Product Specification

37180J

Genset Control for


• FlexAppTM Technology
Single Unit Operation
• Flexible and
multifunctional
DynamicsLCDTM
DESCRIPTION • AMF/loss of mains
auto start/stop
I/Os
• FlexRangeTM - true RMS 3phase generator and • Complete engine,
mains voltage, measuring inputs: generator, and mains
o Rated 120 Vac (max. 150 Vac) and protection in one unit
o Rated 480 Vac (max. 600 Vac) in 1 unit
APPLICATIONS • True rms 3phase generator current/power • True rms voltage sens-
• True rms 1phase current input alternatively ing with FlexRangeTM
The 2nd Generation of genset controls is designed to and freely configurable for
provide a maximum of flexibility in a user friendly and o Mains current • True rms current/power
intuitive design with a large graphical display for various o Ground current (ground fault protection) sensing
applications. This controller is one of a series of new and • 1 speed input (magnetic/switching)
powerful genset controls (easYgen). This trend-setting • up to 8 configurable discrete alarm inputs
• kWh meter
technology offers a maximum of flexibility for each user. • LogicsManagerTM - up to 9 program. relays • Counters for engine
New technologies included are: • FlexInTM - 2 configurable analog inputs starts, operating hours,
• FlexCANTM - CAN bus communication (32 par-
FlexAppTM - This intelligent and flexible feature provides ticipants, isolated)
maintenance call
the tools to easily configure for multiple applications. The
Protection (ANSI #)
• Freely configurable
user can configure the easYgen-1000 Series for use as
• Measuring transducer/engine control [0-CB-Mode {0}] Generator / Engine: Battery voltage, discrete inputs
for start/stop and measuring conversion overspeed (12), over-/undervoltage (59/27),
• Freely configurable
• 1-breaker-control [GCB open, {1o}] over-/underfrequency (81O/U), overload (32),
above plus engine/generator protection reverse/reduced power (32R/F), unbalanced analog FlexInTM inputs
• 1-breaker-control [GCB open/close, {1oc}] load (46), definite time-overcur. (50/51), inverse • Freely programmable
above plus stand-by power applications time-overcurrent (IEC255), calculated + meas-
ured ground fault relay outputs with
• 2-breaker-control [GCB/MCB open/close, {2oc}]
above plus AMF, and open transition applications
LogicsManagerTM
Features
DynamicsLCDTM - The graphical LCD provides softkeys • FlexAppTM Technology (4 application modes) • PC and/or front panel
that vary depending on application and operation. • DynamicsLCDTM - 128×64 pixel graphical in- configurable
teractive LC display with softkeys
FlexInTM - The two analog inputs can be freely configured • Multi-lingual capability
• Start/stop logic for Diesel/Gas engines
(adaptable for each type of sensor) by the user as:
• Engine pre-glow or purge control 10 languages in 1 unit
• VDO (0 to 180Ohm [0 to 5bar/0 to 10bar]; 0 to 380Ohm [40 to
• kWh meter, kvarh meter
120°C/50 to 150°C]; 0 to 180 Ohm [0 to 100% level]; isolated (2-
pole) and non-isolated (1-pole) ground senders only) • Operating hours/start/maintenance counters
• FlexCANTM communi-
• Resistive input (Pt100 / linear 2point / user-defined 9point) • Configurable trip levels/delays/alarm classes cation (32 participants,
• 0/4 to 20 mA (linear 2point / user-defined 9point) • Push-buttons (softkeys) for direct control isolated)
• PC and/or front panel configurable
FlexCANTM - Flexible isolated CAN bus for multiple use.
• Multi-level password protection
• Modbus RTU Slave
Selectable during configuration: CANopen, or CAN
(CAL); coupling of easYlite remote annunciator; coupling • Multi-lingual capability (10 languages in 1 unit con- • 6.5 to 40.0 Vdc power
figurable: English, German, French, Italian, Spanish, Por-
of 3rd party expansion cards supported (request detailed tuguese, Russian, Turkish, Chinese, Japanese) supply
information from our sales department). • Event recorder (300 events, FIFO) with real
J1939 protocol for ECU coupling and alarm manage- time clock (battery backed; min. 6 years)
• Flush-mounting
ment, remote start/stop with ECU possible (Scania, Vol- • Modem connectivity with DPC
vo, Deutz, mtu). • CE marked
• easYlite annunciator support via CAN bus
LogicsManagerTM - A large number of measuring values, • Remote control via interface / digital signals • UL/cUL Listed
inputs, internal states or constant values can be com-
bined logically to operate a relay contact or an internal Differentiation • GL, LR Marine Approval
function. • Current input as ../5 A (standard) or ../1 A
SPECIFICATIONS
Power supply .................................................... 12/24 Vdc (6.5 to 40.0 Vdc) Discrete inputs .................................................................................. isolated
Intrinsic consumption ..................................................................max. 15 W Input range ........................................................... 12/24 Vdc (6.5 to 40.0 Vdc)
Ambient temperature (operation) ....................... -20 to 70 °C / -4 to 158 °F Input resistance....................................................................... approx. 6.7 kΩ
Ambient temperature (storage) ........................ -30 to 80 °C / -22 to 176 °F Relay outputs .................................................................................... isolated
Ambient humidity...................................................... 95 %, non-condensing Contact material ................................................................................... AgCdO
Voltage ................ (both ranges within one unit on different terminals, /∆) Load (GP) .........................................................................2.00 Aac@250 Vac
100 Vac [1] Rated (Vrated) ............................................69/120 Vac 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Max. value (Vmax)............................................86/150 Vac Pilot duty (PD) ..................................................................................................
Rated (Vphase-ground) .................................................150 Vac 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Rated surge volt.(Vsurge) ....................................................2.5 kV Analog input ..........................................................................freely scaleable
and 400 Vac [4] Rated (Vrated) ..........................................277/480 Vac Type .................................................................................................... variable
Max. value (Vmax)..........................................346/600 Vac Resolution .............................................................................................. 10 Bit
Rated (Vphase-ground) .................................................300 Vac Housing Flush ...................................Type easYpack
Rated surge volt.(Vsurge) ....................................................4.0 kV Dimensions Flush ................................ 219×171×61 mm
Accuracy .......................................................................................... Class 1 Front cutout Flush .................. 186 [+1.1]×138 [+1.0] mm
Measurable alternator windings ...................... 3p-3w, 3p-4w, 1p-2w, 1p-3w Connection ........................................................screw/plug terminals 2.5 mm²
Setting range ..................... primary .................................50 to 650,000 Vac Front.....................................................................................insulating surface
Linear measuring range .............................................................. 1.25×Vrated Protection system ...............................................with professional installation
Measuring frequency ................................................50/60 Hz (40 to 70 Hz) Front................. IP54 (with clamp fastening)
Input resistance per path..................................... [1] 0.498 MΩ, [5] 2.0 MΩ Front................. IP65 (with screw fastening)
Max. power consumption per path ................................................ < 0.15 W Back ..................................................... IP20
Current Rated (Irated) .............................. [1] ../1 A or [5] ../5 A Weight ........................................................................................approx. 800 g
Linear measuring range ............................. Igen = 3.0×Irated, Imains = 1.5×Irated Disturbance test (CE) .............tested according to applicable EN guidelines
Burden .......................................................................................... < 0.15 VA Listings ..................................................................................... UL/cUL listed
Rated short-time current (1 s) .................................[1] 50×Irated, [5] 10×Irated Marine Approvals ............................................ GL, LR , others upon request

DIMENSIONS
219 mm 61 mm
185 mm 50 mm
58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30

NOTE
Connected inductances (e.g. coils of operating current
or undervoltage tripping devices, auxiliary contactors PC
and power contactors) must be wired with an appropriate Configuration
interference protection. Port
WARNING
171 mm
136 mm

Before disconnecting the current transformer/CT secondary


connections or the connections of the current transformer/CT
at the device, ensure that the current transformer/CT
is short-circuited.
Dimensions
Cutout [WxH]:186 x 138 mm Back view
Total [WxHxD]: 219 x 171 x 61 mm 2006-09-05 | easYgen-300 Dimensions eYg300ww-3606-ab.skf Right view
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

PART NUMBERS AND ORDER CODES

Model Rated PT secondary Rated CT Part Number Description


Mounting FlexRangeTM secondary (P/N)
69/120 Vac ../5 A 8440-1809 EASYGEN-1500-55B
1500 and
277/480 Vac ../1 A 8440-1810 EASYGEN-1500-51B
WIRING DIAGRAM

The socket for the PC configuration is situated on the


back of the item.This is where the DPC has to be plugged in.
CAN-H
FlexApp / DynamicsLCD

11 12 13 9 10 3 4
FlexCAN CAN bus
CAN-L The Mode of the control can be configured
alternatively as an:
only connection {0} - Measuring transducer/engine control [0CB]
for two-pole Pickup {1o} - 1-CB-control [GCB open]
sensors is switching/inductive {1oc} - 1-CB-control [GCB open/close]
shown below: {2oc} - 2-CB-control [GCB/MCB open/close]
Analog input 1 [T1]
Sensor VDO & resistive & 0/4 to 20 mA Depending on the setting you have
Battery ground/common or
48 FlexIn different I/O's available, respectively
Drive

genset chassis ground the control can operate the breakers


Sensor Analog input 2 [T2] for protection/closing or not.
VDO & resistive & 0/4 to 20 mA
Model easYgen-1500
- P/N 8440-1750 = ../5 A
- P/N 8440-1751 = ../1 A
G

3
1

12 MCB
3

open/close

open/close
open
GCB GCB GCB
480 Vac
5 6 7 8 22 23 24 25 26 27 28 29

3 3 3 3

Generator voltage L1 3 3 3 3

120 Vac
G G G G
1 1 1 1

480 Vac S/S S/S S/S S/S

Generator voltage L2
FlexRange

120 Vac {0} {1o} {1oc} {2oc}

480 Vac Relay [R11]

48 49 50 51 52 53 54 55 56 57 58 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
Generator voltage L3 - LogicsManager or
120 Vac - Ready for operation

480 Vac Relay [R10]


Generator voltage N - LogicsManager or
120 Vac - "Command: close GCB"

../1 A or ../5 A Generator current L1 Relay [R9]


- LogicsManager or

LogicsManager
../1 A or ../5 A Generator current L2 - "Command: open MCB"

../1 A or ../5 A Generator current L3 Relay [R8]


- LogicsManager or
GND Common - "Command: close MCB"
Reply: GCB is open
=> use discrete input [D8] Relay [R7]
- LogicsManager or
- "Command: open GCB"
GCB

Command: close GCB


FlexApp

=> use relay [R10]


Relay [R6] (LogicsManager)
- Auxiliary services
Command: open GCB
=> use relay [R7]
Common (terminals 30-34)
3

Reply: MCB is open Relay [R5] (LogicsManager)


easYgen-1500 V2.1xxx (Genset Control)

LogicsManager

=> use discrete input [D7] - Diesel: Preglow; Gas: Ignition ON


Enable MCB Relay [R4]
=> use discrete input [D6] - Diesel: Fuel relay; Gas: Gas valve
MCB

Relay [R3]
FlexApp

Command: open MCB - Crank


=> use relay [R9] Relay [R2] (LogicsManager)
- Alarm class C/D/E/F active
Relay [R1] (LogicsManager)
Command: close MCB - Centralized alarm
=> use relay [R8] Discrete input [D8] - Alarm input (LogMan)
or "Reply: GCB is open" 8 NO/NC#1

Discrete input [D7] - Alarm input (LogMan)


../1 A or ../5 A 7
14 15 16 17 18 19 20 21 1 2

NO/NC#1
Mains current L1 or or "Reply: MCB is open"
Ground current Discrete input [D6] - Alarm input (LogMan)
GND
or "Enable MCB" 6 NO/NC#1

Discrete input [D5]


480 Vac
- Alarm input (LogicsManager) 5 NO/NC#1
{2oc}
#2Battery or another power supply; terminal 50 is pos. or neg. signal

Mains voltage L1 Discrete input [D4]


120 Vac 4 NO/NC#1
- Alarm input (LogicsManager)
3

480 Vac
Discrete input [D3] 3 NO/NC#1
{2oc} - Alarm input (LogicsManager)
FlexRange

Mains voltage L2
#1configurable during setup (NO/NC)

120 Vac
Discrete input [D2] 2 NO/NC#1
- Start in Auto (LogicsManager)
480 Vac
Discrete input [D1] 1 NO/NC#1
{2oc} - Emergency stop (LogicsManager)
Mains voltage L3
120 Vac Common (terminals 51 to 58) #2Battery

480 Vac 12/24 Vdc


{2oc}
Mains voltage N
120 Vac 0 Vdc
Battery
Subject to technical mocifications. 2006-12-19 | easYgen-1500 V21 Wiring Diagram eYg1500ww-5106-ap.skf
FEATURES OVERVIEW

CONTACT easYgen-1500
Configured as ... {0} {1o} {1oc} {2oc}
North & Central America 1 CB control 2 CB control
No CB 1 CB control
Tel.: +1 970 962 7331 (GCB (GCB / MCB
control (GCB open)
open / close) open / close)
SalesPGD_NAandCA@woodward.com
Measuring
South America Generator voltage (3phase/4-wire) rated 69/120 Vac    
Tel.: +55 19 3708 4800 - true rms max. 86/150 Vac    
 SalesPGD_SA@woodward.com - FlexRangeTM rated 277/480 Vac    
max. 346/600 Vac    
Europe Generator current #1 (3phase/4-wire, true RMS) ../1 A or ../5 A    
Tel. Stuttgart: +49 711 78954 510 Mains voltage (3phase/4-wire) rated 69/120 Vac ()#2 ()#2 ()#2 
Tel. Kempen: +49 2152 145 331 - true rms max. 86/150 Vac ()#2 ()#2 ()#2 
 SalesPGD_EUROPE@woodward.com - FlexRangeTM rated 277/480 Vac ()#2 ()#2 ()#2 
max. 346/600 Vac ()#2 ()#2 ()#2 
Middle East & Africa Mains current #1 (1phase/2-wire, true RMS) ../1 A or ../5 A ()#2 ()#2 ()#2 
Tel.: +971 2 6275185 Control
 SalesPGD_MEA@woodward.com
Breaker control logic FlexAppTM 0 0 1 2
Number of controlled power circuit breakers GCB open#3   
Russia
can be user configured depending on GCB open/close#3  
Tel.: +7 812 319 3007
application needs out of 4 Modes GCB/ MCB open/close#3 
 SalesPGD_RUSSIA@woodward.com
Isolated single-unit operation  
AMF (auto mains failure operation) 
China
Stand-by operation 
Tel.: +86 512 8818 5515
 SalesPGD_CHINA@woodward.com
Open transition (break-before-make) 
ATS (automatic transfer switching) 
India Accessories
Tel.: +91 124 4399 500 Softkeys (advanced LC display) DynamicsLCDTM    
 SalesPGD_INDIA@woodward.com Start/stop logic for Diesel/Gas engines    
kWh meter, kvarh meter    
ASEAN & Oceania Operating hours/start/maintenance counter    
Tel.: +49 711 78954 510 Configuration via PC #4    
 SalesPGD_ASEAN@woodward.com Event recorder with real time clock (battery backup) 300 300 300 300
Flush-mounting    
Protection ANSI#
Generator: voltage/frequency 59/27/81O/81U ()#6   
www.woodward.com Generator: overload, reverse/reduced power 32/32R/32F ()#6   
Generator: unbalanced load 46 ()#6   
Generator: definite time-overcurrent 50/51 ()#6   
Generator: inverse time-overcurrent IEC255 ()#6   
Generator: ground fault #5 ()#6   
Subject to alterations,
errors excepted.
I/Os
Speed input (magnetic/switching; Pickup)    
Subject to technical modifications. Discrete alarm inputs (configurable) 8 8 7 5
Relay outputs (configurable) LogicsManagerTM 8 7 6 4
This document is distributed for Analog inputs #7 (configurable) FlexInTM 2 2 2 2
informational purposes only. It is not
to be construed as creating or CAN bus communication #8 FlexCANTM    
becoming part of any Woodward RS-232 Modbus RTU Slave #9    
Company contractual or warranty
obligation unless expressly stated in
Listings/Approvals #10
a written sales contract. UL/cUL Listed    
LR, GL Marine Approval    
We appreciate your comments about
the content of our publications. CE Marked    
Please send comments including the
document number below to
#1 Selection during order; both ../5 A #7 selectable during configuration Example of the LogicsManager
(standard) or both ../1 A (alternatively); VDO (0 to 180 Ohm, 0 to 5 bar, 2-pole)
stgt-doc@woodward.com
#2 the mains are measured and may be VDO (0 to 180 Ohm, 0 to 10 bar, 2-pole)
displayed, but they will not be VDO (0 to 380 Ohm, 40 to 120°C, 2-pole)
© Woodward evaluated VDO (0 to 380 Ohm, 50 to 150°C, 2-pole)
#3 dedicated to a fixed relay Pt100
All Rights Reserved #4 external Woodward DPC cable Resistive input (linear 2pt. or free chart 9pt.)
required. 20 mA (0/4 to 20 mA, freely configurable)
USB connector: P/N 5417-1251 / #8 freely selectable during configuration
RS-232 connector: P/N 5417-557 or CANopen, CAN (CAL), or J1939; request info
37180J - 2013/7/Stuttgart
CAN connection by LeoPC1 software #9 external electrical isolation required (e.g. DPC
#5 calculated + measured ground current cable P/N 5417-557)
#6 possible (not dedicated to a fixed #10 contact your sales rep to find out whether your
relay) desired unit has the required approval