06-Electrical Installations For Day Procedure Centres
06-Electrical Installations For Day Procedure Centres
1
Outline
2
Electrical Systems in DPC
3
Requirements by CoP for DPC
Electrical Installations are designed and installed to
meet the electrical demand
4
Technical Requirements
Statutory Requirements
Risk
Resilient Maintenance
Management
Design Access
Approach
6
HTM 06-01 –
Electrical System
Infrastructure
Primary Electrical • Supplies from power
Infrastructure
(PEI): companies
Secondary Power
Supply (SPS) • Emergency generators
7
Backup Power Supplies
Secondary Power Supplies Tertiary Power Supplies
(SPS) (TPS)
9
Electrical Systems for DPC in
Existing Buildings
10
Sufficient Spare Capacity?
Existing electrical infrastructure may NOT have
sufficient spare capacity for DPC operation
➔Upgrade system components, e.g. transformers, rising mains,
sub-main conductors and corresponding protective/switching
components
➔Protection scheme and protective components
settings will require review after major alteration
of the system
11
Availability of Emergency Generator?
HBN 10-02:
● Emergency generator providing electricity … should be capable of
providing full (100%) backup … to the exclusion of refrigeration
plant serving air-conditioning and comfort cooling plant.
● If an existing generator is to be used, …, if minimum requirement
cannot be met:
Replace existing generator with a larger set;
Provide an additional generator that can be run in parallel;
or
Provide an additional generator dedicated to the surgical
procedures facility.
12
Application of UPS in DPC
DPC may require UPS of large power (VA)
rating for medical equipment
➔Larger battery size
➔More space for settling UPS
13
Commonly Used UPS
Double- When power loss occurs, the rectifier drops out and batteries keep the power steady
without loss of supply
conversion
(Online) When power is restored, rectifier resumes carrying most of the load and charging
batteries
UPS
Applications: High-risk clinical areas, life-supporting systems, OT lightings, critical
medical equipment, critical medical IT systems, etc.
14
Maintenance for UPS
15
Maintenance for UPS
Not less than
Monthly Quarterly 5-10 yearly
yearly
• System log, • Input and Output • Terminal voltage • Replacement of:
alarm signals and voltage and and internal • capacitors
status indicators current impedance • cooling fans
checking • Load level (%) measurement for
• batteries
• Visual inspection and power each battery cell
• UPS units
• Abnormal noise / • UPS temperature • Battery discharge
heat (using IR • Battery surface and charge-up
(subject to
scanner) temperature test on full load
manufacturer’s
• Ventilation fans (actual / dummy
• AC / DC recommendation)
and filters load)
capacitors
• Harmonic filter surface • Functional test
unit temperature for Automatic
Transfer Switch
• Static and
(ATS)
external
maintenance by-
pass switches
16
UPS Room Condition
Avoid proximity to
wet services
(toilets, water
pipes, etc.)
Temperature and
RH control (air
conditioning)
Ventilation
Spatial clearance
for battery cells
17
Proper Maintenance Record Keeping
18
Battery Monitoring System
19
Other Requirements –
Electricity Ordinance (Cap. 406)
Periodic Inspection, Testing and
Work Completion Certificate (WR1)
Certification (WR2)
20
Summary
Design to
Statutory Effective
Reliable and
Requirements Planning and
Safe Electricity
and Execution of
Supplies
Healthcare Maintenance
Standards
21