You are on page 1of 1

M/s DYNAMIC CABLES LIMITED

V.K.I. AREA, JAIPUR


ACCEPTANCE TEST REPORT AS PER IS 398 Part 2 (1996)

Customer Name :- M/s Tamil Nadu Transmission Corporation Ltd.


PO. No. :- CE/TR/SE/TR-II/EL/A2/T.1975/RCTR.2935/D.674/17, Dt 31.10.2017
Size :- ACSR Panther Conductor
Drum No. C-77 Date of Inspection :- 15.07.2019 & 16.07.2019
Resistance Resistance
Standard Breaking Wrapping
Strands Strands Diameter in ohm per in ohm per
Strandard Conductor Over all Load in on its own Remarks
No. Remarks No. in mm Km. at Km. at
Diameter KN Diameter
33ºC 20ºC
in mm
Lay Ratio Spec. Min.2.97 8 ON
Spec. 6+1 Wire
12 Wire 18 Wire 24 Wire Alu. Std.3.00 1.11 4.079 6 OFF
Steel
Alu. Layer Alu. Layer Layer Max.3.03 (Min.) (Max.) 6 ON
Layer 21.00
Max. 28 16 14
N.A.
Min. 13 10 10
L.R. 15.96 12.12 11.13 N. A. 21.10 12 WIRE ALUMINIUM LAYER
24 WIRE ALUMINIUM LAYER

1 3.00 1.26 3.99 3.793 OK


Resistance Wrapping 2 3.00 1.26 3.96 3.764 OK
Breaking of 100 Cm Resistance on its own Remarks 3 3.00 1.28 4.04 3.840 OK
Strands Diameter
Load in Wire at Lab in ohm per Diameter
No. in mm 4 3.01 1.28 4.15 3.945 OK
KN Temp.in Mili Km. at 20ºC
ohm 5 2.99 1.27 4.01 3.812 OK
6 3.00 1.28 4.08 3.878 OK
Spec. 7 3.00 1.27 4.01 3.812 OK
8 3.01 1.26 4.09 3.888 OK
9 3.00 1.27 4.16 3.954 OK
1 10 2.99 1.27 3.99 3.793 OK
2 11 2.99 1.25 4.19 3.983 OK
3 12 3.00 1.25 4.05 3.850 OK
4
5 18 WIRE ALUMINIUM LAYER
6
7 1 3.00 1.26 4.19 3.983 OK
8 2 3.01 1.27 4.17 3.964 OK
9 3 3.01 1.26 4.16 3.954 OK
10 4 3.00 1.25 4.10 3.897 OK
11 5 2.99 1.27 4.03 3.831 OK
12 6 3.00 1.25 4.15 3.945 OK
13 7 3.00 1.28 4.11 3.907 OK
14 8 3.01 1.26 4.17 3.964 OK
15 9 3.00 1.27 4.18 3.973 OK
16 10 3.01 1.25 4.05 3.850 OK
17 11 3.00 1.25 4.10 3.897 OK
18 12 3.00 1.27 3.93 3.736 OK
19 13 3.00 1.26 4.05 3.850 OK
20 14 3.00 1.26 3.92 3.726 OK
21 15 3.00 1.26 4.08 3.878 OK
22 16 2.99 1.25 4.01 3.812 OK
23 17 3.00 1.28 4.14 3.935 OK
24 18 3.00 1.27 4.09 3.888 OK
ZINC COATED STEEL WIRE
Duclity Test
Wrapping Uniformity Wt. of
Breaking Torsion on Elongation
Strands Diameter 4 X Dia of Zinc Zinc
Load in 100 X D on 200 mm
No. in mm No. Coating Coating
KN Length No. G. Length
Cracks Dips gm/m²
of Twists
8 ON
Max. 3.06
Min. Min. Min.
Spec. Std. 3.00 6 OFF
8.83 16 240
Min. 2.94 6 ON DYNAMIC CABLES LTD. Witnessed by
1 3.00 10.33 25 4.5 OK OK 299
2 3.01 10.67 24 5.5 OK OK 291
3 2.99 10.28 23 5.0 OK OK 288 ( K. Sridharan)
4 2.99 10.46 27 5.0 OK OK 281 Auth Sign. Executive Engineer
5 2.99 10.18 23 4.5 OK OK 288 Inspection/TR-1
6 3.00 10.83 26 5.0 OK OK 295 TANTRANSCO, Chennai
7 3.00 10.75 23 4.5 OK OK 300

You might also like