be used followed by
submersible types and be linked to low water sand and activated carbon filters.
cut-out probes in the well. The pumps should
4.6.7 Domestic water supplies
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
t Reverse osmosis membrane system (spiral The internal water supply system should be designed
wound cartridge tube filter). to meet the requirements of the building, layout of
t Electro-dialysis membrane system (flat the sanitary fittings, the pattern of use and the water
‘sandwich’ filter). supply network. Materials should be specified to
suit the type of water available.
t Desalination flash evaporation.
t Sand-bed filteration/chlorine dosing. During the summer period, the temperature of
water supplied by the AHJ may be 25–40 ˚C. The
When considering any of the above, it is designer should consult with the project team on the
recommended that advice be obtained from need to mechanically cool this water when ambient
specialist manufacturers to find the most efficient temperatures are at their peak.
and economical solution. Due to the fluctuations
in water temperature delivered from the mains Any cool water storage systems should be protected
(20–42 ˚C), the designer should determine whether from extreme changes in temperature and direct
cooling of potable water is required. sunlight to avoid deterioration of the system and
to avoid increasing the temperature of stored water.
When calculating supplies to membrane filtration The system should be located within a ventilated
systems, allowance must be made in the calculations plant room, if possible.
for the quantity of reject water and final product
water. The total amount of product water is related As the stored water is used both for ablution and
to the total dissolved solids (TDS) content of the raw consumption, the system should be sealed and filters
water. A considerable quantity of water with a high fitted to overflows, warning pipes and vent pipes to
prevent entry of airborne contamination. Where t partially treated sewage effluent (but this
a bowser fill-point is required, this should be in a should not be used in public areas due to health
form of a screwed cap with retention chain fixed to risks and possible odour problems)
a pipe entry. t sea water (but expert advice should be obtained
before making a final decision)
The water storage tank must be sectionalised to
allow drainage and cleaning. t fully treated/chlorinated sewage effluent (TSE).
Where pipework serves bidets, garden watering The extent of irrigation requirements should
points and other possible sources of contamination, be established and the total water requirements
anti-syphonage (back flow) preventers must be fitted. calculated allowing for absorption, evaporation and
plant requirements. The irrigation system may be:
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
the treatment equipment is regularly maintained by should be kept as simple as possible; effective and
trained personnel. reliable control may be achieved with relatively
simple control systems.
4.6.11 Sewage pumping
Pumping plant may be of the following types. Although technological advancements have been
incorporated into projects, the designer must
t Submersible sewage pumps. be aware that the individual components that
t Sewage ejectors incorporating compressed air. make up the system may be subject to the harsh
local environment. The external location of
t Dry well pump linked to a wet sump.
ambient temperature sensors will require careful
t Vertical spindle pumps located in surface plant consideration to ensure they are not unduly subject
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
out should be provided for maintenance and safety BS EN 62305-1 (BSI, 2011a) are met. A strict regime
reasons. Alternatively, motor control centres should for testing protection systems should be engaged,
be constructed to suitable IP rating to withstand as the earth resistance can vary considerably
prevailing external conditions. with seasonal changes in the region. Any special
protection measures required for critical equipment/
4.8.7 Loading parameters telecommunication/data processing systems should
It must be noted during the planning stages that be accounted for in accordance with BS EN 62305-4
the connected load/maximum demand assessment (BSI, 2011b).
should consider the cooling loads as the predominant
4.8.10 Batteries
loading for the arid regions and any seasonal variants
are less distinct. Air conditioning loads will need Batteries perform best at moderate rather than
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
to allow for any air-cooled or water-cooled chiller extreme temperatures due to the varying rate of
units (if the project is on standalone cooling plant), chemical reactions. Where batteries are proposed,
associated pumping systems and the air handling they should be housed in proper conditioned/
systems. As all these elements are motor-related ventilated areas suitably de-rated for the expected
loads, the maximum demand parameters will not be temperatures and the application proposed. Spill
applicable as the diversities are low. Any applicable containment should be provided. Batteries serving
de-rating factors imposed by the AHJ should be any critical systems (e.g. generator cranking
accounted for. application) should be constantly under trickle
charge and monitored. Float charging across a small
4.8.8 Pumping systems electrical reliability non-critical load will give rise to an alarm. When
Dependency on mass water storage is a common located in remote areas, suitable redundancy should
phenomenon in arid climate regions, so reliability be built in to the charging systems.
of pumping systems is paramount. Designs for such 4.9 Lighting
applications should build in sufficient resilience
4.9.1 Interior lighting
to cater for any unforeseen circumstances. All
motors should be suitably de-rated for the correct As discussed in section 2.3.2, if the interior
insulation class and temperatures selected, and all environment is being designed to ambient
associated cabling and controls should be to suit the temperatures similar to temperate climates, there
application. All pumping systems should incorporate are no specific special design issues to consider and
standby equipment to cater for the loads in the the general recommendations of the SLL Code for
event of any failures. The configuration of pumps Lighting (SLL, 2012) will apply. However, there
could be electric + electric or electric + diesel to may be situations when interior luminaires are
suit the application. used in areas where the internal environment is
not controlled in terms of temperature, filtration
4.8.9 Lightning protection and humidity control—for example, external
Static charges in structures are induced in dry air, stores, loading bays, mechanical and electrical
adding the need to carry out proper equipotential plant rooms—thus, they will have to withstand the
bonding for structures in those regions. Lightning is peculiarities of the local climate. In these cases the
also common in arid climates, so protection systems following points should be addressed.
should be used to protect structures. Tall structures 1. Has the fitting been tested for operation in
can utilise inherent structural reinforcement +50 °C ambient?
components for conducting paths. Continuity
2. How is the lamp life and initial lumen output
should be ensured for all conducting parts to
affected over time at this temperature?
facilitate an easy path for discharge to earth. This
is best achieved by welding of down conductors, 3. Are the entire internal components/electronics/
which will negate the effects of corrosion and bad devices/wiring etc treated at +85 °C storage
conductivity. Sufficient grounding points should temperature (i.e. daytime or non-operating)?
be provided for the lightning protection system to 4. The lamps must fall within specific colour
ensure that the minimum requirements required by temperature band and colour rendering
requirements and actual must be values stated might differ significantly and manufacturers’ details
(set limits vary and depend on type of product should be consulted.
use).
"! J
5. The luminaire must be designed to IP6X for
Lantern bodies should be corrosion resistant and
dust ingress
made from aluminium or reinforced plastic material.
6. Heat sinks/thermal dissipation system should Totally enclosed lanterns should be particularly well
be designed to minimise build up of sand and sealed with an IP rating of at least IP 65. Special
dirt, and operation/efficiency should not be attention must be paid to gasket material, especially
affected by any natural build-up. its resistance to tropical climates and insects.
7. Alloys should be corrosion resistant with
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
At the significantly higher temperatures experienced Some lift suspension ropes contain an inner core
in arid environments, depending on the type of that contains a lubricant to minimise internal
luminaire-lamp-ballast system applied, lighting wear caused by steel wires rubbing together; this
characteristics will deviate from those under can require rope dressing to be applied regularly
standard conditions. Ignition, amount of light if the core is drying out but will inevitably lead to
available and start/run-up characteristics of lamps premature wear. The ingress of dust into lift door
the levels of maintenance, they can also be minimised 2010) for detailed design guidance, which looks at
by an initial specification that ensures vulnerable the following subjects in detail:
components are protected.
t legislation, standards and strategy
In some cases, lifts and escalators are used more
t building designation
intensely over a short period of time for cultural
reasons, such as the annual hajj pilgrimage, and at t performance-based design principles
these times more directed maintenance is required. t application of risk assessment to fire
It is not unknown for these lifts and escalators to engineering designs
be isolated all year round and under ‘caretaker’
t fire dynamics
maintenance, so case-specific and intensive
maintenance prior to restarting would be required. t means of escape and human factors
t fire detection and alarm
At the point of specification, the number, size and
t emergency lighting
speed of lifts and escalators needs to be considered,
as the passenger loading in the case of religious t fire and smoke ventilation
gatherings can range from zero to incredibly high, t fire suppression
although overprovision can be costly.
t compartmentation
The effects of different materials need also to be t fire fighting
considered, for example, lacquered brass-effect t fire safety management
fittings, such as push buttons, quickly become
t fire safety on construction sites.
blackened by their use as a result of salt created on
human hands due to perspiration. The obvious issue 4.11.1 Cultural differences
of metals becoming hot and expanding, as well as
4.11.1.1 Fire risk
being difficult to touch, also need to be considered.
Passenger comfort should be maintained in Smoking is a major fire risk, and many Middle Eastern
circumstances such as a lift failure. Glass lift cars countries still allow smoking in public buildings. The
act like greenhouses and insufficient air changes majority of fires in hotels, for example, are started by
and/or cooling combined with passenger panic at smoker’s materials, so sprinklers are important.
being entrapped could cause suffering, especially
Cooking in areas other than kitchens is common.
when the entrapment is prolonged, so the ability to
rescue people quickly in these circumstances needs Traditional Arabic pipes and incense burners
to be considered. require hot charcoal and so represent another source
of ignition. The charcoal is slow burning and can be
4.11 Fire life safety
easily left unattended.
Fire life safety (FLS) encompasses all the major
disciplines including: Building owners and operators, especially from
developing countries, will often have lower standards
t architecture of fire safety than required or assumed by UK/US
t structures codes that are normally used in the region.
Staircases are often misused and it is common to design of fire systems including sprinklers and fire
find egress stairs blocked by stored furniture. detection and alarm systems.
Many of the buildings in the Middle East are not UK standards are sometimes used for design of
inspected on a regular basis or to the required fire alarm and detection systems but rarely for
standards, so the on-going maintenance of fire automatic sprinklers.
measures is not to the same standard as the UK/US.
The majority of projects in the Middle East are
"! =
sprinklered. Underground car parks are required to
In the Middle East, the Civil Defence authorities will be fully sprinklered, which is a different approach
place much larger responsibility on the consultant from the UK codes.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
to ensure that the design meets code. Obtaining The following are the popular standards used in the
Civil Defence approved and stamped drawings Middle East.
does not necessarily mean that the design meets the
applicable code and standards. It is expected and t NFPA 1 Fire Code (NFPA, 2012c)
assumed that the consultant will ensure full design t NFPA 10 Standard for Portable Fire Extinguishers
compliance with applicable codes. (NFPA, 2013a)
The consultant should also ensure that fire systems t NFPA 13 Standard for the Installation of Sprinkler
are installed as per design, therefore third party Systems (NFPA, 2013b)
site inspection of fire system installation is crucial t NFPA 14 Standard for the Installation of
during construction. Experience suggests that Standpipes and Hose Systems (NFPA, 2013c)
consultants should not rely on the civil defence t NFPA 20 Standard for the Installation of
authority to inspect buildings to the same standard Stationary Pumps for Fire Protection (NFPA,
as in the UK. 2013d)
" H
Q t NFPA 22 Standard for Water Tanks for Private
Fire Protection (NFPA, 2013e)
In some Middle Eastern countries, for example
Oman Civil Defence will only accept designs from t NFPA 24 Standards for the Installation of Private
qualified and known fire consultants. As a result, Fire Service Mains and their Appurtenance
fire consultants are required to be registered with (NFPA, 2013e)
Civil Defence before being allowed to submit t NFPA 70 National Electrical Code (NFPA, 2014)
designs. Foreign fire consultants will not be allowed t NFPA 72 National Fire Alarm and Signalling
to submit designs for approval unless they are Code (NFPA, 2013f)
registered locally. t NFPA 88A Standard for Parking Structures
4.11.2 Codes and regulations (NFPA, 2011)
Middle Eastern states have based their old local t NFPA 92 Standard for Smoke Control Systems
codes on UK building regulations. In recent years (NFPA, 2012d)
the majority of countries in the Middle East now "! K
follow US codes, including:
It is important that quality fire products are used for
t NFPA 101 Life Safety Code (LSC) (NFPA, the design of buildings. Products should be certified
2012a) and NFPA 5000 (NFPA, 2012b) to internationally recognised bodies such as:
t International Building Code (IBC) ICC (2012) t Universal Laboratories (UL)
For example, in Saudi Arabia, the Saudi Building t Factory Mutual (FM)
Code (SBC) is adapted from the International t Loss Prevention Council Bureau (LPCB).
Building Code (IBC).
Care should be taken to ensure that products are
National Fire Protection Association (NFPA) approved. In the Middle East, fake or counterfeit
standards are widely used in the Middle East for products are on the market and have been installed
# %
%! X !
# !
"
@
services
t sprinklers
4.11.3.1 Vehicle access
t fire dampers
As streets and hydrants are not often in place in
t ductwork.
the Middle East, fire access roads will need to be
Clearly, counterfeit products will jeopardise the provided to the site. The US codes are generally
safety of the public and the consultant should check used for design, however local fire vehicles will be
that installed fire products are certified and listed as of the smaller European type and so relaxation of the
per the design. US codes may be sought.
"! X
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
"!! X
US codes allow the provision of fire dampers to be Private fire hydrants are often required to supply
relaxed where buildings are sprinklered and metal fire fighting water, as the local town main may not
ducts are provided. be in place or be reliable.
NFPA 5000: Building Construction and Safety Code 4.11.3.3 Fire command centre
(NFPA (2012b) only requires fire dampers in the Where a building is designated as a high rise, a fire
following locations as per clause 8.8.8.2.3 of NFPA command centre is required. The location of the
5000. central control station must be approved by the fire
department. Central control stations are typically
t Ducts and air-transfer openings penetrating
located on the ground floor near an entrance to
walls or partitions having a fire resistance
the building. It is common practice to share the
rating of two or more hours.
command centre with security rooms.
t Ducts and air transfer openings penetrating
vertical shaft walls having a fire resistance 4.11.3.4 Hosereels
rating of one or more hours. Many jurisdictions require hosereel cabinets to be
t Ducts and air transfer opening penetrating provided in addition to the minimum requirements
floors that are required to have a protected given in the US codes.
opening where the duct also is not protected by
a shaft enclosure. "%
Z
t Air transfer openings that occur in walls or Sprinklers are provided in most buildings in the
partitions that are required to have a fire Middle East and are required for any building over
resistive rating of 30 minutes or more. 23 m in height.
Code (NFPA, 2013f). Strobe lights are commonly 4.11.3.11 Parking garages
provided as per NFPA in public areas. Parking structures follow NFPA 88A Standard
for Parking Structures (NFPA, 2011). Enclosed
"( ^?
parking structures are ventilated by a mechanical
system capable of providing a minimum of
A high-rise structure is required to have an
0.3 m3/min/m2 of floor area per hour during hours
emergency voice alarm (VA) communication system.
of normal operation. Under NFPA codes there is no
VA systems will broadcast alert messages in both
additional fire mode operation.
English and Arabic with an intermediate alert tone.
The UK code requirement for increasing from 6 air
4.11.3.9 Smoke control design changes to 10 in a fire condition does not apply in
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
US codes.
Due to high external temperatures, natural or
buoyancy driven designs are rarely accepted by Civil Ductless smoke extract systems (jet fans) are
Defence. Smoke control systems normally comprise accepted in some jurisdictions in the Middle East
powered extract fans with natural make-up air. but are not allowed in others; for example, neither
Dubai nor Abu Dhabi allow ductless systems.
Smoke control systems for large spaces, such as
indoor arenas, exhibition centres or airport terminal Underground parking garages are normally fully
buildings, will typically have a design smoke sprinklered.
layer temperature at or below external ambient
"![
Z
\
]
temperatures. External ambient temperatures can
reach 50 °C in summer and are typically 45 °C. In high-rise buildings, staircases need to be protected
from smoke. The term ‘smoke proof ’ is commonly
For very tall buildings, reverse stack effect should used in US codes and can be achieved by:
be considered when designing stair pressurisation
t pressurisation
systems. Stairwell pressurisation will require
control that can vary the flow according to the actual t lobby protection (mechanically ventilated)
pressure in the stairwell. t lobby protection (naturally ventilated).
4.11.3.10 Cold smoke testing US codes require pressures of only 12.5 Pa for
sprinklered buildings as opposed to 50 Pa required
Cold smoke testing is carried out to demonstrate by UK codes. Consultants should follow the
activation sequence or smoke clearance of public pressurisation methods in NFPA and not British
spaces. It is important that the external make-up standards to avoid over-design.
air temperature is taken into account. Make-up air
at 45–55 °C will be introduced into a conditioned 4.11.3.13 Cooled refuge areas
space where the cold smoke is at 21 °C. The hot Where areas of refuge are provided in a high-rise
replacement air will rise quickly to a high level where building, the inclusion of ‘cooled refuges’ consisting
the extract fans are typically placed. The cold smoke of spot cooling in the pressurised refuge areas by fan
will be forced down and away from the smoke extract coil units maintained on emergency power should
fans and the system will short-circuit. As a result, the be considered. With outside air temperatures
system will not perform as designed. Cool air from potentially reaching 50 °C, this measure is essential
the main building should be used for replacement air to ensure that the refuges remain tenable in the
where possible to mitigate short-circuiting. event of power loss to the building.
Sustainability 99
Buildings for extreme environments: Arid
process is the most prominent in Middle East needs. The early engagement of users and builders
and certain developing countries with extreme and allows the build, handover and implementation
arid climates. to be smoother, as everyone becomes involved
in the design process and is familiar with the
Figure 39 demonstrates this idea. The opportunity to design decisions. This, in turn, requires a project
influence and for the design to accept changes easily manager and client that realise the complexities of
always occurs during early stages of design process incorporating sustainability into building design and
when there is minimum abortive work and when employ—from the very beginning—a sustainability
equipment and construction has not been procured specialist who understands the intricacies of project
or started yet. Design changes implemented later team relationships and can manage everyone’s role
in the project’s lifecycle often have high cost and in the design process, not just tick boxes for credits
programme implications. A practical example of this in a building rating system.
is when a developer decides to pursue sustainability
goals for the project after the design is completed The traditional design process relies heavily on
or towards the latter stages of detailed design, and drafting during detailed design and tender packages
sustainability features have to be added to the documentation. As technology evolves and building
building in a hurry, as bolt-on solutions. Inevitably, information modelling (BIM) and 3D design packages
this leads to the conclusion that sustainability in are becoming available, designers are increasingly
buildings is expensive, when in reality the problem working with design tools common to all design
is often with the management of the design process team members; a new concept, which allows for the
itself. accountability and easier transferring of information
and sharing of knowledge. These tools allow for
Realising a sustainable project that works for the earlier testing of design alternatives and modelling
client and project occupant requires the input of of energy conservation measures without the need
Figure 39: @ ## Brief Concept Design Construction Construction
MacLeamy curve shows and scheme development documents
Specialist
Contractor/facilities
Time
Low High Low Time
100 Sustainability
Buildings for extreme environments: Arid
for these options to be fully developed. This, in turn, 5.4.2 Water use
allows for further exploration of design alternatives
%"! :
and greater integration as the design continues.
Water is a scarce resource in most parts of arid
LEED, the Pearl Rating System Estidama and regions, so a key design objective should be to
BREEAM—among other rating systems—strive for minimise or eliminate impacts on natural surface
this design approach as the preferred methodology and groundwater flows.
to be achieved in sustainable design projects. Some
rating systems even go beyond the design process. Typically, the building services engineer will be
For instance, LEED has a ‘Measurement and involved with the provision of irrigation water
Verification’ credit that requires the design team particularly associated with landscaping, but
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
and the commissioning agent to be engaged with possibly to assist in the growing of agricultural
the project after one year of substantial completion crops and revegetation of disturbed soils in dry
of the project, and BREEAM with the Soft Landings areas and during periods of inadequate rainfall.
process requires even further contact between Water efficiency needs to be carefully considered
designers and building owners and occupants. and water balance calculations should be part of
These post-occupancy evaluation analyses allow the design early on. Water practices developed for
the building to get fine tuned and the design to be temperate climates may not work as well in arid
understood by the user but also provide the platform regions for technological, environmental, economic
for the designers to understand human behaviour and cultural reasons. There are two fundamental
and lessons learnt for future designs. approaches to water management in the context of
buildings: increasing the supply of usable water and
5.4 Sustainability considerations in reducing the demand for water.
arid climates
5.4.1 Site and masterplanning Increasing the supply of usable water could be
Sustainable design balances human needs (rather achieved by the following methods.
than human wants) with the limits of acceptable
change of the natural and cultural arid environments. t Irrigation with brackish water: brackish
It minimises environmental impact, import of goods water is widely available and with care and
and energy, and waste generation. under certain favourable conditions, it can be
profitably used for irrigation of certain types
Building services engineers should strive to ensure of plants; however this needs to be carefully
the project has minimal impact on the natural and professionally planned and managed, as
environment. The complexity of site preparation not many plant species can tolerate high salt
and construction can be magnified in an arid concentrations for a prolonged period.
environment by the value of the resource, physical
t Reuse of water: using recycling and advanced
remoteness and limited availability of craftsmen
waste treatment.
and materials.
t Wells: hand-dug wells, which began thousands
Local construction techniques and building of years ago, are regaining popularity with
materials should be used as long as they do not the help of new materials and construction
adversely affect the natural and cultural resources equipment. Examples are qanats and horizontal
of the area. The methods and techniques used wells—methods for tapping underground water
should ensure that there will be no residual signs of without using pumps, illustrated in Figure 40.
construction or environmental damage.
t Other approaches include groundwater mining,
Infrastructure availability should be considered desalination, solar distillation, the use of
well before any design activity starts and the site’s satellites and aircraft for detecting water in arid
geology and topography should also be investigated. lands, rainfall augmentation, the possibility of
Proposals should consider the development’s visual using icebergs as a source of water and dew and
and acoustic impact on the surrounding areas. fog harvesting.
Sustainability 101
Buildings for extreme environments: Arid
Irrigated land
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Wa
te r ta Alluvium
ble
Bedrock
Figure 41: Decision Is there an option for the Is it viable for standalone
$+ #&! %! project to connect to local No air-cooled plant to be
cooling system cooling infrastructure? used for the project?
No
Is the project scale such that
the use of water-cooled Yes
chiller plant is necessary?
Yes
No
In addition to increasing the supply of freshwater, water and nutrients via mulch covers on the
designers should also consider minimising water soil surface help to reduce erosion, retain
demand. Examples for reducing water demand moisture and minimise the fluctuation in soil
include the following methods: temperature.
t Xeriscaping and xerogardening—landscaping
t Efficient irrigation design, including
and gardening in ways that reduce or
minimising leakage and reducing the rate of
eliminate the need for supplemental water
evaporation for irrigation water. Drip irrigation
from irrigation through the use of appropriate
techniques for suitable plant species can ensure
plant species and careful siting to minimise
delivery of water directly to the plant’s roots,
evaporation and transpiration by exposure
rather than onto the soil surface.
to wind. This is often promoted as a
t Improving the capacity of the soil to hold sustainability concept in arid regions.
102 Sustainability
Buildings for extreme environments: Arid
t Operational considerations such as night-time In addition to heat rejection, the project team will
irrigation and adaptive mowing of lawns. also need to consider the use of low and ultra-
t Treated wastewater effluent can also be used low flow water fixtures and aerators, as these will
to irrigate landscaped areas: this will reduce contribute to lowering water demand.
demand for potable water and provide a Generally, on-site water treatment (greywater and
means of disposing of treated wastewater blackwater) requires careful deliberation to address
effluent. However, in some countries the use cultural, technical and cost issues. The use of
of wastewater effluent for irrigation may be treatment plants may also require system registration
prohibited by local regulations. Often these and operator licensing at the start of the project.
regulations have no scientific or engineering
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
Sustainability 103
Buildings for extreme environments: Arid
The integrated approach to energy conservation Building energy costs over the life of the building
needs to consider the performance of the building’s can be as high as 10 times the capital cost of building
facade in terms of thermal insulation, extent of services systems, and therefore energy metering
glazing, external shading devices and the overall air must be considered during design. The provision
tightness of the façade. of energy meters into a project will provide the
operator with the tools to measure, record and better
A less quantifiable, but nevertheless critical, manage the building.
consideration is that of the quality of the installation
and maintenance personnel, since energy-saving Load demand limiting may be applied to
devices may require skills not readily available refrigeration plant during peak cooling load periods
locally. This risk may result in the practice of but care should be taken to ensure that the resulting
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
incorporating higher design margins into a project, deviation from indoor design conditions is not too
rather than addressing the source of the problem. abrupt or excessive.
Higher design margins will result in less efficient
plant operation. Energy tariffs should be examined to determine
whether a project will benefit from off-peak
Sophisticated energy conservation systems should electricity strategies such as thermal energy storage
generally be avoided. Experience has shown that (TES) systems.
system reliability and simplicity of operation are the
dominant criteria for applications in arid climates. Building management systems (BMS) incorporating
Sensitive equipment may be prone to failure due to energy management functions are regularly installed
extreme temperature and humidity combined with in most projects. The inter-operability of the various
dust and saline atmosphere in certain arid climates. systems should be considered early in the project.
It may be necessary to operate the air conditioning Although intelligent BMSs may be installed in a
plant continuously to prevent condensation project, the transfer of knowledge (design intent)
occurring on interior surfaces of the building during together with training the building operators and
the evenings. facilities management staff remains an area for
In coastal areas, the combination of high ambient attention. Structured training sessions, ideally
temperature and humidity results in high cooling occurring during the final stages of construction,
loads for fresh air cooling plants. The use of will allow the operators to better understand the
dedicated outside air system (DOAS) to provide design intent and the building’s control strategies.
preconditioned ventilation air is a common approach Training must be structured to be successful.
to most designs. The DOAS provides centralised Ensuring the operating staff are suitably skilled
plant to precondition air whilst recovering sensible remains a challenge.
and latent energy from the relief or exhaust air. The
(b) Renewables
fresh air quantity may be controlled automatically
through CO2 sensors to provide substantial energy Renewable energy studies should form part of the
savings. design process for all arid climate projects. Although
renewable energy is a topic gaining attention
Thermal wheels and other energy transfer devices
throughout the world, there are several factors that
may be utilised for energy recovery, although due
may impact the adoption of renewable energy systems
regard should be given to corrosion arising from the
for arid climates, including the following points:
saline atmosphere in coastal areas.
t Low consumer charges for baseline electricity.
Heat pipes, passive heat transfer devices, have been
used in various applications ranging from orbiting t Limited or no tariff structure for peak energy
satellites to the Alaskan pipeline ground spikes. By consumption.
applying heat pipes to standard air conditioning t Extreme environmental conditions (dust,
coil systems, the dehumidification performance and haze, humidity and fog), which will impact on
efficiency was greatly enhanced, with no increase in the system performance and also reduce the
energy use. economic life of components.
104 Sustainability
Buildings for extreme environments: Arid
$+
& +!
"
# "!
"!>
!#" pollution. arid climates or in climates with seasonal water
electricity. Renewable $+
Hydropower systems can be adapted from energy.
large-scale to micro and pico systems for remote
projects.
Solar hot The fundamental requirement for a solar system Renewable Relatively high embodies energy.
water is to have a sunny location where the solar energy. Keeping them clean can be a challenge.
collectors can be located. No localised
Thermal collectors absorb the sun’s radiation to pollution.
produce hot water. The collector can be either
$ ! <"# ">
The location and orientation of the solar
collectors should ensure that the collectors have
full sun from 9am to 3pm. The collectors should
face south at approximately the same angle as the
latitude of the project.
Photovoltaic Photovoltaic (PV) cells utilise the sun’s light to Renewable It is important to note that system performance
create an electric current and generate electricity. energy. is dependent on ambient conditions such as
The two most important factors when No localised temperature and dust. In a high temperature
considering the size of a system are the sunlight pollution.
<!
^>< [_ X !%!
%
intensity in the region and the average power the PV cells starts to deteriorate.
consumption of the project. A ‘rule of thumb’ for this deterioration is a
Even though the sun may be above the horizon !#"
"" +! %! <! [
for 14 hours a day, the site may only receive 6
!
%!
#!# !"! % [
hours of equivalent full sun. Similarly, as dust settles on the panels, the overall
performance of the system will be reduced. This
is addressed by regular cleaning, but this in turn
requires a source of clean water and for the
panels to be located in an accessible location.
Wind Wind energy converts kinetic energy that is Free energy. The reliability of wind must also be considered in
present in the wind into mechanical energy Low the feasibility assessment process. Although wind
or electricity. The amount of potential energy maintenance. delivers renewable energy, the reliability of wind
depends primarily on the wind speed and wind is presumed to be 30%.
No localised
speed generally increases as height above ground This then requires a baseload plant to be
pollution.
increases. provided that is capable of covering the times
Day and night.
Average wind speeds above 4–5 m/s are required when there is no wind generated.
to make small-scale wind-powered electricity
generation a viable option.
Concentrated These systems are made up of a large array of Large generation Due to high capital cost, the plant is used for
solar power mirrors to concentrate solar energy to generate capacity. large-scale power generation (100 MWe).
steam to drive turbines, which create electricity. Higher Pilot projects show 1 km2 of panels will generate
There are many variations in applying this %
X
80 MWe.
technology. $
!
collectors.
Sustainability 105
Buildings for extreme environments: Arid
t There is no rebate scheme to overcome the commissioning process covers system design,
high capital cost for the implementation plant selection, procurement, storage, installation,
of renewable technology. Small-scale and operation and ongoing performance and involves
decentralised renewable energy systems are the project design team as well as the contractor and
more capital intensive per kW of energy when project owner, as illustrated in Figure 43.
compared with large-scale renewable energy
projects and in some countries, systems parallel There are many detailed handbooks and literature
to the grid are not allowed. on commissioning, so this section is only intended
to provide an overview of commissioning.
When considering the implementation of
renewable energy systems, the design team One aspect of commissioning in an arid climate is
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
should consider all attributes including capital considering activities outside of the peak conditions
cost, maintenance, energy tariff structures and on the schedule. Regardless of scheduling, it is likely
decommissioning of the systems. that the commissioning activities will be performed
whilst the project is subject to the ingress of dust and
The main types of renewable energy systems that if they are performed during the warmer months,
may be appropriate for arid climates are shown in condensation is likely to be an issue.
Table 21.
Ideally, the commissioning process itself represents
(c) Metering an integrated approach whereby project team
participants—employer, engineer, contractor and
The operational performance of a building over operator—are involved. This process commences
its life has significant financial and environmental in establishing project goals, ideally at the start of
capital attached to it. In order to maximise the project, developing plans to achieve the goals
efficiencies, it is important for the building owner/ within design and construction and finally the
operator to have the tools and opportunity to implementation of activities to demonstrate that the
undertake diagnostics and also fine tuning, including goals are achieved.
intelligent energy and water meters, which measure
and record consumption within the project. These The commissioning plan ensures that the
meters are integrated through the project’s building intellectual knowledge, decision-making processes
management system. and stakeholder sign-offs during the various phases
of the project (e.g. from the concept phase to the
The design team should consider metering of operational acceptance phase) are documented
utilities such as chilled water energy, electricity, in an exact and usable manner that will provide a
gas and water. These categories can then be further smooth and transparent transfer of responsibility
broken down to include potable and non-potable from design and construction teams to the building
water, utility and renewable energy and other operations team. The transfer of knowledge must be
attributes appropriate for the particular project. performed in such a documented manner to allow
Understanding the employer’s aspirations and the operation of the facility without impacting the
requirements is a key part of the integrated approach building occupants or deviating from the original
to metering. This is reflected in the complexity of design intent. Understandably, the management
the metering strategy and is also project specific— of this process requires an experienced team
too complex and it will not be utilised by building player, who carries the title of (or is known as) the
operators; too simple and the plan will not permit commissioning authority (CxA).
diagnostics. A simple block diagram, as shown in The function of the commissioning plan is
Figure 42, is a recommended tool to establish and to provide a structured process whereby the
agree on the metering strategy. contractor demonstrates to the commissioning
(c) Commissioning authority, as the employer’s representative, that
the equipment and systems they have installed
Commissioning is a key ingredient of a strategic function in accordance with the design intent.
plan to deliver a high performance building. The The commissioning plan (which incorporates the
106 Sustainability
Buildings for extreme environments: Arid
(b) Product transparency and eco-labelling While some product labels are verified by a third-
party auditor and, as such, are reasonably rigorous
Environmental performance is becoming an and transparent, other claims are uncontrolled and
increasingly important differentiation tool for are often difficult to substantiate. A typical example
product manufacturers around the world. As a result, of this is recycled content, where many producers
many construction industry products now feature include scrap from their own manufacturing process
some kind of (and in some cases many different in their calculations of recycled content. It should
types of) product certification labels. These labels are be noted that the internationally accepted ISO
intended to give the buyer the impression that the definition of recycled content does not include
product is of superior environmental performance: industrial scrap, as re-incorporating scrap back into
Sustainability 107
Buildings for extreme environments: Arid
the original manufacturing process is considered that produce less waste will be preferred, if cost,
merely good economic sense. Therefore, design schedule and exploration or production goals are
teams should be careful of relying on claims not adversely affected.
about the environmental performance of building
materials and, if necessary, ask the supplier to verify As arid environments tend to currently be
their claims. underdeveloped, typical challenges to sustainable
waste management include:
(c) Adaptive reuse of buildings
t an absence of in-country contractors that
By definition, arid climates are generally less recycle and handle hazardous, non-hazardous
populated than moist or wet regions and although and mixed waste
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
As a result, most construction projects in these areas Culturally, it can be a new experience that requires
have limited or no opportunity to reuse existing substantial stakeholder education, especially if there
buildings, either because these building do not exist is a low population density, which may not create a
or they are not of suitable condition or specification market to drive up landfill prices, so there may be
to be reused. little incentive to do this.
Nonetheless, opportunities for adaptive reuse should Examples of possible sustainable waste management
be found when possible, as the reward and public opportunities include:
support for these projects can be enormous.
t converting biodegradable waste to compost,
(d) Designing for sustainable waste management
t waste-to-energy systems,
Sustainable waste management aims to address the
long-term pressures that arid climates face through t utilising the biomass in worm farming or
the recovery, recycling and reuse of resources, and sending the waste to anaerobic digestion
the minimisation of waste streams, with a focus systems
on reducing what ends up in landfill. Processes t collaborating with suppliers to minimise waste.
108 Sustainability
Buildings for extreme environments: Arid
ANSI/ASHRAE/IES (2013) Standard 90.1-2013: Energy Hedrick R (2009) ‘Generation of hourly design-day weather
Standard for Buildings Except Low-Rise Residential Buildings data (RP-1363)’ ASHRAE Research Project, Final Report (draft)
(Atlanta, GA: ASHRAE) HSE (2013) Legionnaires’ Disease: The Control of Legionella
ASHRAE (2001) ASHRAE Handbook: Fundamentals (Atlanta, Bacteria in Water Systems (Sudbury: HSE Books)
GA: ASHRAE) Hubbard K, Kunkel K, DeGaetano A and Redmond K (2004)
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
ASHRAE (2005) 2005 ASHRAE Handbook: Fundamentals ‘Sources of uncertainty in the calculation of the design weather
(Atlanta, GA: ASHRAE) conditions in the ASHRAE Handbook of Fundamentals (RP-
1171)’ ASHRAE Research Project, Final Report
ASHRAE (2006) ANSI/ASHRAE Standard 169-2006: Weather
HVCA (2000) Ductwork Specification DW/143: Practical Guide
Data for Building Design Standards (Atlanta, GA: ASHRAE)
to Ductwork Leakage Testing (5th edition) (HVCA: London)
ASHRAE (2009) 2009 ASHRAE Handbook: Fundamentals ICC (2012) 2012 International Building Code (Washington DC:
(Atlanta, GA: ASHRAE) ICC)
ASHRAE (2013) 2013 ASHRAE Handbook: Fundamentals IPCC (2007) Fourth Assessment Report: Summary for Policy
(Atlanta, GA: ASHRAE) Makers (Geneva: International Panel on Climate Change,
ASHRAE (2010) ASHRAE Handbook: Refrigeration (Atlanta, World Meteorological Organization)
GA: ASHRAE) Iqbal M (1983) An Introduction to Solar Radiation (Toronto:
BSI (2003) BS ISO 18738:2003 Lifts (Elevators): Measurement of Academic Press)
Lift Ride Quality (London: BSI) Kasten F and Young T (1989) ‘Revised optical air mass tables
BSI (2008) BS 6472-1:2008 Guide to Evaluation of Human and approximation formula’ Applied Optics 28 4735–4738
Exposure to Vibration in Buildings (London: BSI) Kottek MJ, Grieser C, Beck B, Rudolf and F Rubel (2006)
‘World Map of the Köppen-Geiger climate classification
BSI (2009) BS EN 60598-1:2008 Luminaires General
updated’ Meteorologische Zeitschrift 15 259–263 DOI:
Requirements and Tests (London: BSI)
10.1127/0941-2948/2006/0130
BSI (2011a) BS EN 62305-1:2011 Protection Against Lightning: Lamming SD and Salmon JR (1996) ‘Wind data for design of
General Principles (London: BSI) smoke control systems (RP-816)’ ASHRAE Research Project,
BSI (2011b) BS EN 62305-4:2011 Protection Against Lightning: Final Report
Electrical and Electronic Systems Within Structures (London: Lamming SD and Salmon JR (1998) ‘Wind data for design
BSI) of smoke control systems’ ASHRAE Transactions 104 (1A)
CIBSE (2002) Guide J: Weather, solar and illuminance data (CD- 742–751
ROM) (London: CIBSE) Livezey, RE, Vinnikov KY, Timofeyeva MM, Tinker R and
CIBSE (2005a) AM10 Natural ventilation in non-domestic Van Den Dool HM (2007) ‘Estimation and extrapolation
buildings (London: CIBSE) of climate normals and climatic trends’ Journal of Applied
Meteorology and Climatology 46 175–91776
CIBSE (2005b) Guide B: Heating, ventilating, air conditioning
Lott JN, Baldwin R and Jones P (2001) The FCC Integrated
and refrigeration (London: CIBSE)
Surface Hourly Database, a new resource of global climate data.
CIBSE (2005c) Guide K: Electricity in buildings (London: NCDC Technical Report 2001-01 (Asheville, NC: National
CIBSE) Climatic Data Center)
CIBSE (2006) Guide A: Environmental design (London: CIBSE) National Electrical Manufacturers Association (2004) ANSI/
IEC 60529-2004 Degrees of Protection Provided by Enclosures
CIBSE (2008) TM43: Fan coil units (London: CIBSE) (IP Code) (Rosslyn: National Electrical Manufacturers
CIBSE (2009) Guide H: Building control systems (London: Association)
CIBSE) NCDC (2003) Data Documentation for Data Set 3505 (DSI-3505)
CIBSE (2010) Guide E: Fire safety engineering (London: CIBSE) Integrated Surface Hourly (ISH) Data (Asheville, NC: National
Climatic Data Center)
CIBSE (2013) TM13: Minimising the risk of Legionnaires’ disease
(London: CIBSE) NFPA (2011) NFPA 88A: Standard for Parking Structures
(Quincy, MA)
Gueymard CA (1987) ‘An anisotropic solar irradiance model
NFPA (2012a) NFPA 101: Life Safety Code (Quincy, MA)
for tilted surfaces and its comparison with selected engineering
algorithms’ Solar Energy 38 367–386 and (1988) ‘Erratum’ Solar NFPA (2012b) NFPA 5000: Building Construction and Safety
Energy 40 175 Code (Quincy, MA)
References 109
Buildings for extreme environments: Arid
NFPA (2012c) NFPA 1: Fire Code (Quincy, MA) Rasch PJ, Mahowald NM and Eaton BE (1997)
‘Representations of transport, convection, and the hydrologic
NFPA (2012d) NFPA 92: Standard for Smoke Control Systems
cycle in chemical transport models: implications for the
(Quincy, MA)
modeling of short-lived and soluble species’ Journal of
NFPA (2013a) NFPA 10: Standard for Portable Fire Extinguishers Geophysical Research 102 (D23) 28127–28138
(Quincy, MA) SLL (1999) Lighting Guide 10: Daylighting and window design
NFPA (2013b) NFPA 13: Standard for the Installation of (London: SLL)
Sprinkler Systems (Quincy, MA) SLL (2012) SLL Code for Lighting (London: SLL)
NFPA (2013c) NFPA 14: Standard for the Installation of Stephenson DG (1965) ‘Equations for solar heat gain through
Standpipe and Hose Systems (Quincy, MA) windows’ Solar Energy 9 (2) 81–86
NFPA (2013d) NFPA 20: Standard for the Installation of Strahler AN and Strahler AH (1984) Elements of Physical
Stationary Pumps for Fire Protection (Quincy, MA) Geography. New York: John Wiley and Sons.
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
NFPA (2013e) NFPA 24: Standard for the Installation of Private The Building Regulations (2010) Statutory Instruments 2010
Fire Service Mains and Their Appurtenances (Quincy, MA) No. 2214 (London: The Stationery Office)
Thevenard D (2009) ‘Updating the ASHRAE climatic data for
NFPA (2013f) NFPA 72: National Fire Alarm and Signaling
design and standards (RP-1453)’ ASHRAE Research Project,
Code (Quincy, MA)
Final Report (Atlanta, GA: ASHRAE)
NFPA (2014) NFPA 70: National Electrical Code (Quincy, MA) Thevenard D and Haddad K (2006) ‘Ground reflectivity in the
Perez, R, Ineichen P, Seals R, Michalsky J and Stewart R (1990) context of building energy simulation’ Energy and Buildings 38
‘Modeling daylight availability and irradiance components (8) 972–980
from direct and global irradiance’ Solar Energy 44 (5) 271–289 Threlkeld JL (1963) ‘Solar irradiation of surfaces on clear days’
Randel DL, Greenwald TJ, Vonder Haar TH, Stephens GL, ASHRAE Transactions 69 (24)
Ringerud MA and Combs CL (1996) ‘A new global water WMO (2007) ‘The role of climatological normals in a
vapor dataset’ Bulletin of the American Meteorological Society 77 changing climate’ Technical Document 1377 (Geneva: World
1233–1246 Meteorological Organization)
110 References
Buildings for extreme environments: Arid
Appendix 111
Buildings for extreme environments: Arid
112 Appendix
Buildings for extreme environments: Arid
Appendix 113
Buildings for extreme environments: Arid
building fabric 62, 64–65 dedicated outside air system (DOAS) 104
Index building form 59, 62 degree-days 32, 40
building management systems (BMS) 104 dehumidification 66
Note: page numbers in italics refer
building materials see materials design conditions 25, 31
to figures; page numbers in bold building orientation 59, 62 dehumidifying heat pipes 77–78, 104
refer to tables. building reuse 108 demand control ventilation (DCV) 45
buried plant and pipework 67, 73, 84, 87, 89 desalination 70, 103
acoustic considerations 55–58 design approach 100–101
adaptive reuse 108 capacity ratings 51–52 design conditions see climate design
adiabatic screens 69, 79 car parks 97 conditions; internal design
AHUs (air handling units) 75, 76, 77, 79 carbon dioxide refrigerants 81–82 conditions
air cleaners 78–79 CDD (cooling degree-days) 32, 40 diffuse horizontal irradiance 33, 38
air conditioning ceiling void height 60 district cooling systems 70–74, 72, 75
chilled water temperatures 50 certification DOAS (dedicated outside air system) 104
cooling degree-days (CDD) 32, 40 environmental performance 107–108 domestic hot water supplies 89
Licensed copy from CIS: bobseekings, Foremans Ltd, 27/07/2019, Uncontrolled Copy.
cooling design conditions 25, 31 Eurovent 50, 77 domestic water supplies 88–89
outside air rates 45, 46 fire products 95–96 drainage systems 66, 86–87
plant and equipment selection 50–52 No Objection Certificate (NOC) 74 draught-free comfort 44
room air conditioners 60, 83 chilled panels 44 ductwork 78–79
air distribution 77–79 chilled water temperatures 50, 74 floor ducts 85
air exfiltration 52, 62–63 chiller plant leakage 81
air filters 77, 79 capacities 79 maximum velocities 57, 58
air handling units (AHUs) 75, 76, 77, 79 district cooling systems 71 pressure classification 79
air infiltration 52, 62–63 HVAC systems 76 spatial and structural needs 60
control of 66 location 59–60 dust protection 68, 69, 77, 93–94
air inlet temperatures 79, 81 chimneys dynamic thermal modelling 76
air intakes see fresh-air intakes natural draught 84 dynamic thermal performance 65
air mass 36, 52 wind loads 85
air movement 19–20 clear-sky solar irradiance 28, 33, 37–38 earthing 91
air infiltration and exfiltration 52, 62–63 clear-sky solar radiation 33, 36 earthquake zones 67
for comfort 44, 45 climate 7–41 eco-labelling 107–108
convection 43 analysis 11–18 electric batteries 92
stack effect 52, 53 classification 7, 9–11 electrical distribution systems 90–92
air pollutants 85 illuminance levels 20–24 electrical equipment 91
air quality 65–66 microclimate 18–20 electrical loads 92, 104
air ventilation rates 45, 46, 75, 80 various countries 11–12, 111–113 electricity supply 70, 90–91
airtightness see air infiltration climate change 40 elevators 93–94
ammonia refrigerants 81–82 climate design conditions 24–41, 67 emergency lighting 55, 93, 96
angle of incidence (solar) 8, 9, 37 calculation 29–30 emergency plant 57, 91
annual degree-days 40 data sources 28–29 emergency voice alarm (VA) 97
annual design conditions 25, 30, 31–32 design-day data 38–40, 39, 41 energy conservation 103–107
architectural form 59, 62 solar radiation 28, 33–38 energy demand limiting 104
architectural issues 59–60 various locations 111–113 energy management 104
arid climates 10–18, 111–113 CO2 refrigerants 81–82 energy metering 106
atmospheric circulation 8 cold water storage 88–89 energy performance 47–48, 61, 62
atmospheric pollutants 85 comfort, occupants 43–47 benchmarking 99
atmospheric pressure 52 comfort cooling 44–45 energy recovery 48, 75, 76, 104
commissioning 106–107 energy storage 71, 104
bacteria 65 concentrated solar power (CSP) 48, 105 energy tariffs 104
barometric pressure 52 condensate drainage 83 energy transfer stations (ETS) 73
batteries 92 condensate recovery 103 enthalpy design conditions 25, 31
beam normal irradiance 22, 33, 38 condensation 66 environmental conditions see climate design
below ground plant and pipework 67, 73, 84, control 66, 83–84 conditions
87, 89 control systems 90 environmental impacts 101
benchmarking, environmental performance cooled structure 44 environmental performance 99
99 cooling degree-days (CDD) 32, 40 see also energy performance;
BMS (building management systems) 104 cooling design conditions 25, 31 sustainability
boiler feed water 85 cooling loads 47, 80–81 equation of time 33–34, 34
boiler plant 76, 85 breakdown by source 61 equipment
boilerhouses 85 electrical equipment 81, 92 capacity ratings 50–52
boreholes modelling software 76 design data 67–70
surface water disposal 87 cooling systems 76, 102 enclosures 68–69
water supply 87–88 corrosion protection 69, 84 factory acceptance tests (FATs) 69–70
brackish water 82, 85, 101 corrosive environments 67 location 59–60, 77
BREEAM 99, 101 CSP (concentrated solar power) 48, 105 protection from extreme conditions 68,
building adaptation 108 77
building control systems 90 daily design conditions 27–28, 33, 38–40, 39, selection 50–52, 79, 80
building design 59–66 41 spares 68
building envelope 64–66 daylight design 48, 53–54 transportation, storage and assembly 68
building environment 67 DCV (demand control ventilation) 45 see also plant
114 Index
Buildings for extreme environments: Arid
fire alarm and detection systems 96–97 lightning protection 92 solar degradation 67, 69
fire dampers 96 local materials 107 pollution control 85, 86–87
fire hydrants and standpipes 96 luminaires 92–93 precipitation 9, 17–18
fire life safety (FLS) 94–97 pressurisation of building 75–76
fire risk 94–95 MacLeamy curve 100 pressurised water systems 89
fire suppression 96 maintenance of plant 60, 68 primary air units 77–78
flooding 66, 85 manufacturers’ data 50–52 product transparency 107–108
floor ducts 85 materials project management 100–101
FLS (fire life safety) 94–97 certification 107–108 protected stairways 97
flue gases 85 insulating 78, 80 psychrometrics 17, 29, 76
fog 66 plastic 67, 69, 78, 80, 85 public utility services 70
foul water drainage 86–87 sourcing 107–108 pumping stations 90
fresh-air conditioning 75, 76, 77, 78, 104 thermal conductivity 64–65 pumping systems
fresh-air inlet temperatures 79, 81 mean daily temperature range 27–28, 33 boreholes 88
fresh-air intakes 77, 79 metering 106 chiller plant 71
fresh-air ventilation rates 45, 46, 75–76, 80 microclimate 18–20 condensate drainage 83
fuel storage 84, 85 micro-organisms 65–66 electrical reliability 92
fuels 84 modelling software 76 sewage 90
fungi 65 moist-air properties 39–40 PV (photovoltaics) 105
moisture control 65–66
gas oil tanks 84 moisture penetration 66 qanats 101, 102
geothermal energy 105 monthly design conditions 25, 27, 32–33 QSAS 99
glazing 53–54 mosques 48–49
Green Star 99 mould 65 radiant cooling 44
ground-reflected irradiance 38 multiple chiller configurations 47–48, 51 rainfall see precipitation
rainwater drainage 66, 86
handover 106 NABERS 99 recirculation extract systems 76
HDD (heating degree-days) 32, 40 natural gas 84 recycled buildings 108
health and safety natural lighting 53–54 recycled materials 107–108
ammonia refrigerants 81–82 natural ventilation 43, 43, 62 refrigerants 81–82
fire life safety (FLS) 94–97 night purging 43 refrigeration plant 81–84
heat (system) loads 81 No Objection Certificate (NOC) 74 refuge areas 97
heat conduction 43 noise control 55–58 refuse disposal areas 49–50
heat exchangers 73, 74 reheat 76, 78
heat pipes 77–78, 104 occupant comfort 43–47 relative humidity 16–17, 65–66
heat recovery see energy recovery oil fuel 84 for comfort 44, 45
heat rejection 59, 103 oil storage tanks and mains 84 optimum temperatures 45
heating degree-days (HDD) 32, 40 opening penetrations 60, 96 renewable energy 48, 104–106
heating design conditions 30 orientation of building 59, 62 reuse of buildings 108
heating systems 76, 84–85 outdoor comfort 45, 47 roof lights 54
see also HVAC systems outdoor equipment 68 room air conditioners 60, 83
hot water services 89 outdoor lighting 55
hourly design temperatures 39, 39, 41 outside air intakes 77, 79 safety margins 74
humidification 76 outside air rates 45, 46, 75–76, 80 saline environments 67, 69, 84
design conditions 30 oxidation 69 sand protection 69, 77
humidity see relative humidity sand-trap louvres 77, 78, 79
HVAC systems 74–81 parking garages 97 sanitary accommodation 85–86
air distribution 77–79 peak cooling demand 47 seasons 8–9
cooling loads 80–81 Pearl Rating System 99, 101 seismic design 67
hydropower 105 photovoltaics (PV) 105 sewage pumping 90
pipework sewage treatment 89–90
illuminance levels 20–24, 93 corrosion protection 67 shading 18–19, 54, 62, 63, 77, 82
indoor air quality 65–66 district cooling systems 72–73 slope (solar) 35, 37
infrared radiation 22 materials 79–80, 83, 85, 87 smoke control 97
insulating materials 78, 80 noise and vibration control 58 software, modelling 76
Index 115