Installation location: Not for installation in U.S. or U.S.
territories
Manufacturer: Clarke
1.0 1 Model: JU6H-UF52
Listing: UL/FM
Rated Speed: 2600 rpm
Rated Horsepower: 210 hp
Pump room ambient temp: 32 °F
Installation altitude: 0 ft
Engine derated horsepower: 210 hp
Battery system: Cables, rack and batteries
Battery voltage: 12V Battery System
Exhaust system: Silencer and flexible connection
Exhaust muffler size: 5 in Flanged 150lb
Fuel system: Fuel tank with flame arrestor and fittings
Fuel tank type: Single Wall
Fuel tank size: 240 US Gallon
Type of cooling system: Heat exchanger
FM approved cooling loop: Installed on engine as per
NFPA
Block heater power rating: 115V/1/60
Options:
Testing: Non-Witnessed Certified Fire Pump
Performance Test
Pump Suction Orientation: Right
Single Wall: 240 US Gallon
Shaft and Sleeve: Standard
Page 1 of 4
Quote Reference: SQJST000215_1
Quote Name: 150@151-D
Project Name:
Date: 2022-03-17
Controller options:
Enclosure Rating: NEMA 2 - Standard Enclosure
Language: STD - English
D34A - Rated for 55C Ambient Temperature
D32A - Modbus TCP/IP provision - Standard
Export Crating: Not Required - Customer Supplied
Shipping Container
Accessories Details:
MRV and Waste Cones:
MRV and WC rated flow: 1500 USgpm
MRV Max Working Pressure: 177.2 Psi
MRV Flange Rating: 300lb
MRV Size: 6 inch Angle (std)
MRV Part Number: D975050-212
MRV Quantity: 1
Reducers:
Eccentric part number: D957118-304
Eccentric flange rating: 150/150Lb ANSI
Eccentric size: 8 x 6
Page 2 of 4
Quote Reference: SQJST000215_1
Quote Name: 150@151-D
Project Name:
Date: 2022-03-17
Freight $0.00
Tax $0.00
Page 3 of 4
Quote Reference: SQJST000215_1
Quote Name: 150@151-D
Project Name:
Date: 2022-03-17
Commercial Notes:
Packing:
Guayaquil
Other Terms: According to Armstrong Standard Terms and Conditions of Sale ruling at the date of
order.
Seller reserves the right to adjust price and delivery time exceeding the 30 days
Quotation validity.
Storage: If, for any reason, the buyer is not able to take delivery at the place of delivery on
the agreed delivery date, then either i) the buyer shall take delivery at an alternative
place and bear any additional costs of shipping; or ii) Armstrong will arrange
shipment into storage on the buyer’s behalf, with all costs borne by the buyer. In
any event the warranty period shall become effective from the agreed delivery date.
Page 4 of 4
Submittal Ref. #: SQJST000215_1
PROJECT DETAILS
Tag Num: DRUET Qty: 1
Service: Location: GUAYAQUIL
100
80
Eff
Eff (%)
60
40
20
ACCESSORIES
Exhaust system (Silencer and Flexible connection)
FM Approved Cooling Loop installed on engine per NFPA20
Fuel system (Fuel Tank with flame arrestor and fittings)
LIST OF MATERIALS
ITEM DESCRIPTION ITEM DESCRIPTION
1* FLAME ARRESTER 8* CHECK VALVE
2 VENT PIPE 9* MANUAL VALVE (NOTE 1)
3* FILL CAP 10* DRAIN PLUG – 1” NPT (NOTE 2)
4 FILL PIPE 11* FUEL TANK
5 FUEL LEVEL SWITCH 12* TANK SUPPORT
6* LEVEL GAUGE 13* TANK WHISTLE
7 FUEL LINE 14 1¼" VENT PIPE
Flexible Connector
Controller Details
Manufacturer Tornatech
Model Number GPD-12-120
Control Panel Type Diesel
Power Rating 115/1/60
Approvals UL/FM
The submittal drawings for Tornatech controller model # GPD-12-120 can be found on their web page, see the
link below:
https://www.tornatech.com/
Dimensional data
Reducer Increaser
A(inch) 13.5 A(inch) 15
B(inch) 1
Supply and install as indicated on plans one (1) fire pump system consisting of:
1. FIRE PUMP
One Armstrong, SERIES 4600F, Size 6x5x15F double suction horizontal split case fire pump listed by UL/FM having a capacity
of 1500 usgpm for a pressure boost of 151 psi. Suction pressure 1 psi.
Pump casing shall be cast iron, axially split with a 15-degree angle that will minimize NPSH requirements and dimensions. Lower
half shall contain suction and discharge nozzles. Suction and discharge connections shall be on the same elevation. Top half
and rotating element shall be removable without disturbing the piping. Casing shall be fitted with replaceable bronze wearing
rings. Impeller shall be bronze, double suction, enclosed type fully balanced and keyed to an alloy steel shaft. Shaft shall be
fitted with replaceable bronze sleeves. Shaft shall be mounted in two dust tight deep grooves, sealed, and permanently greased
ball bearings.
Bearings shall be mounted in a cartridge type housing so that they shall be replaceable without opening pump casing. Bearings
shall be removable without the need of special tools or bearing puller only by rotating the bearing removal nut.
Each stuffing box shall be fitted with a three-piece bronze split gland. Stuffing box shall be fitted with an extension to facilitate
the packing rings removal. Packing rings shall be removable without disturbing wetted parts or the pump bearings. Water seal
rings made from non-corroding material shall be piped to pump volute.
2. DIESEL ENGINE
The fire pump shall be direct connected through flexible coupling to a diesel engine, manufactured by Clarke, model JU6H-UF52
UL/FM listed and approved with a net continuous rating of 210 hp at 2600 rpm, 0 ft of elevation above sea level. The diesel
engine shall conform to the requirements of the National Fire Protection Association, Pamphlet #20 and shall be specifically
approved for fire pump service. It shall operate at a rated speed not exceeding the above RPM and shall develop sufficient
horsepower to drive the pump with reserve power.
The cooling water supply for the heat exchanger shall be from the discharge of the pump, taken off prior to the pump discharge
valve. An FM Approved cooling loop to be installed on the engine, per NFPA 20.
B. STORAGE BATTERIES
One set of dual heavy-duty lead acid batteries shall be provided and furnished in a dry charge condition with electrolyte liquid
in separate containers. Suitable battery rack and 60" of battery cables shall be included.
3. FUEL SYSTEM
The fuel system shall include an above ground storage tank, tested and approved to UL 142 and/or ULC S601-07, with a capacity
of 240 US Gallon to meet the recommended sizing per NFPA20 - Fuel supply tanks shall have a capacity at least equal to 1 gal
per HP, plus 5% volume for expansion and 5% volume for sump. The system shall consist of, fill pipe, lockable fill cap, fuel level
gauge, flame arrester, supply line manual cock, return line check valve, drain plug, and tank whistle. Legs for floor mounting,
approved seamless copper tubing, and miscellaneous pipe and fittings shall be supplied by the mechanical contractor.
Fire pump will be hydrostatically tested to a pressure recommended by UL/FM. The fire pump shall be subjected to a performance
test at rated speed. The pump shall furnish not less than 150% of rated capacity at a pressure not less than 65% of rated head.
The shut-off head shall not exceed 140% of rated head. A certified test curve shall be supplied with the pump.
The fire pump manufacturer shall furnish a diesel engine fire pump controller model: GPD-12-120 as manufactured by Tornatech.
The controller shall be UL/FM.
The fire pump controller shall meet the requirements per NFPA20 and shall incorporate the following components:
Two independently functional battery chargers, each having its own power transformer rated for a maximum continuous charge
current of 10 amperes. The charger shall be of solid-state electronic design with a semi-conductor type rectifier, and shall include
the following supervisory and safety features:
a) Current limiting in every charging mode
b) Over-current shut-off
c) Automatic selection of bulk or float charge by battery voltage sensing
d) Lower than 0.5 ampere trickle charge
e) Reverse voltage shut-off
f) Dead cell detection
g) Over and under voltage alarm
h) Charger initiated battery failure alarm with signaling to prevent the use of the defective battery during the engine cranking
(starting) cycle.
All relays shall be equipped with manual test buttons and 'ON' - 'OFF' status indicators and terminal block to indicate the following
engine conditions:
a) Two SPDT contacts for engine running condition
b) One NO/NC contact when the main switch is in the 'AUTO' position
c) One NO/NC contact when the main switch is in the 'MANUAL' or 'OFF' position
d) One SPDT contact indicating engine trouble. The engine trouble condition shall be indicated on engine overspeed, engine
failure to start, low oil pressure, and high coolant temperature conditions
A seven-day pressure recorder shall be provided.
A central annunciator and operator control panel shall be provided inside the controller but visible and accessible through a
breakable glass panel on the enclosure door. This control panel shall incorporate all alarm and status pilot light indicators,
voltmeters, and ammeters for the battery chargers, and the 4 positions main switch manual start push-buttons, combination
Lamptest / Charger reset push-button and the optional 'NORMAL' / 'SILENCE' selector switch for pump room alarms.