You are on page 1of 18

Engineering Structures 173 (2018) 813–830

Contents lists available at ScienceDirect

Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct

The effects of retrofitting RC frames by X-bracing on the seismic T


performance of columns

A Rahimi, Mahmoud R. Maheri
Department of Civil Engineering, Shiraz University, Iran

A R T I C LE I N FO A B S T R A C T

Keywords: One of the common method for retrofitting RC frames is to use steel braces. The majority of reported research
Seismic retrofitting related to steel bracing of RC frames have highlighted the positive effects of bracing such as improving structural
Steel X-bracing performance, increasing shear capacity, reducing displacements and decreasing drifts. Very little is reported on
RC frame the possible side effects of the technique on the RC members, particularly those of columns. This papers aims at
RC column
evaluating, through time history analyses, the behaviour of RC columns before and after retrofitting with steel X-
Seismic response
Performance level
bracing and examining possible complications, increased demands and side effects of such a retrofitting method.
Fatigue life The effects on the level of column shear and axial force, as well as, column performance level and low cycle
fatigue life are investigated. As a general conclusion, it is found that retrofitting low-rise RC frames with steel X
bracing is beneficial to the performance of frame columns in almost every aspect; however, for mid to high-rise
frames, the adverse effects of retrofitting, particularly on columns attached to the bracing system, are con-
siderable and should be taken into consideration and if needed, local strengthening of columns should si-
multaneously be undertaken.

1. Introduction connections between the bracing system and RC frame is needed, hence
less interference with the existing RC frame. It is comparatively cheaper
To enhance the performance of an existing RC frame, there are a and easier to perform. Abou-Elfath and Ghobarah [16,17] investigated
number of retrofitting methods which can be employed. In the past the performance of low rise RC frames before and after retrofitting by
three decades, using different types of steel bracing to increase the direct steel bracing. Maheri et al. [18] conducted pushover tests on
seismic capacity of RC frames has been a popular subject for in- scaled RC frames retrofitted with X and Knee bracing systems and
vestigation. The bracing methods adopted fall into two main categories, showed the effectiveness of X-bracing when increased capacity and
namely (i) external bracing and (ii) internal bracing. In external bra- stiffness was required and Knee-bracing when improved ductility was of
cing, steel bracing system is attached globally to the side of RC frame prime concern. Pincheira and Jirsa [19], Viswanath and Prakash [20]
[1–5]. Architectural concerns and difficulties in providing appropriate also reported the effectiveness of this method in increasing shear ca-
connections between the steel bracing system and the RC frame are two pacity and lateral stiffness and decreasing the global displacement of
of the shortcomings of this method, making the technique rather un- the RC frame. Maheri and Akbari [21] presented the seismic behaviour
popular. In the internal bracing method, the bracing system is placed factor for X-braced and Knee-braced RC frames. Jain [22], also reported
inside the individual bays of the RC frame. The bracing may be attached pushover result of retrofitted RC frames by X and Knee steel bracing and
to the RC frame either indirectly or directly. In the indirect internal reported on better performance of X-bracing to enhance capacity
bracing, a braced steel frame is positioned inside the RC frame. As a compared with Knee-Bracing. To improve the performance of the X-
result, the transfer of load between the steel bracing and the concrete bracing system by avoiding buckling of compression brace, Ghaffar-
frame is achieved indirectly through the steel frame [6–13]. The in- zadeh and Maheri [23] suggested using a mechanical compression re-
direct internal bracing method can be costly and connecting the sup- lease device in the brace to make it tension only. Later, Maheri and
porting steel frame to the RC frame is technically inhibiting and re- Ghaffarzadeh [24] investigated the brace-frame connection over-
quires much interference with the existing RC frame. In the direct strength and presented design procedure and details for X-braced RC
internal bracing, first proposed by Maheri and Sahebi [14,15], the frames at design stage. Rahai and Lashgari [25] reported experimental
bracing system is directly connected to the RC frame, so fewer and numerical results of retrofitting of RC frames by BRB and showed


Corresponding author.
E-mail address: maheri@shirazu.ac.ir (M.R. Maheri).

https://doi.org/10.1016/j.engstruct.2018.07.003
Received 1 August 2017; Received in revised form 14 March 2018; Accepted 1 July 2018
0141-0296/ © 2018 Elsevier Ltd. All rights reserved.
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

Fig. 1. (a) Modelling beam and column cross section, (b) modelling steel brace cross section, (c) Kent-Scott-Park concrete model, (d) Giuffré-Menegotto-Pinto steel
model.

Fig. 2. (a) Dimensions and reinforcement detail of the model RC frames. (b) Detail of the X-bracing system and its connection to the RC frame [18]

an improvement in the seismic performance. Ozel and Guneyisi [26], connections and their elements were strong enough to withstand the
investigated the seismic fragility curves of mid-rise RC frames retro- forces and that the brace failure and rupture preceded the failure of the
fitted by eccentric steel braces and showed a decrease in fragility after connection elements. Later Maheri and Yazdani [28,29] carried out an
retrofitting. To address the important subject of connections between extensive numerical investigation and presented the necessary con-
steel bracing and RC frame, an experimental investigation was con- siderations for design of different components of the brace-frame con-
ducted by Maheri and Hadjipour [27]. They adopted the Uniform Force nection.
Method (UFM) provisions for designing brace-steel frame connections The majority of reported research related to steel bracing of RC
to design their connection specimens. They showed that the frames have highlighted the positive effects of bracing such as:

814
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

Fig. 3. Experimental [18] and numerical pushover response curves for the model unit frame; (a) unbraced frame, (b) braced frame.

improving structural performance, increasing shear capacity, reducing nonlinear beam–column elements along the length of the brace;
displacements and decreasing drifts. Very little is reported on the pos- therefore, in the present study, each brace is modelled using ten ele-
sible side effects of the technique and the level of new demands on the ments.
existing RC frame members, particularly those of columns. The present
work aims at evaluating, through time history analyses, the behaviour 2.3. Material constitutive models
of RC columns before and after retrofitting with steel X-bracing and
examining possible complications, increased demands and side effects In this work, Kent-Scott-Park [33] constitutive model is used to
of such retrofitting on columns. model both confined and unconfined concrete with fˊc = 28 MPa. As the
stress-strain curve shown in Fig. 1(c) indicates, the constitutive model
2. Numerical modelling of steel braced RC frame has tensile strength and linear tension softening and can model de-
gradation of strength during unloading. Also, the concrete cover and
In this study, the OpenSEES software [30] is used to perform time- core are modelled as different materials, using the same material type
history dynamic nonlinear analysis of the RC frame-steel brace assem- but different stress and strain characteristics. The reinforcement and
blage. Based on the needs, the nonlinear beam-column element was steel braces in the model are defined by the Giuffré-Menegotto-Pinto
selected from the large library of finite elements available in the soft- constitutive model [34] shown in Fig. 1(d). It can simulate stiffness
ware. The integration along the element is based on Gauss-Lobatto degradation and buckling of steel. Yield stresses of reinforcements and
quadrature rule. This element can record force (global and local), dis- steel braces are considered as 400 MPa and 240 MPa, respectively and a
placement (include curvature) and stress-strain of element materials. strain-hardening ratio of 0.01 is used.
Fibre cross sections were employed, enabling creation of different cross
sections compatible with plane strain assumption.
2.4. Validation of numerical simulation

2.1. Beams and columns In order to verify the accuracy of numerical simulation, two X-
braced unit RC frames tested by Maheri et al. [18] were numerically
As shown in Fig. 1(a), the cross section of beams and columns is simulated with the OpenSEES. Model unit frames constructed for ex-
divided into concrete core and concrete cover plus steel rebar. Confined perimental investigations were 1:3 scaled models of a typical 3 m × 3 m
concrete is employed for core and unconfined concrete is used for unit ductile frame. The full size unit frame was selected from a typical
cover. For more accuracy, the concrete core is divided into 20 (in 4-storey, 3-bay portal frame of a building and was designed and de-
width) by 20 (in length) fibre segments and cover is divided into 2 (in tailed according to the ACI-89 code provisions for ductile RC frames.
thickness) by 20 (in length) discrete fibres. Also, the X-bracing system was designed according to the LRFD method.
The two unit frames tested by Maheri et al. [18] consisted of an RC
2.2. Brace frame without bracing (unbraced frame) and another identical RC
frame, retrofitted with steel bracing (braced frame). Details of the RC
Steel Braces are also modelled with fibre sections as shown in frame and bracing system are shown in Fig. 2(a) and (b), respectively
Fig. 1(b). The required number of the fibres in the cross section of the [18]. They reported formation of multiple plastic hinges in the beams of
brace is chosen based on the work carried out by Hsiao et al. [31] as unbraced frame as the step-by-step pushover loading increased and the
four fibres along the thickness in each direction at each of the eight maximum load recorded was 34 kN [18]. In the braced frame, failure
quadrilateral patches. For modelling post buckling behaviour of steel initiated by buckling of compression brace followed by multiple hinge
braces, it is generally more accurate to use a continuum model; how- formations in the RC beams. The maximum load recorded for the
ever, this model is time consuming and computationally expensive. braced frame was 119 kN.
Hsiao et al. [31] suggested a more simplified and relatively accurate In the present study, to model the RC frame nonlinear beam-column
nonlinear model which can be developed in OpenSEES using beam- element was used. The nonlinear pushover response of the unbraced RC
column elements. In this method, the braces are modelled with initial frame from the numerical simulation is compared with the experi-
imperfections to capture their post buckling behaviour. Initial im- mental response in Fig. 3(a). It can be seen that the numerical simu-
perfection is modelled as a sine function with the apex equal to 1/500 lation has predicted the nonlinear pushover response well. For the
of the length of the brace [31]. Gunnarsson [32] showed that accurate braced model, steel braces were modelled with an initial imperfection
simulation of brace buckling behaviour is achieved using ten or more as described in Section 2.2, using nonlinear beam-column elements and

815
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

storey Retrofitted frame


Section b h As
b (cm) h (cm) t (cm)
(cm) (cm) (cm2) (cm2)
1 10 10 0.7
C1 60 60 36 -
2 10 10 0.7
C2 60 60 59 -
3 10 10 0.7
C3 50 50 25 -
4 9 9 0.7
B1 60 60 13 20
5 8 8 0.7
B2 60 60 16 24
6 7 7 0.7
B3 60 60 17 25
7 6 6 0.7
B4 50 50 12 22
8 5 5 0.5
B5 50 50 12 22
B6 50 50 9 19
B7 50 50 7 14
B8 50 50 4.5 9

(a) (b)
Fig. 4. Details of the 8-Storey frame; (a) RC frame, (b) steel bracing.

fibre sections. The numerical nonlinear pushover simulation is com- live load were assumed to be 30 kN/m and 10 kN/m, respectively. The
pared with the experimental pushover curve [18], as well as numerical compressive strength, fˊc and tensile strength, ft of concrete were taken
pushover simulation carried out by Maheri and Akbari [21] using as 28 MPa and 3.17 MPa, respectively. In addition, the elastic modulus
DRAIN-2DX software, in Fig. 3(b). It can be seen that the present si- of the concrete Ec was taken as 27.6 GPa and the yield stress of steel
mulation matches well with both the experimental results and numer- reinforcement was assumed to be 412 MPa. Design base shears were
ical results of reference [21]. determined for a Peak Ground Acceleration (PGA) of 0.3 g. In esti-
mating the equivalent static earthquake load, the weights of the frames
2.5. Design details of the braced RC frames were taken as the dead load plus 20% of live load, based on the Iranian
seismic code [36]. The intermediate moment resisting frames were
To conduct the necessary examinations, three planar RC frames all designed using ACI-02 Code [37] as a new building and the steel bra-
having three bays but different heights (4-storey, 8-storey and 12- cing systems were designed using AISC-360 Code [38]. Steel braces
storey) are selected. The 8-storey frame the details of which are shown were designed to sustain 100% of storey shear of the original (un-
in Fig. 4, is a benchmark frame first designed and used by Maheri and braced) RC frames based on recommendations made by Maheri and
Akbari [21] and later by Niroomandi et al. [35] and a number of other Akbari [21] and Niroomadi et al. [35]. Since in each storey one brace
researchers. The 12-storey frame (Fig. 5) and the 4-storey frame (Fig. 6) element is always in tension and the other in compression, the hor-
were also first designed and used by Maheri and Akbari [21]. In de- izontal component of compressive strength (ϕPn) of one brace and
signing the three moment resisting frames, the design dead load and tensile strength of the other (ϕTn) should be equal to the storey shear of

816
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

Storey Retrofitted frame


Section b h As As b (cm) h (cm) t (cm)
(cm) (cm) (cm2) (cm2) 1 11 11 0.7
C1 60 60 60 - 2 11 11 0.7
C2 60 60 36 - 3 10.5 10.5 0.7
C3 50 50 25 - 4 10.5 10.5 0.7
B1 60 60 15 21 5 10 10 0.7
B2 60 60 17 26 6 9.5 9.5 0.7
B3 60 60 15 25 7 9.5 9.5 0.6
B4 50 50 11 20 8 9 9 0.6
B5 50 50 8 17 9 8 8 0.6
B6 50 50 7 14 10 7 7 0.6
B7 50 50 4.5 8 11 6 6 0.6
12 6 6 0.6

(a) (b)
Fig. 5. Details of the 12-Storey frame; (a) RC frame, (b) steel bracing.

the original frame as in Eq. (1). distance, and source mechanisms that are consistent with those that
control the maximum considered earthquake”. The selection was made
Vi = (ϕTn + ϕPn ) ∗cos(α ) (1)
in such a way that records with different frequency contents are among
where Vi is ith storey shear of the original frame and α is the inclination the records. Details of the selected earthquake records are listed in
angle of braces. Details of shear reinforcements and shear capacities of Table 1. Both horizontal and vertical components of the earthquakes
columns for the three frames are shown in Fig. 7. In this figure, S1 and are used.
S2 are tie spacing in L0 and central parts of the columns, respectively
and φVn-1 and φVn-2 are shear capacities inside and outside L0 regions,
3. Shear and axial forces in columns
respectively.
To examine the demand on RC columns of the selected frames due
2.6. Selection of earthquake records to retrofitting and to investigate their performance, they are divided
into two types namely: middle columns and side columns. Middle col-
The earthquake records used for time history analysis are selected umns are those columns with direct connections to steel braces. The
based on the ASCE/SEI 7-10 provisions [39] stating that: “Appropriate side columns are those located at the far sides of the frames with no
ground motions shall be selected from events having magnitudes, fault connections to steel bracing. Since no tensile force develop in the side

817
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

Section b h As As
(cm) (cm) (cm2) (cm2)
C1 50 50 25 - storey Retrofitted frame
C2 40 40 16 - b (cm) h (cm) t (cm)
C3 40 40 20 - 1 5.5 5.5 0.5
B1 50 50 8 16 2 5.1 5.1 0.5
B2 40 40 7 16 3 4.7 4.7 0.5
B3 40 40 5.5 10 4 4 4 0.5

(a) (b)
Fig. 6. Details of the 8-Storey frame; (a) RC frame, (b) steel bracing.

columns and as the results of Section 3.3 indicate, the number of cycles The high D/C ratios at lower stories of the taller frames indicate that the
in which tensile forces develop in the middle columns of the 8-storey middle columns at these storeys need further attention. The increase in
and 12-storey frames are very few and their cumulative duration is only D/C may be as high as 45% as seen in the 2nd storey of the 12-storey
a fraction of a second, the effect of tensile force on reducing the shear frame. The low-rise, 4-storey frame, however, seems to fair better after
capacity of columns is ignored. retrofitting as shear D/C for all columns are below unity.
With reference to the results of the 12-storey frame (Fig. 9a), it is
also noted that by adding the steel braces, the average shear D/C ratio
3.1. Shear in middle columns of column in the first three storeis are increased. The trend changes to
decreasing shear D/C due to retrofitting at higher stories (4th storey
The maximum shear in central columns of the three frames before upwards). However, in the 9th and 10th storeis at which locations there
retrofitting and after retrofitting, subjected to the selected earthquake is a change in columns cross section, an increase in shear D/C is seen
records were extracted. Typical variations in storey shears of the 8- under some earthquake records.
storey frame subjected to Kobe and Northridge records are shown in Similarly, the average column shear D/C in the 1st and 2nd stories
Fig. 8. It is noted that retrofitting has increased column shear at lower are above unity. The average column shear, however, reduces to under
storeys, but has resulted in a decrease in column shear at higher storeys, unity as we move towards higher storeys. This general trend is inter-
except at storeys where a change in column cross section has occurred rupted in the sixth storey which is the location of change in columns
(such as storey No. 6 in the 8-storey frame of Fig. 8). cross section. The condition of the middle columns of the 4-storey frame
To gain a complete picture of the effect of retrofitting on the shear in due to retrofitting appear to be better than those of the 8-storey and 12-
middle columns, the member’s shear demand-capacity ratio (D/C) is storey frames. The column shear D/C in all 4 stories are below unity
evaluated for all middle columns in all storeys of the three frames under and they follow a sharp reducing trend at higher stories (Fig. 9c). It
different earthquake records and are plotted in Fig. 9. In this figure, the seems that in all frames, the possible increase in the middle column
‘Average’ lines represent average values for the 20 earthquake records. shear due to retrofitting occurs in the lower stories and as we go higher
The variation in data are also plotted as average ± standard deviation up, the column shears are reduced. Also, an increase in column shear
(AVG ± STDV) in the figure. For all the three frames, a general de- may occur at locations of change in column cross section. These two
creasing value of D/C is noted as we move from the lower stories up- issues need special attention since local, secondary retrofits may be
wards; exceptions being when there is a change in the cross section of required to enhance shear capacity of mid-columns. Regarding the first
the column, where shear D/C may increase. In the 12-storey frame, this issue, a possible explanation may be that; by adding steel bracing, the
happens in stories 9 and 10 (Fig. 9a), in the 8-storey frame it is the 6th effects of higher modes on the response is reduced, hence the shear
storey (Fig. 9b) and in the 4-storey frame it is the 3rd storey (Fig. 9c).

818
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

Typical
Storey Column L0 (mm) S1 (mm) S2 (mm) -1 (kN) -2 (kN)
section
C1 B 500 100 150 467 361
4-Storey C2 A 500 100 150 258 203
C3 A 500 100 150 258 203
C1 C 600 150 200 477 413
8-Storey C2 C 600 150 200 477 413
C3 B 500 100 150 467 361
C1 C 600 150 200 477 413
12-Storey C2 C 600 150 200 477 413
C3 B 500 100 150 467 361

Fig. 7. Details of shear reinforcement and shear capacity in columns of the frames.

Table 1 force distribution pattern moves from an exponential form towards a


List of selected earthquake records. linear form [39], resulting in reduced shear in the upper stories. Re-
ID No. Earthquake Record PGA (g) PGV Magnitude Significant
garding the second issue, it appears that by adding steel braces, natural
(cm/s) duration (s) period of vibration of the frame decreases, resulting in an increase in
spectral acceleration, in turn causing an increase in the base shear.
1 FRIULI 0.35 22 6.5 4.24 However, as it will be discussed later, the increase in base shear for 8-
2 IMPERIAL VALLEY 0.31 31.5 6.4 8.92
3 IMPERIAL VALLEY 0.23 26.3 6.4 51.4
storey and 12-storey frames is around 130%, whereas, for the 4-storey
4 KOBE 0.34 27.7 6.9 12.86 frame it is 55%. Since the bracing systems were designed to sustain
5 KOBE 0.225 31.3 6.9 10.35 100% of the storey shear, in the 8-storey and 12-storey frames, 30%
6 KOCAELI 0.35 62 7.6 15.62 extra base shear must be transferred through columns to the base.
7 KOCAELI 0.21 13.93 7.6 11.05
However, in the 4-storey frame the 55% extra demand can be easily
8 LANDERS 0.78 31.6 7.3 13.73
9 LANDERS 0.42 43 7.3 8.24 sustained by the bracing system alone.
10 LOMA PRIETA 0.36 44.7 6.9 11.37
11 LOMA PRIETA 0.56 36.3 6.9 6.37
12 NORTHRIDGE 0.56 51.8 6.7 9.06 3.2. Shear in side columns
13 NORTHRIDGE 0.47 41.1 6.7 5.58
14 DUZCHE 0.73 55.9 7.5 8.55 The D/C for shear in side columns of the three retrofitted frames
15 MANJIL 0.51 42 7.4 28.6
16 HECTOR 0.32 44.7 7.1 9.65
subjected to different time history records are plotted in Fig. 10. Similar
17 SAN FERNANDO 0.22 21.7 6.6 13.15 to the trend observed for the middle columns, in all three frames, for
18 Chi-Chi, Taiwan 0.39 109 7.6 26.48 side columns a general decreasing value of shear D/C is noted as we
19 Chi-Chi, Taiwan 0.47 50 7.6 11.34 move from the lower stories upwards; again, exceptions being when
20 Superstition Hills 0.35 48.07 6.5 28
there is a change in the cross section of the column, where shear D/C
may increase. With reference to Fig. 10 it is noted that, unlike the
middle columns, all shear D/C in side columns of the three frames

819
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

8 8

7 7

6 6

5 5
Storey

Storey
4 4

3 3

2 2

1 1

0 0
0 100 200 300 400 500 600 0 100 200 300 400 500 600
Column shear (kN) Column shear (kN)

ORIGINAL FRAME Retrofitted frame ORIGINAL FRAME R2


(a) (b)
Fig. 8. Middle column shear in (a) Kobe and (b) Northridge earthquakes.

12 8 Average
11 Avg+STDV
7
10 AVG-STDV
9 6 4
8
5
Storey

7
Storey

6 3
4 Storey
5
4 3
2
3
2
2
1 1
1
0.40 0.70 1.00 1.30 1.60 0.40 0.70 1.00 1.30 1.60
0.40 0.70 1.00 1.30 1.60
Shear D/C ratio Shear D/C ratio Shear D/C ratio

(a) (b) (c)


Fig. 9. Shear D/C in middle columns of: (a) 12-storey (b) 8-storey (c) 4-storey frames.

(except for the first storey in the 8-storey and 12-storey frames) fall first storey columns is around 58%. A general decreasing in Retrofitted/
below unity; indicating positive effects of brace retrofitting on reducing Original demand ratio may be noted for all three frames as we move to
demand on side columns. In the first storey of 12-storey frame, average higher stories. In the 4-storey frame, the average Retrofitted/Original
shear demand of side columns is only 7% greater than the shear ca- demand ratio reaches unity for the top storey, whereas, in the 8 and 12-
pacity and the maximum shear demand, occurring in Friuli earthquake, storey frames the increase in demand is still notable even for the top
is 18% higher than capacity. However, the situation in the first storey storey.
side columns of the 8-storey frame is more critical. The average and Also, in earthquake returning cycle, the columns may undergo
maximum shear demands are respectively 25% and 46% greater than tensile loads. Table 2 shows the maximum and minimum axial loads
the shear capacity. excreted on the first storey middle columns of both the original frame
and the retrofitted frame, subjected to different earthquake records. It
can be seen that, for the 8 and 12-storey frames while in the original
3.3. Axial force in middle columns frame the axial force remains always compressive, in the retrofitted
frame, the middle columns also undergo substantial tensile loads of up
To evaluate the effects of X-brace retrofitting on axial force demand to 89% of their tensile strength. This is due to the fact that in retrofitted
of middle columns, the compressive axial Retrofitted/Original demand frames under lateral loading, the bracing system exerts large axial
ratios for these columns are plotted in Fig. 11. The average demand tensile forces on the columns connected to the bracing system. In taller
ratio for the first storey of the 8 and 12-storey frames is about 2.4, frames, due to increased overturning moment, these tensile forces may
indicating a substantial increase in compressive axial force due to ret- become larger than the compressive forces present due to gravity,
rofitting. For the 4-storey frame, the average increase in demand for the

820
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

12 8 Average
11 AVG+STDV
7
10
AVG-STDV
9 6 4
8
5
Storey

Storey
6 3
4

Storey
5
4 3
2
3
2 2

1
1 1
0.40 0.70 1.00 1.30 1.60
0.40 0.60 0.80 1.00 1.20 1.40 0.40 0.60 0.80 1.00 1.20 1.40
Shear D/C ratio Shear D/C ratio Shear D/C ratio

(a) (b) (c)


Fig. 10. Shear D/C in side columns of: (a) 12-storey (b) 8-storey (c) 4-storey frames.

12 8 Average
11
Avg+STDV
7
10
AVG-STDV
9 6
4
8
5
Storey

7
Storey

6 3
4
Storey

5
4 3
2
3
2
2
1 1 1
0.00 1.00 2.00 3.00 0.00 1.00 2.00 3.00 0.00 1.00 2.00 3.00

Retrofitted/Original axial Retrofitted/Original axial Retrofitted/Original axial


force force force
(a) (b) (c)
Fig. 11. Retrofitted/Original compressive axial force demand in middle columns of: (a) 12-storey (b) 8-storey (c) 4-storey frames.

therefore, the net effect would be traction in these columns. different. Although adding steel bracing increases the axial load de-
For the shorter, 4-storey frame, however, axial forces after retro- mand, the demand increase is much less than those in the 8 and 12-
fitting remain compressive. The maximum tensile forces in the middle storey frames. Also, as it was stated, no tensile forces develop in the
columns in all stories of the 8 and 12-storey frames under different middle columns due to retrofitting.
earthquake records are plotted in Fig. 12. It may be noted that for these
taller frames, middle columns undergo tensile forces. Tensile force is
expectedly maximum at the first storey, being as much as 1150 kN in 3.4. Axial force in side columns
the 8-storey frame and 1550 kN in the 12-storey frame. The tensile force
reduces gradually as we move up the frames with the top three storeys The Retrofitted/Original demand ratios for compressive axial forces
showing almost zero values. The occurrence of tensile forces in middle in side columns of the three frames under investigation are plotted in
columns by such considerable amounts is alarming since lap splice Fig. 13. For the 12-storey frame, the increase in demand in side columns
failure at the lower storeys may occur. With respect to force transfer due to retrofitting is relatively small; averaging around 5% up to storey
mechanism at lap splice region, the presence of high tensile forces can 9 and increasing to a maximum average of 20% in the 12th storey. This
adversely affect this mechanism and reduce the splice performance. The is in sharp contrast with the middle columns discussed above. The in-
situation for the middle columns in the 4-storey frame is somewhat crease in demand is even less for the 8-storey frame (Fig. 13b), starting
from 2% and reaching a maximum of 15% at the top storey. The

821
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

Table 2
Axial force in the middle columns of the first storey of the three frames (kN). (Note: Negative value indicate tensile force.)
4 Storey 8 Storey 12 Storey

Original Retrofitted Original Retrofitted Original Retrofitted

Max Min Max Min Max Min Max Min Max Min Max Min

FRIULI 795 667 1275 235 1785 1648 4581 −1128 2717 2472 6327 −1305
IMPERIAL 824 687 1285 294 1805 1619 4503 −961 2766 2472 6416 −1521
IMPERIAL 2 811 690 1266 249 1796 1598 4395 −978 2723 2395 6157 −1350
KOBE 795 667 1256 255 1815 1619 4483 −981 2747 2462 6200 −1256
KOBE 805 698 1293 283 1749 1600 4386 −913 2782 2511 6733 −1374
KOCAELI 804 697 1285 245 1884 1501 4444 −981 2747 2472 6475 −1128
KOCAELI 802 693 1240 253 1820 1533 4311 −981 2749 2497 6275 −1295
LANDERS 814 706 1246 265 2090 1265 4238 −834 2757 2472 6023 −1138
LANDERS 2 815 715 1290 295 1923 1395 4427 −995 2813 2450 6324 −1200
LOMA 804 687 1246 334 1766 1599 4365 −775 2727 2482 5700 −912
LOMA 2 819 710 1213 305 1850 1560 4165 −895 2694 2535 5910 −1000
NORTHRIDGE 824 667 1285 275 1756 1658 4513 −1010 2757 2462 6308 −1226
NORTHRIDGE 2 827 696 1309 268 1776 1597 4403 −921 2827 2531 6938 −1107
DUZCHE 830 716 1310 303 1785 1604 4558 −761 2787 2513 6763 −1277
MANJIL 809 722 1275 329 1783 1595 4012 −565 2771 2528 5712 −697
HECTOR 835 719 1298 242 1802 1565 4488 −1028 2796 2530 6050 −627
SAN FERNANDO 825 678 1310 280 1799 1586 4611 −864 2779 2540 7057 −1382
Chi-Chi 820 690 1287 278 1764 1634 4238 −794 2745 2438 6532 −875
Chi-Chi 813 687 1279 269 1842 1554 4652 −1005 2680 2497 6872 −994
Superstition 814 701 1305 253 1765 1589 4352 −971 2795 2518 6369 −1154

12 Average clear that in the original frame the axial forces in the middle columns
11 Avg+STDV are almost constant and do not greatly fluctuate during the earthquake
10 (Fig. 14(a)). However, after retrofitting by steel braces, the axial force
AVG-STDV
histories considerably fluctuate around a constant value in a number of
9
8 cycles as seen in Fig. 14(b). The level of tensile forces has a profound
8
7 effect on the performance of lap splices. However, as it is stated in JSCE
Storey

7 [40], as loading cycles increase, the state of lap splices in columns also
6
6 becomes critical. As a result, in the present study the number of load
Storey

5 5 cycles are also considered to evaluate lap splice performance in col-


4 umns. In counting the number of cycles, it was decided to remove cycles
4
with small amplitudes. For this purpose, the mean value of the max-
3 3 imum tensile and maximum compressive responses is first evaluated.
2 2 Then, the peaks with values 50% higher than the mean value are se-
1 lected as significant peaks. This is shown graphically for the first storey
1
0.00 500.00 1000.00 1500.00 of the 8-storey frame under Kobe earthquake record in Fig. 14. It can be
0 500 1000 1500
seen that in the original frame (Fig. 14a), axial force in middle column
Axial tensile force (kN) Axial tensile force (kN)
has relatively small variations; therefore, no peaks 50% larger than the
(a) (b) mean axial force exists. However, in the retrofitted frame, a large
number of peaks are considered significant as they have values more
Fig. 12. Tensile axial force in middle columns after retrofitting: (a) 12-storey
and (b) 8-storey frames. than 50% higher or lower than the mean axial force (Fig. 14b).
Similarly, the number of significant peaks for middle columns in all
storeys of the three selected frames undergoing different earthquake
situation in the 4-storey frame is the reverse in the sense that retro- excitations are evaluated and plotted in Fig. 15. This figure indicates
fitting results in a sharp decrease in demand for the side columns by as that there are a large number of significant peaks in the lower storeys of
much as 24% at the top storey. the 8 and 12-storey frames, the numbers reducing gradually in higher
storeys with the exception of the top storey of the 8-storey frame, in
which the number of significant peaks increase again. The situation in
4. The effects on lap splice in middle columns
the 4-storey frame is again somewhat different. Very few significant
peaks occur in the 1st and 2nd storeys and no significant peaks occur
Specifications regarding the use of lap splice in columns vary in
higher up. The results of this investigation point to the fact that in mid
different codes of practice. ACI 318-02 code of practice [37] prohibits
to high-rise buildings, X-bracing of the frame may result in violation of
the use of lap splice in tensile members and Japan Society of Civil
some code requirements regarding lap splices, whereas, in short frames
Engineering (JSCE) [40] prohibits their use in members subjected to
(4-storey), retrofitting the frame does not affect the performance of lap
cyclic loads in which the axial force undergoes considerable changes
splices.
from large compression to pure tension. In Section 3.3, it was noted that
middle columns in the taller frames (8 and 12 storeys) may be subjected
to large tensile forces, which violates the code requirements for lap 5. Examination of columns performance level
splice. Regarding the effects of large axial load fluctuation, the number
of fluctuations of the axial force in middle columns of the three frames In this section, a novel representation of performance curves for
is evaluated. As shown in Fig. 14, by comparing axial force histories of columns is first presented and then the performance of different col-
the first storey of the 8-storey frame before and after retrofitting, it is umns of the three selected frames before and after retrofitting,

822
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

12 8 Average
11
7 AVG+STDV
10
AVG-STDV
9 6
4
8
5
Storey

Storey
7
6 3
4

Storey
5
4 3
2
3
2
2
1 1 1
0.4 0.6 0.8 1.0 1.2 1.4 0.4 0.6 0.8 1.0 1.2 1.4 0.4 0.6 0.8 1.0 1.2 1.4

Retrofitted/Original axial Retrofitted/Original axial Retrofitted/Original axial


force force force

(a) (b) (c)


Fig. 13. Retrofitted/Original compressive axial force demand in side columns of: (a) 12-storey (b) 8-storey (c) 4-storey frames.

Fig. 14. Axial force history of first storey middle columns of 8-storey frame under Kobe earthquake record: (a) before and (b) after retrofitting.

subjected to different earthquake records is evaluated. calculated. These capacities are divided into a number of finite levels
and the moment-curvature curve corresponding to different levels of
compressive and tensile axial loads are then evaluated. Fig. 16 shows
5.1. Column performance diagram
moment-curvature curves for column section C1 of the 8-storey frame
(see Fig. 4) for Collapse Prevention (CP) performance level under two
To examine the effects of X-bracing retrofit on the performance le-
different axial force levels. The next step is to find a curvature corre-
vels of columns, both the axial forces and bending moments should be
sponding to the specified performance level for each moment-curvature
considered. Considering that the columns performance under axial
curve. In this study, curvature corresponding to 80% of the maximum
loading is evaluated using force-controlled technique, the value of axial
moment is considered as the CP performance level curvature.
force is considered as the parameter to control performance. However,
By using this procedure, we find a couple of mirror points (P-ϕ) for
performance under bending moment is evaluated using displacement-
every axial force level. By joining these points together we obtain the
controlled method. Since, after formation of plastic hinges the bending
performance curve for the column under study (see Fig. 17).
moment remains constant at these locations, the value of bending
moment cannot be a suitable parameter for determining performance
point; instead, the curvature is used. As a result, the column perfor- 5.2. Typical performance diagrams for 8-storey frame
mance evaluation is carried out by examining the column axial force
and the end curvature. Different performance levels for structures and structural members
To achieve this objective, it is needed to determine the curvature are defined in codes of practice. The three main levels include:
corresponding to the performance level under consideration. Immediate Occupancy (IO), Life Safety (LS) and Collapse Prevention
Considering that moment-curvature curve is a function of axial load of (CP). The evaluation of curvature corresponding to CP level (φCP ) was
the column, the column compressive and tensile capacities are first discussed above. To evaluate curvature corresponding to the other two

823
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

12 8 Average
11
7 AVG+STDV
10
AVG-STDV
9 6
4
8
5
Storey

Storey
7
6 3
4

Storey
5
4 3
2
3
2
2
1 1 1
0 10 20 30 0 10 20 30 0 10 20 30

Number of significant Number of significant Number of significant


peaks peaks peaks
(a) (b) (c)
Fig. 15. Number of significant peaks in retrofitted frame: (a) 12-storey, (b) 8-storey and (c) 4-storey.

1000 1000
800 800
Moment (kN.m)
Moment (kN.m)

600 600

400 400

200 200

0 0
0 0.0001 0.0002 0.0003 0.0004 0 0.0001 0.0002 0.0003 0.0004
Curvature (1/cm) Curvature (1/cm)
a. Moment-curvature with 230 Ton axial force b. Moment-curvature with 620 Ton axial force
Fig. 16. Finding curvature corresponding to CP performance level (Column section C1 of 8-storey frame).

performance levels (LS and IO), the relations given by FEMA 356 [41]
are used:

θLS ∗φCP
φLS =
θCP (2)

θIO ∗φCP
φIO =
θCP (3)

where φLS , φCP and φIO correspond to curvature of LS, CP and IO per-
formance levels, respectively. Also, θLS , θCP and θIO respectively corre-
spond to rotation of LS, CP and IO performance levels.
Fig. 18 shows the performance diagrams for middle columns of the
1st, 2nd and 6th storey of the 8-storey frame before and after retro-
fitting under Imperial Valley earthquake record. In these diagrams the
performance curves for IO, LS and CP levels are drawn (see Fig. 18a).
Also drawn in the diagrams is the demand curve (obtained for the
Imperial Valley record). Fig. 18 an indicates that the middle columns of
the 1st storey before retrofitting do not satisfy any of the three IO, LS
and CP performance levels, whereas, after retrofitting (Fig. 18b), the
Fig. 17. Typical performance curve.
columns satisfy the CP performance level, but fail the IO and LS levels.
The situation for the 2nd storey is somewhat different. Before retro-
fitting, the middle columns in this storey satisfy all three performance
levels (Fig. 18c), however, after retrofitting, they fail the IO and LS
levels and only satisfy the CP level. In the 6th storey, before retrofitting

824
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

(a) Original frame, 1st Storey (b) Retrofitted frame, 1st Storey

(c) Original frame, 2nd Storey (d) Retrofitted frame, 2nd Storey

(e) Original frame, 6th Storey (f) Retrofitted frame, 6th Storey
Fig. 18. Performance diagrams of middle columns in 1st, 2nd and 6th storeys of 8-storey frame under Imperial valley earthquake.

825
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

12 8 Average
11
AVG+STDV
7
10
AVG-STDV
9 6
4
8
5
Storey

Storey
7
6 3
4

Storey
5
4 3
2
3
2
2
1 1 1
0.01 0.03 0.13 0.50 2.00 8.00 0.01 0.03 0.13 0.50 2.00 8.00 0.01 0.03 0.13 0.50 2.00 8.00
Performance number Performance number Performance number

(a) (b) (c)


Fig. 19. Performance of middle columns of original frames: (a) 12-storey (b) 8-storey and (c) 4-storey.

12 8 Average
11 AVG+STDV
7
10
AVG-STDV
9 6 4
8
5
Storey

7
Storey

6 3
4
Storey

5
4 3
2
3
2
2
1 1 1
0.01 0.03 0.13 0.50 2.00 8.00 0.01 0.03 0.13 0.50 2.00 8.00 0.01 0.03 0.13 0.50 2.00 8.00

Performance number Performance number Performance number

(a) (b) (c)


Fig. 20. Performance of middle columns of retrofitted frames: (a) 12-storey, (b) 8-storey and (c) 4-storey frame.

middle columns fail the IO level but satisfy the LS and CP levels, that: φ < φpl . In this study, the performance number for CP level is first
whereas, after retrofitting they satisfy all three performance levels evaluated. Then, with reference to Eqs. (2) and (3), the following re-
(Fig. 18f). lations are derived and used to evaluate the other two performance
levels (IO and LS) without the need to separately evaluate the perfor-
5.3. Quantifying column performance mance numbers for these two performance levels.
φ
It is evident that for every column in every storey of each frame CP performance levelφ < φcp → < 1.0LS performance level φ
φCP
subjected to any of the earthquake records, a different performance
θLS ∗φCP φ θ
diagram may be obtained. This would make comparisons rather diffi- < → < LS IO performance levelφ
cult. To quantify the performance levels in order to facilitate the θCP φCP θCP
comparison of different columns performances, a new parameter in the θIO ∗φCP φ θ
< → < IO
form of φ is defined, in which φ is the demand curvature, which is θCP φCP θCP (4)
φpl
experienced by columns during earthquake and φpl is the curvature φ
Therefore, if the evaluated CP performance number ( ) is less than
corresponding to the desired performance level as defined previously φCP

(Eqs. (1) and (2)). This parameter is termed ‘performance number’ and unity, it is the CP performance level; if the CP performance number is
its values higher than unity represent failure to satisfy the specified larger than θIO and smaller than θLS , it is the LS performance level and if
θCP θCP
θIO
performance level. To reach the desired performance level, it is evident the CP performance number is smaller than it is accepted as the IO
θCP

826
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

8.00
4.00
2.00

Performance number
1.00
0.50 Average (Retrofitted)
0.25 Average (Original)
0.13 CP LEVEL
0.06
IO LEVEL
0.03
LS LEVEL
0.02
0.01
1 2 3 4 5 6 7 8 9 10 11 12
Storey
(a)
8.00 8.00
4.00 4.00

Performance number
Performance number

2.00 2.00
1.00 1.00
0.50 0.50
0.25 0.25
0.13 0.13
0.06 0.06
0.03 0.03
0.02 0.02
1 2 3 4 5 6 7 8 1 2 3 4
Storey Storey

(b) (c)
Fig. 21. Comparison the performance level of mid-column between original and retrofitted frame (a) 12 storey (b) 8 storey (c) 4 storey.

10000 storeys of the three frames before retrofitting and subjected to different
earthquake records are thus evaluated and plotted on semi log axes in
Number of cycle to failure

1000 Fig. 19 and those for the frames after retrofitting are plotted in Fig. 19.
Also plotted in these figures are the performance numbers for the three
IO, LS and CP performance levels, with CP level being taken as the base
100 level (performance number = 1.0). The dotted lines in the figures also
Nf

represent the average values for different earthquake records. Fig. 19a
10 shows that in the 12-storey frame only middle columns of the 1st storey
do not satisfy any of the performance levels; those of the 2nd storey
1 satisfy LS level and middle columns of the 3rd storey upwards satisfy all
three performance levels. Similar results are noted for the 8-storey
frame (Fig. 19b) and the 4-storey frame (Fig. 19c), with the exception
0.1 that in the 4-storey frame, columns of the 3rd storey also do not satisfy
0.002 0.022 0.042 0.062 0.082 the IO and LS levels.
Strain amplitude In order to have a better comparative view of the effects of retro-
fitting on the performance levels of middle columns, the average per-
Fig. 22. Number of cycles to failure in constant strain amplitude.
formance numbers for different earthquake records (shown in Figs. 19
and 20 as dotted lines) for the three frames before and after retrofitting
performance level. CP performance numbers greater than unity are are compared in Fig. 21. With reference to Fig. 21a, it is clear that by
considered as failure. The procedure to evaluate the performance adding steel X braces to the 12-storey RC frame, the average perfor-
number is as follows. The column performance at every levels of mance number in storeys 1–7 and storey 10 actually increases, it is
loading is considered, which includes a pair of (P, φ ); moreover, using unchanged in storeys 8, 9 and 11 and reduces only in storey 12. The
the value of P and evaluating the performance curve defined in the increases in the lower storeys are substantial, such that in the 3rd to 5th
previous section, the value of φpl is obtained. Next, φ parameter is storeys the column performance levels have changed from a high per-
φpl
computed for that specific loading. This process is repeated for the formance IO level. This indicates the adverse effects of X-braced ret-
entire period of time history analysis and the maximum value of φ is rofitting on the performance of middle columns in taller frames. A si-
φpl
milar trend can be seen in the 8-storey frame (Fig. 21b). Retrofitting the
reported as the performance number.
frame has somewhat improved the performance of the 1st storey
The performance numbers evaluated for the middle columns in all

827
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

Fig. 23. Strain time history of the 1st storey middle columns of the 8-storey frame under Imperial Valley earthquake.

12 8
Average
11
7 Avg+STDV
10
AVG-STDV
9 6
4
8
5
Storey

7
Storey

Storey
6 3
4
5
4 3
2
3
2
2
1 1 1
0.000
0.001
0.004
0.016
0.063
0.250
1.000
4.000

0.000
0.001
0.004
0.016
0.063
0.250
1.000
4.000
0.000
0.001
0.004
0.016
0.063
0.250
1.000
4.000

Fatigue damage Fatigue damage Fatigue damage

(a) (b) (c)


Fig. 24. Fatigue damage in the original frames: (a) 12-storey, (b) 8-storey and (c) 4-storey.

columns by 34% but it is still not sufficient to satisfy the CP perfor- due to retrofitting may be different and need to be separately in-
mance level. However, retrofitting has substantially reduced the per- vestigated.
formance of middle columns in the 2nd, 3rd and 4th storeys, reducing
the level from IO to LS. The situation in the 4-storey frame is again 6. Fatigue
different to that of the 8 and 12 storey frames. In the 4-storey frame,
after retrofitting the performance of middle columns in almost all Earthquake loading is cyclic loading in nature and in cyclic beha-
storeys has improved. The average performance number for the 1st viour degradation of stiffness and strength are inevitable, resulting in a
storey columns is reduced by 52%, bringing it down to satisfy the CP cumulative reduction in service life. Under cyclic loading, one of the
performance level. In the 2nd storey, performance number is somewhat most important factors in accumulation of damage is the effect of fa-
increased, but the performance level remains LS and substantial per- tigue intensity of which depends on the amplitude of loading and the
formance enhancement is observed for the 3rd and 4th storey bringing number of cycles. However, the number of cycles induced by earth-
them to well within IO level. quake loading is relatively low, but the amplitude of some of cycles is
Based on the above discussion, it can be stated that in mid to high large and sometimes beyond the elastic range, therefore, so low-cycle
rise RC frames, retrofitting the frame with X bracing system generally fatigue is possible.
reduces the performance level of the middle columns. The 1st storey
fairs better due to retrofitting, but any improvements in the 1st storey is
associated with deterioration in the upper storeys. It appears that ret- 6.1. Fatigue life
rofitting shifts the problem from the 1st storey further up in the frame.
In the shorter frames (4-storey), on the other hand, retrofitting gen- In order to estimate fatigue life of steel rebar in an RC frame, several
erally improves the performance levels of the middle columns. It should relationships have been proposed in literature, predicting the number
be noted that in this section only the performance of middle columns, as of cycles to failure at a given strain amplitude. In this regard, the
structural members, is discussed. The overall performance of the frames Mander relationship, as the first relationship proposed for low-cycle
fatigue behaviour of reinforcing bars, states that [42]:

828
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

12 8 Average
11 AVG+STDV
7
10
AVG-STDV
9 6 4
8
5
Storey

Storey
6 3
4

Storey
5
4 3
2
3
2
2
1 1 1
0.000
0.001
0.004
0.016
0.063
0.250
1.000
4.000

0.000
0.001
0.004
0.016
0.062
0.250
1.000
4.000
0.000
0.001
0.004
0.016
0.063
0.250
1.000
4.000
Fatigue damage Fatigue damage Fatigue damage

(a) (b) (c)


Fig. 25. Fatigue damage in the retrofitted frames: (a) 12-storey (b) 8-storey and (c) 4-storey frame.

εa = 0.0795(2Nf )−0.448 (5) 1st storey and damage in higher storeys is not significant, except for
locations of high stress concentration, caused by a change in column
As show in Fig. 22, by increasing strain amplitude (εa ) number of cross section.
cycles to failure (Nf ) decreases considerably, especially for inelastic The fatigue damages for middle columns of the frames after retro-
strains greater than 2%. fitting by steel X braces are plotted in Fig. 25. It can be noted that by
By adding steel braces, reinforcement strain amplitude increases, adding steel braces, fatigue damage in the 12-storey frame increases in
consequently the number of cycles to failure decreases, increasing the almost all storeys compared to the original frame. The maximum da-
chance of low-cycle fatigue. Fig. 23 shows strain history in middle mage is again observed in the 1st storey (average 73%) which shows a
column of the first storey of 8-storey frame under Imperial Valley 43% increase in damage compared to the original frame. Also, fatigue
earthquake. As it can be seen, the amplitude of strain in earthquake damage increases by 46% in the 2nd storey and 59% in the 3rd storey.
loading is not constant and it changes from cycle to cycle. In a number of cases, in the first three storeys, damage values become
larger than 100%, which means longitudinal reinforcements fail in fa-
6.2. Palmgren-Miner damage rule tigue while in the original frames it only occurs in the 1st storey. It is
clear that retrofitting the 12-storey frame is not successful in reducing
Since Mander’s relationship is based on constant strain amplitude, fatigue damage and also make it worst especially in the first three
Palmgren-Miner [43] damage rule is used to account for the changing storeys. Fatigue damage in first storey is worrying.
strain. This rule simply states that; the fatigue life of a structure or an Fig. 25b shows that the maximum fatigue damage occurs in the 2nd
element is exhausted when the sum of all the fatigue fractions at dif- storey of the 8-storey frame (averaging 35%) which is 32% higher than
ferent loading amplitudes from a random fatigue loading is equal to in the original frame. Also, after retrofitting, fatigue damage in the first
unity. In this paper the number of cycle to failure (Nf ) in each cycle is storey decreases by 8%, whereas, damage in the 3rd and 4th storeys
calculated by the Mander’s relationship and then by using Palmgren- increase up to an average of 12%. Retrofitting the 4-storey frame by
Miner damage rule the cumulative fatigue damage of longitudinal re- steel braces, however, results in reduced fatigue damage in all storeys
inforcement is calculated as follows: (see Fig. 25c) with maximum reduction occurring in the 1st storey.

N1 N N N
+ 2 + 3 + ….= ∑ i = 1 7. Conclusions
Nf 1 Nf 2 Nf 3 Nfi (6)
The possible adverse effects of retrofitting RC frames with steel X
The fatigue damage ratios, calculated as per Eq. (6), for the middle
bracing on the RC columns were explored numerically. The results of
columns of different storeys of the three frames before retrofitting are
the investigation lead to the following conclusions:
plotted on semi log axes in Fig. 24. The results for the 12-storey original
frame show that the maximum fatigue damage has occurred in the 1st
1. In the low-rise, 4-storey frame, the shear in middle columns (col-
storey, averaging around 30%. However, fatigue damage higher up the
umns attached to the steel bracing) decrease due to retrofitting
frame is not significant. Similarly, the results of 8-storey original frame
which is desirable. However, in the 8 and 12-storey frames it in-
show the maximum fatigue damage occurs in the 1st storey averaging
creases, particularly in the lower storeys. It appears that as the
around 38%, with the most fatigue occurring in Kocaeli earthquake by
height of the frame increases, the adverse effect of retrofitting on the
82%. The second most damaged storey (with 6% average accumulative
shear in middle columns increases. The same pattern is noted for
damage) is the 6th, which is the location of change in the column cross
shear in side columns, but with less intensity.
section. In the 4-storey frame, fatigue damage is also localized in the
2. After retrofitting, the axial compression force in the middle columns
first storey by a large amount (136% in average) and the 3rd storey,
increase significantly and as the number of storeys increases, this
being the location of change in column cross section, by 20%. The re-
effect is intensified.
sults of the three frames show that the fatigue damage is localized in the

829
A. Rahimi, M.R. Maheri Engineering Structures 173 (2018) 813–830

3. In taller, 8 and 12 storey frames, the middle columns may experi- Steel Const 1991;4:20–3.
ence large axial tensile forces (up to 1500 kN) after retrofitting. Such [12] Hjelmstad KD, Foutch DA, Del Valle E, Downs RE. Forced vibration studies of an RC
building retrofit with steel bracing. In: Proc 9th world conf. Earthquake. Eng,
considerable tensile forces are alarming as lap splice failure at the Tokyo-Kyoto 1988;2:469–74.
lower storeys of the frame may occur. [13] Tagawa Y, Aoki H, Huang T, Masuda H. Experimental study of new seismic
4. The axial force in side columns does not show any significant change strengthening method for existing RC structures. In: Proc 10th world conf. Earthq.
Eng, Rotterdam 1992:5193–5198.
after retrofitting. [14] Maheri MR, Sahebi A. Experimental investigation on the use of steel bracing in
5. Under earthquake loading, the number of cycles with large fluc- reinforced concrete frames. In: Proc 2th World Conf. Earthquake. Eng., Iran
tuations of axial force are considerable in the retrofitted 8 and 12- 1995:775–784.
[15] Maheri MR, Sahebi A. Use of steel bracing in reinforced concrete frames. Eng Struct
storey frames. This has a negative effect on lap splice performance, 1997;19(12):1018–24.
as well as, on low-cycle fatigue. The 4-storey frame shows a different [16] Abou-Elfath H, Ghobarah A. Behaviour of reinforced concrete frames rehabilitated
behaviour in this regard and performs better after retrofitting. with concentric steel bracing. Can J Civ Eng 2000;27:433–44.
[17] Ghobarah A, Abou-Elfath H. Rehabilitation of reinforced concrete frames using
6. Retrofitting RC frames with steel X braces, increases the perfor-
eccentric steel bracing. Eng Struct 2001;23:745–55.
mance level of all columns in the 4-storey frame. However, retro- [18] Maheri MR, Kousari R, Razazan M. Pushover test on steel X-braced and knee-braced
fitting the 8-storey and 12-storey frames decreases the performance RC frames. Eng Struct 2003;25:1697–705.
level of the lower storeys. [19] Pincheira JA, Jirsa JO. Seismic response of RC frames retrofitted with steel braces
or walls. J Struct Eng 1995;121(8):1225–35.
7. In the 4-storey frame, after retrofitting, the fatigue damage of [20] Viswanath KG, Prakash KB, Anant D. Seismic analysis of steel braced reinforced
middle columns decreases in almost all storeys. However, in the 8 concrete frames. Int J Civ Struct Eng 2010;1(1):114–22.
and 12-storey frame, retrofitting increases the fatigue damage in [21] Maheri MR, Akbari R. Seismic behaviour factor, R, for steel X-braced and knee-
braced RC buildings. Eng Struct 2003;25:1505–13.
lower storeys of the frame. [22] Jain AK. Seismic response of RC frames with steel braces. J Struct Eng
8. As a general conclusion it can be stated that retrofitting low-rise RC 1985;111(10):2138–48.
frames with steel X bracing is beneficial to the frame in almost every [23] Maheri MR, Ghaffarzadeh H. Mechanical compression release device in steel bra-
cing system for retrofitting RC frames. Earthq Eng Eng Vib 2006;5(1):151–8.
aspect; however, for mid to high-rise frames, the adverse effects of [24] Maheri MR, Ghaffarzadeh H. Connection overstrength in steel-braced RC frames.
steel bracing retrofitting, particularly on columns attached to the Eng Struct 2008;30(7):1938–48.
bracing system (middle columns), are noticeable and should be [25] Rahai A, Lashgari M. Seismic strengthening of nine-story RC building using con-
centric and buckling-restrained bracing. In: Proc 31st world conf. Concrete.
taken into consideration. Retrofitting these columns by Steel or RC Structures. Singapore 2006;2:421–6.
jacketing prior to bracing may be necessary to overcome the latter’s [26] Ozel AE, Guneyisi EM. Effects of eccentric steel bracing systems on seismic fragility
side effects. curves of mid-rise R/C buildings: a case study. Struct Safety 2011;23(1):82–95.
[27] Maheri MR, Hadjipour A. Experimental investigation and design of steel brace
connection to RC frame. Eng Struct 2003;25(13):1707–14.
Appendix A. Supplementary material [28] Maheri MR, Yazdani S. Efficiency of the uniform force method in designing steel
brace connection to RC frame. Construct Steel Res 2016;116:131–40.
Supplementary data associated with this article can be found, in the [29] Maheri MR, Yazdani S. Seismic performance of different types of connection be-
tween steel bracing and RC frames. Iranian J Sci Tech Trans Civil Eng (IJSTC)
online version, at https://doi.org/10.1016/j.engstruct.2018.07.003. 2016;40(4):287–96.
[30] Mazzoni S, Mckenna F, Scott MH, Fenves GL. OpenSEES Command Languqage
References Manual[Z]. http://OpenSEES. Berkeley.edu/OPENSEES/manuals/usermanual/
OpenSEES Command Languaeg Manual; June 2006.
[31] Hsiao P, Lehman D, Roeder CH. Improved analytical model for special con-
[1] Sekiguchi I. Seismic strengthening of an existing steel reinforced concrete city office centrically braced frames. J Construct Steel Res 2012;73:80–94.
building in shizuoka. In: Proc. 9th world conference. Earthquake. Eng. Tokyo-Kyoto [32] Gunnarsson IR. Numerical performance evaluation of braced frame systems. Seattle:
1988:2:439–444. University of Washington; 2004. [MSc thesis].
[2] Del Valle Calderon E, Foutch A, Hjelmstad KD, Figueroa-Gutierrez, Tena-Colunga A. [33] Kent DC, Park R. Flexural members with confined concrete. ASCE J Struct Eng
Seismic retrofit of a RC building: a case study. In: Proc. ninth world conference. 1971;97:1969–90.
Earthquake. Eng. Tokyo-Kyoto 1988;2:451–456. [34] Menegotto M, Pinto PE. Method of analysis of cyclically loaded RC plane frames
[3] Badoux M, Jirsa O. Steel bracing of RC frames for seismic retrofitting. Struct. Eng including changes in geometry and non-elastic behavior of elements under normal
1990;116(1):55–74. force and bending. Preliminary Report, IABSE 1973;13:15–22.
[4] Bush TD, Jones EA, Jirsa JO. Behaviour of RC frame strengthened using structural [35] Niroomandi A, Maheri A, Maheri MR, Mahini SS. Seismic performance of ordinary
steel bracing. Struct Eng 1991;117(4):1115–26. RC frames retrofitted at joints by FRP sheets. Eng Struct 2010;32(8):2326–36.
[5] Nateghi-Alahi F. Seismic strengthening of eight story building using steel braces. [36] Iranian code of practice for seismic resistance design of buildings. Standard No.
Eng Struct 1995;17(6):455–61. 2800. 4th. ed. 2014.
[6] Sugano S, Fujimura M. Seismic strengthening of existing reinforced concrete [37] ACI Committee 318. Building code requirements for reinforced concrete (ACI 318-
buildings. In: Proc.7th world conference. Earthquake. Eng, Istanbul 02) and commentary (ACI 318R-02), American Concrete Institute, Detroit,
1980;5:449–456. Michigan.
[7] Higashi Y, Endo T, Shimizu Y. Experimental studies on retrofitting of reinforced [38] AISC 360-05. Specification for structural steel buildings. American Institute of Steel
concrete structural members. In: Proc 2nd Seminar on repair and retrofit of struc- Construction (AISC); 2005.
tures, Ann Arbor, Michigan, National Science Foundation; 1981:126–55. [39] ASCE 7-10. Minimum design loads for buildings and other structures. In: ASCE
[8] Kawamata S, Ohnuma M. Strengthening effect of eccentric steelbraces to existing standard ASCE/SEI 7-10. American Society of Civil Engineers; 2005.
reinforced concrete frames. In: Proc 2nd seminar on repair and retrofit of structures, [40] Japan Society of Civil Engineering (JSCE). Standard specification for concrete
Ann Arbor, Michigan, National Science Foundation; 1981:262–9. structures; 2007.
[9] Usami H, Azuchi T, Kamiya Y, Ban H. Seismic strengthening of existing reinforced [41] American Society of Civil Engineering (ASCE). Prestandard and commentary for the
concrete buildings in Shizuoka prefecture, Japan. In: Proc 9th world conf. seismic rehabilitation of buildings, Prepared for the Federal Emergency
Earthquake. Eng, Tokyo-Kyoto 1988;2:421–6. Management Agency, FEMA 356; 2000.
[10] Ohishi H, Takahashi M, Yamazaki Y. A Seismic strengthening design and practice of [42] Mander JB, Panthaki FD, Kasalanti A. Low cycle fatigue behavior of reinforcing
an existing reinforced concrete school building in shizuoka city. In: Proc. Ninth steel. ASCE Mater Civil Eng 1994;6:453–67.
world conference. Earthquake. Eng. Tokyo-Kyoto 1988;2:415–420. [43] Miner MA. Cumulative damage in fatigue. Appl Mech 1945;3:159–64.
[11] Wylli LA, Dal Pino JA, Cohen J. Seismic upgrade preserves architecture. Modern

830

You might also like