You are on page 1of 14

Document Number: EDS 05-2010

Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
ENGINEERING DESIGN STANDARD

EDS 05-2010

MAIN SUBSTATION FEEDER AND RING MAIN UNIT


PROTECTION SETTINGS (LPN)

Network(s): LPN

Summary: This standard describes the protection settings for main substation feeders and ring
main units in the LPN area.

Owner: Kevin Burt Date: 02/12/2015

Approved By: Barry Hatton Approved Date: 08/01/2015

This document forms part of the Company’s Integrated Business System and its requirements are mandatory throughout UK
Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset
Management. If you have any queries about this document please contact the author or owner of the current issue.

Applicable To
UK Power Networks External
All UK Power Networks G81 Website

Asset Management Contractors

Capital Programme ICPs/IDNOs

Connections Meter Operators

HSS&TT

Network Operations

UK Power Networks Services

Other
Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Revision Record

Version 4.0 Review Date 08/01/2019


Date 02/12/2015 Author Kevin Burt
Why has the document been updated – Periodic review
What has changed – No content changes
Document transferred onto a new template and rules applied
Version 3.2 Review Date 09/11/2015
Date 04/09/2012 Author Lee Strachan
Document reviewed for publishing on G81 website

Version 3.1 Review Date 09/11/2015


Date 25/08/2011 Author Chris Anderson
Reclassified from EI to EDS

Version 3.0 Review Date 09/11/2015


Date 19/08/2010 Author David G Edwards
Rebranded, reviewed and review date extended

Version 2.0 Review Date


Date 30/10/2006 Author David G Edwards
TLF ratings and revised ACB protection settings added Tables (6A and 11A)

Version 1.0 Review Date


Date 07/04/2004 Author David G Edwards
Original, based on Protection Standard Number E 7/6 P 6/1 revision 4. Original no. EI 05-0046

© UK Power Networks 2016 All rights reserved 2 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Contents

1 Introduction ............................................................................................................. 4
2 Scope ....................................................................................................................... 4
3 Glossary and Abbreviations ................................................................................... 4
4 Main Substation Feeder Settings ........................................................................... 4
5 Secondary Distribution Transformers ................................................................... 4
5.1 Transformer Overcurrent Protection .......................................................................... 4
5.2 Transformer Earth Fault Protection ............................................................................ 4
6 HV Supplies ............................................................................................................. 5
6.1 HV Supplies to the Customer’s HV Switchboard ........................................................ 5
6.1.1 Overcurrent Protection .............................................................................................. 5
6.1.2 Earth Fault Protection ................................................................................................ 5

Tables

Table 1 – Main Substation Feeder Settings........................................................................... 6


Table 2 – Ring Circuit Breaker and Service Circuit Breaker – Electromechanical.................. 6
Table 3 – Ring Circuit Breaker and Service Circuit Breaker – VIP 200/300 ........................... 7
Table 4 – SEPAM 1000......................................................................................................... 7
Table 5 – SEPAM 1000+....................................................................................................... 8
Table 6 – Overcurrent Protection of Distribution Transformers (Glass Barrel TLF Fuse
Links) ................................................................................................................... 9
Table 7 – Overcurrent Protection of Distribution Transformers (Tagged TLF Fuse Links) ... 11
Table 8 – Settings for Merlin Gerin Masterpact ACB Control Unit STR58U (Glass Barrel
TLF Fuse Links) ................................................................................................. 11
Table 9 – Masterpact ACB STR 58U - 1200/1600A ACB with MODULE 1600A (Glass
Barrel TLF Fuse Links) ...................................................................................... 12
Table 10 – Masterpact ACB STR 58U – 2000A ACB with MODULE 2000A (Glass Barrel
TLF Fuse Links) ............................................................................................. 12
Table 11 – 1600A and 2000A Module (Glass Barrel TLF Fuse Links) ................................. 12
Table 12 – Micrologic NW16/20 H1 – 1600/2000A Module (Glass Barrel TLF Fuse Links) . 13
Table 13 – Micrologic NW16/20 H1 – 1600/2000A Module (Tagged TLF) ........................... 13
Table 14 – Sensitive Earth Fault Settings............................................................................ 13
Table 15 – Overcurrent Protection of HV Supplies (refer to Section 6.1.1) .......................... 14
Table 16 – Falcon Alpha RMU Overcurrent Trip Times Versus Fault Current...................... 14

© UK Power Networks 2016 All rights reserved 3 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
1 Introduction
This standard describes protection settings for main substation feeders and ring main units
in the UK Power Networks (UKPN) LPN region.

2 Scope
This standard only applies to the London Power Network (LPN) area.

3 Glossary and Abbreviations

Term Definition

UK Power Networks UK Power Networks (Operations) Ltd consists of three electricity


distribution networks:
 Eastern Power Networks plc (EPN).
 London Power Network plc (LPN).
 South Eastern Power Networks plc (SPN).

4 Main Substation Feeder Settings


The overcurrent and earth fault settings shall be as listed in Table 1 unless otherwise agreed
with UKPN Asset Management.

5 Secondary Distribution Transformers


5.1 Transformer Overcurrent Protection

The rating of the time-limit fuse-links or the type of thermal protection modules for
overcurrent protection of secondary distribution transformers applied at ring main units and
their associated air circuit breakers shall be as listed in Table 6.

5.2 Transformer Earth Fault Protection

Instantaneous sensitive earth fault protection with sensitivities as declared in Table 14 is


inherent in the design of all but:

 The Falcon Alpha units (original Falcon units) where it is provided, when specified, via
dedicated core balanced current transformers; and
 Switch fuses, where it is not good practice to provide it.

It should be noted that such a provision is not normally present on transformer mounted
Falcon Alpha units.

© UK Power Networks 2016 All rights reserved 4 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
6 HV Supplies
Where an HV supply is connected directly to the customer’s own transformer, of which the
rating and winding arrangement and impedance are similar to the Company’s distribution
transformers, then Section 5 of this document shall apply. For transformers not so
identifiable, advice should be sought from UKPN Asset Management. Where relays are used
to afford protection then the settings shall be as in Table 1, Table 2 and Table 3.

If Microprocessor relays are used, reference should be made to UKPN Asset Management
with full details of the proposed installation so that individual settings can be supplied.

6.1 HV Supplies to the Customer’s HV Switchboard

6.1.1 Overcurrent Protection

Discrimination with the customer’s own equipment, other than fuses for HV faults, is not
feasible with ring main units protected by time fuse links. Discrimination with the customer’s
equipment can be afforded by use of protective relays. Relays installed with characteristics
based on the standard inverse BS 142 curve shall have settings as in Table 2. Relays
supplied with adjustable complex curves, may need special treatment and shall be referred
to UKPN Asset Management.

In some cases the customer will not require discrimination with the service and thus it may
be possible to use time fuses for overcurrent (and instantaneous protection for earth faults
when applicable). The rating of the time fuse link and thermal modules for these cases shall
be as listed in Table 15.

Limited discrimination is possible with units protected by thermal protection modules, and
Table 16 relates to Falcon Alpha overcurrent trip times to fault current as an application
guide. In cases of doubt advice should be sought from UKPN Asset Management. Where
Falcon Alpha units are used to provide such a supply then the module shall be as specified
in Table 15.

6.1.2 Earth Fault Protection

Earth fault protection can be provided by protection relays and for the standard inverse curve
relay settings refer to Table 2 and Table 3. In the case of Microprocessor relays refer to
UKPN Asset Management.

Instantaneous sensitive earth fault protection with sensitivities as declared in Table 14 is


inherent in the design of all but;

 The Falcon Alpha ring main unit, where it is provided, when specified, via a dedicated
core balance current transformer; and
 Switch fuses, where it is not provided. The switch fuse will, however, discriminate with
the main substation earth fault relay for earth faults exceeding 800A downstream of the
ring main unit.

© UK Power Networks 2016 All rights reserved 5 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Where Falcon Alpha ring main units are installed, and there is a requirement by the
customer for discrimination, no instantaneous earth fault protection is needed and the
following applies:

 For applications (see Table 15) using the ‘D’ module, no specific earth fault protection is
necessary because the ‘D’ module discriminates with the main substation earth fault
relay for earth faults downstream of the ring main unit;
 For applications using the ‘F’ module, a separate IDMT earth fault current relay fed from
the core balance current transformer and set at 120 primary amperes 0.15 time
multiplier, tripping via the shunt trip coil should be installed. This will prevent the main
substation earth fault relay from operating before the ring main unit for earth faults
downstream of the ring main unit.

Table 1 – Main Substation Feeder Settings

High Set Overcurrent IDMT Overcurrent IDMT Earth Fault


when Provided

Feeders without HV 2400-3200A 600A 0.2TM 200A 0.2TM


customers or where HV
supplies are afforded to
customers’ own distribution
transformers
Feeders from which at least Not deployed 600A 0.35TM 200A 0.35TM
one HV supply is afforded to
customer’s HV switchboard

Table 2 – Ring Circuit Breaker and Service Circuit Breaker – Electromechanical

Method of Supply Ring CB Service CB

IDMT IDMT Earth IDMT IDMT Earth


Overcurrent Fault Overcurrent Fault

Unit protected two 450A 0.15TM 150A 0.15TM


feeders in parallel
Unit protected three 600A 0.15TM 200A 0.15TM 450A 0.15TM 150A 0.15TM
feeders in parallel
Directional 600A 0.15TM 200A 0.15TM 450A 0.15TM 150A 0.15TM
protected two
feeders in parallel
Radial Feed 450A 0.15TM 150A 0.15TM

© UK Power Networks 2016 All rights reserved 6 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Table 3 – Ring Circuit Breaker and Service Circuit Breaker – VIP 200/300

CT 200/1 800/1 800/1


Ratio

Position Service Service Ring

O/C SI 200A, t=0.4s SI 448A, t=0.4s SI 576A,T=0.4s


VIP 200/300
(equivalent to (equivalent to (equivalent to tms=0.135)
tms=0.135) tms=0.135)

E/F SI 140A, t=0.4s SI 128A, t=0.4s SI 196A, t=0.4s


(equivalent to (equivalent to (equivalent to tms=0.135)
tms=0.135) tms=0.135)

CT 400/1 Not suitable for Ring Busters


Ratio

Position Service

O/C SI 400A, t=0.4s


VIP 300
(equivalent to
tms=0.135)

E/F SI 160A, t=0.4s


(equivalent to
tms=0.135)

Notes:
1. VIP Relays are self powered from the CT, the maximum setting is 100% of the CT primary rating.
2. As from September 2003 YRM switchgear came with 400/1 CTs.

Table 4 – SEPAM 1000

Position Service Service Ring

CT Ratio 200/1 600/1 600/1

Overcurrent SI 440A, t=0.4s SI 450A, t=0.4s SI 600A,T=0.4s


(equivalent to (equivalent to tms=0.135) (equivalent to tms=0.135)
tms=0.135)

Earth Fault SI 150A, t=0.4s SI 150A, t=0.4s SI 200A, t=0.4s


(equivalent to (equivalent to tms=0.135) (equivalent to tms=0.135)
tms=0.135)

© UK Power Networks 2016 All rights reserved 7 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Table 5 – SEPAM 1000+.

Service Ring
Position
SELECT A+B SELECT A+B

CT Ratio 600/1 600/1

SIT 450, t=0.450s SIT 600A,T=0.450s


Overcurrent
(equivalent to tms=0.15) (equivalent to tms=0.15)
SIT 150A, t=0.450s SIT 200A, t=0.450s
E/F
(equivalent to tms=0.15) (equivalent to tms=0.15)

Notes:
1. For all the above settings refer to Asset Management.
2. Special applications will be considered to assist customers with their downstream protection grading. Such
requests shall be sent to Asset Management and if abnormal settings are to be issued for application to
network protection, a note of this abnormality shall be attached in the control graphics system, adjacent to
the substation concerned.
3. Settings and logic for all microprocessor relays are the responsibility of Programme Delivery, Protection
Applications.

© UK Power Networks 2016 All rights reserved 8 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Table 6 – Overcurrent Protection of Distribution Transformers (Glass Barrel TLF Fuse Links)

Equipment CT Voltage Transformer Ratings


Ratio
500kVA 750/800kVA 1000kVA 2x500kVA 2x
750/800kVA

8/1 6.6kV D D (*3) - - -


Brush
Falcon (*1) 11kV C D D D (*2) -
ALPHA 19/1 6.6kV - - F E (*2) -
RMU
(*1) 11kV - - - - E (*2)
50/5 6.6kV 10A - - - -

Brush 7.5A - see


11kV 10A - - -
Falcon table 8
BETA RMU 100/5 6.6kV - 7.5A 10A 10A -
11kV - - 7.5A 7.5A 10A
Yorkshire 7.5A (*4) -
(*6) 75/5 6.6kV see table 10A (*4) 10A (*4) 10 (*2) -
Switchgear 8
Ringmaster
RMU MK1.5 11kV 5A 7.5A 10A 7.5 (*2)

50/5 6.6kV 10A - - - -


Yorkshire 7.5A - see
Switchgear 11kV 10A - - -
table 8
Ringmaster
RMU MK 2 100/5 6.6kV - 7.5A 10A 10A -
11kV - - 7.5 7.5A 10A
Long & (*7) 140(100)
- 6.6kV 100(80)A 140(100)A - -
Crawford A
(*8) LCGT
RMU 11kV 63(50)A 80(63)A 100(80)A - -
(Switchfuse)
Lucy (*8) - 6.6kV 80A 125A - - -
SFRMU CF1
Switchfuse - 11kV 50A 80A 100A - -

70/5 6.6kV 10A - - - -


7.5A - see
Lucy 11kV 10A - - -
table 8
SCRMU
100/5 6.6kV - 7.5A 10A 10A -
11kV - - 7.5A 7.5 10A

© UK Power Networks 2016 All rights reserved 9 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Equipment CT Voltage Transformer Ratings
Ratio
500kVA 750/800kVA 1000kVA 2x500kVA 2x
750/800kVA

50/5 6.6kV 10A - - - -

ABB 7.5A - see


11kV 10A - - -
Sentinel table 8
RMU 100/5 6.6kV - 7.5A 10A 10A -
11kV - - 7.5A 7.5A 10A
50/5 6.6kV 10A - - - -
7.5A - see
11kV 10A - - -
table 8

All Other 7.5A - see


80/5 6.6kV 10A - - -
RMUs table 8
11kV 5A 7.5A 10A 10A 10A
100/5 6.6kV - 7.5A (*4) 10A 10A -
11kV - - 7.5A 7.5A 10A
Masterpack Standard settings set at factory for 1200 & 1600 amp units see Table 9. Any other units
ACB need to be referred to System Development Protection
800/5 0.433kV 7.5A - - 7.5A -
ACB 1200/5 0.433kV 5A 7.5A - 5A 7.5A
1600/5 0.433kV - - 7.5A - -

Notes:
1. On the Falcon Alpha RMU, current transformers are matched to particular types of protection modules.
Unless specifically agreed with the MPL Protection Section, module types must not be interchanged between
the two CT types. The CTs are mounted inside the SF 6 chamber which must be returned to the manufacturer
if a change is necessary.
2. In the interests of faster fault clearance, discrimination across the distribution transformer is sacrificed if the
LV windings are paralleled.
3. Some loss of discrimination across the distribution transformer results from avoiding a CT change on
uprating to 11kV operation.
4. Discrimination across the transformer is sacrificed in the interest of faster fault clearance.
5. This ratio is not available on Yorkshire Ringmaster, Lucy SCRMU, or Falcon BETA RMUs.
6. Yorkshire Ringmasters, pre-MK 2 on the LPN network, are referred to as MK 1.5.
7. Figures quoted are fuse rating in oil. Ratings in air are shown in brackets.
8. Discrimination with LV ACBs is not guaranteed and should not be used with solidly interconnected LV
systems.
9. Discrimination between Falcon ALPHA RMUs and MSS is not guaranteed for faults between the RMU and
its transformer.
10. There is no overload factor on this application.
11. For applications other than the above, advice should be sought from Asset Management

© UK Power Networks 2016 All rights reserved 10 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Table 7 – Overcurrent Protection of Distribution Transformers (Tagged TLF Fuse Links)
Voltage Transformer rating CT ratio TLF rating SAP code
500 kVA 40/5 N/A N/A
50/5 N/A N/A
800 kVA 80/5 15 A 11947C
11 kV
100/5 15 A 11947C
1000 kVA 80/5 15 A 11947C
100/5 15 A 11947C

Note: For existing distribution substations with a 500kVA transformer where HV switchgear
is to be changed and the 500kVA transformer is to be retained, it is not possible to grade
tag-type TLF’s with the LV fuses. Therefore, when replacement of the HV equipment is
necessary, complete the following:

 Install a Lucy Sabre VRN2A RMU.


 Retro fit clips for glass barrel-type TLFs.
 Install 10A glass barrel-type TLFs.

Table 8 – Settings for Merlin Gerin Masterpact ACB Control Unit STR58U (Glass Barrel TLF Fuse
Links)

Characteristics Setting Value Dial Position Dial Position

Long Time Pick Up LT 1600A IO = 1 Ir =1


Long Time Time Delay LT 15 s tr = 15 -
Short Time Pick Up ST 2400A Im =1.5 -
Short Time Time Delay
0.2 s tm = 0.2 -
ST
2
It ON tm Dial Set Clockwise to 0.2
Instantaneous Pick Up 12800A I=8 -

Notes:
1. For transformers of all sizes associated with 1200A and 1600A ACBs using 1600A sensors.
2. These settings grade with downstream J400A fuses. They will not grade with J-type distribution fuses of
higher rating.
3. Upstream RMU 7.5A TLFs with 50/5, 70/5, 75/5 and 80/5 CTs must be changed to 10A TLFs (Glass Barrel
TLF Fuse Links).

© UK Power Networks 2016 All rights reserved 11 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Table 9 – Masterpact ACB STR 58U - 1200/1600A ACB with MODULE 1600A (Glass Barrel TLF
Fuse Links)

1200/1600amp ACB with MODULE 1600A


2
Transformer TLF Io Ir tr Im tm It I
Size Min CT
ratio

500kVA 50/5 1 1 15 1.5 0.2 on 12


800kVA 80/5 1 1 15 1.5 0.2 on 14
800kVA 75/5 1 1 15 1.5 0.2 on 14
1000kVA 100/5 1 1 15 1.5 0.2 0n 22

Notes:
1. Settings to apply for transformers with services having 630A or 800A fuses and on interconnected areas
using 500A fuses.
2. Always use 10A TLFs (Glass Barrel TLF Fuse Links).

Table 10 – Masterpact ACB STR 58U – 2000A ACB with MODULE 2000A (Glass Barrel TLF Fuse
Links)
2
Transformer CT Io Ir tr Im tm It I
Size Ratio

1000kVA 100/5 1 1 15 1.5 0.2 0n 17

Notes:
1. Where two transformers are connected in parallel at LV from different feeders, in the event of an earth fault
on one feeder, there is the possibility of the feeder being back fed by the other transformer.
2. This will occur with radial LV networks, where hold-up performance is poor in fully interconnected LV
networks.
3. This arrangement is to coordinate with reverse power relays and parasitic trip units.

Table 11 – 1600A and 2000A Module (Glass Barrel TLF Fuse Links)
2
Module Transformer CT ratio Io Ir tr Im tm It I
Size

1600A 2 x 1000kVA 100/5 1 1 15 3 0.2 on 22


2000A 2 x 1000kVA 100/5 1 1 15 3 0.2 on 17

Notes:
1. Masterpact NM ACB.
2. Micrologic 5.0A.
3. Settings to apply for transformers with services having 630A or 800A fuses and on interconnected areas
using 500A fuses.
4. Always use 10A TLFs (Glass Barrel TLF Fuse Links)

© UK Power Networks 2016 All rights reserved 12 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Table 12 – Micrologic NW16/20 H1 – 1600/2000A Module (Glass Barrel TLF Fuse Links)
Protection settings to be applied when grading with a glass barreled TLF fuse link. Refer to Table 6 –
Over-current protection of distribution transformers (Glass Barrel TLF)

Transformer TLF Min


Module Ir tr Isd tsd Iinst
Size CT Ratio
2
Micrologic NW16 H1 All 100/5 1.00 4.0 8.00 0.1+I t 15
- 1600A
2
Micrologic NW20 H1 All 100/5 1.00 4.0 6.00 0.1+I t 15
- 2000A

Note: For all Micrologic these settings are factory set. They will need to be checked at the time of commissioning.

Table 13 – Micrologic NW16/20 H1 – 1600/2000A Module (Tagged TLF)


Protection settings to be applied when grading with a Tagged TLF fuse link. Refer to Table 7 – Over-
current protection of distribution transformers (Tagged TLF).

Transformer TLF Min


Module Ir tr Isd tsd Iinst
Size CT Ratio
2
Micrologic NW16 H1 All 100/5 1.00 12 6.00 0.1+I t 15
- 1600A
2
Micrologic NW20 H1 All 100/5 1.00 4.0 4.00 0.1+I t 15
- 2000A

Note: For all Micrologic these settings are factory set. They will need to be checked at the time of commissioning.
Table 14 – Sensitive Earth Fault Settings

Equipment CT Ratio Sensitive Earth Fault Setting

Brush ALPHA RMU Core balance


400/5 30 A
Brush BETA RMU 50/5 30 A
100/5 40 A
Yorkshire Ringmaster MK1.5 75/5 20A
Yorkshire Ringmaster MK2 50/5 20 A
100/5 25 A
Lucy SCRMU 70/5 20 A
100/5 25 A
ABB 50/5 20 A - 27 A
Sentinel RMU 100/5 28 A - 35 A
All RMUs except Switch Fuses 50/5 20 A
and the above
80/5 20 A
100/5 25 A

© UK Power Networks 2016 All rights reserved 13 of 14


Document Number: EDS 05-2010
Version: 4.0
Date: 02/12/2015

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Table 15 – Overcurrent Protection of HV Supplies (refer to Section 6.1.1)

Equipment Load MVA at 6.6kV MVA at 11kV Module/fuse CT

Brush Falcon 0-100A 0-1.1 0-1.9 d (1) 8/1


ALPHA
100-180A 1.1-2.0 1.9-3.4 F (1) 19/1
>180A >2.0 >3.4 Use extensible switchgear
Yorkshire 0-150A 0-1.7 0-2.85 10A 75/5 MK1
Switchgear
Ringmaster 0-200A 0-2.28 0-3.8 10A 100/5 MK2
MK2 only for downstream discrimination using relays
Long & 100(80)A
Crawford 0-80A 0.9 1.5 -
LCGT Sw/fuse (7)

Lucy SFRMU-
0-83A 0.95 1.58 125A -
CF1 Sw/fuse
All RMUs
except as 0-100A 0-1.1 0-1.9 10A 100/5
above

Notes:
1. For downstream discrimination a relay should be used. Refer to Asset Management for VIP200 Settings.
2. Refer to Section 6.1.2 for earth fault protection requirements.

Table 16 – Falcon Alpha RMU Overcurrent Trip Times Versus Fault Current

Fault Current (A) D Module (s) F Module (s)

1000 0.8 1.0


2000 0.45 0.4
4000 0.3 0.22
6000 0.25 0.17
8000 0.22 0.15
10000 0.2 0.13

© UK Power Networks 2016 All rights reserved 14 of 14

You might also like