Product Specification

37258E

Genset Control
for Multiple
Unit Operation

DESCRIPTION • Peak shaving operation

The easYgen-3000 Series are control units for genset management applications. The numerous inputs and • Stand-by operation
outputs, along with a modular software structure, permit you to use the easYgen-3000 Series for a wide range
of applications with only a single part number. This includes stand-by, AMF, peak shaving, import-export, coge-
neration or distributed generation, among others. Also the easYgen-3000 Series is compatible for island, island • AMF operation
parallel, mains parallel and multiple unit mains parallel operations.

• Cogeneration (CHP)
The easYgen-3000 Series is able to control up to 32 gensets connected in a network with automatic sequenc-
ing.
The easYgen-3000 Series is available in two variants, the easYgen-3100 for cabinet back panel installation,
• Isolated & mains parallel
and the easYgen-3200 with graphical display and soft keys for front panel mounting.
FlexAppTM – This feature provides the tools to easily configure the number of operated breakers: None, GCB,
GCB and MCB.
operation

• Import/export control
LogicsManagerTM – Woodward's LogicsManager software enables to change the operation sequences and
adapt them to specific needs. The LogicsManager accomplishes this by monitoring a range of measuring val-
ues and internal states, which are combined logically with Boolean operators and programmable timers. This
enables to create and/or modify control and relay functions.
• Soft loading features
FlexInTM – The analog inputs are configurable to operate with VDO, resistive, and/or 0 to 20 mA senders.
Flexible Outputs – Speed and voltage bias outputs are configurable to function with all speed governors and • Open/closed transition
voltage regulators. The outputs can also be used as freely scalable outputs (e.g. for driving external meters).
FlexCANTM – Advanced network interfaces ensure unsurpassed control performance – from engine control up
to total plant operation. The easYgen-3000 Series is capable of working with all common industrial interfaces,
• Load sharing and load-
including CAN, RS-232, and RS-485. The multiple communication protocols permit the easYgen-3000 Series to dependent start/stop for
communicate with a vast majority of engine control units (ECUs), external I/O boards, PLCs, and modems.
CANopen, J1939, Modbus RTU, and Modem protocols are supported.
up to 32 units
DynamicsLCDTM – The adaptive and interactive 5.7", 320x240 pixel graphical LC display with soft keys and a
clear menu structure ensures intuitive user operation and navigation.
• Programmable operation
sequences
Features
• Multi-lingual capability
• Operation modes: Auto, Stop, Manual, and Load/No Load test modes via discrete input possible
• Breaker control: Slip frequency / phase matching synchronization, open-close control, breaker monitoring
• Load transfer features: open / closed transition, interchange, soft loading / soft unloading, mains parallel • CANopen / J1939 ECU
• Process and load-dependent start/stop logic for diesel and gas engines programmable for spinning or system Control
reserve with fixed or dynamic priorities.
• Real and reactive power load sharing with up to 32 units
• Remote control via interface and discrete/analog inputs for adjusting speed, frequency, voltage, power, reactive • Modbus RTU Protocol
power, and power factor set points
• Complete integrated engine and generator protection as well as mains monitoring features
• Freely configurable PID controllers for various control purposes, such as heating circuit control (CHP applica- • CE marked
tions), water level, fuel level, or pressure and/or other process values
• Special Scania S6, MTU ADEC, Volvo EMS2 & EDC4, Deutz EMR2, MAN MFR/EDC7, SISU EEM and Wood-
ward EGS02 ECU support (depending on Package) • UL/cUL Listing
• Counters for operating hours / engine starts / maintenance / active energy / reactive energy
• Configurable trip levels / delay timers / alarm classes for monitoring and protective functions • LR & ABS Marine Ap-
• Clear text display and evaluation of up to 100 J1939 analog values
• Discrete and analog I/O expansion board connectivity (Woodward IKD 1 or Phoenix Contact IL series) provals
• Front panel and PC configurable (ToolKit software)
• Multi-level password protection for access via HMI or interface
• Multi-lingual capability (English, German, French, Spanish, Chinese, Japanese, Italian, Portuguese, Turkish, Russian, Polish)
• Event recorder (300 events, FIFO) with real time clock
SPECIFICATIONS
Power supply.......................................................... 12/24 Vdc (8 to 40 Vdc) Relay outputs .................................................................................... isolated
Intrinsic consumption ..................................................................max. 17 W Contact material ...................................................................................AgCdO
Ambient temperature (operation) ....................... -20 to 70 °C / -4 to 158 °F Load (GP) ........................................................................ 2.00 Aac@250 Vac
Ambient temperature (storage) ........................ -30 to 80 °C / -22 to 176 °F 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Ambient humidity...................................................... 95 %, non-condensing Pilot duty (PD) ..................................................................................................
Voltage ...............................................................................................( /∆) 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
100 Vac [1] Rated (Vrated) ............................................69/120 Vac Analog inputs (none isolated) .............................................freely scaleable
Max. value (Vmax) ............................................86/150 Vac Type .................................................................... 0 to 500 Ohms / 0 to 20 mA
Rated surge volt.(Vsurge) ....................................................2.5 kV Resolution .............................................................................................. 11 Bit
and 400 Vac [4] Rated (Vrated) ..........................................277/480 Vac Analog outputs (isolated) ....................................................freely scaleable
Max. value (Vmax) ..........................................346/600 Vac Type ......................................................................... ± 10 V / ± 20 mA / PWM
Rated surge volt.(Vsurge) ....................................................4.0 kV Insulation voltage (continuously) ....................................................... 100 Vac
Accuracy .......................................................................................... Class 1 Insulation test voltage (1s) ................................................................. 500 Vac
Measurable alternator windings ..................... 3p-3w, 3p-4w, 1p-2w, 1p-3w Resolution ......................................... 11/12 Bit (depending on analog output)
Setting range ..................... primary .................................50 to 650,000 Vac ± 10 V (scaleable) ........................................... internal resistance ≤1 kOhms
Linear measuring range .............................................................. 1.25×Vrated ± 20 mA (scaleable) .............................................. maximum load 500 Ohms
Measuring frequency............................................... 50/60 Hz (40 to 85 Hz) Housing (3200) Front panel flush mounting .................. Plastic housing
High Impedance Input; Resistance per path ....... [1] 0.498 MΩ, [4] 2.0 MΩ Dimensions WxHxD .......................................... 282 × 217 × 99 mm
Max. power consumption per path ................................................ < 0.15 W Front cutout WxH .................................. 249 [+1.1] × 183 [+1.0] mm
Current (Isolated) Rated (Irated) ..............................[1] ../1 A or [5] ../5 A Connection ....................................................... screw/plug terminals 2.5 mm²
Linear measuring range ........................................................ Igen = 3.0×Irated Front.................................................................................... insulating surface
Imains/ground = 1.5×Irated Sealing Front .................................. IP66 (with screw fastening)
Setting range .......................................................................... 1 to 32,000 A Front .................................. IP54 (with clamp fastening)
Burden .......................................................................................... < 0.15 VA Back ...................................................................... IP20
Rated short-time current (1 s) .................................[1] 50×Irated, [5] 10×Irated Weight .................................................................................... approx. 1,850 g
Power ......................................................................................................... Housing (3100) Switch cabinet back mounting .....Sheet metal housing
Setting range ..........................................................0.5 to 99,999.9 kW/kvar Dimensions WxHxD .......................................... 250 × 228 × 84 mm
Discrete inputs .............................................................................. isolated Connection ....................................................... screw/plug terminals 2.5 mm²
Input range ............................................................. 12/24 Vdc (8 to 40 Vdc) Protection system ................................................................................... IP 20
Input resistance .............................................................. approx. 20 kOhms Weight .................................................................................... approx. 2,150 g
Disturbance test (CE) ............ tested according to applicable EN guidelines
Listings .............................................. UL, cUL (cUL only for easYgen-3100)
Marine Approvals ...........................................LR, ABS, others upon request

DIMENSIONS

Plastic housing for front panel mounting (3200) Metal housing for cabinet mounting (3100)

216 mm 181 mm
227 mm

282 mm
247 mm

84 mm 250 mm

87 mm
99 mm
TERMINAL DIAGRAM

2: RxD

submin-D-connector

submin-D-connector
2: B (TxD+) Interface #2 Interface #1 3: TxD
9-pin male

9-pin male
4: B' (RxD+) 5: GND
7: A (TxD-) RS-485 (isolated) #1 RS-232 (isolated)
9: A' (RxD-) Serial #2 Serial #1 7: RTS
8: CTS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41
400 Vac
Relay 01: LogicsManager configurable
Busbar voltage (system 1) L2/N [R 01]

FlexRange
Fixed to: Ready for operation
100 Vac
Relay 02: LogicsManager configurable
400 Vac Default: Centralized alarm [R 02]
Busbar voltage (system 1) L1
Relay 03: LogicsManager configurable
100 Vac Default: Starter [R 03]
Relay 04: LogicsManager configurable
terminals:
400 Vac [R 04]
1-2
Default: Fuel solenoid / gas valve
Generator voltage N
100 Vac

400 Vac
Relay 05: LogicsManager configurable
Generator voltage L3 [R 05]
21-28
FlexRange

Default: Preglow
100 Vac

400 Vac Relay 06: Command: close GCB

LogicsManager
Generator voltage L2 (only in {1oc} or {2oc} application mode) [R 06]
100 Vac or LogicsManager configurable

400 Vac Relay 07: Command: open GCB


53-56
100 Vac
Generator voltage L1 (only in {1o}, {1oc}, or {2oc} app. mode)
or LogicsManager configurable
[R 07]
66/73
400 Vac Relay 08: Command: close MCB
Mains voltage N (only in {2oc} application mode) [R 08]
or LogicsManager configurable
100 Vac
Load 37-40
400 Vac Relay 09: Command: open MCB
Mains voltage L3 (only in {2oc} application mode) [R 09]
FlexRange

100 Vac or LogicsManager configurable

Relay 10: LogicsManager configurable


400 Vac Default: Auxiliary services [R 10]
Mains voltage L2
Relay 11: LogicsManager configurable
100 Vac [R 11]
49-52
Default: Alarm class A or B
Relay 12: LogicsManager configurable
400 Vac Default: Alarm class C, D, E, or F [R 12]

100 Vac
Mains voltage L1 66/74
-
29-36
Protective Earth PE
(isolated) Analog output [AO 02] Engine ground
(+/-10Vdc / +/-20mA / PWM)
+ +
3-8
Power supply
isolated, 8 to 40 Vdc
- -
(isolated) Analog output [AO 01] Auxiliary excitation D+ (isolated)
(+/-10Vdc / +/-20mA / PWM)
+ DI Common for terminals 67-78

+ Analog input [AI 03]


Discrete Input 01: Configurable (isolated)
Default: Emergency Stop [DI 01]
G
~
(0 to 500 Ohm / 0/4 to 20 mA)
- Discrete Input 02: Configurable (isolated)
Default: Start in AUTO [DI 02]

+ Discrete Input 03: Configurable (isolated)


[DI 03]
FlexIn

Analog input [AI 02] Default: Low oil pressure

- (0 to 500 Ohm / 0/4 to 20 mA) Discrete Input 04: Configurable (isolated)


[DI 04] 44-48
Default: Coolant temperature
Engine
+ Discrete Input 05: Configurable (isolated)
easYgen-3200 (Genset Control)

Default: External alarm acknowledgement [DI 05]


Analog input [AI 01]
- (0 to 500 Ohm / 0/4 to 20 mA) Discrete Input 06: Configurable (isolated)
Default: Enable MCB [DI 06] SC 15-20
s1 Discrete Input 07: Reply: MCB open (isol.) [DI 07]
L3 AVR
s2 Discrete Input 08: Reply: GCB open (isol.) [DI 08] 79-80
MPU
s1
Generator current
Discrete Input 09: Configurable (isolated) [DI 09] CAN #2
L2 ECU
(isolated)
s2 Discrete Input 10: Configurable (isolated) [DI 10]

s1 Discrete Input 11: Configurable (isolated) [DI 11]


L1
s2 Discrete Input 12: Configurable (isolated) [DI 12] A/D I/Os
s1
L1
Ground current
(or mains current) MPU (pickup)
+ RS-485
s2 (isolated) - SCADA
CANopen


submin-D-connector

submin-D-connector
FlexCAN

FlexCAN

2: CAN-L 2: CAN-L
9-pin male

9-pin male

Interface #4 Interface #3
3: GND
7: CAN-H CAN bus #2 CAN bus #1 3: GND
7: CAN-H CAN/RS-232
Engine level (isolated) Guidance/system level (isolated)
Subject to technical modifications. 2007-06-28 | easYgen-3000 Wiring Diagram eYg3000ww-2607-ap.SKF
ToolKit
FEATURES OVERVIEW
International
Woodward easYgen-3000 Series
PO Box 1519 Model 3100 3200
Fort Collins CO, USA
Package P1 P2 P1 P2
80522-1519
1000 East Drake Road Measuring
Fort Collins CO 80525 Generator voltage (3-phase/4-wire)    
Ph: +1 (970) 482-5811 Generator current (3x true r.m.s.)    
Fax: +1 (970) 498-3058 Mains voltage (3-phase/4-wire)    
Mains or ground current (1x true r.m.s.) #1    
Europe Busbar voltage (1-phase/2-wire)    
Woodward GmbH Control
Handwerkstrasse 29
70565 Stuttgart, Germany Breaker control logic (open and closed transition) FlexAppTM 2 2 2 2
Ph: +49 (0) 711 789 54-0 Automatic, Manual, Stop, and test operating modes    
Fax: +49 (0) 711 789 54-100 Single and multiple-unit operation    
email: stgt-info@woodward.com Mains parallel multiple-unit operation (up to 32 units)   #2   #2
AMF (auto mains failure) and stand-by operation    
Distributors & Service Critical mode operation    
Woodward has an international GCB and MCB synchronization (slipping / phase matching)    
network of distributors and Interchange (import / export control)    
service facilities. For your Load-dependent start/stop    
nearest representative, call the n/f, V, P, Q, and PF remote control via analog input or interface    
Fort Collins plant or see the Load/var sharing for up to 32 gensets    
Worldwide Directory on our Freely configurable PID controllers - 3 - 3
website. HMI
Soft keys (advanced LC display) DynamicsLCDTM - -  
Start/stop logic for diesel / gas engines    
Counters for operating hours / starts / maintenance / active/reactive energy    
Configuration via PC #3    
www.woodward.com/power
Event recorder entries with real time clock (battery backup) 300 300 300 300
Protection ANSI#
Generator: voltage / frequency 59 / 27 / 81O / 81U    
Generator: overload, reverse/reduced power 32 / 32R / 32F    
Generator: unbalanced load 46    
Generator: instantaneous overcurrent 50    
For more information contact:

Generator: time-overcurrent (IEC 255 compliant) 51    


Generator: ground fault #4 50G    
Generator: power factor 55    
Generator: rotation field    
Engine: overspeed / underspeed 12 / 14    
Engine: speed / frequency mismatch    
Engine: D+ auxiliary excitation failure    
Mains: voltage / frequency 59 / 27 / 81O / 81U    
Mains: phase shift / rotation field 78 /    
I/Os
Speed input (magnetic / switching; Pickup)    
Discrete alarm inputs (configurable) 10 10 10 10
Discrete outputs (configurable) LogicsManagerTM max. 12 max. 12 max. 12 max. 12
External discrete inputs / outputs via CANopen (maximum) 16 / 16 32 / 32 16 / 16 32 / 32
Analog inputs #5 (configurable) FlexInTM 3 3 3 3
Analog outputs (+/- 10V, +/- 20mA, PWM; configurable) 2 2 2 2
Subject to technical modifications. External analog inputs / outputs via CANopen (maximum) - 16 / 4 - 16 / 4
Display of J1939 analog values (number of SPNs) 16 - 16 -
This document is distributed for Display and evaluation of J1939 analog values (supported SPNs) - 100 - 100
informational purposes only. It is not
CAN bus communication interfaces #6 FlexCANTM 2 2 2 2
to be construed as creating or
becoming part of any Woodward RS-232/485 Modbus RTU Slave interface(s) 1/1 1/1 1/1 1/1
Governor Company contractual or Listings/Approvals
warranty obligation unless expressly UL Listing    
stated in a written sales contract.
cUL Listing   - -
We appreciate your comments LR & ABS Marine Approval    
about the content of our publica- CE Marked    
tions. Please send comments Part Numbers
including the document number
below to 1A CT inputs / front panel mounting with display #7 P/N 8440- - - 1816 1842
stgt-doc@woodward.com 5A CT inputs / front panel mounting with display #7 P/N 8440- - - 1831 1843
1A CT inputs / cabinet back mounting w/o display P/N 8440- 1818 1844 - -
© Woodward 5A CT inputs / cabinet back mounting w/o display P/N 8440- 1817 1845 - -
Spare connector kit P/N 8923- 1314 1314 1314 1314
All Rights Reserved
#1 mains or ground current selectable #5 selectable during configuration between VDO (0 to 180 Ohm, 0 to 5 bar), VDO (0 to 180 Ohm, 0 to 10 bar), VDO
#2 refer to the Application Manual 37417 for (0 to 380 Ohm, 40 to 120°C), VDO (0 to 380 Ohm, 50 to 150°C), Pt100, Resistive input (one- or two-pole, 2pt.
37258E - 2009/03/Stuttgart applications with more than 8 parallel gensets linear or 9pt. user defined ), or 20 mA (0/4 to 20 mA, freely configurable)
because of bus load limits #6 freely selectable during configuration between CANopen or J1939; request information
#3 via serial connection and ToolKit software (included) #7 a screw and a clamp kit are delivered with the unit for fastening