CHWP-4 (DUTY) CWP-4 (DUTY)


@ 34.4L/S @ 43 L/S
VSD VSD VSD
PT P PT P P T TT WCC-4 (DUTY) TT T P P PT P PT
225 RTON

Ø200 Ø200
ATC
T TT PT P P PT TT T
M M
F F
Ø200 Ø200

CWR-Ø500

CWS-Ø500
CHWR-Ø450

CHWS-Ø450

CHWP-3 (DUTY) CWP-3 (DUTY)


@ 34.4L/S @ 43 L/S
VSD VSD VSD
PT P PT P P T TT WCC-3 (DUTY) TT T P P PT P PT
225 RTON BY ACMV BY PLUMBING
SUB-CONTRACTOR CONTRACTOR
PRESSURE VESSEL
Ø200 Ø200 EFF. CAP. = 1000 LITER Ø150 Ø150
MAKE-UP WATER TANK
ATC EFF. CAP. = 120m3
T TT PT P P PT TT T SIZE : 10m X 12m X 1.5M (H) Ø100 Ø100
M M
PV
F F
Ø200 Ø200
P P
BASE OPTION 1

CHWP-2 (DUTY) CWP-2 (DUTY) P P POST TENDER ADDENDUM1


@ 68.8L/S WCC-2 (DUTY) @ 86 L/S
VSD
VSD 450 RTON VSD
PT P PT P P T TT TT T P P PT P PT
MWP-1 , MWP-2
@ 2.2 L/S
Ø250 Ø250
ATC
T TT PT P P PT TT T TO DRAIN

Ø80
M M Ø100 REVISION BASED ON DPA ARCHITECTURAL
Ø100 3 15/11/19 DPE DRAWINGS DATED 18/10/19 GYP
F F 2 03/06/19 SN REVISED PIPE SIZE AND TANK SIZE SN
Ø250 Ø250

CWR-Ø500

CWS-Ø500
1 21/05/19 SN CHILLER CAPACITY RECONFIGURATION SN
CHWR-Ø450

CHWS-Ø450

COOLING TOWER MAKEUP WATER TANK REV DATE NAME SUBJECT CHK'D
CHWP-1 (DUTY) CWP-1 (DUTY) AMENDMENTS
@ 68.8 L/S WCC-1 (DUTY) @ 86 L/S
VSD THIS DRAWING IS COPYRIGHT
VSD 450 RTON VSD
PT P PT P P T TT TT T P P PT P PT DEVELOPER / LANDOWNER :

CT-2 (DUTY) CT-1 (DUTY) CAPITAL DEVELOPMENT LIMITED


Ø250 Ø250 562.5 TON 562.5 TON PLOT 120-121, MINAYE YAR ROAD
F SHWE THAN LWIN INDUSTRIAL ZONE,
ATC CT-4 (DUTY) CT-3 (DUTY) HLAING THAR YAR TOWNSHIP, YANGON, MYANMAR
T TT PT P P PT TT T
M M 281.3 TON 281.3 TON
F F
Ø250 Ø250

ARCHITECT

CWR-Ø500

CWS-Ø500
FOR FUTURE
COOLING TOWER
DP ARCHITECTS PTE LTD

Ø80
6 RAFFLES BOULEVARD
#02-249 MARINA SQUARE
Ø250 SINGAPORE 039594
FOR FUTURE Ø250
CAP-OFF CAP-OFF TEL 63383988 FAX 63379989
CHILLER
FOR FUTURE FOR FUTURE
Ø250 CAP-OFF

Ø200
Ø200

Ø200

Ø150
CIVIL & STRUCTURAL ENGINEER

Ø50

Ø50

Ø50
Ø50

Ø50

Ø50

Ø50

Ø50

Ø50

Ø50

Ø50

Ø50
FOR FUTURE

Ø150
Ø250

Ø50

Ø50
EQ-Ø400
F
MAKE UP-Ø80 DP ENGINEERS PTE LTD
DRAIN-Ø150 6 RAFFLES BOULEVARD
F T T T T T T T T #02-249 MARINA SQUARE

Ø200

Ø200

Ø200

Ø200

Ø250

Ø250
Ø250

Ø250
TT TT TT TT TT TT TT TT SINGAPORE 039594
TEL 63383988 FAX 63379989
P P P P P P P P
TT TT
PT PT PT PT PT PT PT PT M&E ENGINEER

Ø150
TT TT
M M M M
P P CAP-OFF
TT TT M M M M
PT PT

Ø250

Ø250
FOR FUTURE
TT TT DP ENGINEERS PTE LTD
P P 6 RAFFLES BOULEVARD
CWS-Ø500 CWS-Ø500 #02-249 MARINA SQUARE
PT PT EXP
SINGAPORE 039594
VESSEL
CWR-Ø500 CWR-Ø500 TEL 63383988 FAX 63379989
P
MAKEUP/DEGAS KEY PLAN
Ø50 CONTROL UNIT

Ø20

Ø20

Ø20
BY ACMV BY PLUMBING
SUB-CONTRACTOR CONTRACTOR THEIK PAN STREET

Ø25 TDS & FLOW SENSOR H LANDSCAPE LANDSCAPE


LANDSCAPE
CHWR-Ø450

CHWS-Ø450

PROPOSED NEW ROAD


PH SENSOR

69TH STREET
LANDSCAPE
1755

RETAIL

LANDSCAPE
M
TO SANITARY
H

H H

PRESSURE MAINTENANCE SYSTEM DISCHARGE Ø150 BIN CTR

VILLA
N
LA

PROPOSED NEW ROAD


PROJECT:

PROPOSED 6-STOREY RETAIL MALL WITH 1


CHWR 13.5°C BIOCIDE INHIBITOR ACID BASEMENT, CARPARK AND 26 UNITS VILLA
WITH AMENITIES & BASEMENT CARPARK
AUTOMATIC CHEMICAL TREATMENT SYSTEM AT MANDALAY THATE PAN STREET
CHWS 8.0°C

REFER TO DRAWING NO: MEP-MTP-AC-SC-002


FOR CONTINUITY ON CHILLED WATER DISTRIBUTION
CHILLER PLANT SCHEMATIC DIAGRAM DRAWING TITLE:

ACMV SYSTEM
CHILLER PLANT SCHEMATIC DIAGRAM
(RETAIL)

PROPOSED 2Nos. 450RT DUTY 2Nos.RT DUTY CHILLER CONFIGURATION SCALE DATE DESIGNED DRAWN
N.T.S. MAR 2019 DPE TZA
STAGE CONTRACT CHECKED APPROVED
T GYP GYP
JOB NO. DRAWING NO. REV.
MM18E.0002 MEP-MTP-AC-R-SC-001 3
DATE OF ISSUE: NOVEMBER 2019 THIS DRAWING IS THE PROPERTY OF DP ENGINEERS PTE LTD
NO PART OF THE DRAWING MAY BE REPRODUCED IN ANY MANNER
WHATSOEVER WITHOUT PERMISSION FROM DP ENGINEERS PTE LTD

You might also like