Che c k Val v es
The Tideflex ®
Check Valve:
For Reliable Backflow Protection!
In 1984, the U.S. Environmental Protection Agency commissioned
Red Valve Company to develop and test an alternative to
flapgate valves, stating that, “Increasing the reliability
and performance of tidegates has a beneficial impact
on the general pollution abatement program for the
nation’s waterways.” The elastomer “duckbill”
Tideflex® Check Valve was specifically designed
to eliminate the operational and maintenance
problems associated with flapgate check valves,
including corrosion of mechanical parts, freezing
open or shut, warping
and clogging due to trapped debris. The EPA rigorously tested the Tideflex®
valve for two years and found that Tideflex® showed significant improve-
ment over flapgate valves in terms of leakage inflow, entrapment of
debris, capability to self clean and susceptibility to marine fouling.
Today, hundreds of thousands of Tideflex® valves are installed and
performing reliably worldwide.
Tideflex : The World’s Most Effective
®
Check Valve!
Engineered
Features:
P No moving or
mechanical parts.
P 100% elastomer
construction—completely
corrosion-proof.
P 25-50 years estimated
service life.
P Closes around solids
and debris.
P Extremely low headloss
for low-lying areas.
P Sensitive enough to 3
open with as little as 1"
Introducing the New Curved Bill Tideflex®! of water pressure.
Red Valve is committed to continually improving upon our products. The P Custom-built to your flow
specifications.
new Curved Bill Tideflex® is the latest example of that commitment. P Sizes ranging from 1/2"
to 96" diameter.
The Curved Bill Tideflex® uses the same construction for the body of the
P Cost-effective, reliable
replacement for traditional
valve as the traditional Tideflex® Check Valve but has a bill that is thinner flapgates.
and more resilient. The bill is formed in a 180-degree curve that returns to P Silent, non-slamming.
P Curved-bill design
the closed position even more naturally than a enhances sealing.
P Self-draining, eliminates
straight bill. The curved bill increases the
standing water.
Effluent
Discharge
Tide
4
Tideflex® valves protect
discharge lines from rising
waters that can flood and
surcharge a treatment plant.
Techn
Ecosystems are also protected
by the Tideflex® Check Valve’s
ability to diffuse effluent and
Engine
prevent backflow.
Reli
Airport/Highway Runoff Perfor
Tideflex® valves are used extensively for large
surface water areas that require backflow
prevention, such as airport runways, highways
and parking lots. Tideflex® provides an ideal
solution where regulations require treatment
of toxic hydrocarbons from runoff.
CSO/SSO
Systems
Combined sewer and sanitary
sewer overflow systems use
Tideflex® valves to prevent
receiving water from
backflowing to the sewage
treatment plant. The new
flat-bottom TF-1 is designed for
CSO/SSO manhole installations.
Stormwater
Discharge
Tideflex® Check Valves are
the first choice of coastal and
inland municipalities for
stormwater systems. Tideflex®
valves discharge with 1" of differ-
ential pressure, which maximizes
pipeline storage capacity.
flex ®
Site Drainage
ered for
backflow and flooding from
canals, streams and rivers.
able
mance.
Flood Control Systems
Tideflex® valves are used extensively for flood control. They can
sit inactive for years and still be ready to provide backflow
protection in the event of a flash
flood. Typical applications include
retention basins, levees, locks
and dams, fish bypass systems,
city stormwater collection
systems, highways, parking
lots, airport runways
and large industrial
and office complexes.
Floatables Control
Tideflex® valves are used as part of a
floatables control strategy to prevent
accumulated debris from being washed
out of collection areas by floodwaters.
Sandy Beaches
Sand, silt, rocks, vegetation and
marine growth that render traditional
flapgate valves inoperable are no
problem for the Tideflex® Check Valve.
Even partially buried in sand, the
Tideflex® valve can continue to
Marinas
operate, eroding away the sand
when open and keeping it from
clogging the pipe when closed.
Tide
6
Marinas and discharge lines can peacefully
coexist because the rubber construction
Engine
Mainten
of the Tideflex® valve is quiet, safer to
boat hulls than a rigid metal valve
and resistant to spills such as
oil and fuel.
Operati
Levees
Enviro
Low-lying areas protected by levees depend on
Tideflex® valves to prevent high water levels from Groundwater Relief
backflowing from the river and allow stormwater to Inground storage basins use
freely drain into the river. The low cracking pressure Tideflex® valves to relieve
of the valve allows easy draining even when little pressure from groundwater.
difference in elevation exists. The valves allow groundwater
to enter the basin while
preventing stored fluid
from escaping. Tideflex®
valves can be fitted to
concrete basins, steel
tanks and even
geotextile liners.
Odor Control
Offending odors from sewer systems
can be prevented from escaping with
lightweight Tideflex® valves while
water is still allowed to discharge
when needed.
Coastal Discharge
Rocky areas cause problems for a
flapgate valve because stones become
lodged in the valve, preventing it from
closing fully, or pile up in front of the
valve, preventing it from opening.
Tideflex® valves installed in these areas
completely eliminate these problems
for maintenance-free operation.
flex :
®
nment!
Residential
Tideflex® Check Valves have become frequently specified
for commercial and residential areas where dependable
backflow prevention is necessary. The valve is maintenance-
free. Passive and silent operation are key benefits.
Wetlands
Tideflex® valves prevent hazardous
spills, runoff from mining operations,
leachate from landfills and saltwater
from infiltrating protected wetland areas.
Tideflex in Drinking Water ®
8 Ti d e f l e x ® M i x i n g S y s t e m s f o r R e s e r v o i r s
The Tideflex® Mixing System was designed holds the “drain” valves closed on the Figure A: filling sequence
,,
to be simple, reliable and cost effective. The opposite side. The Tideflex® Check Valve
,
system makes use of the patented Tideflex® increases the jet velocity of the discharge,
,,
,
Check Valve and a simple piping manifold increasing mixing. When the reservoir is
within the tank. This reduces cost by drained (Figure B), the head pressure above
,,
minimizing the amount of pipe and fittings the manifold holds the discharge valves
required for a separate inlet and outlet. By closed and forces the drain valves to open.
discharging water from one side of the This two-stage system ensures that the
reservoir and draining from the other, the water is continually cycled.
system ensures that the water supply is
The simplicity of the system makes it reli-
constantly “turned over” to avoid stagnation
able, with no moving parts, electric motors,
and dead zones.
bearings or seals to maintain. There is no
The mixing system works in two phases. additional energy consumption and no equip-
When the reservoir is being filled (Figure A), ment exposed to the elements. The system Figure B: draining sequence
the pressure of the water in the manifold can be fitted as part of a new construction or
forces the “discharge” valves to open and easily retrofitted to an existing reservoir.
System:
P Eliminates short circuiting,
stagnation and “dead zones.”
P Minimizes the amount of pipe
and fittings required for a separate
inlet and outlet.
,,,
,,,
NSF-61-approved elastomers.
,,,
,,,
Mixed Water
filled and drained from a single location. Red Valve
designs custom mixing
arrangements for elevated
P Operates on differential
storage tanks. pressure; no external energy
source required.
Custom “T” P Can be designed for new and
configuration
for tank mixing. retrofit applications, standpipes
and elevated tanks.
P Flanged, slip-on or custom
Tideflex® valves are installed on overflow pipes to configuration. Systems 1/8" - 96".
prevent birds, insects and rodents from entering
the storage tank and contaminating the water supply.
Proven
Performance On:
P Circular reservoirs.
P Rectangular reservoirs.
P Elevated storage tanks.
P Standpipes.
Consulting Engineers Worldwide
35SQ square
35D with flange
90° elbow
Tideflex ®
Diffuser Valves:
P Prevent intrusion of debris,
sediment, saltwater and
aquatic life.
P Provide proven long-term,
maintenance-free service life.
P Enhance jet velocity.
P Improve initial dilution.
P Provide a more uniform flow
distribution across ports.
P Promote significant improve-
(12) 6 " Tideflex Diffuser Valves with integral three-
®
ment in saltwater purging.
foot-long rubber risers discharging to a shallow river.
11
SOLUTION
35D with
rubber riser
Tideflex Air Diffusers Are Revolution
®
DuPage County,
Ill., solved its
continual problem
of clogging by
12 replacing its
high-maintenance,
fine-membrane
panels with
Red Valve’s Air
Diffuser System.
Bubble Diffusers:
P Optimize oxygen transfer
and mixing characteristics.
P Provide proven long-term,
maintenance-free service life.
P Provide reliable
backflow prevention.
P Prevent clogging and
fouling—no jet wash or
acid baths required.
P Offer durable, heavy-
duty construction.
13
Proven
Performance On:
P Aeration basins.
P Sludge-holding tanks.
P Equalization basins.
P Aerated grit chambers.
P Pre-/post-aeration processes.
P Channels.
P Aerobic digesters.
P Flocculation.
P Storage tanks.
P Landfill odor control systems.
P Industrial mixing systems.
CORRUGATED • CLAY • CONCRETE • PVC
Series TF-2
Ther
Tidefle
Engin
14
Thimble Plate
Where the pipe terminates flush with a headwall,
for E
Piping
a plate is secured over the opening, and the Tideflex®
valve is slipped onto the pipe thimble. This mounting
can also be used to cover square culverts and
oversized openings.
Integral Rubber
Flange
An integral rubber flange allows
direct connection to flanged-end
pipe or headwalls and seawalls.
Flanges can be ANSI, DIN or
special drill patterns,
Series 35 including square and
rectangular. Backup
rings are provided,
and gaskets are not
required.
• HDPE • ELLIPTICAL • DUCTILE • STEEL
e’s a
x Valve
®
eered
15
Series 37
Series 37G
Thimble Insert
FLOW A thimble insert is used to add a Tideflex® valve
to the influent pipe of a manhole whenever
clearance is not sufficient to allow the valve to
protrude into the manhole. The assembly is
inserted into the influent pipe and anchored to the
manhole wall. This assembly can also be used at the
end of a pipe where protrusion into a waterway is
not desired.
Series TF-2
P 100% elastomer construction Red Valve’s Tideflex® Check Valve has a revolutionary design for backflow pre-
vention. It offers low cracking pressure to eliminate standing water and very low
P Will not rust or corrode
headloss that is not affected by rust, corrosion or lack of lubrication. Tideflex®
P Will not warp or freeze open or shut Check Valves are cost-effective because they require no maintenance or repairs
P Custom-built to customer specifications and have a long operational life span. Tideflex® operate using line pressure and
backpressure to open and close so no outside energy source is required. Sliding,
P Low cracking pressure, low headloss rotating, swinging and plunging parts are completely eliminated.
P Eliminates backflow Tideflex® valves are excellent replacements for ineffective metal flapgate valves.
Millions of dollars each year are lost in the re-treatment of unnecessary backflow
because of faulty check valves that have corroded open or have been wedged
open by debris. Tideflex® Check Valves close drop-tight and seal around debris
with less than one psi of backpressure. Tideflex® valves will not warp or freeze
and are virtually maintenance free. They will handle large obstructions without
jamming, and there is no gate to hang open.
The inside diameter of the TF-2’s cuff is constructed to exactly match the
outside diameter of the pipe.
16 The valve is slid onto the pipe and held in place with steel or stainless steel
band clamps, eliminating flanging costs. Tideflex® TF-2 valves 18" and larger
Materials of Construction are constructed with a curved bill as standard.
L
Neoprene, Hypalon®, Buna-N, EPDM, Viton®
and NSF-61-approved SBR.
A H
Mounting Bands
Carbon steel or stainless steel. C
Pipe O.D. Length Bill Height Cuff Length Pipe O.D. Length Bill Height Cuff Length
(A) (L) (H) (C) (A) (L) (H) (C)
3/4 3 1 1/2 1 28 39 37 8
1 3 1 1/2 1 30 42 50 9
1 1/2 6 3 1 32 48 53 10
2 6 4 1 36 49 61 10
2 1/2 8 5 1 38 49 61 10
3 9 5 1/2 1 1/2 40 49 61 10
4 12 7 1 1/2 42 54 71 10
5 15 1/2 9 2 44 54 71 10
6 16 10 1/2 2 48 59 78 10
8 16 1/2 13 2 50 59 78 10
10 21 1/2 17 3 54 69 97 10
12 26 1/2 20 1/2 4 1/2 58 69 97 10
14 26 22 4 60 74 97 14
16 26 27 5 68 74 97 14
18 30 29 6 72 95 115 16
20 33 33 8 84 92 111 16
22 36 33 8 90 101 119 16
24 39 37 8 92 101 119 16
26 39 37 8 96 101 119 16
Numbers indicate maximum dimensions in inches.
Series TF-1
P Ideal for manhole installations The TF-1 is designed for installation in existing structures such as interceptors,
manholes and vaults. These structures are designed to maintain the maximum
P Minimal bottom clearance required
amount of head pressure from gravity; thus, the invert pipe is as close to the floor
P Lightweight, all-elastomer design or base of the structure as possible. The flat-bottom and offset-bill design of the
P Seals around entrapped solids TF-1 allows it to be installed without any modifications to the structure.
P Available in slip-on or flanged design The TF-1 offers low cracking pressure to eliminate standing water and very low
headloss that is not affected by rust, corrosion or lack of lubrication. Tideflex®
Check Valves are cost-effective because they require no maintenance or repairs
and have a long operational life span. Tideflex® operate using line pressure and
backpressure to open and close so no outside energy source is required. Sliding,
rotating, swinging and plunging parts are completely eliminated.
The TF-1 is ideal for sewer systems because it will seal around small debris with
less than one psi of backpressure. Tideflex® valves will not warp or freeze and are
virtually maintenance free. The TF-1 design is available with a slip-on or flanged
pipe connection. Tideflex® TF-1 valves 18" and larger are constructed with a
curved bill as standard.
TF-1 L 17
Materials of Construction
Neoprene, Hypalon®, Buna-N, EPDM, Viton® H
A
and NSF-61-approved SBR.
H
F
TF-1 35-1
Pipe O.D. Cuff Length Flange Size Flange O.D. Length Bill Height
(A) (C) (ANSI) (F) (L) (H)
4 1.5 4 9 10 8
6 2 6 11 14 11 1/2
8 2 8 13 1/2 17 1/2 15 1/2
10 3 10 16 21 1/2 19
12 4 12 19 26 22 1/2
16 5 16 23 1/2 32 30
20 8 20 27 1/2 42 37
24 8 24 32 46 43
30 9 30 38 3/4 56 55
36 10 36 46 65 69
42 10 42 53 60 71
48 10 48 59 1/2 65 78
60 13 60 73 73 91
72 16 72 86 1/2 84 110
Numbers indicate maximum dimensions in inches.
Series 35
P Integral, all-rubber flange In some applications and installations, a slip-over pipe check valve (TF-2) is not
feasible because of an existing flange in the piping system or an existing flange
P Lightweight, all-elastomer design
cemented in the outfall piping system vault. In these cases, the Series 35 Check
P Seals around entrapped solids Valve is the solution. The Tideflex® Series 35 Check Valve is manufactured with
P Cost-effective, maintenance-free design an integral elastomer flange as part of the valve. The flange size drilling con-
forms to ANSI B 16.10, Class 150#, or can be constructed with DIN, 2632 and
other standards. The Series 35 Check Valve is furnished complete with steel or
stainless steel backup rings for installation.
The Series 35 is often a direct replacement for flanged flapgates. Hinge pins
rust and corrode if not routinely lubricated, causing the flapper to hang open
and allow backflow. Small debris that collects in the seating area of the valve
will also keep the flapper open. Millions of dollars each year are lost in the
re-treatment of unnecessary backflow because of these faulty check valves.
Tideflex® Check Valves require no maintenance and will seal around debris with
less than one psi of backpressure. Tideflex® valves will not warp or freeze. Tideflex®
Materials of Construction Series 35 valves 18" and larger are constructed with a curved bill as standard.
Neoprene, Hypalon®, Buna-N, EPDM, Viton®
and NSF-61-approved SBR.
18
Backup Rings
Galvanized steel or stainless steel.
F H
Flange Size Flange O.D. Length Bill Height Flange Size Flange O.D. Length Bill Height
(ANSI) (F) (L) (H) (ANSI) (F) (L) (H)
1/2 3 1/2 2 1/2 1 1/2 16 23 1/2 26 27
3/4 3 7/8 3 1 1/2 18 25 30 29
1 4 1/4 3 1 1/2 20 27 1/2 33 33
1 1/2 5 6 3 22 29 1/2 36 33
2 6 6 4 24 32 39 37
2 1/2 7 8 5 30 38 3/4 42 50
3 7 1/2 9 5 1/2 32 41 3/4 48 53
4 9 12 7 36 46 49 61
5 10 15 1/2 9 42 53 54 71
6 11 16 10 1/2 48 59 1/2 59 78
8 13 1/2 16 1/2 13 54 66 1/4 69 97
10 16 21 1/2 17 60 73 74 97
12 19 26 1/2 20 1/2 72 86 1/2 95 115
14 21 26 22 84 99 3/4 92 111
Numbers indicate maximum dimensions in inches.
Series 37
P Fits inside pipe diameter The Series 37G is designed to allow a Tideflex® Check Valve to be installed in a
pipe that is buried or otherwise inaccessible. The outside diameter of the Series
P Eliminates digging and construction
37G is custom-built to match the inside diameter of the pipe. The valve is slipped
P Lightweight, all-elastomer design into place and secured by means of an expanding steel clamp. This allows check
P Custom-built to customer specifications valves to easily be added to pipes from inside a manhole to prevent backflow into
the structure.
The Series 37G has a low cracking pressure, but headloss will be increased
relative to the original pipe due to the smaller effective inside diameter. Red Valve
also recommends pinning the valve to the pipe to further secure the valve,
especially where smooth-walled steel or plastic pipe is being used.
The Series 37G is ideal for CSO and SSO systems, with an all-rubber construction
that will not rust or corrode. The valve will not hang open on entrapped debris,
Series 37 and it provides a tight seal. The Series 37G requires no routine maintenance and
provides the proven backflow prevention performance of a Tideflex® Check Valve.
37
Materials of Construction
Neoprene, Hypalon®, Buna-N, EPDM, F H
Viton® and NSF-61-approved SBR. 19
Expansion Band L
Galvanized steel or stainless steel. L
37G
Series 37G A H
1 Select Model: Choose the model that best suits your application,
installation and space requirements.
2 Supply Dimensions: The exact outside diameter of pipe is
required for slip-on valves, TF-2, TF-1; the inside diameter for
slip-in valves, Series 37G, or flange drilling details for flanged
valves, Series 35-1, Series 35, Series 37.
3 Calculate Backpressure: Specify the amount of backpressure
the valve has to withstand, most commonly supplied in feet of head.
www.redvalve.com
FIRST CLASS
Model: Backpressure:
■ Series 35-1 ■ Series 35 ■ Series 37 Flange:
Postage will be paid by addressee:
Name
Title
Company
Address
UNITED STATES
NO POSTAGE
NECESSARY
IF MAILED
Telephone