FAULT CALCULATION

GUT
SERVICE ENTRANCE:
230 VOLTS
SINGLE PHASE, 60HZ

²
MAIN FEEDER:
2-14.0 mm² THHN copper wire ²
on 25 mmØ uPVC conduit pipe

C1 C2
60 A 40 A

C3 C4
15 A 20 A

C5 C6
20 A 20 A

C7 C8
20 A 15 A

C9 C10
20 A 20 A

GROUND

SINGLE-LINE DIAGRAM

VOLTAGE DROP CALCULATION