Flat Slab
Flat Slab
1.6
6.4
column strip
3.2
6.4
3.2
6.4
Middle strip
1.6
1.8 3.6 3.6 3.6 1.8
9 Load calculations
2
Self wt. of slab = 6 KN/m
Floor finishes = 0.45 KN/m2
Live Load = 4 KN/m2
2
Total load, w = 10.45 KN/m
Ultimate design load, wu = 16.511 KN/m2
All the requirements are satisfied and, therefore, direct design method
can be used
11 Drop
Minimum dimensions of drop in each direction
Length of drop along long span L1/3 = 2.4 m
Length of drop along long span L2/3 = 2.1333 m
Size of drop is conveniently selected such that it lies
along the column strips.
Minimum width of column strip = 3.2 m
Provide drop size 3.2m x3.2m
Thickness of drop Thickness of slab/4 = 60 mm
Total thickness of drop, required = 300 mm
Total thickness of drop, provided = 350 mm
Eff. Thicness = 324 mm
12 Design moments in longitudinal direction
Mo = wu L2 Ln2/ 8
Ln = L1 - 0.89D
= 6799.5 mm > 4680 mm
Ln = 6799.5 mm
Mo = 610.69 KN.m
13 Edge Beam
Beam must have a beam stiffness parameter αc > 0.8
450 3900
240
240
600
300
C.g from top of L-beam, yt = 270 mm
C.g from bottom of L-beam, yb = 330 mm
Second moment of area of beam,Ib = 6.54E+09 mm4
For the edge beam along the long edge,
Second moment of area of slab,Is = 4.493E+09 mm4
αb = Ib/Is
= 1.46 > 0.8
O.K
For the edge beam along the short edge,
Second moment of area of slab,Is = 3.341E+09 mm4
αb = Ib/Is
= 1.96 > 0.8
O.K
14 Distribution of total design moments in longitutinal direction as panel moment
Ratio, αc = εkc/ks
Equalent side of column(if column has circular c/s) = 450 mm
εkc = 2 x (4EIc/Lc)
= 8E+06 E N.mm
ks = 4EIs1/Ls1
= 4E+06 E N.mm
αc = 1.9923
factor, β = 1+1/αc
= 1.5019
A) Exterior Panel (Panel Moments)
Total Negative moment at exterior support = 0.65 x Mo/β
= 264.29 KN.m
Total Negative moment at Interior support = (0.75 -0.1/β)x Mo
= 417.35 KN.m
Total Positive Moment at mid span = (0.63-0.28/β) x Mo
= 270.88 KN.m
B) Interior Panel (Panel Moment)
Total Negative Moment = 0.65 Mo
= 396.95 KN.m
Total Positive moment = 0.35 Mo
= 213.74 KN.m
Distribution of Longitudinal Panel Moments into Strip Moments
(A) Exterior Panel ( Strip moments)
a) Negative Panel moment
Negative moment at the exterior support in to be taken fully
by colum strip, = 82.59 KN.m
Negative panel moment at the interior support is distributed
in the transverse direction
Negative moment in the column strip = 97.817 KN.m
Negative moment in the middle strip = 32.606 KN.m
b) Total Positive Panel moment is dist. In trans. Dn
Positive moment in the column strip = 50.791 KN.m
Positive moment in the middle strip = 33.86 KN.m
(B) Interior Panel moment (Strip moment)
a) Total -ve Panel moment
Negative moment in the column strip = 93.034 KN.m
Negative moment in the middle strip = 31.011 KN.m
b) Total Positive Panel moment
Positive moment in the column strip = 40.076 KN.m
Positive moment in the middle strip = 26.717 KN.m
17 Moment distribution
long direction (column strip)
20 Bar dia/Spacing
long direction (column strip)
12 90c/c 12 70c/c 80c/c 12 80c/c 80c/c
10 110c/c 10 140c/c
d/2
d/2
c1 d/2
c2
3.2
d/2
Gcd Gab d/2
cGD d/2
c1/2 g
Perimeter along the critical section = 2a1+a2
= 1998 mm
Design shear at critical section = 379.94 KN
Area at critical section = 647352 mm2
GAB = 187.46 mm
GCD = 424.54 mm
g = 199.54 mm
Jc = 2da12/13 + 2a1d3/12 + a2d x GAB2+2a1d(a1/2-GAB)2
= 3.023E+10 mm4
ζmax = Vu/Ac + (1-α)(Mu-Vuxg)GAB/ Jc
2
= 0.9616 N/mm
ζuc = 1.118 mpa
= Safe