It is very essential information for parallel operation of transformers and is very interesting
also.
There are four vector groups and each group includes three methods of connection of high
voltage and low voltage windings.
Phase displacement between EMFs of high voltage and low voltage windings is expressed as the
clock hour number and is designated by symbols 0, 6, 1, and 11.
For example, the clock hour number 0 represents zero degrees phase displacement between
primary and secondary EMFs. The clock hour number 6 is for 1800 phase displacement, 1 for –
300, 11 for +300.
On the nameplate of three-phase transformer vector group is printed as Yy0, Dd1 etc. Here
Yy0 will mean it’s both the windings are star-connected and phase displacement between
primary and secondary EMFs is zero degree. It is belonging to Group No.1 (refer to table).
Winding Winding
Group Connection Connection Phase Clock – Hour Vector
No. (Primary) (Secondary) Displacement Number Symbol