Professional Documents
Culture Documents
37258E
Genset Control
for Multiple
Unit Operation
The easYgen-3000 Series are control units for genset management applications. The numerous inputs and • Stand-by operation
outputs, along with a modular software structure, permit you to use the easYgen-3000 Series for a wide range
of applications with only a single part number. This includes stand-by, AMF, peak shaving, import-export, coge-
neration or distributed generation, among others. Also the easYgen-3000 Series is compatible for island, island • AMF operation
parallel, mains parallel and multiple unit mains parallel operations.
• Cogeneration (CHP)
The easYgen-3000 Series is able to control up to 32 gensets connected in a network with automatic sequenc-
ing.
The easYgen-3000 Series is available in two variants, the easYgen-3100 for cabinet back panel installation,
• Isolated & mains parallel
and the easYgen-3200 with graphical display and soft keys for front panel mounting.
FlexAppTM – This feature provides the tools to easily configure the number of operated breakers: None, GCB,
GCB and MCB.
operation
• Import/export control
LogicsManagerTM – Woodward's LogicsManager software enables to change the operation sequences and
adapt them to specific needs. The LogicsManager accomplishes this by monitoring a range of measuring val-
ues and internal states, which are combined logically with Boolean operators and programmable timers. This
enables to create and/or modify control and relay functions.
• Soft loading features
FlexInTM – The analog inputs are configurable to operate with VDO, resistive, and/or 0 to 20 mA senders.
Flexible Outputs – Speed and voltage bias outputs are configurable to function with all speed governors and • Open/closed transition
voltage regulators. The outputs can also be used as freely scalable outputs (e.g. for driving external meters).
FlexCANTM – Advanced network interfaces ensure unsurpassed control performance – from engine control up
to total plant operation. The easYgen-3000 Series is capable of working with all common industrial interfaces,
• Load sharing and load-
including CAN, RS-232, and RS-485. The multiple communication protocols permit the easYgen-3000 Series to dependent start/stop for
communicate with a vast majority of engine control units (ECUs), external I/O boards, PLCs, and modems.
CANopen, J1939, Modbus RTU, and Modem protocols are supported.
up to 32 units
DynamicsLCDTM – The adaptive and interactive 5.7", 320x240 pixel graphical LC display with soft keys and a
clear menu structure ensures intuitive user operation and navigation.
• Programmable operation
sequences
Features
• Multi-lingual capability
• Operation modes: Auto, Stop, Manual, and Load/No Load test modes via discrete input possible
• Breaker control: Slip frequency / phase matching synchronization, open-close control, breaker monitoring
• Load transfer features: open / closed transition, interchange, soft loading / soft unloading, mains parallel • CANopen / J1939 ECU
• Process and load-dependent start/stop logic for diesel and gas engines programmable for spinning or system Control
reserve with fixed or dynamic priorities.
• Real and reactive power load sharing with up to 32 units
• Remote control via interface and discrete/analog inputs for adjusting speed, frequency, voltage, power, reactive • Modbus RTU Protocol
power, and power factor set points
• Complete integrated engine and generator protection as well as mains monitoring features
• Freely configurable PID controllers for various control purposes, such as heating circuit control (CHP applica- • CE marked
tions), water level, fuel level, or pressure and/or other process values
• Special Scania S6, MTU ADEC, Volvo EMS2 & EDC4, Deutz EMR2, MAN MFR/EDC7, SISU EEM and Wood-
ward EGS02 ECU support (depending on Package) • UL/cUL Listing
• Counters for operating hours / engine starts / maintenance / active energy / reactive energy
• Configurable trip levels / delay timers / alarm classes for monitoring and protective functions • LR & ABS Marine Ap-
• Clear text display and evaluation of up to 100 J1939 analog values
• Discrete and analog I/O expansion board connectivity (Woodward IKD 1 or Phoenix Contact IL series) provals
• Front panel and PC configurable (ToolKit software)
• Multi-level password protection for access via HMI or interface
• Multi-lingual capability (English, German, French, Spanish, Chinese, Japanese, Italian, Portuguese, Turkish, Russian, Polish)
• Event recorder (300 events, FIFO) with real time clock
SPECIFICATIONS
Power supply.......................................................... 12/24 Vdc (8 to 40 Vdc) Relay outputs .................................................................................... isolated
Intrinsic consumption ..................................................................max. 17 W Contact material ...................................................................................AgCdO
Ambient temperature (operation) ....................... -20 to 70 °C / -4 to 158 °F Load (GP) ........................................................................ 2.00 Aac@250 Vac
Ambient temperature (storage) ........................ -30 to 80 °C / -22 to 176 °F 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Ambient humidity...................................................... 95 %, non-condensing Pilot duty (PD) ..................................................................................................
Voltage ...............................................................................................( /∆) 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
100 Vac [1] Rated (Vrated) ............................................69/120 Vac Analog inputs (none isolated) .............................................freely scaleable
Max. value (Vmax) ............................................86/150 Vac Type .................................................................... 0 to 500 Ohms / 0 to 20 mA
Rated surge volt.(Vsurge) ....................................................2.5 kV Resolution .............................................................................................. 11 Bit
and 400 Vac [4] Rated (Vrated) ..........................................277/480 Vac Analog outputs (isolated) ....................................................freely scaleable
Max. value (Vmax) ..........................................346/600 Vac Type ......................................................................... ± 10 V / ± 20 mA / PWM
Rated surge volt.(Vsurge) ....................................................4.0 kV Insulation voltage (continuously) ....................................................... 100 Vac
Accuracy .......................................................................................... Class 1 Insulation test voltage (1s) ................................................................. 500 Vac
Measurable alternator windings ..................... 3p-3w, 3p-4w, 1p-2w, 1p-3w Resolution ......................................... 11/12 Bit (depending on analog output)
Setting range ..................... primary .................................50 to 650,000 Vac ± 10 V (scaleable) ........................................... internal resistance ≤1 kOhms
Linear measuring range .............................................................. 1.25×Vrated ± 20 mA (scaleable) .............................................. maximum load 500 Ohms
Measuring frequency............................................... 50/60 Hz (40 to 85 Hz) Housing (3200) Front panel flush mounting .................. Plastic housing
High Impedance Input; Resistance per path ....... [1] 0.498 MΩ, [4] 2.0 MΩ Dimensions WxHxD .......................................... 282 × 217 × 99 mm
Max. power consumption per path ................................................ < 0.15 W Front cutout WxH .................................. 249 [+1.1] × 183 [+1.0] mm
Current (Isolated) Rated (Irated) ..............................[1] ../1 A or [5] ../5 A Connection ....................................................... screw/plug terminals 2.5 mm²
Linear measuring range ........................................................ Igen = 3.0×Irated Front.................................................................................... insulating surface
Imains/ground = 1.5×Irated Sealing Front .................................. IP66 (with screw fastening)
Setting range .......................................................................... 1 to 32,000 A Front .................................. IP54 (with clamp fastening)
Burden .......................................................................................... < 0.15 VA Back ...................................................................... IP20
Rated short-time current (1 s) .................................[1] 50×Irated, [5] 10×Irated Weight .................................................................................... approx. 1,850 g
Power ......................................................................................................... Housing (3100) Switch cabinet back mounting .....Sheet metal housing
Setting range ..........................................................0.5 to 99,999.9 kW/kvar Dimensions WxHxD .......................................... 250 × 228 × 84 mm
Discrete inputs .............................................................................. isolated Connection ....................................................... screw/plug terminals 2.5 mm²
Input range ............................................................. 12/24 Vdc (8 to 40 Vdc) Protection system ................................................................................... IP 20
Input resistance .............................................................. approx. 20 kOhms Weight .................................................................................... approx. 2,150 g
Disturbance test (CE) ............ tested according to applicable EN guidelines
Listings .............................................. UL, cUL (cUL only for easYgen-3100)
Marine Approvals ...........................................LR, ABS, others upon request
DIMENSIONS
Plastic housing for front panel mounting (3200) Metal housing for cabinet mounting (3100)
216 mm 181 mm
227 mm
282 mm
247 mm
84 mm 250 mm
87 mm
99 mm
TERMINAL DIAGRAM
2: RxD
submin-D-connector
submin-D-connector
2: B (TxD+) Interface #2 Interface #1 3: TxD
9-pin male
9-pin male
4: B' (RxD+) 5: GND
7: A (TxD-) RS-485 (isolated) #1 RS-232 (isolated)
9: A' (RxD-) Serial #2 Serial #1 7: RTS
8: CTS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41
400 Vac
Relay 01: LogicsManager configurable
Busbar voltage (system 1) L2/N [R 01]
FlexRange
Fixed to: Ready for operation
100 Vac
Relay 02: LogicsManager configurable
400 Vac Default: Centralized alarm [R 02]
Busbar voltage (system 1) L1
Relay 03: LogicsManager configurable
100 Vac Default: Starter [R 03]
Relay 04: LogicsManager configurable
terminals:
400 Vac [R 04]
1-2
Default: Fuel solenoid / gas valve
Generator voltage N
100 Vac
400 Vac
Relay 05: LogicsManager configurable
Generator voltage L3 [R 05]
21-28
FlexRange
Default: Preglow
100 Vac
LogicsManager
Generator voltage L2 (only in {1oc} or {2oc} application mode) [R 06]
100 Vac or LogicsManager configurable
100 Vac
Mains voltage L1 66/74
-
29-36
Protective Earth PE
(isolated) Analog output [AO 02] Engine ground
(+/-10Vdc / +/-20mA / PWM)
+ +
3-8
Power supply
isolated, 8 to 40 Vdc
- -
(isolated) Analog output [AO 01] Auxiliary excitation D+ (isolated)
(+/-10Vdc / +/-20mA / PWM)
+ DI Common for terminals 67-78
submin-D-connector
submin-D-connector
FlexCAN
FlexCAN
2: CAN-L 2: CAN-L
9-pin male
9-pin male
Interface #4 Interface #3
3: GND
7: CAN-H CAN bus #2 CAN bus #1 3: GND
7: CAN-H CAN/RS-232
Engine level (isolated) Guidance/system level (isolated)
Subject to technical modifications. 2007-06-28 | easYgen-3000 Wiring Diagram eYg3000ww-2607-ap.SKF
ToolKit
FEATURES OVERVIEW
International
Woodward easYgen-3000 Series
PO Box 1519 Model 3100 3200
Fort Collins CO, USA
Package P1 P2 P1 P2
80522-1519
1000 East Drake Road Measuring
Fort Collins CO 80525 Generator voltage (3-phase/4-wire)
Ph: +1 (970) 482-5811 Generator current (3x true r.m.s.)
Fax: +1 (970) 498-3058 Mains voltage (3-phase/4-wire)
Mains or ground current (1x true r.m.s.) #1
Europe Busbar voltage (1-phase/2-wire)
Woodward GmbH Control
Handwerkstrasse 29
70565 Stuttgart, Germany Breaker control logic (open and closed transition) FlexAppTM 2 2 2 2
Ph: +49 (0) 711 789 54-0 Automatic, Manual, Stop, and test operating modes
Fax: +49 (0) 711 789 54-100 Single and multiple-unit operation
email: stgt-info@woodward.com Mains parallel multiple-unit operation (up to 32 units) #2 #2
AMF (auto mains failure) and stand-by operation
Distributors & Service Critical mode operation
Woodward has an international GCB and MCB synchronization (slipping / phase matching)
network of distributors and Interchange (import / export control)
service facilities. For your Load-dependent start/stop
nearest representative, call the n/f, V, P, Q, and PF remote control via analog input or interface
Fort Collins plant or see the Load/var sharing for up to 32 gensets
Worldwide Directory on our Freely configurable PID controllers - 3 - 3
website. HMI
Soft keys (advanced LC display) DynamicsLCDTM - -
Start/stop logic for diesel / gas engines
Counters for operating hours / starts / maintenance / active/reactive energy
Configuration via PC #3
www.woodward.com/power
Event recorder entries with real time clock (battery backup) 300 300 300 300
Protection ANSI#
Generator: voltage / frequency 59 / 27 / 81O / 81U
Generator: overload, reverse/reduced power 32 / 32R / 32F
Generator: unbalanced load 46
Generator: instantaneous overcurrent 50
For more information contact: