You are on page 1of 5

Feature

Cover Story
Report

Assessing Centrifugal
Pump Systems A pump must suit the
system, not the other
way around
Scott Mansfield
iÛiÊ
Consultant >݈“Õ“ÊÃÌ>̈Vʅi>`ÊrÊÇäʇÊÎʳÊxäÊrÊ££ÇÊvÌ Vœ˜ÌÀœ
i>`Ê Õˆ`ˆ˜}
"«iÀ>̈˜}ʏiÛi Ì>˜Ž
n important job we are often

A -Õ««Þ -̜À>}iÊ
tasked with is assessing the op- Ì>˜Ž
xäÊvÌ
eration of a centrifugal pump in /œÊ“ˆÝiÀÃ
a given situation. On some occa- ˆ}… £xÊvÌ
iÛi >LœÛiÊ
sions we will be asked to size a new ÃÕV̈œ˜
pump for a given application. Other ÇäÊvÌ
ˆ FIGURE 1. One of the
times we might be asked to find out most common pumping
why a pump system is not behaving as œÜ ÎÊvÌÊ>LœÛiÊ ­ œÌÊ̜ÊÃV>i® configurations is for the
iÛi transfer of liquid from a low
had been hoped. Finally, we might be ÃÕV̈œ˜
elevation to a higher elevation. The system
asked to change something in a pip- shown here is for Case 1 discussed in the text
ing system, perhaps a control valve or
a spray nozzle, and we want to make TABLE1. DESIGN PARAMETERS, CASE 1
sure the pump continues to perform Design flow rate 280 gpm, controlled (average flowrate on flowsheets)
acceptably in the new configuration.
Maximum flow rate 310 gpm, controlled
To address these tasks, we will first
take a look at the basic flow require- Discharge line 490 ft x 4 in. (includes equivalent lengths for fittings)
ments of the most common pumping Suction line 14 ft x 5 in. (includes equivalent lengths for fittings)
configuration namely, the transfer of Supply level, high 15 ft above suction
liquid from a low elevation to a higher
elevation. Then we will have a close Supply level, low 3 ft above suction
look at this same system for a better Pump elevation 1,000 ft above mean sea level
understanding of what is going on.
Next we will have a brief view of one sider the proposed system shown in exit are taken as one velocity head. Be-
other pumping system to appreciate Figure 1. A manufacturing operation cause length of pipe already includes
how a similar pump will respond to a on a hill requires water from a source allowances for fittings, fittings are not
different application. Finally, we will down the hill. The supply water origi- listed separately.
quickly cover some aspects of pump nates in a treatment plant and is to be We are now ready for the first esti-
protection. accumulated in a storage tank at the mate of control valve friction.
bottom of the hill. From there it will Control valve: Because the head tank
Case 1: the basics be pumped up the slope (70 ft vertical is operated at a constant level, a level
The starting point in pump analy- rise) to the base of the structure, and control valve is employed, as shown in
sis should be to establish the system then vertically upward to the discharge Figure 1. We note in Table 1 that both
characteristic, or system curve. The point in the side of a small constant- the average and the maximum flow-
system curve is the curve that would head tank. The design parameters are rates must be lower than the flowrate
result from plotting pressure drop ver- given in Table 1. Control-valve param- corresponding to the wide-open con-
sus flow with the pump absent. The eters are not included; they are listed trol valve. This is because a wide-open
main reason for starting here is that separately below. Note that the level control valve is not controlling, yet the
the curve defines what is required of of water in the supply tank varies. specification in Table 1 is for the maxi-
the pump. The pump must suite the Our calculations begin with an es- mum flowrate to be controlled.
system; not the other way around. timate of friction losses in the piping To get started, we will assume a con-
It doesn’t make sense to examine a for the maximum controlled flow (310 trol-valve size and valve position (per-
pump catalog or to contact a pump gpm). A breakdown of the losses is centage open) for the 310 gpm case;
vendor until this easy task has been given in Table 2. To save time, we use then we will do some calculations and
carried out. the tables in Cameron Hydraulic Data review the results. Looking in a ran-
System curve: As an example, con- [1]. Individual losses for entrance and dom (or old) control-valve catalog, we
34 CHEMICAL ENGINEERING WWW.CHE.COM AUGUST 2005
TABLE 2. FRICTION LOSSES, AT 310 GPM (WITHOUT VALVE)
Description Loss Loss, ft v, ft/s tank. During this process, the flowrate
(velocity heads) would be quite small, and the friction
1. Entrance to suction line 1.00 0.38 4.97 loss would be negligible. This part of
2. Suction line 0.23 4.97 the system curve, coincides with the
vertical axis (Q 5 0) up to 117 ft of
3. Discharge line 25.58 7.81
water.
4. Discharge to head tank 1.00 0.95 7.81 If the (imaginary) air pressure on
Sum: 27.14 the storage tank is fixed at 117 ft (50.7
psi), flow will stop, i.e. Q = 0. If the air
pressure is increased to 117 + 38.46 ft
TABLE 3. CASE 1, POINTS ON THE £Çä
™ä¯
= 155 ft of water, flow will occur at the
SYSTEM CURVE, QMAX = 310 GPM maximum design rate: Q = 310 gpm.
£Èä
Friction: Obviously, if the pressure is increased
Piping Valve Total: even more, the flow will increase cor-
/œÌ>Ê…i>`]ÊvÌʜvÊÜ>ÌiÀ

£xä respondingly. Our curve goes out to


Q, gpm Loss, ft 6P, ft Hsf + 117
nearly 350 gpm, well beyond the range
0 0 0 117 £{ä of interest. This is our first analysis of
50 0.832 0.294 118.1 the system curve.
£Îä Pump curve: Now we go through a
100 3.130 1.177 121.3
similar exercise (using another random
150 6.792 2.650 126.4 £Óä or old catalog) for determining a plau-
££ÇÊvÌ 6iÀ̈V>Ê
200 11.76 4.711 133.4 «œÀ̈œ˜
sible pump curve. We select a pump
£ä that at 1,750 rpm will deliver about
250 18.02 7.362 142.3
450 gpm. Our system conditions fit
300 25.53 10.60 153.1 ä xä £ää £xä Óää Óxä Îää Îxä {ää into the center of the range of service
310 27.14 11.32 155.5 œÜÀ>Ìi]}«“ described by the vendor. This pump has
350 34.27 14.42 165.7
FIGURE 2. The system curve for Case 1 a housing that will accommodate an
is shown here for a maximum controlled impeller of size 9 to 12 in. in diameter.
400 44.23 18.84 180.0 flowrate of 310 gpm (control valve 90%
We construct our pump curve by inter-
open, maximum static head)
polating between impellers of 11.25
home in a 4-in. equal-percentage valve in the same manner as with Table 2. and 12 in. Our hypothetical impeller is
that, at 310 gpm, would operate about Valve friction for these flows was esti- 11.5 inches. The results are shown as
90% open. This is acceptable for the mated by ⌬P = 11.32.(Q/310)2. Several the pump curve in Figure 3. This shows
moment, so we set about calculating a flowrates were selected for flows from total dynamic head (TDH*; ft) plotted
system curve with the valve 90% open. 0 to 400 gpm. For each flow a value of versus throughput (gpm).
To obtain the pressure drop across Hsf was calculated. Since the system Operating point: We note that in Fig-
the control valve we use the equation curve includes static head as well as ure 3, the two curves (pump curve and
for the valve coefficient, cv: friction head, we add 117 ft to each of 90% curve from Figure 2) cross at Q =
the friction values. Table 3 lists the 310, H = 155. This is confirmation of
cv = Q.(sp.gr./⌬P)1/2 (1)
results. Total head versus flowrate is our pump choice. Whether or not it is
where Q is flowrate (gpm), sp.gr. is spe- plotted in Figure 2. This is the system a valid design statement is still under
cific gravity of the fluid (water sp.gr. = curve for the case where the control question as this is an intermediate
1), and ⌬P is pressure drop across the valve is 90% open, required static result in a trial-and-error process. Be-
valve (psi). head is highest (low level in the sup- fore looking at system curves for our
The cv given in the vendor catalogue ply tank), and flow is at the maximum proposed design flow and other logical
for the 90% open, 4-in. valve is 140. We controlled rate. operating points, we take a look at the
rearrange Equation 1 and (keeping in Before looking at how the pump case where the control valve is wide
mind that in this case, sp.gr. = 1) cal- fits into this analysis, we will exam- open. This curve was obtained by using
culate ⌬P from, ine the system curve some more. To valve data from the valve vendor’s cat-
start with, imagine Figure 1 without alog. It is based on a valve coefficient
⌬P = (Q/cv)2 = (310/140)2 = 4.90 psi
the pump (and with the control valve of 210 for a wide open valve. This curve
which is 11.32 feet of water. To obtain 90% open). Without a motive force, the is also shown in Figure 3 as the lower
the total system friction loss, Hsf, we flow would be zero, and the level in the (100%) system curve. We note that the
add the values for piping plus valve: discharge leg would be at the same operating point for this case would be
level as the liquid in the storage tank. about 330 gpm. So far we don’t see
Hsf = 27.14 + 11.32 = 38.46 ft H2O
Imagine applying air pressure slowly anything that would suggest a system
To build the rest of the curve, data in the supply tank. The level in the
for pipe friction for other flows were discharge leg would slowly rise until 1. TDH is the pressure increase across the pump,
measured from suction centerline to discharge
taken from Cameron [1] and compiled reaching the control level of the head centerline.

CHEMICAL ENGINEERING WWW.CHE.COM AUGUST 2005 35


£Çä £Çä
£ää¯ £{äÊ Ó£äÊ ÓnäÊ £ää¯
Cover Story *Փ« ™ä¯ }«“ }«“ }«“ ™ä¯
£Èä £Èä ÇäÊ
}«“

/œÌ>Ê…i>`]ÊvÌʜvÊÜ>ÌiÀ

/œÌ>Ê…i>`]ÊvÌʜvÊÜ>ÌiÀ
£xä £xä
that would not operate properly.
We complete our analysis of the
£{ä £{ä
pump-piping-valve system by look- *Փ«
ing at the design flow (280 gpm), and VÕÀÛi

other logical operating points. We note £Îä £Îä


that the user of the stream from the
pump is a mixing operation consisting £Óä £Óä
of four identical mixers. Each mixer on
ä ä
the average will use 70 gpm; therefore, ä xä £ää £xä Óää Óxä Îää Îxä {ää ä xä £ää £xä Óää Óxä Îää Îxä {ää
œÜÀ>Ìi]}«“ œÜÀ>Ìi]}«“
depending on how many mixers are op-
erating, the normal flowrates would be FIGURE 3. Two system curves and a FIGURE 4. A summary of the calcula-
70, 140, 210, and 280 gpm. possible pump curve for Case 1. based tions (system and pump curves)
on a valve coefficient of 210 for Case 1
Table 4 summarizes calculations for
these added conditions plus the two TABLE 4. ARRAY OF DESIGN CONDITIONS
cases already discussed. All the sys-
Case Valve Operating, Description Valve
tem curves and the pump curve are No. position gpm 6P, ft
shown in Figure 4.
At this point, our trial and error pro- Case 1a. 100% open 330 no control 5.7
cess is just about complete. We have Case 1b. 90% open 310 nominal max. rate 11.3
started with a pump, a control valve, Case 1c. 82% open 280 nominal design rate 18.1
a supply source, a discharge point and
Case 1d. 70% open 210 one user off line 30.3
a piping configuration. We have looked
at flowrates, pressures and valve posi- Case 1e. 53% open 140 two users off line 39.0
tions and have not encountered diffi- Case 1f. 35% open 70 three users off line 44.7
culties.

NPSH the eye of the impeller, and where p experience, we suspected that NPSH
Before leaving our hypothetical pump is absolute pressure head (ft of fluid would not be a problem; this analysis
selection, we must have a look at the flowing), z is elevation above the pump confirms it. Below, we will check out
net positive suction head (NPSH) that suction (ft) and v is fluid velocity (ft/s). a design condition where NPSH is
would result from our stated operation. First we determine subscript 1 expres- somewhat in doubt.
Specifically, we will examine one con- sion using the known conditions at the It is important to note that all these
dition only: the worst condition. This surface of water in the tank: tasks can be carried out using random
would be at the highest flow, 330 gpm. (or old) catalog information. When
(p + z + v2/64.34)1 – friction loss =
Available NPSH is the calculated equipment procurement is initiated,
(32.5 + 3 + 0) – 0.7 = 34.8
pressure (absolute) at the eye of the the system and pump curves should
impeller minus the vapor pressure of because the water surface is 3 ft above be included as part of the bid package.
the fluid at the same place. We start the suction and the velocity at that This way, the vendors will have a head
by using known conditions of the fluid point is negligible, and the entrance start on understanding what they have
at the surface of the supply tank. loss and the line loss are 0.7 ft. to bid. They will love you for it, and
Since the tank is located about 1,000 The left side of Equation 2 must be you will get better, lower bids, because
feet above sea level (see Table 1), the equal to this, so the vendors will not be adding money
atmospheric pressure acting on the to cover contingencies. Of course their
(p + z + v2/64.34)2 = 34.8
water therein will be about 32.5 ft of pump and valve curves will not exactly
water. Since no source of energy ex- or match what you use from your catalogs,
ists between the surface of the water but they will be close enough so that no
p2 + 0 +0 = 34.8
in the tank and the pump suction, we major surprises will be encountered.
can use a simple form of the Bernoulli so p2 = 34.8 ft. We use v = 0 because
equation* [2]: we note that our pump vendor as- Case 2: suction lift
sumes that velocity in the suction line Let’s now say that, instead of pumping
(p + z + v2/64.34)2 = is converted into pressure at the im- from a supply 3 ft higher than the suc-
(p + z + v2/64.34)1 – friction loss (2) peller. NPSH is the value of p minus tion, we are pumping from a supply 20
the vapor pressure, so: ft lower than the suction. The situa-
where the Subscript 1 refers to condi- tion is shown in Figure 5. The pump
available NPSH = 34.8 – 0.84 = 34.0 ft
tions at the surface of liquid in the tank location and the discharge side con-
and Subscript 2 refers to conditions at Checking the vendor’s catalog, we figuration are the same as Case 1, but
2. A good discussion of the Bernoulli equation note that the required NPSH is about the suction side comes from a lake.
plus different forms of it can be found in Engi- 8 ft of water. Thus we meet, and eas- To make things simple, we will
neering Design for Process Facilities, McGraw-
Hill, 1993. See endnote [2]. ily exceed, this requirement. From only look at the case where the con-
36 CHEMICAL ENGINEERING WWW.CHE.COM AUGUST 2005
£™ä

œÌÊ̜ÊÃV>i ™ä¯
*Փ«
ÓäÊvÌ µÕˆÛ>i˜Ìʏi˜}̅ÊrÊnäÊvÌ°
£nä £Ó°xʈ˜

FIGURE 5. Case 2 considers

/œÌ>Ê…i>`]ÊvÌʜvÊÜ>ÌiÀ
£Çä
a situation where pumping from a
>À}i supply that is 20 ft lower than the suction
*Փ«
£Èä ££°xʈ˜

TABLE 5. FRICTION LOSSES, AT 310 GPM (WITHOUT CONTROL VALVE) £xä


Description Loss (velocity heads) Loss, ft v, ft/s
1. Foot valve 3.00 1.14 4.97 £{ä
2. Suction line, 80 ft equiv. 1.31 4.97 ä
3. Discharge line 25.58 7.81 ä xä £ää £xä Óää Óxä Îää Îxä
œÜÀ>Ìi]}«“
4. Discharge to head tank 1.00 0.95 7.81
Sum: 28.98 FIGURE 6. System and pump curves
for Case 2

trol valve is set for 310 gpm (that is, (p + z + v2/64.34)2 = 10.05 shut off the pump automatically once a
maximum controllable flow). Figure 5 or minimum acceptable level in the tank
shows a barge supporting part of the is no longer available. Remember that
p2 + 0 + 0 = 10.05
suction line and a foot valve (to keep vortex action can allow entry of air into
from losing prime). Table 5 summa- where, as before, we adopt the pump the suction line; this too can stop flow.
rizes the conditions. manufacturer’s standard of assuming Vortexes can be prevented by the addi-
The static TDH head is 20 + 70 + 50 the velocity in the inlet line is con- tion of baffles inside the tank.
or 140 ft. The TDH head at 310 gpm is verted to pressure at the eye of the Automated alarm and shutdown can
140 + 28.98 + 11.32 or 180.3 ft, where impeller. be initiated from a flow switch that ac-
the control valve adds 11.32 ft, as in As before, this result minus the tuates on a minimum flow condition.
Case 1. This is the operating point on vapor pressure of water is the avail- In Case 2 the supply could become
the system curve. Other points on the able NPSH: blocked by algae growing in the suc-
system curve are calculated as was tion line. Blockage could also be due to
available NPSH = 10.05 – 0.84 = 9.2 ft
done with Case 1. These points are some debris getting caught, so intake
shown as the system curve in Figure We see in the vendor’s data that this screens are advised. A drop in supply
6. Note that the system curve climbs pump requires 4 ft of NPSH, so we are level has already been mentioned. An-
the vertical axis to 140 ft (compared in good shape here. We should, however, other possibility is the entry of air in
to 117 ft earlier) until incipient flow be asking what the chances are for a the suction line. Possible entry points
begins. Now, as we did with Case 1, we drop in the lake level. A drop of five feet for air are through a hole formed by
search in the pump catalog for a pump would be disastrous. A drop of three feet corrosion, or through a failed gasket
that will deliver 310 gpm at 180.3 ft. is reason for serious concern. at a flange. In any event, the use of a
As it turns out, this pump is the next flow switch is advised.
series larger and has an impeller 12.5 Pump protection Shutoff: Shutoff occurs when the dis-
in. diameter. This pump and the pump The safety of employees, the integrity charge line is blocked. (In the examples
from Case 1 are shown in Figure 6. of the operation, and the investment above, shutoff would occur as a result
It is interesting to note that using capital can be imperiled if measures of all four mixers going off line.) This
the pump from Case 1 would have de- to protect the pump are overlooked. results in the fluid being churned end-
livered only 220 gpm. This is far less Here we discuss three of them, but lessly inside the pump. Power from the
than the required 310 gpm maximum there are quite a few others. During driver (usually an electric motor) is
controlled rate. all phases of design and procurement converted into heat. This is not usually
Now let us have a look at NPSH for these issues must be examined. In the a problem for fractional-horsepower (<1
Case 2. To find conditions at the im- cases presented here, the power input h.p.) steel or alloy pumps. For pumps
peller, we start out with known con- will often be in excess of 30 h.p. Such with large drivers or delicate parts,
ditions at the surface of the lake and a level of power can be lethal (besides however, shutoff can be destructive. Its
apply the Bernoulli equation. Specifi- electrical, there are pressure, velocity detrimental effects can be avoided by
cally, we use the right side of Equation and heat hazards). providing a small recycle line back to
2 and plug in the values appropriate Running dry: Unless a pump is spe- the supply tank to maintain a flow ad-
for Case 2: cifically designed to run dry, it should equate to dissipate heat, or by detect-
never be allowed to do so. The main ing a zero flow condition (as with the
(p + z + v2/64.34)1 – friction loss =
cause of running dry is a loss of supply blocked suction) and shutting down
(32.5 – 20 – 0) – 2.45 = 10.05
liquid. This could occur in Case 1 by an the pump. Recycle lines are simple, re-
The left side of Equation 2 must be interruption to the feed into the supply liable, and maintenance free, so Case 1
equal to this, so tank. The way to prevent this problem might best be served by a recycle line.
is add provisions to sound an alarm and Since Case 2 will require a flow switch
CHEMICAL ENGINEERING WWW.CHE.COM AUGUST 2005 37
Cover Story

in any case, a flow switch is indicated, pump is needed for good control-valve Final remarks
but the inclusion of a recycle line also performance (a system curve with The starting point for studying most
would have the added benefit of drain- a negative static head). If the pump pump systems should begin with the
ing the discharge line when the pump should experience a loss of power, the system curve. Typical system curves
is halted (assuming the discharge line control valve would most likely re- for a variety of applications can be
is equipped with a check valve). This spond by opening 100%, and an un- found in textbooks, such as refer-
would result in less strain on the motor wanted flow in the forward direction ence [3]. Once the system curve has
when the pump is started and would would result; this could be detrimental. been determined, the quest for a TDH
help prevent freezing in cold weather. A check valve is no good in this situa- source can be undertaken. ■
Unwanted flows: When a centrifu- tion. The indicated remedy would be to Edited by Gerald Ondrey
gal pump loses power, it no longer add a valve in the discharge line that
provides TDH, and then it simply be- would automatically close in the event
comes another restriction in the line. that the pump rpm were to drop below Author
Scott Mansfield is currently a
For the two cases shown here, the a minimum value. Other triggers could private consultant (626 E. Roses
fluid in the discharge line would flow be employed such as loss of discharge Rd., San Gabriel, Calif. 91775.
Phone: 626-285-9609; Email:
back through the pump and into the pressure or loss of power. smansfield7@mindspring.
supply source. For many installations com). He has more than 30
years experience in selecting,
this is not a problem. In the examples sizing, installing, and run-
presented here, the elevations and line References ning process equipment. In
the past, Mansfield worked
sizes are such that an unrestrained 1. Westway, C.R., Loomis, A.W., “Cameron Hy- for DuPont, Foote Mineral Co.,
draulic Data,” 15th Edition, Ingersoll-Rand, Jacobs Engineering, and Inte-
backward flow would probably be det- Woodcliff Lake, N.J., 1977. grated Equipment Services. He is the author of
rimental; thus a check valve in the 2. Mansfield, S., “Engineering Design for Process
McGraw Hill’s “Engineering Design for Process
Facilities,” and has authored numerous articles.
discharge line is warranted. Facilities,” McGraw Hill, New York, 1993. He has a B.S. in chemical engineering from the
Occasionally the discharge is located 3. Hicks, T.G., “Pump Application Engineering,” University of Arizona, and is a member of the
McGraw Hill, New York, 1971. AIChE and the National Society of Professional
at a level lower than the suction, but a Engineers.

Circle 25 on p. 58 or go to adlinks.che.com/4819-25
38 CHEMICAL ENGINEERING WWW.CHE.COM AUGUST 2005

You might also like