Professional Documents
Culture Documents
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
Freestanding cartridge filters.
Carbon filters.
Multimedia sand filters.
Ultra violet sterilizing unit
Aircrafts Blue and Potable Water Treatment
Aircrafts Blue and Potable Water Pop-Up Pits
B. Related Sections:
1. Division 22 Section "Domestic Water Piping Specialties" for plumbing piping strainers.
A. Seismic Performance: freestanding cartridge filters, carbon filters, and multimedia sand filters shall
withstand the effects of earthquake motions determined according to ASCE/SEI 7.
1. The term "withstand" means that "the unit will remain in place without separation of any parts
from the device when subjected to the seismic forces specified and the unit will be fully
operational after the seismic event.
A. Product Data: For each type of product indicated. Include construction details, material
descriptions, dimensions of individual components and profiles, and finishes for filters and
separators. and Include rated capacities, operating characteristics, electrical characteristics, and
furnished specialties and accessories.
B. Shop Drawings: For water filtration equipment. Include plans, elevations, sections, details, and
attachments to other work.
Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of
field assembly, components, and location and size of each field connection.
Wiring Diagrams: For power, signal, and control wiring.
A. Seismic Qualification Certificates: For freestanding cartridge filters, carbon filters, multimedia sand
filters , accessories, and components, from manufacturer.
B. Certificates of Shop Inspections and Data Reports: For products required to have ASME label,
signed by product manufacturer.
C. Welding certificates.
A. Operation and Maintenance Data: For water filtration equipment to include in emergency, operation,
and maintenance manuals.
A. Furnish extra materials that match products installed and that are packaged with protective covering
for storage and identified with labels describing contents.
1. Cartridge-Filter Elements: Elements for cartridge filters equal to 200] percent of amount
installed for each size and media indicated.
A. Source Limitations: Obtain each type of water filtration equipment through one source from a single
manufacturer.
B. Welding Qualifications: Qualify processes and operators according to ASME Boiler and Pressure
Vessel Code.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a
qualified testing agency, and marked for intended location and application.
D. Comply with NSF 61, "Drinking Water System Components - Health Effects," for all components
that will be in contact with potable water.
A. Feedwater Analysis: To be carried out by contractor to obtain data for the below water components:
1. Alkalinity
2. Arsenic
3. Calcium
4. Chlorine
1.10 COORDINATION
A. Coordinate size and location of concrete bases with actual equipment provided.
PART 2 - PRODUCTS
C. Description: Simplex carbon filter, with media tank, media, and automatic backwash for removing
chlorine from and improving color, odor, and taste of water.
1. Media Tank: Corrosion resistant with distribution system and media.
a. Construction:
1) Fabricate and label steel filter tanks to comply with ASME Boiler and Pressure
Vessel Code, Section VIII, Division 1.
2) Fabricate and label FRP filter tanks to comply with ASME Boiler and Pressure
Vessel Code, Section X, if indicated.
3) Fabricate supports and base and attachment to tank with reinforcement strong
enough to resist filter movement during a seismic event when filter base is
anchored to building structure.
4) Pipe Connections NPS 2 (DN 50) and Smaller: Threaded according to ASME
B1.20.1.
5) Steel Tank Pipe Connections NPS 2-1/2 (DN 65) and Larger: Steel, Class 150
flanges according to ASME B16.5 or grooved according to AWWA C606.
Provide stainless-steel flanges if tank is stainless steel.
6) FRP Tank Pipe Connections NPS 2-1/2 (DN 65) and Larger: Type A, integral;
Designation E, 125-psig (0.862-MPa) or Designation F, 150-psig (1.034-MPa)
pressure category flanges of grade same as tank material according to ASTM D
5421.
7) Support: Base, feet, or skirt.
2. Controls: Automatic for control of backwash; factory wired for single, external electrical
connection.
a. Panel: NEMA 250, Type 4 enclosure.
b. Backwash Initiation Device: Differential pressure gages
Unit: to include 304 stainless steel sterilizing chambers with removable head. UV lamps to slide into high
purity sleeves. Sleeves are attached to chamber head so they may be easily removed as a bundle for
inspection or cleaning. Flow regulator on discharge line to maintain flow to ensure an exposure dosage of
30000 micro watt-sec/cm2. Sterilizer to include high powered ballast, fuse, power safety switch, all inside
white enamel housing with stainless steel cover and electrical cord.
Unit: to include UV intensity sensor and meter with safe/unsafe zones to indicate UV below effective
range, mounted on sterilizer housing
Unit pressure rating to be 1.5 times the system operating pressure.
A. Provide all water treatment needed to achieve the quality standard for blue water in accordance with
ICAO regulations including: sand filtration, cartridge filtration, sterilization and blue disinfectant
dosing system. Water treatment system shall be designed and installed complete with all necessary
mixing tanks, dosing pumps and associated automatic control system, interfaced with Building
Management System. System equipment shall be provided in duplex in order to ensure full
redundancy.
B. Provide all water treatment needed to achieve the quality standard for potable water in accordance
with ICAO regulation including: sand filtration, cartridge filtration, and sterilization. Water treatment
system shall be designed and installed complete with all necessary mixing tanks dosing pumps and
associated automatic control system, interfaced with Building Management System. System
equipment shall be provided in duplex in order to ensure full redundancy.
A. Before shipping, hydrostatically test carbon filters,and multimedia sand filters to minimum of one
and one-half times pressure rating.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and conditions, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance of filters.
B. Examine roughing-in for piping systems to verify actual locations of piping connections before
equipment installation.
C. Examine walls and floors for suitable conditions where [filters] [and] [separators] will be installed.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
A. Equipment Mounting: Install filters on concrete bases. Comply with requirements for concrete
bases specified in Division 03 Section
Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install
dowel rods on 18-inch (450-mm) centers around full perimeter of concrete base.
For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and
anchor into structural concrete floor.
Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and
directions furnished with items to be embedded.
Install anchor bolts to elevations required for proper attachment to supported equipment.
A. Install cartridge filters level and plumb, according to layout drawings, original design, and
referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls
and devices needing service are accessible.
C. Attach wall brackets for off-floor, wall-mounted, cartridge filter to vertical surface. Attach
housing(s), and base if any, to wall bracket.
F. Install seismic restraints for freestanding cartridge-filter housings and anchor to building structure.
A. Install carbon filters on concrete base. Comply with requirements for concrete base specified in
Division 03 Section
B. Prepare carbon-filter tank distribution system and underbed, if any, for filter media and place
specified media into tanks.
C. Install seismic restraints for carbon-filter housings and anchor to building structure.
A. Install sand-filter tanks on concrete base. Comply with requirements for concrete base specified in
Division 03 Section
B. Prepare sand-filter tank distribution system and underbed for filter media and place specified sand
and other media into tanks.
C. Install seismic restraints for sand-filter tanks and accessories and anchor to building structure.
3.6 CONNECTIONS
A. Comply with requirements for piping specified in Division 22 Section "Domestic Water Piping."
Drawings indicate general arrangement of piping, fittings, and specialties.
C. Make piping connections between water filtration equipment and dissimilar-metal water piping with
dielectric fittings. Comply with requirements for dielectric fittings specified in Division 22 Section
"Domestic Water Piping."
D. Install shutoff valves on feedwater-inlet and filtrate-outlet piping of each water filtration equipment
filter and on inlet and outlet headers.
Comply with requirements for metal general-duty valves specified in Division 22 Section "General-
Duty Valves for Plumbing Piping."
Comply with requirements for plastic valves specified in Division 22 Section "Domestic Water
Piping."
Exception: Water filtration equipment with factory-installed shutoff valves at locations indicated.
F. Install valved bypass water piping around each water filtration equipment filter.
Comply with requirements for metal general-duty valves specified in Division 22 Section "General-Duty
Valves for Plumbing Piping."
Comply with requirements for plastic valves specified in Division 22 Section "Domestic Water Piping."
Comply with requirements for water piping specified in Division 22 Section "Domestic Water Piping."
G. Install drains as indirect wastes to spill into open drains or over floor drains.
3.7 IDENTIFICATION
A. Identify system components. Comply with requirements for identification specified in Division 22
Section "Identification for Plumbing Piping and Equipment."
D. Domestic water filtration equipment will be considered defective if it does not pass tests and
inspections.
A. Engage a factory-authorized service representative to perform startup service for multimedia sand
filters.
1. Complete installation and startup checks according to manufacturer's written instructions.
B. Sample filter filtrate after startup and at three consecutive seven-day intervals (total of four samples),
and prepare certified test reports for required water performance characteristics.
3.10 DEMONSTRATION