N202 IDMT Earth-Fault Relay User’s Guide 2.

Light Indicators
a b c
a - Low-set start/trip status indicator The light indicators display the status of the system.
I> I>> AUX
b - High-set start/trip status indicator Indicator
Status
IDMT EARTH FAULT RELAY c - Auxiliary power supply indicator AUX I> I>>
h d - Test button Off Off Off No auxiliary power supply.
f 1A 0.4 0.5 0.6 X6

0.5A
1.5A 0.3
0.7
0.8
X4 X8 On Off Off System normal mode. No tripping.
0.2 e - Trip reset button
0.1 0.9 X2 X10 On Blink Off Earth-fault low-set start.
0.1A 2A 0.05 1.0 X1
I TM I f - Earth-fault low-set adjustment On On Off Earth-fault low-set tripped.
g
g - Delay time adjustment On Off Blink Earth-fault high-set start.
TEST RESET h - Earth-fault high-set adjustment On Off On Earth-fault high-set tripped.
N202

d e f
3. Push Buttons
Reset Button
TECHNICAL DATA - The reset button is for resetting the light indicators (I> or I>>) after an earth-fault tripping
has occured.
1. Current and Time Adjustments - To reset, press the reset button once.

Test Button
Earth-fault Low-set Current (I>) Adjustment
- Test button is for checking the relay operation.
- This adjustment is for setting the minumum earth-fault
- Push and hold the test button, I> and I>> LEDs start blinking then LEDs turn On and relay
current for tripping with time delay.
contacts will be activated after 3s.
- The setting range is between 0.1A to 2A

Earth-fault High-set Current (I>>) Adjustment


- This adjustment is for setting the instantaneous tripping 4. Trip Contacts
current due to an earth-fault. There are two set of tripping contacts namely, R1 and R2.
- The setting range is between 1x to 10x of the earth-fault
low-set setting value. R1,R2 - Manual Reset Type
I>> = a x I> (a= 1 to 10) - These contacts is activated during an earth-fault trip. The contacts remain activeted
- This high-set feature can be disabled by setting the regardless of the removal of fault current. This relay can only be reset by pressing the
tripping current to infinity (∞). “RESET” button.

Time Delay (TM) Adjustment


- The time multiplier is for setting the normal inverse
time/ current characteristic (IDMT) as according to
BS142. IDMT Normal Inverse Curve
- The setting range between 0.05 to 1.0 .
5. Electrical Specification 7. Connection Diagram

Auxiliary Supply N 202


N202-240AD............................................ 85 ~ 265 VAC or 110 ~ 370 VDC NO NC COM COM NC NO
Supply frequency.................................. 50Hz or 60Hz 1 2 3 4 5 6
VA rating................................................... 3 VA typical
R1 R2
Trip Contact
Rated Voltage......................................... 250 VAC 7 8 9 10 11 12
Continuous carry................................... 5A (cos = 1.0)
Expected electrical life........................100,000 operations N L
Aux !
Expected mechanical life................... 5 million operations DANGER
L1

Setting Ranges L2

LOAD
Low-set (I>)..............................................0.1A to 2.0A (2% to 40%) L3
Low-set delay time (TM).....................0.05 to 1.0 N
High-set (I>>)......................................... I> to 10x I> or disable
High-set delay time (t>>).................. Instantaneous

Indicators
8. Case Dimensions
Auxiliary supply..................................... Green LED indicator
97 mm
Pick-up...................................................... Red LED indicator 72 mm 89 mm 68.0 ± 0.5 mm
Trip............................................................. Red LED indicator

68.0 ± 0.5 mm
Side

72 mm
6. Mechanical Front
Mounting.................................................. Panel mounting
Front panel............................................... 72x72 mm
Approximate weight............................. 0.6 kg