c60h DC Iec PDF
c60h DC Iec PDF
IEC/EN 60947-2
DB123430
DB123525
PB107194-34.eps
Catalogue numbers
C60H-DC
Type 1P 2P
DB116588
DB124110
DB124111
Supply from above or below, Supply from Supply from
observing the polarity above below
Auxiliaries Remote signalisation and tripping, module CA907008
DB118787
DB122945
DB122946
DB122935
DB118789
F
O-OF
F
O-OF
DB122946
DB122945
DB118787
PZ2
F
O-OF
F
O-OF
Technical data
b Tripping curves: C curve - Overcurrent protection for any type of application.
b Positive break indication - the green strip indicates that all the poles are open and
allows work to be carried out on the downstream circuit in complete safety.
b 6XLWDEOHIRULVRODWLRQDVGH¿QHGLQ,(&(1
b Increase in the service life of the product: thanks to fast closure independent of the
speed of action on the handle.
Clip on DIN rail 35 mm. b Current limitation in the event of a fault: fast opening of the contacts prevents the
loads from being destroyed in the event of a short-circuit.
DB123312
Main characteristics
According to IEC/EN 60947-2
Insulation voltage (Ui) 500 V DC
Rated voltage (Un) 1P 250 V DC
2P 500 V DC
Pollution degree 3
Rated impulse withstand voltage (Uimp) under 6 kV
Indifferent position of installation. frame
Magnetic tripping (Ii) 8.5 In (± 20 %) (compatible with curve C)
Additional characteristics
DB123314
d
Failure to match polarity during connection may lead to a fire hazard
and/or serious injury.
PB124305.eps
Weight (g)
Circuit-breaker
Type C60H-DC
1P 128 g
2P 256 g
Dimensions (mm)
DB124113
C60H-DC
DB124112
10 10
t 35
t
35
t
Details of minimum distance between circuit-breaker
and earthed metal parts for circuit-breaker intended for
use without enclosure.