PROJECT NAME : KYOKUYO PROJECT OPT-2

PANEL NAME : LP-F3 MCCB AT 80 TOTAL CAP


FEEDER CCT. BRANCH CAPACITY
CONNECTION LOAD BREAKER 3Phase 1Phase (k
NO NO. TYPE POLE AF AT KW kVA KW

MAIN CIRCUIT BREAKER MCCB 3P 125 80

E1 EMERGENCY LIGHT MCB 2P 16 0.48


L1 LIGHITNG -1 MCB 2P 16 0.50
L2 LIGHITNG -2 MCB 2P 16 0.99
L3 LIGHITNG -3 MCB 2P 16 0.99
L4 LIGHITNG -4 MCB 2P 16 0.99
L5 LIGHITNG -5 MCB 2P 16 0.99
L6 LIGHITNG -6 MCB 2P 16 0.99
L7 LIGHITNG -7 MCB 2P 16 0.99
L8 LIGHITNG -8 MCB 2P 16 0.40
L9 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 0.75
R2 SOCKET OUTLET MCB 2P 16 0.75
R3 SOCKET OUTLET MCB 2P 16 0.75
R4 SPARE MCB 2P 16 0.00
P1 DRAIN PUMP -1 MCCB 3P+N 15 0.64 0.80

FAN,PUMP 0.80
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET
OTHER
SPARE
INITIAL : 9.25 DEMAND FACTOR :
MAX DF. : 6.92 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
9.25 Cable CV 4C-35, E16
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

CV 4C-35, E16

0.53 NYM3C-2.5
0.55 NYM3C-2.5
1.10 NYM3C-2.5
1.10 NYM3C-2.5
1.10 NYM3C-2.5
1.10 NYM3C-2.5
1.24 NYM3C-2.5
1.24 NYM3C-2.5
0.50 NYM3C-2.5
0.00
0.94 NYM3C-2.5
0.94 NYM3C-2.5
0.94 NYM3C-2.5
0.00
NYY 4C-2.5, E2.5

( 0.80 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
1.63 1.65 2.20 ( 5.48 )kVA Df= 0.90
1.24 1.24 0.50 ( 2.97 )kVA Df= 0.40
( )kVA Df= 0.60
0.30 0.30 0.30 ( )kVA Df=
0.75 TOTAL LOAD ( 9.25 )kVA
Rate Current 14.07 A