You are on page 1of 7

Dolphin Selection Package 19.

Customer Technical Offer


Customer For Quotes Pump Size / Stages TD12F / 1
Item number 001 Pump speed 2950 rpm
Customer enquiry 1100 gpm - 150 psi Quote number 319880

Pumpset
Qty Description
1 TD12F - 1100 USgpm @ 150 psi
Order Type
Order Details
Order For: Pumpset
Lead Time: Standard Lead Time
Site Details
Site Mains voltage (for motor/ controllers/ Engine instrumentation): 380V / 50 or 60Hz
Auxillary site Voltage (for Jockey pump / controller): 3 Phase / 50 Hz / 380-415V
Site Suction pressure: Enter Suction pressure here (Mandatory for order processing): 0.00 psi.g
Start-up: Startup
HazMat Certification: Not Required
Pump
Materials of Construction
Design: Standard MOC (Material of Construction Code)
Material Code: All Iron with Bronze Impeller
Pump casing material: Cast Iron (ASTM A48 Class 40 #)
Impeller material: Bronze (ASTMB 584 - C90500 #)
Shaft material: High Tensile Steel (BS970 080 M46)
Casing ring material: Leaded Gunmetal (BS1400 LG2-C)
Shaft sleeve material: Bronze (ASTMB 584 - C90500 #)
Construction Options
Impeller Trimming: Required
Flange Drilling (Suc & Del)
Suction Flange Drilling: ANSI B16.1 CL250lb (FF)
Delivery Flange Drilling: ANSI B 16.1 Cl 250 (FF)
Tapping type: NPT Tapping
Sealing arrangement: Gland Packing (Standard)
Stuffing box sealing / flushing: Internal Seal/Flushing with External pipe (Standard)
Direction of rotation: Clockwise (Standard)
Driver
Driver Type
Driver Selection: Diesel Engine
Emmisssion Level: Any
Engine options (Catalog)
Engine manufacturer: Clarke
Battery Voltage: 12 V
Engine Cooling Method: Heat Exchanger Cooled
Engine Derate based on Site Conditions
Site altitude as entered on condtions of service page: 0.00 ft
The resulting derate factor for engine is 1
The rated power of selected engine (175HP) is now derated to 175HP
Engine performance is not adjusted for altitude and temperature, please make sure that you enter site altitude on "Conditions of service
page"
Diesel Engine: Engine-Clarke, T1, JU6H-UF34, 3000rpm, 175 HP, FM/UL,HE with baseplate, guard, drive shaft,batteries, rack and cables
Engine Cooling Loop: Cooling Loop Std 250 PSI HSC, 1"
Silencer: Residential Silencer, 5 inch
Coupling
Coupling details
Drive Shaft: Drive Shaft - (CDS20-S1)
BasePlate
Baseplate Type
Baseplate Options
Coupling guard: Non-Sparking Guard

Fitflow Supplies · · ,
Phone: · fax: Page 1 of 7
Dolphin Selection Package 19.0

Pumpset
Qty Description
Engine Baseplate Type: Single Baseplate
Single Baseplate - Diesel Engine: HSC / ES Baseplate
Accessories
Accessories menu
Pump Gasket Kit (A-GK-060-3): Gasket Kit for Pump Flanges
Fuel Tank
Fuel Tank Fittings: UL142 Fittings
Gauges
Delivery side Pressure gauge
Pressure Gauge selected (GGDEL300NGLY1111): 4" Pump Discharge Gauge 0-300 PSI, 1/4" NPT
Suction side Pressure gauge
Compound Gauge selected (GGSUC300NGLY1111): 4" Pump Suction Gauge 30-0-300 PSI, 1/4" NPT
Testing / Painting / Freight and Packing / Enginneering / Documentation
Documentation and Tests
Painting selection
Painting selection: Standard Painting

Pump
Qty Description
1 Order Type
Order Details
------------ Important --------------: Please note that we will discontinue using Grundfos Jockey pumps starting 11th March 2019. We will be
offering SPP Inc Jockey Pumps (EVMSU series) starting monday. Size cross references are available with applications team. This will not
affect processed orders as of 8 th March 2019.

Main Fire Pump Controller


Qty Description
1 Driver
Driver Type
Engine options (Catalog)
Operating (Instrumentation) voltage: 220-240V Preheater
Accessories
Accessories menu
Control Panel
Make: Torna Tech
Controller Enclosure (Cabinet): Nema 2 Standard
Frequency: 50Hz
Operating (Instrumentation) voltage: 220-240V Preheater
Space Heater (Anti condensation Device): None
Nameplate / Labels Language: English Labels (Standard)
Controller: EngCtlr-GPD-12VDC-220VAC-50HZ-ENG

Battery Total
Qty Description
1 Accessories
Accessories menu
Battery
Battery: Battery Kit - 12 V

Fuel Tank Total


Qty Description
1 Accessories
Accessories menu
Fuel Tank
Fuel Tank Type
Single Wall
Fuel Tank: Fuel Tank, 225 GAL, SINGLE Walled with UL142 Fittings
Fitflow Supplies · · ,
Phone: · fax: Page 2 of 7
Dolphin Selection Package 19.0

Jockey Pump
Qty Description
1 Accessories
Accessories menu
Jockey Pump and / or Controller {)
Enter the duty parameters for jockey pump
Select the desired duty flow (usgpm): 15
Enter the desired Head (psi)160: 160
Jockey Pump / Controller Frequency: 50 Hz
Jockey Pump: Special Jockey Pump
Jockey Pump Gasket Kit(JPFLANGEKIT-1-1/4): 1-1/4" class 250 jockey pump flange kit

Jockey Pump Controller


Qty Description
1 Accessories
Accessories menu
Jockey Pump and / or Controller {)
Jockey Pump Controller ()
Jockey Controller Make: Any
Jockey Controller Voltage: 380 V
Jockey PumpController Enclosure: Nema 2
Jockey Controller Labels: English
Jockey Pump Controller: Special Jockey Pump Starter

Flow Meter
Qty Description
1 Accessories
Accessories menu
Flow Meter Details (F710001111111111)
Flow Meter Option
Flow Meter End: Grooved
Flow Meter Size: Flometer-6Inch dia, 1000 gpm, Grooved

Main Pressure Relief Valve


Qty Description
1 Accessories
Accessories menu
Main Pressure Relief Valve (MPRV4300150UL00111)
Main Pressure Relief Valve Size: 4" #300x150 Flanged Main Relief Valve UL

Waste Cone
Qty Description
1 Accessories
Accessories menu
Waste Cone ()
Waste cone: 4" x 8" Enclosed Waste Cone - Cla-Val

Tests and Documentation


Qty Description
1 Testing / Painting / Freight and Packing / Enginneering / Documentation
Documentation and Tests
Hydro Test: Non-Witness Hydrotest
Fix Speed Performance Test: Non-Witness Fixed Speed Performance

Freight
Qty Description
1 Freight: Freight
Fitflow Supplies · · ,
Phone: · fax: Page 3 of 7
Dolphin Selection Package 19.0

Taper Spool Pieces


Qty Description
1 End Type: Flanged
Flange Rating: CL 125 X CL 250
Eccentric Suction Reducer: Ecc Suc Reducer, 8"x6", #125x250
End Type: Grooved
Flange Rating: CL 250 X Grooved
Concentric Discharge Increaser: Con Dis Increaser, 5"x6", 250xGrooved

Tests and Documentation


Qty Description
Standard Documents for UL/FM fire pumps
1 Certified pump performance curve and test report

Fitflow Supplies · · ,
Phone: · fax: Page 4 of 7
Fitflow Supplies

Pump Performance Datasheet


Customer : For Quotes Quote number : 319880
Customer enquiry : 1100 gpm - 150 psi Pump Size : TD12F
Item number : 001 Stages :1
Usage - Tertiary : Based on curve number : TD12F-FMT-C2950 Rev 1G-A1
Quantity :1 Date last saved : 17 Apr 2019 12:18 PM
Operating Conditions Liquid
Flow, rated : 1,100.0 USgpm Liquid Type/ Application : Water
Differential Head (requested) : 150 psi Additional liquid description :
Suction pressure, rated / max : 0.00 / 0.00 psi.g Temperature, max : 68.00 deg F
NPSH available, rated : Ample Fluid density, rated / max : 1.000 / 1.000 SG
Frequency : 50 Hz Viscosity, rated : 1.00 cP
NFPA Limits Performance
Flow, rated : 1,000.0 USgpm Speed, rated : 2950 rpm
Head, rated : 154 psi Impeller diameter, rated (approx.) : 12.01 in
Power, rated : 122 hp Impeller diameter, maximum : 12.13 in
NPSHr, rated : 8.40 ft Impeller diameter, minimum : 9.06 in
Efficiency, rated : 74 % Efficiency : 76 %
Flow at 150% : 1,500.0 USgpm NPSH required / margin required : 8.98 / 1.64 ft
Head at 150%, actual/limit : 134 psi Head, maximum, rated diameter : 177 psi
Efficiency at 150% : 81 % (approx.)
NPSHr at 150% flow : 12.29 ft Diameter ratio (rated / max) : 99.03 %
Power required at 150% flow : 145 hp Driver & Power Data (@Max density)
Peak power : 153 hp Power, hydraulic : 96.24 hp
Closed valve pressure : 176.9 psi.g Power, rated : 127 hp
140% Head at shutoff : 215 psi Power, maximum, rated diameter : 153 hp
65% Head at 150% flow : 100 psi Material
Cooling flow (None) : 0.00 USgpm Material selected : CI / Br / CS (Standard)
Pressure Data Selection status
Maximum working pressure : 176.9 psi.g FM/UL/cUL approved : FM/UL/cUL
Maximum allowable working pressure : 224.8 psi.g Near miss reasons :
Maximum allowable suction pressure : 72.52 psi.g
Hydrostatic test pressure : 212.3 psi.g
200
Power - hp

150 Power
100

50

250 100

225 90

200 80

175 70
Efficiency - %

12.01 in
Head - psi

150 Efficiency 60

125 50

100 40

75 30

50 20

25 10

0 0
NPSHr - ft

80
NPSHr
40

0
0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400 2,600 2,800 3,000
Flow - USgpm

Fitflow Supplies · · ,
Phone: Page 5 of 7
Version: 19.0
Fitflow Supplies

Pump Performance Datasheet


Customer : For Quotes Quote number : 319880
Customer enquiry : 1100 gpm - 150 psi Pump Size : TD12F
Item number : 001 Stages :1
Usage - Tertiary : Based on curve number : TD12F-FMT-C2950 Rev 1G-A1
Quantity :1 Date last saved : 17 Apr 2019 12:18 PM
Operating Conditions Liquid
Flow, rated : 1,100.0 USgpm Liquid Type/ Application : Water
Differential Head (requested) : 150 psi Additional liquid description :
Suction pressure, rated / max : 0.00 / 0.00 psi.g Temperature, max : 68.00 deg F
NPSH available, rated : Ample Fluid density, rated / max : 1.000 / 1.000 SG
Frequency : 50 Hz Viscosity, rated : 1.00 cP
Flow Head Pump Efficiency Power Required NPSH required
(USgpm) (psi) (%) (hp) (ft)
0.00 177 0 69.85 1.26
332.0 171 39 84.34 6.35
663.9 164 62 102 7.34
995.9 154 74 121 8.38
1,327.9 141 79 138 10.68
1,659.8 126 82 149 13.95
1,991.8 107 82 153 18.79
2,323.8 85 76 151 30.32
2,655.7 58 61 146 59.05

Fitflow Supplies · · ,
Phone: Page 6 of 7
Version: 19.0
1 2 3 4 5 6 7 8 9 10 11

C1.00 X 2.00 BASE EXTENSION FOR


1.00" SLOT 6X CONTROLLER (OPTIONAL)
A A
1 Raw Water-Inlet 1" NPTF

2 Heater Junction Box HEATER VOLTAGE REQUIREMENTS:


115 VAC 1500 WATT, 230 VAC OPTIONAL
(Flexible Hose)
15"
3 Fuel Return Conn. (Shipped Loose)
3/8" NPTF Farside
4.90"
(Flexible Hose) 32"
4 Fuel Supply Conn. (Shipped Loose)
1/2" NPTF Farside

B 5 Raw Water-Outlet 1 1/4" NPT B

6 Flexible Exhaust Outlet 5" Class 150 Flanged


Conn.
7 Drive Shaft CDS20-S1
5.00" 39" 39" 5.00"
88" 25.00"
C C

63.63"
58.44"
41.25"
6

D D

M ANUAL RUN
TO START ENGINE
1.Position MODE SELECTOR switch to MANUAL RUN.
2.Lift and hold MANUAL CRANK #1 until engine starts, or release

5
after 15 seconds. If unit fails to start, wait for 15 seconds,
use MANUAL CRANK #2 and repeat step.
3.If COOLING WATER is not flowing or engine TEMPERATURE is too HIGH,
open cooling system manual by-pass valve.
AUT O M AT IC
OR
M ANUAL ST O P
TO STOP ENGINE
1.Return MODE SELECTOR switch to AUTOMATIC and MANUAL STOP position,
engine will stop.
2.Close cooling system manual by-pass valve.
IMPORTANT
DO NOT leave the MODE SELECTOR switch in the MANUAL RUN position
during AUTOMATIC operation. (The controller will be unable to stop
the engine and DAMAGE MAY RESULT)

00009 46 OVERSPEED RESET


M O DE SEL ECT O R NO T 1.After problem has been corrected, reset the speed sensing device by
IN AUT O M AT IC lifting the OVERSPEED RESET.
ENG INE W IL L
NO T ST O P
TACH/HOUR METER

35.44" OIL PRESSURE VOLTS VOLTS WATER TEMPERATURE 46.18"

E 19.69" FUEL PUMP


CENTERLINE
E
13.19" 11.42"
7 24.25"

0.35 ± 0.10 14.62"


SEE NOTE 1

6.89"
F 13.39" 12.06" F
6" SUCTION 5" DISCHARGE 21.00"
1

6" CHANNEL

12.51" 2 3 4
10.31"
23.75"
G APPROX. EQUIPMENT WT. [LBS.] G
25.77"
3274 27.77"

NOTES:
DRN : MFH 06/8/12
1) THE DRIVESHAFT IS DESIGNED TO OPERATE AT A 2) FLANGE DRILLING AS PER ANSI B16.1 CLASS 250 FF. PUMP MODEL: TD12F
2° ANGLE WITH THE INPUT AND OUTPUT SHAFTS APP'D : RLM 06/8/12
IN PARALLEL. THE ENGINE CRANKSHAFT 3) ALL DIMENSIONS IN INCHES. ENGINE MODEL: JU6H-UF34
DRAWN SCALE : N/A
IS TO BE SET WITH A PARALLEL OFFSET OF 4) BASE MUST BE COMPLETELY FILLED WITH GROUT PER NFPA 20.
H 0.35±0.10 INCHES VERTICALLY ABOVE DIESEL DRIVEN HORIZONTAL SPLIT CASE
H
THE PUMP SHAFT AND 0.00±0.10 INCHES PARALLEL 5) PUMP IS CW (CLOCKWISE) ROTATION WHEN VIEWED FROM SPP PUMPS LP FIRE PUMP SET
OFFSET HORIZONTALLY RIGHT OR LEFT OF THE COUPLING END. 6716 BEST FRIEND ROAD
THE PUMP SHAFT. REFER TO THE ENGINE MANUAL NORCROSS, GA. 30071
SHOP ORDER
NUMBER
BORDER
SIZE A2
FOR ALIGNMENT. (770)409-3280 DRAWING
NUMBER TD12F - JU6H-UF34 SHEET 1 OF 1

Page 7 of 7