3 4MAU10CT351 Main tank oil ℃ >35 Automatic stop lubricating oil heater
4 4MAU10CT352 Main tank oil ℃ >35 Automatic stop lubricating oil heater
5 4MAU10CP207 LUBE OIL PRESSURE L Mpa 0.049 PSA1 lubricating oil pressure alarm
LUBE OIL PRESSURE LOW START
6 4MAU10CP201 Mpa 0.049 PSA2 lubricating oil pump down start exchange
AC LUBE OIL PUMP
LUBE OIL PRESSURE LOW START
7 4MAU10CP202 Mpa 0.039 PSA3 DC lube oil pump lubricating oil pressure started
DC EMERGENCY OIL PUMP
PSA4 lubricating oil pressure shutoff
8 4MAU10CP209 LUBE OIL PRESSURE LOW TRIP MPa 0.039
(two out of three)
PSA5 lubricating oil pressure shutoff
9 4MAU10CP210 LUBE OIL PRESSURE LOW TRIP MPa 0.039
(two out of three)
PSA6 lubricating oil pressure shutoff
10 4MAU10CP211 LUBE OIL PRESSURE LOW TRIP MPa 0.039
(two out of three)
LUBE OIL PRESSURE LOW STOP
11 4MAU10CP212 MPa 0.029 PSA7 lubricating oil down to stop cranking
JIGGER
4 4MAU10CP204 JACKING OIL PUMP B INLET PRESS Mpa ≤0.03 Stop the pump inlet oil ≤0.03Mpa
(TURBINE TSI)
LEFT HP CYLINDER HOT
13 4MAA00HE001 mm Monitoring
EXPANSION
14 4MAA00KP001 KEY PHASE mm no
1 4MAG10CL001 CONDENSER HOT WALL WATER LEVEL mm >800 Start condensate pump
3 4MAG10CL202 CONDENSER HOT WALL WATER LEVEL mm <200 Trip condensate pump
℃ <110 Alarm
A condensate pump motor stator
8 4LCB10CT354-359
temperature
℃ >120 Trip
mm <300 Alarm
℃ >90 Trip
Circulating water pump motor
5 0PAA10CT707-708
thrust bearing temp.1
℃ <80 Start pump
SOURCE OF SETTING
VALUES