Load distribution for Equip. no.

D3029-001 Footing
P

Pxe

Footing Area = 21.547 m2


Allowable Contact stress = 250 kpa
Total footing force at C.G of the footing = 5386.75 kN
Nos. of cement mixing columns = 9

Max. Axial load on improved column (P1= P/n+MLx/∑x2 )

p1 = (5386.75)/9 + (5386.75*0.507*1.5) / (3*1.52+ 3*1.52)


= 901.9 kN

P3 507mm P1
Min. Axial load on improved column (P3= P/n - MLx/∑x2)
500mm
p3 = (5386.75)/9 - (5386.75*0.507*1.5) / (3*1.52+ 3*1.52)
= 295.10 therefore no tension force is expected at the contact surface due to eccentricity Along Transverse axis