PROJECT: ZEALAX HOTEL

BMS POINT SCHEDULE (VE VERSION)

D/O A/O DIGITAL INPUT ANALOG INDICATION SOFTWARE PROGRAM

COLD WATER DIGITAL METER READING

PH/TDS LEVEL OF CONDENSER WATER


PRESSURE DIFFERENTIAL SET POINT

BATTERY BANK VOLTAGE/CHARGING

High Level Interface with Mod-bus Com


EXTERNAL TEMP DB/WB AND %RH
WATER DIFFERENTIAL PRESSURE

HEADER RETURN TEMPERATURE


HEADER SUPPLY TEMPERATURE

START/STOP TIME PROGRAMME


SPACE RELATIVE HUMIDITY(RH)
STACTIC PRESSURE SET POINT

WATER FLOW RATE/ METERING

DAMPER POSITION INDICATION


MODULATING VALVE CONTROL

RUNNING HOUR TOTALISATION

EQUIPMENT/PLANT EFFICIENCY
DAMPER/ACTUATOR CONTROL

POWER(KW)&POWER FACTOR
MOTORISED DAMPER STATUS

CHW OUTLET TEMPERATURE

HEADER RETURN PRESSURE


HIGH / LOW SPEED CONTROL

KWH/DIGITAL POWER METER


VALVE OPEN/CLOSE STATUS

HEADER SUPPLY PRESSURE


HIGH TEMPERATURE ALARM

RETURN AIR TEMPERATURE

SUPPLY AIR TEMPERATURE

DIESEL TANK HI/LOW LEVEL


CW OUTLET TEMPERATURE
CHW INLET TEMPERATURE
TEMPERATURE SET POINT

SELECTOR SWITCH MODE

CW INLET TEMPERATURE
No. Panel name System description Code

CHW OUTLET PRESSURE

LOAD/BTU CALCULATION
POWER FAILURE ALARM
START/STOP COMMAND

2 WAY VALVE CONTROL

2 WAY VALVE STATUSE


SPEED MEASUREMENT

STATIC AIR PRESSURE

SPACE TEMPERATURE
CO2 LEVEL SET POINT

WATER FLOW SWITCH

ENERGY MONITORING
CHW INLET PRESSRE
FILTER DIRTY ALARM

MONITORING (KW/RT)

SET POINT CONTROL

EVENT PROGRAMME
WATER HIGH ALARM
TRIP/FAULT STATUS

WATER LOW ALARM

FIRE/SMOKE ALARM
VAV BOX CONTROL

OVERRIDE STATUS
DAMPER CONTROL

Valve Control On/Off

GRAPHIC DISPLAY
VAV BOX STATUS
CO2 HIGH ALARM

COMMON ALARM

TREND LOGGING
ON/OFF STATUS
VSD CONTROL

VSD STATUS
BTU METER

CO2 LEVEL
QUANTITY

CO LEVEL
VOLTAGE
AMPERE

AMPERE
Remark

I 2ND BASEMENT

1 DB-B2F Distribution boards 1 1 1 1 Power meter by Others

Common area lighting 2 X

2 MCP-ACMV1.B2F 1 1 Power meters in Mech package

Fresh air fan FAF-B2-1 1 1 1 1 0


Exhaust air fan EAF-B2-1 1 1 1 1 0
Exhaust air fan EAF-B2-2 1 1 1 1 0
Exhaust air fan EAF-B2-3 1 1 1 1 0
CO sensor 2 2

3 MCP-FP.B2F 1 1 Power meters in Mech package

Fire electrical pump FP1 1 1 0 0 0


Fire diesel pump FDP1 1 1 0 0 0
Fire jockey pump JP1 1 1 0 0 0
Fire water tank level 2 2 2

4 MCP-SP.B2F Sump pump SP1 1 1 1 1 0


Sump pump SP2 1 1 1 1 0
Sump 1 1

1 Power meter by Others

5 MCP-TP.B2F 1 1 1
Transfer pump TP1.1 1 1 1 1 0 1
Transfer pump TP1.2 1 1 1 1 0 1
Transfer pump TP2.1 1 1 1 1 0 1
Transfer pump TP2.2 1 1 1 1 0 1
Treated Water tank 2 2 2

6 MCP-WTP.B2F 1 1 1 1
Filtration pump FP 1 & 2 2 2 2 0 1 X
Filtration pump FP 1 & 2 2 2 2 0 1 X
Raw Water tank 1 1 1
Waste treatment plant 1 1 1 1 1 1 X 1 Power meters in Mech package

II 1ST BASEMENT

1 DB-B1F Distribution boards 1 1 1 1 Power meter by Others

Common area lighting 2 X

2 MCP-ACMV1.B1F 1 1 Power meters in Mech package

Fresh air fan FAF-B1-1 1 1 1 1 0


Exhaust air fan EAF-B1-1 1 1 1 1 0
jet fan JF-B1-1 1 1 1 1 0
jet fan JF-B1-2 1 1 1 1 0
jet fan JF-B1-3 1 1 1 1 0
Exhaust air fan EAF-B1-2 1 1 1 1 0
Exhaust air fan EAF-B1-3 1 1 1 1 0
Exhaust air fan EAF-B1-4 1 1 1 1 0
Exhaust air fan EAF-B1-4

Exhaust air fan EAF-B1-4

Exhaust air fan EAF-B1-4

CO sensor 4 4

III GROUND FLOOR

1 TR Transformer high temperature TR1 2 2

2 33kV Switch Board 33kV Switch gear MVSB 3 3 3

3 MSB Main switch boards MSB 2 9 2 2 2 2 12 Power meter by Others


GMS ATS board 1

4 GENERATORS Generators GE 3 0 3 Power meter by Others


Bulk oil tank 1 1
Oil pumps 2 0 2 2
Day tanks 2 2

5 DB-GF Distribution boards 1 1 1 1 Power meter by Others


Common area lighting 3 X

6 MCP-TB.GF 1 1 Power meters in Mech package

Well pump TW-1 & 2 2 2 2 2 0 2

7 MCP-ACMV1.GF Exhaust air fan EAF-GF-1 1 1 1 1 0


Exhaust air fan EAF-GF-2 1 1 1 1 0
Exhaust air fan EAF-GF-3 1 1 1 1 0
Exhaust air fan EAF-GF-4 1 1 1 1 0
Exhaust air fan EAF-GF-5 1 1 1 1 0
Fresh air fan FAF-GF-1 1 1 1 1 0 1
Fan coil unit FCU-GF-1 1 1 1 1 1 1
Fan coil unit FCU-GF-2 1 1 1 1 1 1
Fan coil unit FCU-GF-3 1 1 1 1 1 1
Fan coil unit FCU-GF-4 1 1 1 1 1 1
Fan coil unit FCU-GF-5 1 1 1 1 1 1
Air handling unit AHU-GMF-1 1 1 1 1 1 0 1 1 1 1
Air handling unit AHU-GMF-2 1 1 1 1 1 0 1 1 1 1
Air handling unit AHU-GMF-3 1 1 1 1 1 0 1 1 1 1

IV 1ST FLOOR

1 DB-1F Distribution boards 1 1 1 1 Power meter by Others


Common area lighting 2 X

V 2ND FLOOR

1 DB-2F Distribution boards 1 1 1 1 Power meter by Others

2 DB-COM.2F Fan coil unit FCU-2F-1 1 1 1 1 1 1


Fan coil unit FCU-2F-2 1 1 1 1 1 1
Fan coil unit FCU-2F-3 1 1 1 1 1 1
Exhaust air fan EAF-2F-1 1 1 1 1 0
Fresh air fan FAF-2F-1 1 1 1 1 0
Common area lighting 2 X

3 DB-RES.2F Air handling unit AHU-1F-1 1 1 1 1 1 0 1 1 1 1


Air handling unit AHU-1F-2 1 1 1 1 1 0 1 1 1 1

4 DB-KIT.2F Primary fan coil unit PAU-1F-01 1 1 1 1 1 0 1 1


Exhaust air fan EAF-1F-1A 1 1 1 1
Exhaust air fan EAF-1F-1B 1 1 1 1
Fresh air fan FAF-1F-1 1 1 1 1

5 DB-BUS.2F Fan coil unit FCU-2F-04 1 1 1 1 1 1


Fan coil unit FCU-2F-05 1 1 1 1 1 1

VI 3RD FLOOR

1 DB-3F Distribution boards 1 1 1 1 Power meter by Others

2 DB-COM.3F Fan coil unit FCU-3F-13 1 1 1 1 1 1


Fan coil unit FCU-3F-14 1 1 1 1 1 1
Fan coil unit FCU-3F-15 1 1 1 1 1 1
Fan coil unit FCU-3F-16 1 1 1 1 1 1
Exhaust air fan EAF-3F-1 1 1 1 1 0
Exhaust air fan EAF-3F-3 1 1 1 1 0
Fresh air fan FAF-3F-2 1 1 1 1 0
Fresh air fan FAF-3F-3 1 1 1 1 0
Common area lighting 2 X

3 DB-OFF.3F Fan coil unit FCU-3F-1 1 1 1 1 1 1


Fan coil unit FCU-3F-2 1 1 1 1 1 1
Fan coil unit FCU-3F-3 1 1 1 1 1 1
Fan coil unit FCU-3F-4 1 1 1 1 1 1
Fan coil unit FCU-3F-5 1 1 1 1 1 1
Fan coil unit FCU-3F-6 1 1 1 1 1 1
Fresh air fan FAF-3F-1 1 1 1 1 0

4 DB-SPA.3F Fan coil unit FCU-3F-7 1 1 1 1 1 1


Fan coil unit FCU-3F-8 1 1 1 1 1 1
Fan coil unit FCU-3F-9 1 1 1 1 1 1
Fan coil unit FCU-3F-10 1 1 1 1 1 1
Fan coil unit FCU-3F-11 1 1 1 1 1 1
Fan coil unit FCU-3F-12 1 1 1 1 1 1

5 DB-SWP.3F Swimming pool filtration pump SP 2 2 2 2


Swimming pool balancing tank 1 1 1
Swimming pool heater pump 2 2 2 2 X
Exhaust air fan EAF-3F-2 1 1 1 1 0

6 Chiller plant

MCP-CH.3F 1 1 1 1 1
Chillers CH1 ~ 3 3 3 3 3 3 3 3 3 3 3Hi 3Hi 3Hi 3Hi 3 X X X X X X X Chiller High Level Interface
Chillled water side 3 3 Hi = High Level interface
Condenser water side 3 3
Chilled water pumps CHWP1~4 4 4 4 4 4 4 4 4Hi 4Hi 4Hi 4Hi 4 X X X X X Chiller Plant Header Equipment have to
follow Singapore Green Mark Standard.
Condenser water pumps CWP1~4 4 4 4 4 4 4 4 4Hi 4Hi 4Hi 4Hi 4 X X X X X Target Kw/ton effecency 0.7 kW/ton
Cooling towers CT1~3 3 3 3 6 3 3 3 3 3 6 3Hi 3Hi 3Hi 3Hi 3 X X X X X
1T=Use data logger; Header temp sensor
Chilled water header 1 1 1T 1T X X X use touch water type with two test plug
Condenser water header 1 1 1T 1T X X X
By-pass control 1 1 1
Plant main incoming power 2 2Hi 2Hi 2Hi 2 2 Power meters in Mech package
VII 4TH FLOOR

1 DB-4F Distribution boards 1 1 1 1 Power meter by Others

2 DB-COM.4F Fan coil unit FCU-5F-6 1 1 1 1 1 1


Exhaust air fan EAF-4F-1 1 1 1 1 0
Exhaust air fan EAF-5F-1 1 1 1 1 0
Common area lighting 2 X

3 DB-MT.4F Fan coil unit FCU-5F-1 1 1 1 1 1 1


Fan coil unit FCU-5F-2 1 1 1 1 1 1
Fan coil unit FCU-5F-3 1 1 1 1 1 1
Fan coil unit FCU-5F-4 1 1 1 1 1 1

4 DB-BR1.4F Air handling unit AHU-5F-1 1 1 1 1 1 0 1 1 1 1 1 X

5 DB-BR2.4F Air handling unit AHU-5F-2 1 1 1 1 1 0 1 1 1 1 1 X

VIII 5TH FLOOR

1 DB-5F Distribution boards 1 1 1 1 Power meter by Others


Common area lighting 3 X
UPS Power supply monitoring 2

2 MCP-ACMV1.5F Fan coil unit FCU-5F-05 1 1 1 1 1 1


Heat water primary air unit HWPAU-5F-1 1 1 1 1 1 0 1 1 1 1 X
Heat water primary air unit HWPAU-5F-2 1 1 1 1 1 0 1 1 1 1 X
Heat water primary air unit HWPAU-5F-3 1 1 1 1 1 0 1 1 1 1 X
Fresh air fan FAF-5F-1 1 1 1 1 0
Fresh air fan FAF-5F-2 1 1 1 1 0
Fresh air fan FAF-5F-3 1 1 1 1 0
Fresh air fan FAF-5F-4 1 1 1 1 0
Exhaust air fan EAF-5F-2 1 1 1 1 0

3 MCP-SPF.5F Stairs Pressure fan SPF-5F 1 1 1 1 1 0 1


Duct smoke detector 1

4 SEVER ROOM Sever room RMS 1 1 1 1

IX 6TH~19TH FLOOR

1 DB-6F~19F Distribution boards 14 14 14 14 Power meter by Others

2 DB-SK-1~16(6F~19F) King guest room

Fan coil unit FCU-KR-1~16 224 0 0 0 0 Local control only


Room controller unit RCU-KR-1~16 0

3 DB-COM.6F~19F Fan coil unit FCU-6F~19F-01 14 14 14 14 14 14 14


Fan coil unit FCU-6F~19F-02 14 14 14 14 14 14 14
Fan coil unit FCU-6F~19F-03 14 14 14 14 14 14 14
Common area lighting 28 X

X 20TH FLOOR

1 DB-20F Distribution boards 1 1 1 1 Power meter by Others

2 DB-SK-1~12 King guest room

Fan coil unit FCU-SK-1~12 12 0 0 0 0 Local control only


Room controller unit RCU-SK-1~12 0

3 DB-ST-1~2 Twin guest room

Fan coil unit FCU-ST-1~2 2 0 0 0 0 Local control only


Room controller unit RCU-ST-1~2 0

4 DB-ES-1 Executive suite guest room

Fan coil unit FCU-ES-1 1 0 0 0 0 Local control only


Fan coil unit FCU-ES-2 1 0 0 0 0 Local control only
Room controller unit RCU-ES-1 0

5 DB-COM.20F Fan coil unit FCU-20F-01 1 1 1 1 1 1 1


Fan coil unit FCU-20F-02 1 1 1 1 1 1 1
Fan coil unit FCU-20F-03 1 1 1 1 1 1 1
Common area lighting 2 X

XI 21TH FLOOR

1 DB-21F Distribution boards 1 1 1 1 Power meter by Others

2 DB-ES-1~4 Executive suite guest room

Fan coil unit FCU-ES-1~2(1~2) 4 0 0 0 0 Local control only


Fan coil unit FCU-ES-3~4(1~2) 4 0 0 0 0 Local control only
Room controller unit RCU-ES-1(1~4) 0

3 DB-COM.21F Fan coil unit FCU-21F-01 1 1 1 1 1 1 1


Fan coil unit FCU-21F-02 1 1 1 1 1 1 1
Fan coil unit FCU-21F-03 1 1 1 1 1 1 1
Common area lighting 2 X

4 DB-KIT.21F Primary fan coil unit PAU-21F-01 1 1 1 1 1 0 1


Exhaust air fan EAF-RF-1 1 1 1 1 0
Fresh air fan FAF-RF-1 1 1 1 1 0

5 DB-RES.21F Fan coil unit FCU-21F-04~10 7 7 0 7 7 7 0 Local control only

XII ROOF FLOOR

1 DB-RF Distribution boards 1 1 1 1 Power meter by Others

2 DB-COM.RF Exhaust air fan EAF-RF-2 1 1 1 1 0


Exhaust air fan EAF-RF-3 1 1 1 1 0
Common area lighting 3 X

3 MCP-FL.RF Fire lift FL1 1 0

4 MCP-PL.RF Passenger lift PL1 ~ 4 4 0

5 MCP-SPF.RF Stairs Pressure fan SPF-RF 1 1 1 1 1 0 1

6 MCP-FP.RF 1 1 1 1 Power meter in Mech package


Fire electrical pump FP1 1 1 0 0 0
Fire electrical pump FP2 1 1 0 0 0
Fire diesel pump FDP1

Fire diesel pump FDP2 1 1 0 0 0


Fire jockey pump JP1 1 1 0 0 0
Fire water level 2 2 2

7 MCP-BP.RF Booster pump BP1 ~ 2 2 2 2 0 2


Booster pump BP3 ~ 4 2 2 2 0 2

8 MCP-HWP.RF Hot water circulatiom pump HWCP-1 ~ 2 2 2 2 2 2 X


Hot water circulatiom pump HWCP-3 ~ 4 2 2 2 2 2 X
Heat pump circulation pump HWP-1 ~ 2 2 2 2 2 2 X
Heat pump circulation pump HWP-3 ~ 5 3 3 3 3 3 X
Low Zone Hot water return pipe 1 1 X
High Zone Hote water return pipe 1 1 X

9 MCP-HWEC.RF Hot water electric calorifiers HWEC-1 ~ 5 5 5 5 5 5 5 5 1 X Power meter in Mech package

10 MCP-ASHP.RF Air- source heat pump ASHP-1 ~ 5 5 5 5 5 0 5 5 X

11 AIR-CON Make-up water pump MUMP-1~2 2 2 2 2 0 2


Make-up water tank 1 1 1
Chilled waetr expansion tank 1 1 1

12 WEATHER STATION 1 1

Total 532 233 7 0 0 93 0 13 5 2 0 0 0 12 0 245 232 14 11 0 13 15 13 12 0 2 0 1 8 0 31 0 2 1 3 3 0 0 3 3 10 7 0 0 97 0 1 3 0 12 3 3 3 49 0 3 0 0 0 0 0 0 1 6 68 0 0 0 0 0 0 0 0 1


240 125 597 213 69