Professional Documents
Culture Documents
net/publication/265877511
CITATIONS READS
7 2,090
3 authors:
Toader Munteanu
Universitatea Dunarea de Jos Galati
33 PUBLICATIONS 55 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
KNOWLEDGE TRANSFER REGARDING THE ENERGY EFFICIENCY GROWTH AND INTELLIGENT POWER SYSTEMS View project
All content following this page was uploaded by Gurguiatu Gelu on 04 March 2015.
va ia iLa va
vb ib iLb vb
Microgrid vc ic iLc vc
Non-linear
vN iN iLN vN Loads
ifN ifc ifb ifa
L
IDC
VDC
C1
Main Renewable vN vc va
vb
Grid Energy
Sources C2
where: PCC. Consequently, the control strategy for the APC has
ifa, ifb, ifc are phase APC currents and ifN is the APC neutral to be designed in order to ensure a sinusoidal wave for the
current. grid current (ix):
Therefore, the total DC voltage will oscillate not only at ~
the switching frequency but also at the corresponding ilx1 + ilxk + ilxq + i1fx + i fx =
ix (5)
frequency of the neutral current. As shown in [2], if the
The APC switches generate undesirable current
current control is made by hysteresis, the above
mentioned drawback can be limited with a dynamic offset harmonics around the switching frequency and its
level added to both limits of the hysteresis band. multiples. Considering the switching frequency of the
APC sufficiently high, these undesirable current
For the investigated topology presented in Fig. 2, the harmonics can be filtered with the LR passive filter.
current at (PCC) is:
ix= ilx + i fx (2) 3. Control of APC
where: A. Control Strategy
ix, ilx, ifx are the microgrid side current, the load current, There are many ways to design a control algorithm for an
and the APC current respectively. The x index points the APC [7]. Generally, the controller design is made
a, b and c current phases. considering that the grid voltage at the PCC is balanced. In
a microgrid, the supply voltage itself can be distorted
The instantaneous load current is: and/or unbalanced. Consequently, the controller of an
APC used to improve the power quality in the microgrid
ilx =ilx1 + ilxk + ilxq (3)
has to be designed according to the weakness of this kind
where: of grid.
- i1lx the fundamental active current component; The proposed control algorithm is a compensation
method that makes the APC compensate the current of a
- ilxk the addition of current harmonics; non-linear load by forcing the microgrid side current to
- ilxq the reactive current component. become sinusoidal and balanced (Fig. 3). The controller
requires the three-phase grid current (ia, ib, ic), the three-
The three-phase APC current is given by: phase voltage at the Pcc (va, vb, vc) and the DC-link
~ voltage (VDC). As shown in Fig. 3, the sinusoidal
i fx= i1fx + i fx (4) waveform and the phase of the grid current reference
i1
- the fundamental conditioner current component; (ia*, ib*, ic*) comes from the line voltage thanks to a
fx
~
PLL. The magnitude of the same current is obtained by
i fx - the deforming component of the current. passing the error signal (ε) between the DC-link voltage
*
As shown in Fig. 2 the current drawn from the grid has to ( VDC ) and a reference voltage ( VDC ) through a PI
be sinusoidal and moreover, in phase with the voltage at controller.
ia va ila
ib vb ilb
Microgrid ic vc ilc
iN vN iN
Non-linear loads
sin(wt-4π/3) ifc ifb ifa iN
PLL vc
sin(wt-2π/3) vb
va
sin(wt)
ia
ia* -
+ IGBT Active
ib Power Filter
ib* -
+
ic* i-a
+
PI
ε -
+ VDC
Renewable
V*DC Energy
Control strategy
Figure 3. APC control strategy
Using this magnitude and phase displacement of 120° investigated active power conditioner has been simulated
and 240° respectively, the reference three-phase grid with six IGBTs controlled by the system illustrated in
currents ia* , ib* and ic* can be expressed as: Fig.3. All the parameters are shown in Table 1.
ia*= ε ⋅ sin (ωt ) (6) Table 1: Parameters of the APC
Parameters Value
2π
ε ⋅ sin ωt −
ib* = (7) AC voltage vabc [V] 230
3
DC-link voltage (VDC) [V] 750
4π
ε ⋅ sin ωt −
ic* = (8) Inductor (L) [mH] 3,3
3
Capacitor (C) [µF] 20000
B. Switching control
Hysteresis Band [A] 0.5
As shown in Fig. 3, the hysteresis control has been used
to keep the controlled current inside a defined band The simulation results are grouped and presented
around the references. The status of the switches is according to the following power quality indicators: THD
determined according to the error. When the current is (Total Harmonic Distortion), power factor.
increasing and the error exceeds a certain positive value,
the status of the switches changes and the current begins A. The current and voltages in PCC
to decrease until the error reaches a certain negative The light energy from the sun can be converted in
value. Then, the switches status changes again. electrical energy using photovoltaic panels. This energy
Compared with linear controllers, the non-linear ones can be added to grid by the APC. Also other renewable
based on hysteresis strategies allow faster dynamic sources can be added in DC BUS to inject energy in Pcc.
response and better robustness with respect to the In Fig. 4 are presented: iS – the current from the grid
variation of the non-linear load. A drawback of the which is decreasing at t=0.1s when the renewable source
hysteresis strategies is the switching frequency which is is starting to inject current; iL – is the load current which
not constant and can generate a large side harmonics have no variations; if – is the current through APC which
band around the switching frequency. at t=0.1s is increasing. This means that the current from
To avoid this drawback, the switching frequency can be the renewable source is added to grid current; v – is the
fixed using different solutions like variable hysteresis voltage in PCC.
bandwidth or modulated hysteresis. But this is not the B. The current and voltages in PCC when is used a
object of this paper. non-linear load
In Figure 5 are presented the current variations in Pcc
when the renewable source inject the current at t=0.1s
4. Simulation Results and the load is a nonlinear one: iS – the current from the
grid which is decreasing at t=0.1s when the renewable
To validate the proposed control algorithm, many source is starting to inject current; iL – is the load current
simulations have been run in various operating conditions which have no variations but is a non-sinusoidal current;
using Matlab, SimPowerSystems toolbox. The if – is the current through APC which at t=0.1s is
increasing which mean that the current from the
renewable source is added to grid current; v – is the 500 15
vLa [V]
iLa [A]
0 0
It can be seen that the energy from the renewable source is -7.5
used and in the same time the power quality indicators can -500
0.06 0.08 0.1 0.12 0.14
-15
0.16
be improved. 500 15
7.5
vSa [V]
[A]
0 0
sa
20
i
-7.5
10
[A]
-500 -15
0.06 0.08 0.1 0.12 0.14 0.16
S-abc
-10 500 10
i
-20
0.06 0.08 0.1 0.12 0.14 0.16
vFa [V]
[A]
0 0
Fa
20
i
10
iL-abc [A]
-500 -10
0
0.06 0.08 0.1 0.12 0.14 0.16
-10 400
-20 200 v
0.06 0.08 0.1 0.12 0.14 0.16 a
vSabc
0 v
b
20 v
-200 c
10
if-abc [A]
-400
0.06 0.08 0.1 0.12 0.14 0.16
0
time [s]
-10
-20
0.06 0.08 0.1 0.12 0.14 0.16
Figure 6. Currents and voltage in the PCC during
400
200
power factor correction
vabc [V]
0 4. Conclusion
-200
-400
0.06 0.08 0.1
time [s]
0.12 0.14 0.16 The active power conditioner presented is capable to use
energy from a renewable source and in the same time to
improve the power quality indicators on grid.
Figure 4. Currents and voltage in PCC The load feed by the microgrid is not affected in voltage
level.
12 The limitation for the proposed solutions is regarding the
ia ib ic
6
in
switching frequency.
iS-abc [A]
-6
This APC can be used in a microgrid where there are
-12
interconnections between renewable sources and grid.
0.06 0.08 0.1 0.12 0.14 0.16
12
6 ia ib ic References
iL-abc [A]
in
0
-6
-12
[1] H. Ibrahim, A. Ilinca and J. Perron, “Energy Storage
0.06 0.08 0.1 0.12 0.14 0.16
Systems – Characteristics and Comparisons,” Elsevier
12
ia ib ic
Renewable & Sustainable Energy Reviews, Vol. 12, pp.
6
in 1221-1250, 2008.
[A]
0
[2] M. Abdusalama, P. Poureb, S. Karimia and S. Saadatea
f-abc
-6
-12
0.06 0.08 0.1 0.12 0.14 0.16 power filter under distorted voltage conditions,” Electric
400
va
Power Systems Research, vol. 79, pp 759-765, May 2009.
vb vc
200 [3] M.Montero, E.R. Cadaval, F. Gonzalez, “Comparison of
[V]
-200
-400
0.06 0.08 0.1 0.12 0.14 0.16
Electronics, vol. 22, pp. 229–236, January 2007.
time [s]
[4] B. Singh, K. Al-Haddad, A. Chandra “A Review of Active
Filters for Power Quality Improvement” IEEE
Figure 5. Currents and voltage in the PCC during Transactions on Power Electronics, vol. 46, pp. 960-971,
October 1999.
harmonics compensation test
[5] J. Chen, F. Liu , S. Mei, “Nonlinear disturbance
attenuation control for four-leg active power filter based
C. The current and Voltages in PCC when is used a on voltage source inverter,” Journal of Control Theory and
load with a low power factor Applications vol. 3 pp. 261–266, August 2006.
In Figure 6 there are presented simulations results when [6] M. Ucara and E. Ozdemir “Control of a 3-phase 4-leg
active power filter under non-ideal mains voltage
it is simulated a load with a natural PF of 0,69. condition,” Electric Power Systems Research, vol. 78, pp.
It can observed the load voltage and current for phase a 58-73, January 2008.
(vLa; iLa), the grid voltage and current for phase a (vSa; [7] A. Zhikang, S. Wenji Z. Ruixiang and F. Chunming Tu
iSa); the APC current and voltage (vFa; iFa) and the “Development of Hybrid Active Power Filter Based on the
voltage in Pcc (va, vb, vc). Adaptive Fuzzy Dividing Frequency-Control Method,”
IEEE Transactions on Power Delivery, vol. 24, pp. 424 –
Using the energy from renewable source the amplitude of 432, January 2009.
grid current is reduced and the power factor is increased.