OPERATING MANUAL
TA110X-220
Twin Thunder 220
NOTICE FOR USE
Please read the Operation Manual carefully and follow the instructions while operating this unit.
For a long lifetime and safe running, please read this manual carefully before operating, testing
CONTENT
GENERAL SAFETY ………………………………………………………………………1
OPERATION GUIDELINES……………………………………………………………....3
SPECIFICATIONS…………………………………………………………………………6
RECOVERY METHOD……………………………………………………………………10
SELF-PURGE METHOD………………………………………………………………….11
TROUBLE SHOOTING……………………………………………………………………14
1 .GENERAL SAFETY
SECURITY LABELS
Warning
Warning means that mis-operation can lead to body injury.
Notice
Notice means that mis-operation can do harm to the unit and lower the performance of the unit,
or even make the unit unable to work properly.
For your better understanding of the security labels in this manual, we have listed the
Warning
Warning
While using electrical wire, the wire must be well connected and grounded.
Warning
Warning
Be sure the power is off before examining or repairing the recovery unit.
Warning
If the original power supply cord is damaged, choose carefully for the replacing one,
Warning
When the unit breaks down, be sure the power is off before you do any operation.
Warning
Please consider the current capacity of power supply, ammeter, electrical wire and socket.
Warning
Use only authorized refillable refrigerant tanks. It requires the use of recovery tanks
with a minimum working pressure of 4.0MPa(580psi). Do not overfill the recovery tank .Tank
is full at 80% capacity. There should be enough space incase liquid expansion. Overfilling
Warning
Always wear safety goggles and protective gloves while working with refrigerants to
protect your skin and eye from refrigerant gases or liquid. Avoid getting in touch with
Warning
Be sure that the room where you are working is thoroughly ventilated.
Notice
Notice
2
When using an electric cable ,it should be a minimum 2.0mm AWG and no longer
than 7.5 meters, or it may cause the voltage drop and damage the compressor.
Notice
Notice
The unit need to be laid horizontally, otherwise it will lead to unexpected vibration,
Notice
Notice
There is a safe valve with the recovery unit, when the high pressure switch damaged and
internal pressure above 4.0 MPa(580psi), safe valve will release pressure to ensure
safety.
OPERATION MANUAL
1. Do not mix different refrigerants together in one tank, or they could not be separated or used.
2. Before recovering the refrigerant, the tank should achieve the vacuum level: -75cmHg(29.6inHg), which is for purging
non-condensable gases. Each tank was full of nitrogen when it was manufactured in the factory, thus the nitrogen should be
3. The input and out valves must be closed, the recover/self-purge valve to position "self-purge",
the input and output fittings should be covered with protective caps when the unit is not in operation .The air moisture is harmful to
the recovery and will shorten the life span of the unit.
4. A filter drier should always be used and should be replaced frequently. And each type of refrigerant must have its own filter. For
the sake of ensuring the normal operation of the unit, please use the filter specified by our company. High quality filter drier will
5. Special-caution is needed when recovering from burnt system, and two dry filters are needed.
6. The unit has an Internal High Pressure Shut-Off Switch. If the pressure inside the system is above 3.0MPa (435psi), compressor
will automatically shut off and the red light turns on. To restart the compressor, please lower the internal pressure and press the start
When High Pressure Protection is initiated, please find out the cause and deal with it before restarting the unit.
Cause of High Pressure Protection and Trouble Shooting:
①The input value of the refrigerant tank is closed——open the valve will help solve the problem.
②The connecting hose between the recovery unit and refrigerant tank is stuck——close all the valves and replace the
connecting hose.
③The temperature of the refrigerant tank is too high, pressure is too high——give it some time to cool down and the
7. The unit has an Internal Low Pressure Shut-Off Switch and Bypass Switch. When the Bypass Switch is on“Auto”, if the
pressure inside the system is below -8inHg~ -12inHg(-20.3cmHg~-30.4cmHg), the unit will automatically shut off and the Green
Alarm Light turns on.If it needs restart the compressor, please increase the input pressure above 0.08MPa(11psi) or turn the
9. In order to gain maximum recover speed, a hose with inner diameter bigger than 4mm is recommended and the hose should
better be shorter than 1.5m.Too narrow or too long hose will reduce the recovery rate.
10. While recovering large amounts of liquid, please use the Push/Pull Mode.
11.After recovering, make sure there is no refrigerant left in the unit. Read the Purge Operation carefully. Liquid refrigerant
12. If the unit is to be stored or not used for any length of time, we recommend that it be completely evacuated of any residual
13. Connection hose with check valve is recommended, it can prevent refrigerant lose.
14. The intake port is equipped with filter screen, please wash it frequently to keep it clean.
15. The Low Pressure Gauge shows the pressure of the intake port of the compressor and the High Pressure Gauge shows the
Recovery
Rate Liquid 3.00Kg/min 3.50Kg/min 3.50Kg/min
7 Running Capacitor
Wiring diagram
7.Recovery Method
1. Turn the Input Valve Knob to position "Close", turn the Recover/Self-Purge Valve Switch
to position "Recovery", turn Bypass Switch to position "MANUAL".
2. Correctly and firmly connect the pipes (see Connection Drawing)
3. Connect the unit to the right power supply (as shown on the Name Plate), turn the power
on
7. Turn the Output Valve Switch to position "ON" to recover the liquid.
8. Please turn the Bypass Switch to position "AUTO" so that the unit will automatically stop
when finished.
Notice:
① If compressor impact occurs, turn the Input Valve Switch slowly to position
"liquid" in a clockwise direction until the impact stops, don’t let the pressure
goes below to“ 0 “, otherwise the inlet mouth can’t exhaust the gas.
②If it is difficult to start or restart after power off, please turn the input
valve to position "off", turn the power on and press the Start Button to start
the unit.
9. When liquid recovery is finished, turn the input valve to position "Open" and open the
10. The unit will automatically stop when recovery is finished, please do the purge operation
CAUTION:
After each use the unit must be purge, make sure there is no refrigerant left in the unit. Liquid refrigerant remained may
expand and damage the components.
9.Push-Pull Method
Push/Pull method only works with large systems where the liquid refrigerant is no less than 10 Kg.
CAUTION:
While using the “push/pull” method, a electric scale must be used to avoid overfilling the recovery tank. Once the siphon is
started, it can overfill the recovery tank even if the tank is equipped with a float level sensor. The siphon can continue even if the
machine was turned off. You must manually close the valves on the tank and the unit to prevent overfilling.
1.Turn the input valve switch to “Open” position, turn the self purge valve to “self-purge” position, turn the output valve to
“Open” position .
2.Correctly and firmly connect the hoses(See Connection Drawing):
3. Turn on the power and turn the bypass switch to “MANUAL” position, press the start button
to start the unit.
CAUTION:
When the scale rises to 80% capacity of the recovery tank, turn off the power right away and close all input valves and
Compressor don't 2.80%O.F.P cable and tank are not 3、Check if the hoses are well connected.
3.Lower pressure
protection,green light
Compressor can't 1、External pressure is too high 1、Lower the pressure of the unit.
the unit off, like: 2.Give the motor some time to restart
Compressor starts the motor off 5. Turn the bypass switch to “MANUAL”
but stops within a 3.80% Over Filling Protection position, turn input valve knob to “off”
few minutes shut the motor off. position, then restart the unit.
4.Revovery finished, green light 6.After cooling the circuit breaker for 5
and off.
is damaged
Warranty
Terms of Warranty
1. This product is to be repaired free of charge if a failure occurs despite proper use during the period of
warranty.
2. This warranty is valid for 1 year starting from the date of purchase.
3. In any of the following cases, this product is to be excluded from free-of-charge repair.
1) Failures incurred by improper use.
2) Failures due to handling and storage beyond its specifications.
3) Failures due to modifications or repairs not done by the manufacturer or its entrusted
technicians.
4) Failures due to consumable components.
5) Other failures not deemed to be the manufacturer’s responsibilities.
Address:
Phone number:
Dealer
Address and name:
* To the dealer: Kindly take a few minutes and fill out the above form.