REM615 is a dedicated motor protection and control relay Standardized communication and redundancy
for protection, control, measurement and supervision of REM615 fully supports the IEC 61850 standard for
asynchronous motors in the manufacturing and process communication and interoperability of substation automation
industry. devices, including fast GOOSE messaging and IEC 61850-
9-2 LE, and can now also benefit from the extended
Application interoperability provided by Edition 2. The motor relay
REM615 has been designed to be the main protection for further supports both the parallel redundancy protocol
asynchronous motors and their drives in manufacturing and (PRP) and the high-availability seamless redundancy (HSR)
process industry. Typically, the motor relay is used with protocol, together with the DNP3, IEC 60870-5-103 and
circuit-breaker and contactor-controlled MV motors and Modbus® protocols. With the protocol adapter SPA-ZC 302,
medium-sized and large contactor-controlled LV motors Profibus DVP1 can also be used. REM615 is able to use two
in a variety of drives. The drives include both continuously communication protocols simultaneously.
and intermittently operated asynchronous motor drives with
varying load, such as pumps and conveyors, crushers and For redundant Ethernet communication, REM615 offers either
choppers, mixers and agitators, fans and aerators. two optical or two galvanic Ethernet network interfaces. A
third port with a galvanic Ethernet network interface provides
REM615 is available in four standard configurations, one connectivity of any other Ethernet device to an IEC 61850
of which includes support for three combi-sensor inputs station bus inside a switchgear bay. The redundant Ethernet
for phase currents (Rogowski coil) and voltages (voltage solution can be built on the Ethernet-based IEC 61850,
divider) and the other for conventional current and voltage Modbus ® and DNP3 protocols.
instrument transformers. The standard configurations can be
tailored to meet application-specific requirements using the The implementation of the IEC 61850 standard in REM615
IEC 61850-compliant Protection and Control IED Manager covers both vertical and horizontal communication, including
PCM600. GOOSE messaging with both binary and analog signals as
well as parameter setting according to IEC 61850-8-1. Also
To minimize the effects of an arc fault, REM615 can be IEC 61850-9-2 LE process bus with sending sampled values
equipped with high-speed outputs decreasing the operate of not only analog voltages but now also currents, in addition
time by four to six milliseconds compared to conventional to receiving sampled values of voltages, is supported. For
binary outputs. process bus applications, which require high-accuracy time
synchronization, IEEE 1588 V2 is used, with a time stamp
Human-machine interface resolution of not more than four microseconds. IEEE 1588
As a member of the Relion® product family, REM615 shares V2 is supported in all variants with a redundant Ethernet
the same human -machine-interface (HMI) look and feel as the communication module. In addition, REM615 supports
other Relion protection and control relays and IEDs. The same synchronization over Ethernet using SNTP or over a separate
look and feel includes the location of a push button with a bus using IRIG-B.
certain function and the menu structure.
2× - User management
IL2 0 A
O R
L
OR
Io>>
CONTROL AND INDICATION 1) MEASUREMENT
51N-2
Io - I, U, Io, P, Q, E, pf, f
Object Ctrl 2)
Ind 3)
- Limit value supervision
CB 1 - - Load profile record
- RTD/mA measurement (optional)
DC 2 3 - Symmetrical components
Io>→
67N-1 ES 1 2
1)
Check availability of binary inputs/outputs Analog interface types 1)
3)
Status indication function for
primary object
1)
Conventional transformer inputs
UL1UL2UL3 2×
3U< U2> U1< f>/f<, ESTART
df/dt
27 47O- 47U+ ESTART
81
REMARKS
18× Optional 3× No. of Calculated OR Alternative
MAP function instances value function to be
MAP Io/Uo defined when
6xRTD ordering
2xmA
Standard configurations
Standard
Description
configuration
Basic motor protection (RTD option) A
Motor protection with voltage and frequency based protection and measurements (RTD option) B
Motor protection with voltage and frequency based protection and measurements C
Motor protection with voltage and frequency based protection and measurements (sensor inputs) D
PHPTUV 3U< 27 - 1 1 1
PSPTUV U1< 47U + - 1 1 1
NSPTOV U2> 47O - - 1 1 1
FRPFRQ f>/f<, df/dt 81 - 2 2 2
MNSPTOC I2>M 46M 2 2 2 2
LOFLPTUC 3I< 37 1 1 1 1
JAMPTOC Ist> 51LR 1 1 1 1
STTPMSU Is2t n< 49, 66, 48, 51LR 1 1 1 1
PREVPTOC I2>> 46R 1 1 1 1
MPTTR 3Ith>M 49M 1 1 1 1
CCBRBRF 3I>/Io>BF 51BF/51NBF 1 1 1 1
TRPPTRC Master Trip 94/86 2(5) 2)
2(5) 2)
2(5) 2)
2(5) 2)
CBXCBR I ↔ O CB I ↔ O CB 1 1 1 1
DCXSWI I ↔ O DCC I ↔ O DCC 2 2 2 2
ESXSWI I ↔ O ESC I ↔ O ESC 1 1 1 1
DCSXSWI I ↔ O DC I ↔ O DC 3 3 3 3
ESSXSWI I ↔ O ES I ↔ O ES 2 2 2 2
ESMGAPC ESTART ESTART 1 1 1 1
RDRE DR DFR 1 1 1 1
LPDMSTA LOADPROF LOADPROF 1 1 1 1
FLTRFRC FAULTREC FAULTREC 1 1 1 1
CMMXU 3I 3I 1 1 1 1
CSMSQI I1, I2, I0 I1, I2, I0 1 1 1 1
RESCMMXU Io In 1 1 1 1
VMMXU 3U 3V - 1 1 1
RESVMMXU Uo Vn - - 1 -
VSMSQI U1, U2, U0 V1, V2, V0 - 1 1 1
PEMMXU P, E P, E - 1 1 1
XRGGIO130 X130 (RTD) X130 (RTD) (1) (1) - (1)
FMMXU f f - 1 1 -
SMVSENDER SMVSENDER SMVSENDER - (1) (1) (1)
SMVRCV SMVRCV SMVRCV - (1) (1) (1)