You are on page 1of 4

Harmonic Analysis and IEEE 1992 Guidelines

Application Note

New Information Table 1. Harmonic Current Distortion Limits (I h and TDD) in % of IL (≤ 69 kV)
April 2007 ISC/IL Ratio Ih ≤ 11 11 ≤ Ih < 17 17 ≤ Ih < 23 23 ≤ Ih < 35 TDD

<20 4.0 2.0 1.5 0.6 5.0


20 – 50 7.0 3.5 2.5 1.0 8.0
Harmonic Analysis and IEEE 50 – 100 10.0 4.5 4.0 1.5 12.0
100 – 1000 12.0 5.5 5.0 2.0 15.0
1992 Guidelines > 1000 15.0 7.0 6.0 2.5 20.0

IEEE 519-1992 provides guidelines IEEE 519-1992 recommends different For a free computerized harmonic
for applying limits to the level of limits on Individual Harmonics (I h) and analysis of AFD contribution to
harmonic distortion that a utility Total Demand Distortion (TDD), system harmonics or for additional
customer may inject into the power depending on the ISC/IL ratio. ISC is information, contact your local
system. This is a concern, since the short circuit current at the PCC, Cutler-Hammer® sales office. A one-
Adjustable Frequency Drives (AFDs) and IL is the maximum demand load line drawing of the electrical distribu-
can contribute significant harmonic current (fundamental) at the PCC. tion system and specification criteria
distortion to a power system. The More current distortion is allowed at will be required. A harmonic analysis
guidelines pertain to percent harmonic higher ISC/IL ratios, since voltage dis- worksheet for required data is
current and voltage distortion at the tortion decreases as the ratio attached.
point of common coupling (PCC), increases.
which is defined as the point where Any additional harmonic mitigation
the utility connects to multiple The voltage distortion guidelines for equipment requirements will be
customers. IEEE-1992 (at 480V) remain the same determined during the analysis. If
as IEEE 519-1981: there are harmonic constraints during
Although many customers and system AFD operation on a standby generator,
designers interpret the PCC to be at ■ 3% — Special systems (i.e. a separate analysis will be required for
the AFD input or various locations hospitals or universities) the generator, and assumptions on
within the 480V distribution, this is not ■ 5% — General systems load-shedding strategies during
consistent with the intent of IEEE ■ 10% — Dedicated systems (AFDs generator operation should be
guidelines. There are no limits only) provided. Several data runs may be
recommended for individual loads, required to evaluate various harmonic
only for the overall system. Customers The best way to estimate AFD har- mitigation methods. Resultant
and system designers can choose the monic contribution to an electrical sys- recommendations may include 1%,
point of analysis (POA) where they tem is to perform a harmonic analysis 3%, or 5% line reactors, phase-shifting
desire, but it may add substantial based on known system characteris- transformers, filters, or CPX9000 Clean
filtering costs if the POA is tics. An individual AFD may meet the Power.
downstream of the PCC. IEEE guidelines in one system and not
meet the guidelines in another system
Current distortion drawn through an depending on the pre-existing charac-
impedance (transformer, cable teristics of the specific system.
resistance) causes voltage distortion.
The distorted current will also cause Some AFD vendors, upon seeing a
additional heating of the input cables specification requirement for IEEE 519-
and the transformer. Excessive voltage 1992, will simply add a line reactor.
distortion is a concern, since it may This is the wrong approach, since
cause interference with other some systems will not require a line
electronic equipment and additional reactor and others will not benefit suf-
motor heating. ficiently to meet the guidelines (or the
specification).

AP04014002E For more information visit: www.eaton.com


Application Note Harmonic Analysis and
Page 2 Effective: April 2007 IEEE 1992 Guidelines

PCC Possible POAs


(Utility Side) (Customer Side)
Source A Source B MCC-1 MCC-2

AFD AFD
XFMR
AFD ???

??? AFD

Gen
Set ??? ???

??? = Linear Loads for % Current Distortion Dilution

Figure 1. One Line Diagram


Helpful Facts
■ Harmonics are supply system dependent. As the short ■ % current distortion is the same across a transformer.
circuit amps available (SCA) increase, % voltage distortion Voltage distortion percentage is lower on the primary than
decreases, and % current distortion increases. on the secondary, assuming the harmonic loads are on
■ For each PCC or POA analysis required, provide SCA and the secondary.
IL (load current) values for that point. SCAs used must be ■ A harmonic analysis is only as accurate as the
without motor contribution to SCA. assumptions made for the analysis!
■ Current distortion percentages are dependent on overall
system loading. As linear loads (non-harmonic loads such
as AC motors on line power) increase, the percent current
distortion decreases through dilution.

For more information visit: www.eaton.com AP04014002E


Harmonic Analysis and Application Note
IEEE 1992 Guidelines Effective: April 2007 Page 3

Harmonic Analysis Data Worksheet


(Use separate sheets if necessary. Provide a 1-line drawing or sketch.)

Customer/Project Name as it should appear on analysis GO # or Negotiation #

Specification Requirements:

IEEE519-1981 (Voltage Only) Voltage Distortion:


IEEE519-1992 (Most Recentt) 3% (Special) 5% (General) 10% (Dedicated)
Other Requirements:

PCC and POA (Point of Analysis) Information:


(Show equipment and analysis points on 1-Line Diagram)

Location Voltage Maximum Load Current (IL) Short Circuit Amps (SCA) 
(All Loads) (Not including motor contribution)

PCC

POA #1

POA #2
 If SCA (without motor contribution) is not provided, infinite SCA will be assumed on primary of distribution transformer. This will result in lower calcu-
lated voltage distortion and higher calculated current distortion on the transformer secondary.

Distribution Transformer(s) Data: Generator Data:


kVA Impedance X/R Ratio kW kVA Volts X"d IL (amps)

#1 #1

#2 #2

Tie Breakers Normally Open Describe load-shedding scheme for generator operation in
Tie Breakers Normally Closed “AFD Data” below.

AFD Data:
AFD Type (SVX9000, Quantity Operated Desired, existing or specified line reactor or
hp Clean Power, etc.) on Line / Generator isolation transformer (none, 1% / 3% / 5%)

AP04014002E For more information visit: www.eaton.com


Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN CARE (877-386-2273)
Eaton.com

© 2007 Eaton Corporation


All Rights Reserved
Printed in USA
Publication No. AP04014002E/CPG
April 2007

You might also like