Professional Documents
Culture Documents
Operation, &
Maintenance
4550 FSXB
High Read these instructions prior to
Pressure installation.
Manual #: IP55836XA
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
i
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Index
Section Page
Introduction 1
1. General Information 1
3. Installation 4
4. Coupling Alignment 7
5. Lubrication 11
6. Startup / Operation 12
7. Preventive Maintenance 13
8. Maintenance 15
9. Maintenance Data 23
10. Troubleshooting 25
Drawings
Sectional Assembly
Outline
Mechanical Seal
ii
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Introduction
This manual is intended to assist those
concerned with installation, operation and - Refers to a general note.
maintenance of Warren 4550 FSXB screw
pumps. It is the manufacturer’s hope that the - Designates an important note or step.
following discussions will be clearly and
easily understood. Should questions arise
- Designates the need for lockout / tag-
that cannot be answered from the material
out procedures.
contained in this manual, we suggest that the
Warren Sales Department be contacted at
413-436-7711 or by email at: - Designates possible injury to
warrensales@colfaxcorp.com personnel if proper lifting equipment is not
Symbols found within these instructions are used.
used to highlight important notes, precautions
- Overhead crane or other, suitable
and to draw attention to steps that may cause
lifting device required.
damage to equipment or personal injury if not
conducted properly.
1. General Information
The 4550 FSXB screw pump is made up of Integral Screw/Shaft – Each rotor is of an
two pairs of opposed screws. Each pair of integral design, meaning the entire screw and
screws conveys liquid to the center of the shaft is machined out of one piece of material
pump where the discharge port is located. allowing for maximum rigidity and stiffness.
Because the hydraulic forces generated are This minimizes shaft deflection, an important
opposite and equal, the rotor is hydraulically consideration in high-pressure service.
balanced axially.
The pumps have the shortest possible span Bearing Brackets – Single piece brackets
between bearings. This design produces a allow for shortened bearing spans. The
rigid rotor capable of continuous duty and brackets may be modified for seal leakage
permits high-pressure operation with reduced detection, vibration sensors, pressurized flush
bore contact. systems, etc.
Body – The solid cast body is has thick cross Double Helical Timing Gears – Timing
sections for pipeline pressures and rigidity. gears are used to prevent contact between the
meshed, rotating screws. The clearance
Liner – The solid cast liner separates suction between the pumping screws relates to
and discharge chambers and acts as the wear extended pump life and higher, average
item in the pump. This allows for field repair efficiency over the life of the pump. Factory
reducing down time as well as reducing performed timing is easily repeated with
repair costs. Warren’s method of gear and screw
Page 1
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
synchronization (timing). Gears are oil bath heavy-duty, double row thrust bearing locks
lubricated or by pressurized systems and are the driveshaft in position axially.
sealed off from the pumped fluid by internal
mechanical seals and /or lip seals. Coolers or Wear Protection - To insure long life in
external cooling systems are used when tough services, the critical pumping surfaces
required for the given conditions of service. may be coated. The liner bores can be coated
with electrolytic applied hard chrome. The
Bearings – Radial loading is handled by screws may have a variety of OD coatings
heavy-duty roller bearings at five locations with hardness in excess of 60 (Rockwell C).
that are sized to handle maximum loads. Nitride and other coating combinations are
They are oil lubricated and are sealed off added features that, when combined with the
from the pumped fluid by internal chrome lined bore have proven to be the best
mechanical seals and/or lip seals. One, wear protection in the industry.
Page 2
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Page 3
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
3. Installation
3.2. Foundation - Foundations should be of
Important – The following installation suitable mass to absorb vibration and provide
instructions are a guide to assist you in a rigid support for the unit. Use reinforcing
proper installation procedures. Probably the steel as necessary.
most important thing you can do to enhance A template should be made to position and
the life and smooth operation of this machine hold the foundation bolts in place while
is to plan your installation by following these pouring the concrete. Location and sizes of
installation procedures and other good boltholes are shown on the certified outline
machinery practices. If questions should drawing supplied to the purchaser. Each bolt
arise, contact the Warren Aftermarket is installed in a pipe sleeve, the inside
Department for assistance. diameter of which should be three times the
outside diameter of the bolt. The pipe sleeve
allows for minor adjustments in bolt spacing
Note: Protect your investment. A after foundation is in place (Fig. 3-1). Two
properly planned and executed installation is methods commonly used to secure and
necessary for trouble free pump performance. prevent bolts from turning are:
1. A washer is placed between the bolt
3.1. Location – Screw pumps are purchased head and pipe sleeve with a lug
to deliver a specific capacity at a specific welded to the bolt head (Fig. 3-1).
pressure. To accomplish this, the designer 2. The bolt may be of rod construction,
must take into consideration the conditions bent 90o below the pipe sleeve.
that will exist on the suction and discharge Foundation bolts must be long enough to
sides of the pump after installation such as allow from ¾” to 1” for grouting under the
suction lift or head, temperature and viscosity base plate (Fig. 3-1). When pump is level,
of the oil. This information is given to the the bolts should extend ¼” through the nuts.
pump engineer by the purchaser and is based Leave top surface of foundations rough for
on a preplanned location of the pump in a adherence of grout.
system. In order for the pump to operate as
designed, it must be located in this 3.3. Base Plate
preplanned location. If, after receipt, another
location is considered that might alter the 3.3.1. Leveling – Before placing the unit on
preplanned conditions, it is recommended the foundation, be sure the surface of the
that Warren Engineering be consulted to foundation is clean and roughed. Place the
insure satisfactory operation of your FSXB leveling wedges adjacent to foundation bolts.
Series Screw Pump. Clean underside of pump foundation, lower
Locating the pump as near to the source of unit over base plate bolts and onto wedges.
supply as possible is advisable. Ideally, the Adjust the wedges to allow for ¾” to 1” of
location should be well lit and dry with grout, being sure pump flanges are plumb.
enough room to perform routine maintenance This unit has been factory aligned and
and space enough for rigging, etc. If you find uneven bearing of wedges can cause
it necessary to locate the unit in a pit, be sure misalignment. Snug up, but do not make up
to make provisions to prevent flooding. hard the foundation bolts. Check coupling
alignment and correct as necessary. Avoid
Page 4
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
base plate distortion. Level the pump with a aligned with pump flanges. Piping, subject to
spirit level. high temperatures, must be fitted with a
3.3.2. Grouting – Build a board dam around means of absorbing expansion. Piping strain
the foundation to the desired height for on the pump may cause distortion resulting in
finished grouting (See Fig. 3-1). A mixture misalignment or vibration.
of one part Portland cement to two parts 5. If pumps have studded flanges, piping
clean sand with just enough water to mix to a alignment is correct if flange studs are
thick creamy consistency should be made for centered within holes of pipe flanges and if
grout. Wet the underside of the base plate pump and pipe flange faces are parallel with
and foundation top then, pour the grout each other. To check piping alignment of
through the holes in the base plate. pumps having bolted flanges, insert flange
Thoroughly puddle the grout during pouring bolts through pipe and pump flange. If bolts
to prevent air pockets and hollow spots. are easily moved within the boltholes and if
After grout has set sufficiently remove the flange faces are parallel with each other,
board dam and finish off the grout as desired. piping is properly aligned.
When grout has hardened, usually in about 6. Maintain sufficient gap between
48 hours, pull up on foundation bolts. flange faces for inserting the gasket. Flanges
must not butt tightly before being secured.
3.4. Piping
Page 5
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
valve must be installed. This valve will the pump may completely dry out while idle,
prevent hydraulic shock acting upon the a foot valve may be used to help keep the
pump and will also prevent reverse rotation pump primed. Foot valves are not usually
of the pump when stopping the unit. required when handling liquids of higher
3. Relief Valves – Pressure relief valves viscosity.
must be installed between the discharge valve
and discharge valve of screw pumps to 3.6. Doweling – After the unit has been
protect both the pump and piping system. running for about one week, the coupling
The valve and piping system must be solidly halves must be given a final check for
constructed of proper material with ample possible misalignment caused by pipe strains
opening for passage of full discharge or strains caused by thermal growth. This
capacity, because positive displacement check must be made immediately after unit is
pumps can build up pressure rapidly, if the shut down, before it has a chance to cool. If
discharge is restricted or shut off. This type alignment is correct, and unless Warren
of relief valve must lead back to the source of instructs otherwise, the driver must now be
supply or other suitable collecting point to doweled on diagonal feet.
prevent product loss and an excessive
temperature rise of the re-circulated fluid in
pump that operate unattended. Note: With the exception of vertical
4. Vent – If pump is required to operate units, which are completely doweled at the
with a suction lift, a suitable means for factory, the pumps are normally doweled in
venting the pump must be installed in the the field. The dowel size for the driver will
discharge piping adjacent to the pump. usually be the same size as the pump dowels.
5. Foot Valves – For pumping low
viscosity liquid with a high static lift, where
Page 6
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
4. Coupling Alignment
4.1. Alignment – The flexible coupling record the reading at the 9 o’clock
supplied with your pump is not designed to position. The purpose in rotating
operate with excessive misalignment. both halves together is to eliminate
Reducing misalignment in your coupling the possibility of inaccurate shaft
installations will increase coupling life and centerline alignment due to coupling
greatly in crease operating life of associated run-out.
equipment such as bearings, packing and 3. The indicator reading will show
seals. double the amount of correction
Check the following prior to aligning the required to true the coupling side to
pump and driver. Set the coupling gap side. If the indicator moved in a
within tolerances given on the supplied counter-clockwise direction, the
outline drawing. During any work reading is considered negative. If
performed on either the pump or the driver, the movement was clockwise, it is
considered a positive reading.
BE CERTAIN THAT ACCIDENTAL 4. If the reading was positive, push the
ENERGIZING OF THE SYSTEM motor in the 3 to 9 o’clock direction
CANNOT OCCUR. ½ the total indicator reading. Push
the motor towards the starting point
Coupling alignment must be handled in all (3 o’clock) ½ the indicator reading if
three planes. it was negative.
To set side to side alignment: 5. Return to the 3 o’clock position and
1. Mount a dial indicator rigidly on the reset at zero.
driver half of the coupling and set 6. Turn the coupling halves together
the indicator button on the rim of the and re-check the alignment. If not
pump half (Fig. 4-1). quite zero at 9 o’clock, repeat the
procedure until a 0-0 reading is
obtained in the 3 and 9 o’clock
positions.
Page 7
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Should the top be open in relation to 2. Turn both coupling halves together
the bottom, the back feet must be and take the readings in the 6 o’clock
shimmed. position.
2. Side-to-side variance in the coupling 3. If the reading is negative, place shim
gap (Fig. 4-3) is compensated for by stock equivalent to ½ the indicator
moving the back of the driver in the reading under each of the driver feet.
appropriate direction to equalize the If the indicator has a positive
gap. reading, shims equivalent to ½ the
reading must be removed from each
of the driver feet.
4. Return to the 12 o’clock position and
reset to zero. Turn the coupling
halves and check the reading. If the
reading is not zero, repeat the
preceding steps until the zero reading
is obtained.
Fig. 4-2 Upon completion of the alignment
procedure for the third axis, the alignment in
Various factors affect the shimming of the the other two axes must be checked.
driver feet to correct coupling gap. For Setting the vertical alignment may throw the
example, the distance of the driver foot from side-to-side and / or face-to-face alignment
the coupling will affect the amount of out of tolerance. Due to the affect each axis
compensation seen when using a shim of has on the others, it is often necessary to
specific thickness. In other words, the operate at least one alignment axis
amount of correction seen using a 0.020” approaching the allowable misalignment
shim on the front feet of the driver will be tolerance of 0.003”.
different from the amount seen when that The importance of checking the alignment
same 0.020” shim is used on the back feet. once the unit has been piped and run cannot
Each situation is sufficiently unique that the be understated. To insure that dangerous
best results are achieved through stresses are not imposed on the pump or
experimentation. driver during operation, which would reduce
operating life and may create hazards to
operating personnel, the coupling alignment
must be checked with the unit at operating
temperature within a week after initial
startup.
Fig. 4-3
Page 8
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Page 9
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
bearing life. Soft foot may be checked as 5. Shim under the soft foot to reduce
follows: the indicator travel to less than
1. Attach the base of a dial indicator to 0.002”. If multiple shims are
the base plate, placing the button of already in place, the use of fewer,
the indicator one of the pump’s feet. thicker shims will reduce the
2. Adjust the indicator to read zero. tendency of soft foot to occur.
3. Loosen the hold down bolt at the 6. Repeat this process until all of the
foot on which the indicator is pump feet have been checked and
reading. corrected for a soft foot condition.
4. If the indicator shows movement of If a dial indicator is not available, feeler
greater than 0.002” the foot is said gauges may be used.
to be soft.
Page 10
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
5. Lubrication
Page 11
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
6. Start-up / Operation
6.1. Pre Startup - Pre start-up checks are 6.2. Startup –
essential to avoid operational difficulties. 1. Fully open suction and discharge
Listed below are several items, which valves. If a bypass line is installed,
should be checked prior to the release of open the bypass valve.
equipment to regular operation. 2. If operating with hot liquids, open
1. Inspect all piping. Check for leaks and valves to admit liquid to the pump and
unnecessary piping strain on the allow sufficient time to elapse for
equipment. Flush all piping to ensure pump to warm up and expand prior to
removal of foreign material from the starting.
system. Check that all valves and 3. If pump operates in a lift condition, the
remote control equipment is body must be filled with liquid prior to
functional. initial start-up, AFTER installation of
2. Check rotating element to see that it overhaul and possibly after lengthy
turns freely. Jacking may be necessary periods of idle time. Once initial prime
on large units. IF there is any rubbing has been attained, the pump will not
or binding at this point, the equipment require priming on each start-up. A
should not be started until the cause of vent would be helpful for initial
this rubbing for binding has been priming. If the pump operates under a
located and corrected. flooded suction, simply open the
3. Before making up the pump and driver valves and allow the liquid to flood the
coupling halves, check that driver pump while venting air from some
rotation is correct. The directional convenient point in the discharge
arrow attached to the pump shows system.
rotation. 4. Start the lubrication, cooling system to
4. Align coupling halves, lubricate and the timing gears and ensure proper
make up the coupling. (See operation.
Alignment, Section 4). 5. Start driver.
5. Check oil level at both ends of pump.
Drain any oil remaining from storage. 6.3. Pump in Operation -
Recharge with new oil as prescribed in 1. Check unit for unusual noise or
Lubrication, Section 5. Check to vibration. Any unusual vibration or
ensure that oil is at the proper level in change in sound should be
both oil reservoirs. This is at the center investigated, as it may be the first sign
of the sight glass when the pump is of impending trouble.
NOT running. 2. Check bearing housing temperatures
6. If installed, remove all shipping plugs using a laser temperature detector or
as noted on the outline drawing similar device. The temperature of the
provided to the purchaser. housings can safely go to 180oF
provided the proper oil has been used.
See Section 5 - Lubrication.
3. Check suction and discharge pressure
gauges where installed.
Page 12
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
7. Preventative Maintenance
7.1. Periodic Inspection – Following are 2. Check existing pump capacity, power
periodic inspection procedures, which if and horsepower requirements against
carried out conscientiously, should pump nameplate data.
contribute to longer intervals between 3. Good timing gear maintenance will
shutdowns. result in longer pump life and
smoother operation. Timing gears
Daily – should be examined for wear and
1. Check oil levels in front head and chipping or scoring. At this time it
lubrication skid. would also be advisable to ensure that
2. Listen for unusual noise or vibration. all parts are properly secured.
Page 13
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Fig. 7-1
Page 14
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
8. Maintenance
Part numbers shown inside ( ) refer to part between the timing gear housing and
numbers shown on the sectional drawing rear bearing housing (70) using
sent to the purchaser. jacking bolts (14) supplied.
The following discussion covers the When the timing gear housing (48) is
disassembly and reassembly procedure for removed, the outer race and roller
all pump parts. Procedures for maintenance assembly of bearings (19) will be
of specific areas will follow and refer the removed with the timing gear
reader to these disassembly and reassembly housing.
procedures for instruction concerning the 6. Remove snap rings (20) from the end
removal, handling and replacement of of both shafts (7 & 8).
associated parts.
Important – The use of a Tag 7. Remove nuts (40) securing the front
Out / Lockout system is highly head (38) to bearing bracket (30).
recommended to prevent injury to personnel Break the joint between the front
or damage to equipment. Ensure proper head and front bearing housing (30)
safety measures are in place during any using jacking bolts (14) supplied.
maintenance procedures. Dowel pins (37) may be removed if
they will be replaced. Remove oil
1. Isolate the pump and driver seal (43).
hydraulically and electrically as 8. Remove locknut (63) and spacer (81)
appropriate. from coupling end of long shaft (7).
2. Disconnect piping and drain oil from Remove snap ring (11) from short
the timing gear housing (48) and shaft (8).
front head (38).
3. Disconnect any external piping Note – If bearings (10) are to be re-
connected to the pump including used, the removal of snap ring (11) is not
vents (41) and piping (93-95). necessary.
4. Remove coupling (Customer furnished).
Page 15
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
casing (1) then remove bearing 17. Install thrust bearing removal tool as
housing (30). Remove O-ring (82). shown on drawing SK-4878. Using
10. Remove mechanical seal (9) mating special tool, push the long shaft
rings from bearing bracket. bearing shoulder off of the thrust
11. If bearings will be replaced, remove bearing (22).
the inner races of roller bearings (19) 18. Remove cap screws (32) securing
from both shafts. rear bearing housing (70) to pump
12. Match mark timing gear teeth at their casing (1) then remove bearing
point of mesh. Also mark the long housing. Remove O-ring (82).
shaft timing gear in such a manner 19. Remove mechanical seal (9) mating
that it may be identified when pump rings from bearing bracket.
is to be reassembled. 20. Slide the short and long shafts (7 &
8) out of the liner (83).
21. Remove the four mechanical seal (9)
Note – The timing gears (15) have rotating assemblies from shafts.
been match marked at the factory. The 22. Inner races of bearings (10, 19 & 71)
gear associated with the long shaft (7) are shrunk on the shaft. Do not
will be marked with a single punch mark remove these parts unless they are to
or grind mark while that associated with be renewed. To remove, apply heat
the short shaft (8) will have two such lightly to expand the bearing rings
marks. then slide them off the shafts.
23. Outer races of all roller bearings are
secured in their bores with
WARNING! – The gears LOCTITE®. Do not remove these
are held in place by Ringfeders. The parts from their bores unless they are
bolts used on the Ringfeders are to be replaced. If they are to be
under great tension, DO NOT loosen removed, they must be driven out of
one bolt at a time, the bolts must be their bores using a drift pin and
loosened gradually and evenly to hammer. The timing gear housing is
prevent damage and to prevent equipped with plugged holes (36) for
personal injury. this purpose.
24. With bearings removed, shims (26)
13. Loosen Ringfeder bolts (17) (SEE lip seals (31 & 86) may now be
ABOVE) and remove timing gears removed from the front and rear
(15) from short and long shafts (7 & bearing brackets.
8). 25. Remove liner (83) from casing (1).
14. Remove cap screws (27), washers Dowel pins (84) may be removed if
(28), bearing retainer (23), and shims they are to be replaced.
(80). 26. Remove O-rings (85) from liner (83).
15. Loosen and remove locknut (87) &
lock washer (88) from the long shaft
(7). Remove spacer (24).
16. Loosen and remove locknut (89) and
lock washer (90) from the short shaft
(8).
Page 16
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Page 17
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Page 18
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Figure 8-5
Page 19
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Fig 8-8b
Figure 8-7
35. With the clearances split, remove the
34. Using a shaft turning tool and a dial backlash from the gears in the
indicator set, gently rotate the long direction of rotation. Gradually and
shaft back-and-forth until contact is evenly torque the collar (17) bolts of
felt with the short shaft. Record total
Page 20
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
the long shaft gear to the value Eliminator 515 to the other surface
provided in the table on sectional. circling all boltholes.
Page 21
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
rear bearing bracket and record as B. 2. Measure the gap between the retainer
(Average = 3.812) See figure 8-10. and the rear bearing bracket face,
6. Shim = A – B. (Approximately record as C.
0.062”) 3. Shim = C + 0.003”
7. Re-verify dimension taken in step 2
accounting for the thickness of the (0.003” is the average of the required
front bearing bracket. If this 0.002” to 0.004” on the sectional
dimension is within +/- 0.030” of the drawing)
recorded dimension shimming is
satisfactory. If dimension is more 4. Remove retainer and install shims
than +/- 0.030” the shimming is equal to the thickness calculated in
incorrect and needs to be inspected step 3.
for correctness. 5. Install lock washers (28) and cap
screws (27). Torque to value shown
in table on sectional.
6. Return to step 31 of section 8.2.
Figure 8-10
Page 22
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
9. Maintenance Data
9.1. Minor Kit
The purpose of this kit is to enable the user to have immediate access to routine maintenance
parts for use during pump commissioning or for emergency repair during the first two years of
operation.
Pc # Name Qty
9 Seal, Mechanical 4
10 Bearing, Roller 2
11 Ring, Snap 1
19 Bearing, Roller 3
20 Ring, Snap 2
22 Bearing, Roller 2
26 Shim Set 1
31 Oil Seal 3
43 Oil Seal 1
71 Bearing, Roller 2
80 Shim Set 1
82 O-ring 2
85 O-ring 2
86 Oil Seal 1
The purpose of this kit is to enable the user to have immediate access to routine maintenance
parts for use during pump commissioning or for emergency repair during the first five years of
operation. The kit contains a factory timed rotating assembly as well as parts found in the
Minor Kit.
Pc # Name Qty
* Minor Kit 1
7 Screw, Long Shaft 1
8 Screw, Short Shaft 1
15 Gear, Timing 2
17 Collar (gear) 2
63 Locknut 1
83 Liner 1
84 Pin, Dowel 2
87 Locknut 1
88 Lock Washer 1
89 Locknut 1
90 Lock Washer 1
Page 23
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Page 24
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
10. Troubleshooting
Trouble Cause of Trouble
Pump Does Not Discharge: 1. Pump Not Primed
2. Suction lift too high
3. Clogged suction
4. Incorrect rotation
5. Air leaks in suction line
6. Relief valve improperly adjusted
Page 25
Installation – Operation – Maintenance
FSXB - High Pressure Screw Pumps
Page 26
DRAWING NO. QLM-1425
CUSTOMER Solar Turbines SERVICE CRUDE OIL SHIPPING WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
1 Casing 1 WQ-4320A 0039F0150B023Z Cast Steel A216 Grade WCB (Test Reports)
2 Not Applicable
3 Not Applicable
6 Not Applicable
7 Screw, Long Shaft 1 0010F1963K276Z St. Steel A705 UNS S17400 Cond.
H1150M (Test Reports)
Eutectic 13017 on Scr O.D.
8 Screw, Short Shaft 1 0010F1964K276Z St. Steel A705 UNS S17400 Cond.
H1150M (Test Reports)
Eutectic 13017 on Scr O.D.
12 Not Applicable
DRAWING NO. QLM-1425
CUSTOMER Solar Turbines SERVICE CRUDE OIL SHIPPING WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
13 Not Applicable
18 Not Applicable
21 Not Applicable
25 Not Applicable
26 Shims 1 0745A0061R002A Steel Use as required
CUSTOMER Solar Turbines SERVICE CRUDE OIL SHIPPING WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
29 Not Applicable
30 Assm,Hsg., Brg., Front 1 WQ-4317A 6027D0330B023A Cast Steel A216 Grade WCB (test reports)
(Includes Pc’s 34,34A,35 & 35A)
CUSTOMER Solar Turbines SERVICE CRUDE OIL SHIPPING WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
44 Not Applicable
46 Not Applicable
47 Not Applicable
49 – 59 Not Applicable
CUSTOMER Solar Turbines SERVICE CRUDE OIL SHIPPING WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
64 – 69 Not Applicable
70 Assm, Hsg., Brg., Rear 1 WQ-4317A 6027D0329B023A Cast Steel A216 Grade WCB (test reports)
(Includes Pc’s 34, 34A,
35 & 35A)
72 Not Applicable
74 Not Applicable
75 Not Applicable
CUSTOMER Solar Turbines SERVICE CRUDE OIL SHIPPING WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
91 Not Used
CUSTOMER Solar Turbines SERVICE CRUDE OIL SHIPPING WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
Rev. A. - Pc. 7, Part No. was 0010F1963K276A, Pc. 8 Part No. was 0010F1974K276A, and Pc. 83 was
0132D0041A414A. PCN 11928 08-25-05 DRL
Rev. B. - Pc’s 7 & 8, “ Eutectic 13017” on scr O.D. was “ Stellite 6 “. Pc 13 was Key, Coupling, Qty 1, Service Part No 3245-016016X208F021A
( PCN 12060) 02-24-06 D.T / RD DRL
8 7 6 5 4 3 2 1
REVISIONS MICRO
ZONE LTR DESCRIPTION DATE APPROVED FILMED
A ADDED " SEE NOTE 1" FLAG TO PC's 10, 19 & 71.
SEE NOTE 1 PICTORALLY CHANGED PC 7 CPLG END TO
SHOW TAPER, REMOVED PC 13 (CPLG KEY).
NOTES: TORQUE VALUE FOR PC 40 WAS 1365 FT/LBS.
SEE NOTE 1 SEE NOTE 1 ADDED TORQUE VALUE FOR PC 63. ADDED NOTE 8.
90
( PCN 12058) D.T / RD 02-24-06 DRL FEB 24 2006
1. PC. NO'S 10, 19 & 71 ; THOROUGHLY CLEAN MATING SURFACES, APPLY LOCTITE
19 17 89 71 70 31 1 83 85 9 37 14 10 60 PRIMER T . USE LOCTITE RETAINNG COMPOUND #635 ACCORDING TO
MANUFACTURERS INSTRUCTIONS TO LOCK OUTER BEARING RACES. HEAT SHRINK
D 11
INNER RACES ONTO SHAFT.
2. PC. NO'S 4 & 39: THOROUGHLY CLEAN MATING SURFACES WITH LOCTITE PRIMER T. D
8 APPLY LOCTITE #277 TO THE INTERNAL THREADS AND END OF STUD TO BE INSTALLED
IN CASTING. INSTALL BY HAND TO BOTTOM OF HOLE. ALLOW A MINIMUM OF 30
20 MINUTES CURE TIME AT ROOM TEMPERATURE BEFORE HANDLING.
38
3. USE LOCTITE PST PIPE SEALANT 567 WITH 'N' PRIMER ON ALL PIPE THREADS.
43 4. JOINTS INDICATED TO BE SEALED WITH LOCTITE 515 GASKET ELIMINATOR
OR EQUIVALENT.
SEE NOTE 1 19 5. USE LUBRICANT ON ALL O-RINGS.
7 6. PC. NO'S 34 & 35; LUBRICATE O-RING AND INSTALL ON PLUG, THOROUGHLY
20
CLEAN THREADS AND MATING SURFACES WITH LOCTITE PRIMER T. APPLY
(1) DROP OF LOCTITE #277 TO THREAD OF PLUG AND INSTALL.
14
32 22 86 31 30 40 39
23 80 SEE NOTE 2
COAT SHAFT WITH ANTI-SEIZE
SEE NOTE 8 PRIOR TO INSTALLING BEARING
SHIM FOR .002 - .004" END PLAY SEE NOTE 4
SEE NOTE 4
SEE NOTE 2
15 76
41 95 93 96 82 26 4 82 96 41 81
5 78 76
33 77
B
94
33
95
DRAWING NO.
93
TORQUE TABLE
B 3.812
36 PC.
73 No. FT / LBS LUBRICANT
D-4797
76 79
17 74 FT/LBS MOLYKOTE GN PASTE OR EQUAL
27 45 FT/LBS NONE
32 SNUG ANTI-SIEZE
40 1000 FT/LBS LIGHT OIL
SHEET
1
45 63 500 FT/LBS LIGHT OIL
REV.
A
63 87/89 500 FT/LBS LIGHT OIL
73
62 92 24
73 34 35 84 32 42 A
A Warren Pumps LLC
ASSEMBLE WITH SUCTION FLANGE 34A 35A FILL PIN HOLES WITH BELZONA OR SIMILAR UNLESS OTHERWISE Warren 82 Bridges Ave
SPECIFIED DIMENSIONS
LOCATED PER OUTLINE DRAWING METAL FILLER PRIOR TO PAINTING. ARE IN INCHES.
D R Landry 05-24-05 PO Box 969
(LEFT HAND ASSEMBLY SHOWN ). APPROVED DATE A Member of the COLFAX PUMP GROUP Warren, MA 01083.0969
SEE NOTE 6
DIMENSIONS AND
TOLERANCES IN
CHECKED R PD 5-24-05
TITLE
ASSEMBLY, SECTIONAL
ACCORDANCE WITH
DRAWN D R L 5-20-05
FOR # 4550 FSXB SCREW PUMP
ASME Y14.5M-1994
SIZE CAGE CODE ESWBS DRAWING NO. REV
D 63857 D-4797 A
SCALE: 1/8 MASS (WEIGHT) 12,500 lbs (est.) SHEET 1 OF 1
DRAWING NO. QLM-1427
CUSTOMER Solar Turbines SERVICE Crude Oil Shipping WARREN PUMPS LLC
PUMP TYPE #4550 FSXB Screw Pump FIRST WARREN ORDER NO. IP55836XA
PC. PATT.
NO. NAME OF PIECE QTY. NO. SERVICE PART NO. MATERIAL ASTM SPEC. & REMARKS
201 RTD, 100 Ohm, 3-wire 2 2111MINAS7604PD254Z3 Platinum Minco AS760, 254 mm
202 RTD, 100 Ohm, 3-wire 2 2111MINAS7604PD267Z3 Platinum Minco AS760, 267 mm
207 Nut, Hex 1-1/2 - 6 4 3365-2406N011A Steel SAE J995 Gr. 2 or Equal
Rev. A : Pc’s 200, 201 & 202 Service Part No’s, last two digits were “ Z1 “. Pc 203 Service Part No was 2527BEN107770-03-01
( PCN 12042 ) D.T
Rev. B : Pc 200 was RTD, 100 Ohm, 3-wire, Qty 1, Service Part No 2111MINAS7604PD292Z3.
Pc 201 qty was 1. (PCN 12059) 02-24-06 D.T / RD DRL
REVISIONS
C-3558 12.00 - 900# DISCHARGE LTR DESCRIPTION DATE APPROVED
ARCHIVED
O 15.00 R. F. ANSI FLANGE 203 A ADDED KEYLESS-HYDRAULIC FIT AT SHAFT END,
20x O 1.375 - 6 STUDS 202 SEE NOTE 2 WAS STRAIGHT SHAFT W/ 1" SQ x 7 LG KEY.
ON O 21.000 B.C. REPLACED PC 200 WITH 201, ADDED NOTE 2 &
CALLOUT FOR NOTE 2 TO PC'S 201 & 202.
IN PUMP DATA, B.H.P. WAS 1330.
SEE NOTE 2 201 OIL VENT ADDED " ESTIMATED" TO PUMP DATA TITLE.
ADDED FLANGE LOADING DATA. (PCN 12057) D.T/RD 02-24-06 DRL FEB 24 2006
CENTERLINE PUMP DISCH.
AND MOUNTING FEET
OIL VENT
4.63 OFFSET
+.015
2x O 1.125 -.005 THRU
5
6.00
4.50
5 SCREW, LONG SHAFT
9.00
4
12.00
+.015
O 1.625 -.005 THRU
1.50 3.00
1 2 3
ASSEMBLY DETAIL
3.00 250
1 2
PO Box 969
82 Bridges Avenue
Warren, Massachusetts 01083-0969
Phone: 413-436-7711
Fax: 413-436-5927
www.warrenpumps.com
.
AMERICAN 1390 John Fitch BLVD
South Windsor, CT 06074
DESIGN & MANUFACTURING. INC. Tel. (860) 282-2719
Fax (860) 282-2721
E-Mail: ADMSYS@AOL.COM
Web Page:AMERICANDES-MFG.COM
HEAT EXCHANGER /
LUBRICATION SYSTEM
P/O# 41414
WARREN PUMP LLC.
ADM #3533
. AD&M INC.
DESIGNERS / BUILDERS OF
ENGINEERED SYSTEMS
HYDRAULIC, PNEUMATIC, MECHANICAL, ELECTRICAL
.
AMERICAN
DESIGN & MANUFACTURING. INC.
HEAT EXCHANGER /
LUBRICATION SYSTEM
P/O# 41414
REF: 3533
INDEX
1. DRAWINGS
2. BILL OF MATERIAL
3. COMPONENT LITERATURE
. AD&M INC.
DESIGNERS / BUILDERS OF
ENGINEERED SYSTEMS
HYDRAULIC, PNEUMATIC, MECHANICAL, ELECTRICAL
ROSEMOUNT
ADM PROJECT 3533 LUBRICATION SYSTEM REV C. 7/19/05
WARREN P/N 41414
SYSTEM BILL OF MATERIALS
GEAR PUMP, SIZED TO SUPPLY 7.6 GPM AT 1800 RPM, 3/4" NPT
4 2 VIKING SG-40519-GOO VN CG .75T-CS
CONNECTIONS, VITON MECHANICAL SEAL
PRESSURE RELIEF VALVE, 3/4" NPT, CAST IRON BODY, SS PISTON, 60-
6 1 FULFLO VJ-4R-SS-XS
175 PSI RANGE
316SS AIR COOLER, RATED FOR 45000 BTU/HR HEAT REMOVAL, 105
DEG. F MAX. AMBIENT AIR TEMP., 1 HP 460V/3/60HZ EXPLOSION PROOF
8 1 HAYDEN MOTOR AND VIBRATION SWITCH, CLASS I, DIV. I, GRP. D, 1"-150# R.F. TTA 214A
FLANGED CONNECTIONS, FINS COATED WITH COPON COATING AND
SUITABLE FOR MARINE USE. SHIPPED LOOSE
Page 1
ADM PROJECT 3533 LUBRICATION SYSTEM REV C. 7/19/05
WARREN P/N 41414
SYSTEM BILL OF MATERIALS
19 4 PARKER IN LINE CHECK VALVE, SERIES C, SAE 12 PORTS, CARBON STEEL C1220
Page 2
®
J.I.C. Reservoir
Dimensional Data
AA BB
C
CC
DD
A
10-100 GALLON, 1x3/4 SLOT 4 PLACES
120-UP, 3/4 ROUND HOLE 4 PLACES
HIGH
RESERVOIR WEIGHTS
°C °F
LOW
Model lbs
B WC-10-10 100
WC-15-15 125
WC-20-20 130
WC-30-30 175
WC-40-40 190
WC-50-50 195
6 WC-60-60 235
WC-80-80 400
1-1/4 1-3/8 WC-100 425
D C WC-120 540
WC-150 595
WC-200 940
WC-250 1000
WC-300 1075
MP-1 50
COUPLING GUARD MP-2 100
MP-3 185
Y MOUNTING PLATES
MODEL NO. AA BB CC DD THICKNESS MAX FR HOLES
X Z
MP-1 12.0 7.0 9.50 24.0 3/4 254 3
X, Y and Z dimensions to MP-2 13.0 9.0 11.50 30.0 1 286 3
be supplied by customer MP-3 16.0 11.0 15.0 36.0 1-1/4 365 5
VESCOR Standard Fluid Sight Level Gauges are available in three sizes 3”, Mounting Information
5” and 10”. Gauges are available with or without thermometer in standard • Standard back mount gauges require access to reservoir. (2) 17/32 diameter holes
back mount design or optional front mount design. to match mounting centers are required.
Benefits and Features: • Standard front mount gauges do not require access to reservoir. Gauge can be
• Provides positive check of fluid • Thermometer with readings in installed from the outside on (2) 1/2-20 tapped holes (when wall thickness
level and temperature centigrade and fahrenheit permits) or (2) 1/2-20 hex nuts welded inside reservoir to match mounting centers.
• Rugged aluminum construction • Buna-N O’-ring seals
• Durable pyrex glass tube • 250° F maximum temperature Ordering Information
• 70 PSI max. pressure • Minimum protrusion from reservoir • Order sight level gauge by VESCOR part numbers
Mounting Information:
• Existing reservoir applications: Access to reservoir is required. (2) 21/32 diameter holes to match
mounting centers are required. From inside reservoir install check portion of sight gauge check. From
out side reservoir install sight gauge. Sight Gauge may now be removed and/or changed at any time
without draining reservoir. (Note-reservoir may have to be drained to a level below lowest mounting
hole for initial installation.)
• New reservoir applications: Before filling reservoir drill (2) 21/32 diameter holes to match mounting
centers. From inside install check portion of Sight Gauge Check. From outside reservoir install
sight gauge. Fill reservoir. Sight Gauge may now be removed and/or changed at any time without
draining reservoir.
Vescor
Description
Part Number
5” Front Mount Sight Gauge with
SGC5 Quick Change Sight Gauge Check Ordering Information:
10” Front Mount Sight Gauge with • Order Quick Change Sight Gauge
SGC10 Quick Change Sight Gauge Check Check by VESCOR Part Number
NOTE: WITH VESCORS' POLICY OF CONSTANTLY IMPROVING ITS PRODUCTS, SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. 42
1 JULY 03
Instruction Bulletin No. 72978 (Rev N)
Installation Multi-station level switches install vertically in tank top (mounting up) or in tank bottom (mounting down).
Level switches will operate normally inclined up to 30°.
Mounting Types
Types Type 1 Type 2 Type 3 Type 4
Type
* Note
Note:: Units greater than 72” 1/2” NPT 1-1/4” NPT 2” NPT 3” Dia., 150# Flangeype
overall length are supplied with 6” Bolt
collars with setscrews (made of Circle
1/2” 1/2”
same material as stem and
1/2” NPT NPT
mounting), in place of float-stop NPT
rings. Collars are optional on 3/4”
units less than 72” overall length. Dia.
1” SQ.
à
1-1/4” SQ.
à
Units requiring 316 SS float à à à
7-1/2” Dia. à 1/2”
stops must be special-ordered NPT
with 316 SS collars instead of
grip rings. 1-1/4” 2”
à
NPT NPT 1”
à
Stem and Mounting Material Flange: Carbon Steel or 316 SS
Brass or 316 Stainless Steel
Stem: 316 SS
Max. Length (LO) 36” 60” 140”
Mounting Position Vertical ±30° Inclination
* Float Stops (See *Note Above) Brass Units: Beryllium Copper Grip Rings; Stainless Steel Units: S.S. ARMCO PH-15-7MO Grip Rings
Upward
1-3/4” (44.5mm) LS-800 Series Mounting Types 2, 3,
and 4. A special cinch nut on the
à
LO Union
± 1/6” mounting allows the stem to travel
Unit Length
up or down for fine tuning of the
LO +2” Mounting
actuation points. The extent of ad-
justment depends on the unit length
à
3/4” NPT Ports (2X) Max
and the distance from the mounting
Adjust
à
2” (50.8mm)
to the highest float stop.
à
) ➔
➔
➔
m
➔
0 . 2”
➔
8m
1-3/4” 1-13/16” 2-11/16”
(5
2-3/32”
Float Dimensions (44.5mm) (68.3mm)
➔
(46.0mm) (53.3mm)
➔
➔
➔
➔
➔ 1-1/4” Dia. ➔
➔ 2-1/16” ➔ 2-1/16” Dia.
(31.8mm) ➔ 1-7/8” Dia.
➔
➔
(52.4mm)
(47.6mm) (52.4mm)
Group III Group IV * Level switch units with 50 VA and 100 VA swtiches are
SPDT SPDT not UL recognized or CSA approved.
A
Types 1, 3, 4 and 5 units with stainless steel float P/N 15666:
L4
A = 1-5/8" minimum distance to highest level (2", Type 5 only)
L B = 2-1/2" minimum distance from end of unit to lowest level
L3 O
(Length C = 4" minimum distance between levels
Overall) D = 1/4" minimum distance between actuation levels (Note: One float
for two levels can be used only when low level is N.C. dry and
D high level is N.O. dry.)
L2
Notes:
Return Policy
Returns are accepted on stock items up to 30 days from date of order. You must contact our Returns Department for
a Return Authorization (RA) number. Return the goods - freight prepaid - in the original container and include original
packing slip. C. O. D. returns are not accepted. Gems reserves the right to apply restocking charges.
Tel: 860-793-4357
Fax: 860-793-4563
Important Points:
• Gems products must be maintained and installed in strict accor- • NSF-approved sensors are made of materials approved for potable
dance with the National Electrical Code and the applicable Gems water applications according to Standard 61.
product instruction Bulletin that covers installation, operation and • Stainless steel is generally regarded as safe by NSF and FDA.
proper maintenance. Failure to observe this information may result • Life expectancy of switch contacts varies with application. Contact
in serious injury or damages. Gems if life cycle testing is required.
• For hazardous area applications involving such things as, but not • Ambient temperature changes do affect switch set points, since the
limited to, ignitable mixtures, combustible dust and flammable gravity of a liquid can vary with temperature.
materials, use an appropriate explosionproof enclosure or intrinsi- • Our sensors have been designed to resist shock and vibration.
cally safe interface device. However, shock and vibration should be minimized.
• Please adhere to the pressure and temperature limitations shown • Filter liquid media containing particulate and/or debris to ensure the
throughout this catalog for our level and flow sensors. These proper operation of our products.
limitations must not be exceeded. These pressures and tempera-
• Electrical entries and mounting points in an enclosed tank may
tures take into consideration possible system surge pressures/
require liquid/vapor sealing.
temperatures and their frequencies.
• Our sensors must not be field-repaired.
• Selection of materials for compatibility with the media is critical to
the life and operation of Gems products. Take care in the proper • Physical damage sustained by product may render it unserviceable.
selection of materials of construction, testing is required.
WARNING
THE FOLLOWING SAFETY PRECAUTIONS MUST BE OBSERVED:
1. Electric rotating machinery and high voltage can cause serious or fatal injury if improperly
installed, operated or maintained. Responsible personnel should be familiarized with
NEMA MG2; Safety Standards for Construction and Guide Selection. Installation and Use
of Electric Motors and Generators; National Electric Code and all local safety requirements.
2. When servicing, all power sources to the motor and to the accessory devices should be de-
energized and disconnected and all rotating parts should be at standstill.
3. Lifting means, when supplied, are intended for lifting the motor only. When two lifting
devices are supplied with the motor a dual chain must be used.
4. Suitable protection must be used when working near machinery with high noise levels.
5. Safeguard or protective devices must not be by-passed or rendered inoperative.
6. The frame of this machine must be grounded in accordance with the National Electric Code
and applicable local codes.
7. A suitable enclosure should be provided to prevent access to the motor by other than
authorized personnel. Extra caution should be observed around motors that are
automatically or have automatic re-setting relays as they may restart unexpectedly.
8. Shaft key must be fully captive or removed before motor is started.
9. Provide proper safeguards for personnel against possible failure of motor-mounted brake,
particularly on applications involving overhauling loads.
10. Explosion proof motors are constructed to comply with the label service procedure manual,
repair of these motors must be made by TECO-Westinghouse Motor Company or U/L listed
service center in order to maintain U/L listing.
LOCATION
1. Drip-proof motors are intended for use where atmosphere is relatively clean, dry, well
ventilated and non-corrosive.
2. Totally enclosed motors may be installed where dirt, moisture, or dust are present and in
outdoor locations.
3. Explosion-proof motors are built for use in hazardous locations as indicated by
Underwriters’ label on the motor.
4. Chemical duty enclosed motors are designed for installation in high corrosion or excessive
moisture locations.
Note: in all cases, no surrounding structure should obstruct normal flow or
ventilating air through or over the motor.
MOUNTING
1. Mount motor securely on a firm, flat base. All ball bearing normal thrust motors up to and
including 256T frame size may be side-wall or ceiling mounted; all others check nearest
TECO-Westinghouse office for mounting recommendations.
2. Align motor accurately, using a flexible coupling if possible. For drive recommendations,
consult with drive or equipment manufacturer, or TECO-Westinghouse.
3. Mounting bolts must be carefully tightened to prevent changes in alignment and possible
damage to the equipment. The recommended tightening torque’s for medium carbon steel
bolts, identified by three radial lines at 120 degrees on the head, are:
4. V-belts Sheave Pitch Diameters should not be less than those shown in Table 1 (NEMA
recommended values)
5. Tighten belts only enough to prevent slippage. Belt speed should not exceed 5000 ft. per
min.
*Important: For Part Winding Start, M2 contactor should be closed within two (2) seconds
after M1 contactor is closed.
Only 4 pole and above (e.g., 6P, 8P…) motors are satisfactory for Part Winding
Start at low voltage.
START UP
1. Disconnect load and start motor. Check direction of rotation. If rotation must be changed,
ALLOW THE MOTOR TO STOP COMPLETLEY. Interchange any two leads of a three-
phase motor.
2. Connect load. The motor should start quickly and run smoothly. If no, shut power off at
once. Recheck the assembly including all connections before restarting.
3. If excessive vibration is noted, check for loose mounting bolts too flexible motor support
structure or transmitted vibration from adjacent machinery. Periodic vibration checks
should be made; foundations often settle.
4. Operate under load for short period of time and check operating current against nameplate.
TESTING
If the motor has been in storage for an extensive period or has been subjected to adverse
moisture conditions, it is best to check the insulation resistance of the stator winding with a
megometer. Depending on the length and conditions of storage it may be necessary to
regrease or change rusted bearings.
If the resistance is lower than one megohm the windings should be dried in one of the following
two ways:
1. Bake in oven at temperatures not exceeding 194°F until insulation resistance becomes
constant.
2. With rotor locked, apply low voltage and gradually increase the current through windings
until temperature measured with a thermometer reaches 194°F. Do not exceed this
temperature.
MAINTENANCE
INSPECTION
Inspect motor at regular intervals. Keep motor clean and ventilation openings clear.
LUBRICATION
1. Frame 143T-256T: Double shielded and pre-lubricated ball-bearing motors without grease
fittings and don’t need relubrication, except on MAX-E1® and MAX-E2® products which
have regreasable features.
2. Frames 280TS, 320-449TZ(TS): Motors having grease fittings and grease discharge
devices at brackets. Motors are shipped with grease for initial running. It is necessary to
relubricate anti-friction bearing motors periodically, depending on size and type of service.
See Table 2 to provide maximum bearing life. Excessive or too frequent lubrication may
damage the motor.
TABLE 2
Note:
A. Standard conditions: 8 hours operation per day, normal or light loading, clear and 40°C
ambient conditions.
B. Severe conditions: 24-hour operation per day or light shock loading, vibration or in dirty
or dusty conditions.
C. Extreme conditions: With heavy shock loading or vibration or dusty conditions.
D. For double shielded bearings, above data (lubrication frequency) means that the
bearing must be replaced.
3. Be sure fittings are clean and free from dirt. Using a low-pressure grease gun, pump in the
recommended grease until new grease appears at grease discharge hole.
4. Use Exxon Polyrex EM (polyurea based) or equivalent grease for regreaseable open
bearings, and Shell ALVANIA R3 (lithium based) or equivalent grease for motors with
double shielded (ZZ) bearings, unless special grease is specified on the nameplate.
5. If relubrication is to be performed with the motor running, stay clear of rotating parts. After
regreasing, allow the motor to run for ten to thirty minutes.
RENEWAL PARTS
1. Use only genuine TECO-Westinghouse renewal parts or as recommended by TECO-
Westinghouse Motor Company.
2. When you order renewal parts please specify complete information to TECO-Westinghouse
office/agent such as type, frame no., poles, horsepower, voltage, series no., quantity, etc.
V-SERIES
VALVES
Standard Standard Stainless Steel Handwheel Handwheel
with Screw with Flange with Screw with Screw with Flange
Connections Connections Connections Connections Connections
11
V-SERIES
SETTING VALVES having a flow meter in the pump discharge line must
be available. With a valve adjusted for cracking
Valves may be set with a hydraulic hand pump for pressure as above, continue closing bypass until the
cracking pressure. If a test stand is available, valve required flow registers on the flow meter and observe
should be connected to the discharge header with the pressure. Readjust pressure, if necessary, to obtain
pump bypass open, and the bypass gradually closed desired pressure at desired flow.
until the desired pressure registers on the gauge.
Adjust valve adjusting screw until valve slightly bleeds
at the set bypass pressure and lock adjusting screw. MAINTENANCE
Fulflo valves are not designed to be positive shut-off, Fulflo valves provide reliable “chatter-free” operation
and will pass a minimal amount of leakage before the when the system is free of abrasives and foreign
V-SERIES
VALVES
set pressure. If a valve is required to bypass a given matter. Continuous filtration of the liquid used is
amount of fluid at a given pressure, a test stand strongly recommended.
C Inspect valve bore and piston for wear and scoring. Replace
broken or damaged parts. Clean all parts thoroughly and
re-assemble by reversing the above procedure.
D
Inspect valve bore and piston for wear or scoring. Replace broken
C or damaged parts. Clean all parts thoroughly and re-assemble by
reversing the above procedure.
I
12
V-SERIES
ASSEMBLY NUMBER IDENTIFICATION CHART
Symbol No. Designation Code Description
1 Style None Standard Model
H Handwheel Model
2 Series V
3 Material J Cast iron
B Brass
S Steel
SS 316 Stainless Steel
4 Connections None Screw Connections
F Flange Connections 300# Flange Class Standard (250# Flange Class - Cast Iron Standard)
V-SERIES
VALVES
5 Size -1 1/4”
-2 3/8”
-3 1/2”
-4 3/4”
-5 1”
-6 11/4”
-7 11/2”
-8 2”
6,7,8 ASA None 300# Flange Standard (no designation required)
Flange -150
Rating -600
9 Flange A Raised Face, Staggered Bolt Centers (standard on all Flange rating)
Style B Smooth Face, Staggered Bolt Centers
150# & 600# C Raised Face, Bolts on Valve Centerline
Only D Smooth Face, Bolts on Valve Centerlne
10 O-Ring R Buna O-Ring Cap Seal (standard)
Material RV Viton O-Ring Cap Seal
RS Silicone O-Ring Cap Seal
RT Teflon O-Ring Cap Seal (standard on VSS Series)
RA Aflas O-Ring Cap Seal
11 Options SP Steel Parts (used on cast iron only)
P Panel Mount on Handwheel Series
12 Piston /HS Hardened Steel
Material /SS 416 Stainless Steel
/3SS 303 Stainless Steel
13 Spring AS
US
WS
XS
YS
ZS
14 Setting Desired Pressure Setting
EXAMPLES:
VJ-1RVSP/HS/WS VJF-5R/HS/WS VJF-5-150AR/HS/WS
V J -1 RV SP /HS WS V J F -5 R /HS WS V J F -5 -150 A R /HS WS
Series Cast Iron 1/4” Viton O-Ring Steel Parts H.S. Piston WS Spring Series Cast Iron Flanged 1” Buna O-Ring H.S. Piston WS Spring Series Cast Iron Flanged 1” Rating Style Buna O-Ring H.S. Piston WS Spring
NOTE: Stainless steel pistons are supplied on brass valves, unless hardened steel is specified. Hardened steel pistons are supplied on cast iron or steel unless stainless steel is
specified. Buna O-Rings are supplied as standard unless other material is specified.
13
VJ VB Brass
V-SERIES VS
Cast Iron
Steel VSS Stainless Steel VJ-SP Cast Iron with Steel Parts
DIMENSIONS Valve
Size
DIMENSIONS IN INCHES
AA BB CC DD
1/4” 5 / 11
32 1 /
11
32 1 /
11
32 13/8
C 1/2” 6 /163
1 /16
11
1 /16
7
17/16
F 3/4” 615/16 115/16 113/16 111/16
1” 87/32 29/32 29/32 21/16
K E
D 11/4” 99/16 29/16 29/16 21/2
FULFLO
V-SERIES
AA REF.
G 1 /2” 1
11 /16 1
2 /16
11
2 /16
11
27/8
VALVES
CAP A 2” 13 3 3 31/4
(GASKET SEAL) I
PIPE SIZE
OUT
DD
REF
BB
H IN
CC
PIPE SIZE
DD
REF
PARTS LIST
SYM. NAME MODEL VALVE SIZE
1/4” 3/8” 1/2” 3/4” 1” 11/4” 11/2” 2”
VJ, VJ-SP 100 200 300 400 500 600 700 800
VB 100-B 200-B 300-B 400-B 500-B 600-B 700-B 800-B
A BODY VS 100-S 200-S 300-S 400-S 500-S 600-S 700-S 800-S
VSS 100-SS 200-SS 300-SS 400-SS 500-SS 600-SS 700-SS 800-SS
VJ, VJ-SP 201-SR 201-SR 301-SR 401-R 501-R 601-R 701-R 801-R
CAP VB 201-BR 201-BR 301-BR 401-BR 501-BR 601-BR 701-BR 801-BR
B (O-RING SEAL) VS 201-SR 201-SR 301-SR 401-SR 501-SR 601-SR 701-SR 801-SR
VSS 201-SSR 201-SSR 301-SSR 401-SSR 501-SSR 601-SSR 701-SSR 801-SSR
VJ, VB 202-B 202-B 302-B 402-B 502-B 602-B 702-B 802-B
C ADJUSTING VS, VJ-SP 202-S 202-S 302-S 402-S 502-S 602-S 702-S 802-S
SCREW VSS 202-SS 202-SS 302-SS 402-SS 502-SS 602-SS 702-SS 802-SS
VJ, VB 203-B 203-B 303-B 403-B 503-B 603-B 703-B 803-B
D RETAINER VS, VJ-SP 203-S 203-S 303-S 403-S 503-S 603-S 703-S 803-S
VSS 203-SS 203-SS 303-SS 403-SS 503-SS 603-SS 703-SS 803-SS
VJ, VJ-SP, VB, VS 204-* 204-* 304-* 404-* 504-* 604-* 704-* 804-*
E O-RING ✝ VSS 204-RT 204-RT 304-RT 404-RT 504-RT 604-RT 704-RT 804-RT
VJ, VJ-SP, VB, VS 205-S 205-S 305-S 405-S 505-S 605-S 705-S 805-S
F LOCK NUT VSS 205-SS 205-SS 305-SS 405-SS 505-SS 605-SS 705-SS 805-SS
G SPRING ✝ ALL MODELS 207-** 207-** 307-** 407-** 507-** 607-** 707-** 807-**
VJ, VB 208-B 208-B 308-B 408-B 508-B 608-B 708-B 808-B
H STOP RING VS, VJ-SP 208-S 208-S 308-S 408-S 508-S 608-S 708-S 808-S
VSS 208-SS 208-SS 308-SS 408-SS 508-SS 608-SS 708-SS 808-SS
HARDENED STEEL 206 206 306 406 506 606 706 806
I PISTON ✝ 416 STAINLESS STEEL 206-A 206-A 306-A 406-A 506-A 606-A 706-A 806-A
303 STAINLESS STEEL 206-SS 206-SS 306-SS 406-SS 506-SS 606-SS 706-SS 806-SS
CAP VJ, VJ-SP 201-S 201-S 301-S 401 501 601 701 801
J VB 201-B 201-B 301-B 401-B 501-B 601-B 701-B 801-B
(GASKET SEAL)
VS 201-S 201-S 301-S 401-S 501-S 601-S 701-S 801-S
VJ, VB 204 204 304 404 504 604 704 804
K GASKET ✝ 204-S 204-S 304-S 404-S 504-S 604-S 704-S 804-S
VS, VJ-SP
14
VJF Cast Iron VSF Steel
V-SERIES VBF Brass VSSF Stainless Steel VJF-SP Cast Iron with Steel Parts
Valve
Size AA BB
J B
C 1” 91/2” 31/2”
F
11/4” 1013/16” 33/4”
K E
11/2” 127/16” 41/16”
D
2” 149/16” 49/16”
V-SERIES
G
VALVES
Note: Dimensions reflect
CAP 150# and 300# only
A
AA REF.
(GASKET SEAL) 45˚
I
45˚
221/2˚
PIPE SIZE
45˚
H
221/2˚
BB
-------
-------
-------
-------
FOR 2” VALVE ONLY
PIPE SIZE
BB
PARTS LIST
SYM. NAME MODEL VALVE SIZE
1” 11/4” 11/2” 2”
VJF, VJF-SP 500-F 600-F 700-F 800-F
VBF 500-BF 600-BF 700-BF 800-BF
A BODY VSF 500-SF 600-SF 700-SF 800-SF
VSSF 500-SSF 600-SSF 700-SSF 800-SSF
VJF, VJF-SP 501-R 601-R 701-R 801-R
CAP VBF 501-BR 601-BR 701-BR 801-BR
B (O-RING SEAL) VSF 501-SR 601-SR 701-SR 801-SR
VSSF 501-SSR 601-SSR 701-SSR 801-SSR
VJF, VBF 502-B 602-B 702-B 802-B
C ADJUSTING VSF, VJF-SP 502-S 602-S 702-S 802-S
SCREW VSSF 502-SS 602-SS 702-SS 802-SS
VJF, VBF 503-B 603-B 703-B 803-B
D RETAINER VSF, VJF-SP 503-S 603-S 703-S 803-S
VSSF 503-SS 603-SS 703-SS 803-SS
VJF, VJF-SP 504* 604* 704* 804*
E O-RING ✝ VBF, VSF 504-* 604-* 704-* 804-*
VSSF 504-RT 604-RT 704-RT 804-RT
VJF, VJF-SP 505-S 605-S 705-S 805-S
F LOCK NUT VBF, VSF 505-S 605-S 705-S 805-S
VSSF 505-SS 605-SS 705-SS 805-SS
G SPRING ✝ ALL MODELS 507-** 607-** 707-** 807-**
VJF, VBF 508-B 608-B 708-B 808-B
H STOP RING VJF-SP, VSF 508-S 608-S 708-S 808-S
VSSF 508-SS 608-SS 708-SS 808-SS
HARDENED STEEL 506 606 706 806
I PISTON ✝ 416 STAINLESS STEEL 506-A 606-A 706-A 806-A
303 STAINLESS STEEL 506-SS 606-SS 706-SS 806-SS
VJF, VJF-SP 501 601 701 801
J CAP VBF 501-B 601-B 701-B 801-B
(GASKET SEAL)
VSF 501-S 601-S 701-S 801-S
VJF, VBF 504 604 704 804
K GASKET ✝ VJF-SP, VSF 504-S 604-S 704-S 804-S
* See o-ring selection chart
** See spring pressure chart
✝ Recommended spare parts
15
HVJ Cast Iron HVS Steel HVJ-P Cast Iron HVS-P Steel
V-SERIES HVB BRASS HVSS Stainless Steel HVB-P Brass HVSS-P Stainless Steel
DIMENSIONS Valve
Size
DIMENSIONS IN INCHES
A AA BB CC DD EE
1/4” 8/
1
8 1 /
11
32 1/3
16 1/3
8 7/8
B
C 3/8” 81/8 111/32 13/16 13/8 7/8
D
E 1/2” 9 /8
5
1 /16
11
1 /16
7
1 /16
7
11/8
AA MAXIMUM REF.
G 1” 127/16 29/32 21/16 29/32 13/8
EE 11/4” 137/16 29/16 21/2 29/16 15/8
THD. DIA. H
V-SERIES
1 /2”
1
17 /16
1
2 /16
11
2 /8
7
2 /16
11
21/4
VALVES
M I
FULFLO
J 2” 171/16 3 33/8 3 21/4
K
F
PIPE SIZE
REF
OUT
CC
BB
L
PANEL MOUNT IN
PIPE SIZE DD
CC
REF.
PARTS LIST
SYM. NAME MODEL VALVE SIZE
1/4” 3/8” 1/2” 3/4” 1” 11/4” 11/2” 2”
A LOCK NUT OR 1/4”-20 1/4”-20 1/4”-20 205-S 205-S 1/4”-20 1/4”-20 1/4”-20
SET SCREW ALL MODELS
COMM. COMM. COMM. COMM. COMM. COMM.
B HANDWHEEL ALL MODELS 229 229 229 429 429 629 629 629
ADJUSTING HVJ(P), HVS(P) 222-S 222-S 322-S 422-S 522-S 622-S 722-S 822-S
C HVB(P) 222-B 222-B 322-B 422-B 522-B 622-B 722-B 822-B
SCREW HVSS(P) 222-SS 222-SS 322-SS 422-SS 522-SS 622-SS 722-SS 822-SS
HVJ(P), HVS(P) 205-S 205-S 205-S 305-S 305-S 655-S 655-S 655-S
D LOCK NUT HVB(P) 205-S 205-S 205-S 305-S 305-S 655-S 655-S 655-S
HVSS(P) only 205-SS 205-SS 205-SS 305-SS 305-SS 655-SS 655-SS 655-SS
HVJ(P), HVS(P) 225-S 225-S 325-S 525-S 525-S 625-S 725-S 825-S
E GLAND HVB(P) 225-B 225-B 325-B 525-B 525-B 625-B 725-B 825-B
HVSS(P) 225-SS 225-SS 325-SS 525-SS 525-SS 625-SS 725-SS 825-SS
HVJ, HVS 223-SR 223-SR 323-SR 423-SR 523-SR 623-SR 723-SR 823-SR
HVB 223-BR 223-BR 323-BR 423-BR 523-BR 623-BR 723-BR 823-BR
HVSS 223-SSR 223-SSR 323-SSR 423-SSR 523-SSR 623-SSR 723-SSR 823-SSR
F BONNET 228-SR 228-SR 328-SR 428-SR 528-SR 628-SR 728-SR 828-SR
HVJP, HVSP
HVBP 228-BR 228-BR 328-BR 428-BR 528-BR 628-BR 728-BR 828-BR
HVSSP 228-SSR 228-SSR 328-SSR 428-SSR 528-SSR 628-SSR 728-SSR 828-SSR
HVJ(P), HVS(P) 224* 224* 224* 424* 424* 624* 624* 624*
G O-RING ✝ HVB(P) 224-* 224-* 224-* 424-* 424-* 624-* 624-* 624-*
HVSS(P) only 224-RT 224-RT 224-RT 424-RT 424-RT 624-RT 624-RT 624-RT
HVJ(P), HVS(P) 204* 204* 304* 404* 504* 604* 704* 804*
H O-RING ✝ HVB(P) 204-* 204-* 304-* 404-* 504-* 604-* 704-* 804-*
HVSS(P) only 204-RT 204-RT 304-RT 404-RT 504-RT 604-RT 704-RT 804-RT
HVJ(P) 100 200 300 400 500 600 700 800
HVB(P) 100-B 200-B 300-B 400-B 500-B 600-B 700-B 800-B
I BODY HVS(P) 100-S 200-S 300-S 400-S 500-S 600-S 700-S 800-S
HVSS(P) 100-SS 200-SS 300-SS 400-SS 500-SS 600-SS 700-SS 800-SS
J SPRING ✝ ALL MODELS 207-** 207-** 307-** 407-** 507-** 607-** 707-** 807-**
HARDENED STEEL 206 206 306 406 506 606 706 806
K PISTON ✝ 416 STAINLESS STEEL 206-A 206-A 306-A 406-A 506-A 606-A 706-A 806-A
303 STAINLESS STEEL 206-SS 206-SS 306-SS 406-SS 506-SS 606-SS 706-SS 806-SS
HVJ(P), HVS(P) 208-S 208-S 308-S 408-S 508-S 608-S 708-S 808-S
L STOP RING HVB(P) 208-B 208-B 308-B 408-B 508-B 608-B 708-B 808-B
HVSS(P) 208-SS 208-SS 308-SS 408-SS 508-SS 608-SS 708-SS 808-SS
HVJP, HVSP, 505-S 505-S 605-S 705-S 705-S 805-S 745-S 745-S
M LOCK NUTS 505-S 505-S 605-S 705-S 705-S 805-S 745-S 745-S
HVBP
2 REQ’D HVSSP 505-SS 505-SS 605-SS 705-SS 705-SS 805-SS 745-SS 745-SS
* See o-ring selection chart
** See spring pressure chart
✝ Recommended spare parts
16
V-SERIES HVJF
HVBF
Cast Iron
Brass
HVSF Steel HVJF-P Cast Iron HVSF-P Steel
HVSSF Stainless Steel HVBF-P Brass HVSSF-P Stainless Steel
B Valve
Size AA BB EE
C
D 13 /16 31/2 13/8
11
1”
E
11/4” 1411/16 33/4 15/8
F
G 11/2” 187/16 41/16 21/4
AA MAXIMUM REF.
2” 185/8 49/16 21/4
H
EE Note: Dimensions reflect
THD. DIA. 150# and 300# only
I
V-SERIES
M
VALVES
J 221/2˚
K 45˚
45˚
45˚
PIPE SIZE
F
221/2˚
L
BB
PANEL MOUNT
PIPE SIZE
-------
-------
-------
-------
BB FOR 2” VALVE ONLY
PARTS LIST
SYM. NAME MODEL DIMENSIONS IN INCHES
1” 11/4” 11/2” 2”
A LOCK NUT OR ALL MODELS 1/4”-20 1/4”-20 1/4”-20
SET SCREW 205-S COMM. COMM. COMM.
B HANDWHEEL ALL MODELS 429 629 629 629
HVJF(P) HVSF(P) 522-S 622-S 722-S 822-S
ADJUSTING HVBF(P) 522-B 622-B 722-B 822-B
C
SCREW HVSSF(P) 522-SS 622-SS 722-SS 822-SS
HVJF(P), HVSF(P) 305-S 655-S 655-S 655-S
D LOCK NUT HVBF(P) 305-S 655-S 655-S 655-S
HVSSF(P) only 305-SS 655-SS 655-SS 655-SS
HVJF(P), HVSF(P) 525-S 625-S 725-S 825-S
E GLAND HVBF(P) 525-B 625-B 725-B 825-B
HVSSF(P) 525-SS 625-SS 725-SS 825-SS
HVJF, HVSF 523-SR 623-SR 723-SR 823-SR
HVBF 523-BR 623-BR 723-BR 823-BR
HVSSF 523-SSR 623-SSR 723-SSR 823-SSR
F BONNET HVJPF, HVSPF 528-SR 628-SR 728-SR 828-SR
HVBPF 528-BR 628-BR 728-BR 828-BR
HVSSFP 528-SSR 628-SSR 728-SSR 828-SSR
HVJF(P), HVSF(P) 424* 624* 624* 624*
G O-RING ✝ HVBF(P) 424-* 624-* 624-* 624-*
HVSSF(P) only 424-RT 624-RT 624-RT 624-RT
HVJF(P), HVSF(P) 504* 604* 704* 804*
H O-RING ✝ HVBF(P) 504-* 604-* 704-* 804-*
HVSSF(P) only 504-RT 604-RT 704-RT 804-RT
HVJF(P) 500-F 600-F 700-F 800-F
HVBF(P) 500-BF 600-BF 700-BF 800-BF
I BODY HVSF(P) 500-SF 600-SF 700-SF 800-SF
HVSSF(P) 500-SSF 600-SSF 700-SSF 800-SSF
J SPRING ✝ ALL MODELS 507-** 607-** 707-** 807-**
HARDENED STEEL 506 606 706 806
K PISTON ✝ 416 STAINLESS STEEL 506-A 606-A 706-A 806-A
303 STAINLESS STEEL 506-SS 606-SS 706-SS 806-SS
HVJF(P), HVSF(P) 508-S 608-S 708-S 808-S
L STOP RING HVBF(P) 508-B 608-B 708-B 808-B
HVSSF(P) 508-SS 608-SS 708-SS 808-SS
LOCK NUTS HVJFP, HVSFP, 705-S 805-S 745-S 745-S
M HVBFP 705-S 805-S 745-S 745-S
2 REQ’D HVSSFP 705-SS 805-SS 745-SS 745-SS
* See o-ring selection chart
** See spring pressure chart
✝ Recommended spare parts
17
V-SERIES PERFORMANCE CHARTS
All valve tests 110˚F. to 120˚F. Oil Viscosity 150 S.S.U. at 100˚F.
(Charts good from 30 to 500 S.S.U.)
1/4” VALVE TESTS 3/8” VALVE TESTS
V-SERIES
6
VALVES
5 XS
4 Rated Capacity WS 10 XS
3 G.P.M.
3 Rated Capacity
5 G.P.M.
WS
2 US 5
GALLONS PER MINUTE
RS
10 10 US
XS YS
AS
RS
5 WS XS
5
4 US TS 4
PRESSURE RANGE IN P.S.I.
3 AS ZS 3 407-AS = 3-15
407-US = 7-35
407-WS = 30-100
2 YS 2 407-XS = 60-175
407-YS = 150-350
407-ZS = 300-500
1 1
1 2 4 6 8 10 20 40 60 80 100 150 1 2 4 6 8 10 20 40 60 80 100 150
OVERPRESSURE IN P.S.I. OVERPRESSURE IN P.S.I.
18
V-SERIES PERFORMANCE CHARTS
All valve tests 110˚F. to 120˚F. Oil Viscosity 150 S.S.U. at 100˚F.
(Charts good from 30 to 500 S.S.U.)
V-SERIES
507-YS = 150-350 607-YS = 150-350
VALVES
507-ZS = 300-500 120 607-ZS = 300-500
60 507-R = 500-900 607-R = 500-800
50 100
40 80
Rated Capacity Rated Capacity
30 25 G.P.M.
60 50 G.P.M.
20 ZS
GALLONS PER MINUTE
R
WS ZS
40 AS
50
32 US YS ZS 40
WS XS
24 AS 30 US
16 XS 20 YS
8 10
1 2 4 6 8 10 20 40 60 80 100 150 1 2 4 6 8 10 20 40 60 80 100 150
OVERPRESSURE IN P.S.I. OVERPRESSURE IN P.S.I.
19
12AT/50AT Series
Spin-On Filters
1
Spin-On Filters
12AT/50AT Series
Applications for
Spin-On Filters
Mounting Ports
n 6 hole pattern n Both NPT and
n Mobile Equipment
for flexibility SAE straight
n Hydrostatic Drives thread available
TYPICAL
RETURN
LOCATIONS
RETURN
SUCTION
BREATHER
OFFLINE
20B 25C
.70 12AT ASSEMBLY 03C 10C 25C
.70 50AT-1 ASSEMBLY 03C 10B 10C
10 10
(BAR)
8 8
.50 .50
PRESSURE DROP
PRESSURE DROP
.40 6 .40 6
.30 .30
4 4
.20 .20
(PSI)
(PSI)
2 2
.10 .10
0 0
.0 0 2 4 6 8 10 12 14 16 18 .0 0 5 10 15 20 25 30 35 40 45 50
(BAR)
8 8
.50 .50
PRESSURE DROP
PRESSURE DROP
.40 6 .40 6
.30 .30
4 4
.20 .20
(PSI)
(PSI)
2 2
.10 .10
0 0
.0 0 2 4 6 8 10 12 14 16 18 .0 0 5 10 15 20 25 30 35 40 45 50
LI LO
67.82
MAX
2.67
95.00
3.74
38.10
1.50
RI RO
INLET OUTLET
12.19
.48
172.97MAX
6.81
148.84
5.68
15.7 MINIMUM
.62 REMOVAL
CLEARANCE
10 .4
12AT
DIFFERENTIAL PRESSURE (IN H20)
8
DIFFERENTIAL PRESSURE (PSI)
.3
7
6
12AT
5
.2
4
50AT
3
50AT
.1
2
0
0 10 20 30 40 50 60 70 80 90 100 0 100 200 300 400 500 600
A. Shut down the main system and 25C 925023 926170 N/A
release pressure in the filter line. 10C 921999 926169 927736
B. Unthread the canister and discard 03C 926543 926541 N/A
it along with the accompanying 20B 928764 928767 929446
seal. A strap wrench may be
10B 928763 928766 929445
required.
C. Apply a small amount of lubricant 03B N/A 934200 932073
to the new canister seal.
D. Install the new canister and hand
tighten.
15 15
10
20
10
1.0
20
1.0
12-30 PSI
COLOR BAND (RED) 20-30 PSI
1.5 0.5 1.5 COLOR BAND (RED)
0.5
25
25
5
5
2.0 2.0
bar bar
psi psi
30
30
How To Order
Select the desired symbol (in the correct position) to construct a model code.
Example:
50AT 2 10C N 25 DD N
Sensors-3144_05A
spring-loaded sensor. However, the bayonet connector permits the Glass Layers
sensor to be easily removed from the process without tools. Photolithography
Structured Platinum
FIGURE 6. Series 68, 68Q, 78, and 58C Thin Film
Lead Wire Configurations Al2 O3 Substrate
White
White sensor allows for direct immersion in non-corrosive fluids at
Black reasonable static pressures. For corrosive environments or many
industrial applications, these sensors are widely used with
White
Green standard thermowell assemblies.
White Green
-10
Product Data Sheet
00813-0100-2654, Rev EA
August 2004 Volume 1
Specifications Environmental
Humidity Limits
Performance • Lead seal can withstanding 100% relative humidity.
Vibration Limits
Temperature Range
• ±0.05% maximum ice-point resistance shift due to 30 minutes
–50 to 400 °C (–58 to 752 °F) of 14 g peak vibration from 5 to 350 Hz at 20 °C (68 °F) for
unsupported stem length of less than 6 inches.
Effect of Temperature Cycling
Quality Assurance
±0.05% (0.13 °C or 0.23 °F) maximum ice-point resistance shift
• Each sensor is subjected to a resistance accuracy test at 0 °C
following 10 cycles over the specified temperature range.
and a insulation resistance test.
Stability Enclosure Ratings
±0.11% maximum ice-point resistance shift following 1,000 hours • When installed properly, Rosemount Series 68 sensors are
at maximum specified temperature (400 °C). suitable for indoor and outdoor NEMA 4X and CSA Enclosure
Type 4X installations. See “Hazardous Area Approvals” for
Maximum Hysteresis complete installation information.
±0.1% of operating temperature range.
Insulation Resistance
Time Constant 500 106 ohms minimum insulation resistance when measured at
12 seconds maximum required to reach 63.2% sensor response in 500 Vdc at room temperature.
water flowing at 3 ft/s (0.91 m/s).
Self Heating
16 mW minimum power dissipation required to cause a 1 °C (1.8
°F) temperature measurement error in water flowing at 3 ft/s.
Physical Specifications
Sheath Material
316 SST.
Lead Wire
Teflon® insulated, nickel-coated, 22-gauge stranded copper wire.
Identification Data
The model, serial numbers, and up to six lines of permanent
tagging information are etched on each sensor. Stainless steel
tags are available upon request.
Weight
• Capsule sensors: 5 oz
• General-purpose and spring-loaded sensors: 9 oz
-11
Product Data Sheet
00813-0100-2654, Rev EA
Volume 1 August 2004
ORDERING INFORMATION
TABLE 4. Series 68 RTD Sensor Assemblies WITHOUT Thermowell
-12
Product Data Sheet
00813-0100-2654, Rev EA
August 2004 Volume 1
Code Options
Product Certifications
E5 FM Explosion-proof approval (See Figure 26)
E6 CSA Explosion-proof approval (See Figure 27)
E7(9) SAA Flameproof approval (See Figure 30)
E1(10) ATEX Flameproof approval (See Figure 29)
Calibration
V1-V7 Choose from “option code “V”–Callendar-van Dusen Constants.” See “Option Code “V” Callendar-van Dusen Constants”.
Option code V4 is not available with Series 68 sensors.
X8Q4 Calibrate to customer-specified temperature range (See “Option X8Q4: Sensor Calibrated to a Customer-Specified Temperature Range”)
X9Q4 Calibrate to customer-specified single temperature point (See “Option X9Q4: Sensor Calibrated to a Customer-Specified Single Point”)
Mounting Adapters, Lead Wire Extensions, Connectors, and Seals
M5-M7 Mounting adapters
A1-A8 Twisted lead wire extensions
B1-B8(11) Shielded cable lead wire extensions
C1-C8(11) Armored cable lead wire extensions
D1-D8(11) Armored cable lead wire extensions with electrical plugs
L1-L8 Armored cable mating plugs with lead wire extensions
F1 4-pin bayonet connector
H1-H8 4-pin connector mating plugs with lead wire extensions
J1 Moisture-proof seal assembly for armored cables
XA(12) Assemble connection head or transmitter to a sensor assembly (Teflon (PTFE) paste where appropriate, fully wired.)
(1) FM, CSA, SAA, and ATEX approvals are not available with the polypropylene connection head.
(2) Capsule style available in 1-in. increments only, starting at 1-in. (i.e. 1, 2, 3-inches, etc.) See “Mounting Adapters for Series 58, 68, 78, and 183” on page 51.
(3) This option must be used with Sensor Lead Wire Termination code N and is not available with assembly code XA or with Approval codes E1, E5, E6, and E7.
(4) General-purpose sensors are only available in (L) lengths of 2.5-in. or greater.
(5) Spring loaded sensors must be installed in a thermowell assembly to meet the requirements of explosion-proof approvals code E6.
(6) Not available with Sensor Lead Wire Termination codes R, P, or W or with approval codes E1, E5, E6, or E7.
(7) 1-in. length without extension is only available in capsule style.
(8) Standard configuration with best delivery.
(9) SAA Flame-proof Approval is only applicable if installed with Rosemount 244E, 248, 644, 3144P, or 3244MV transmitters.
(10) ATEX Flame-proof approval is only applicable if ordered with Sensor Lead Wire Terminator code D (Rosemount connection head) or installed with
Rosemount 144, 244E, 248, 644, 3144P, or 3244MV transmitters.
(11) These options are not available with Sensor Lead Wire Termination codes R, P, or W.
(12) If ordering code XA with a transmitter, specify the same option on the transmitter model code.
Ordering Example
Typical Lead Wire Extension Extension Thermowell Immersion Additional
Model Model Termination Sensor Type Type Length Material Length Options
Number
0068 N 11 N 00 N 045 E5
-13
Product Data Sheet
00813-0100-2654, Rev EA
Volume 1 August 2004
-14
Product Data Sheet
00813-0100-2654, Rev EA
August 2004 Volume 1
-15
Product Data Sheet
00813-0100-2654, Rev EA
Volume 1 August 2004
Calibration
V1-V7 Choose from “option code “V”–Callendar-van Dusen Constants.” See “Option Code “V” Callendar-van Dusen Constants”.
Option code V4 is not available with Series 68 sensors.
X8Q4 Calibrate to customer-specified temperature range (See “Option X8Q4: Sensor Calibrated to a Customer-Specified Temperature Range”)
X9Q4 Calibrate to customer-specified single temperature point (See “Option X9Q4: Sensor Calibrated to a Customer-Specified Single Point”)
Thermowell Options
Q8 Thermowell material certificate
R01 Thermowell special external pressure testing
R03 Thermowell dye penetration testing
R04 Special cleaning for oxygen service
R05 Thermowell NACE approval
R06 Stainless steel plug and chain
R07(14) Full penetration weld
R09(14)(15) Concentric serrations of thermowell flange face
R10 (14)(15) Thermowell flat faced flange
R11 Thermowell vent hole
R14 Thermowell special surface finish (12 Ra Max) (Maximum (U) length = 22.5 in.)
R16(14)(15) Ring joint flange (Not available with 0-in. (T) length)
R20 Electropolishing
R21 Thermowell Wake Frequency Calculation (Configuration Data Sheet required)
R22 Internal pressure testing
R23 Brass plug and chain
Mounting Adapters, Lead Wire Extensions, Connectors, and Seals
M5-M7 Mounting adapters
A1-A8 Twisted lead wire extensions
B1-B8(2) Shielded cable lead wire extensions
C1-C8(2) Armored cable lead wire extensions
D1-D8(2) Armored cable lead wire extensions with electrical plugs
L1-L8 Armored cable mating plugs with lead wire extensions
F1(2) 4-pin bayonet connector
H1-H8 4-pin connector mating plugs with lead wire extensions
J1 Moisture-proof seal assembly for armored cables
XA(16) Assemble connection head or transmitter to a sensor assembly (Teflon (PTFE) paste where appropriate, fully wired.)
(1) FM, CSA, SAA, and ATEX approvals are not available with the polypropylene connection head.
(2) Not available with Sensor Lead Wire Termination codes R, P, or W.
(3) Not available with option codes E1, E5, E6, and E7.
(4) Codes A and C must be used with an extension length. Additional non-standard (E) lengths are available in 1/2-in. increments from 2.5 to 9-in.
(5) Standard configuration with best delivery.
(6) Available only with straight stem thermowells.
(7) Thermowells with an overall length (“U” + “T” = 1.75-in.) of 42-in. or less are machined from solid barstock. Thermowells with an overall length larger than
42-in. will be constructed using a welded 3-piece design and are available only with a stepped stem style.
(8) For additional (T) lengths, see Table 28 on page -56.
(9) Straight or tapered stem only
(10) Straight thermowells are not recommended for (U) lengths greater than 6-in.
(11) F88 to F08 cannot be used with 0-in. (T) length. F08 cannot be used with 0- or 1/2-in. (T) length)
(12) SAA flame-proof approval is only applicable if installed with a Rosemount 248, 244E, 644, 3144P, or 3244MV transmitter.
(13) ATEX flame-proof approval is only applicable if ordered with Sensor Lead Wire Terminator code D (Rosemount connection head) or installed with a
Rosemount 144, 248, 244E, 644, 3144P, or 3244MV transmitter.
(14) Available on flanged thermowells only.
(15) Only one flange face option allowed.
(16) If ordering option code XA with a transmitter, specify the same option on the transmitter model code.
-16
PIPE-MOUNTED SUCTION SCREENS
HOW TO ORDER
15
I845300
2 Piece Threaded
and Solder End
Ball Valves
Valves must be installed in piping systems that comply to the applicable A.N.S.I. B31
Standard. Special considerations must be taken with respect to pipe line expansions
and contractions and the media expansions and contractions within the piping system.
1. Piping connections to be soldered into these valves should be cut square and then
cleaned with an appropriate cleaner or flux.
2. These valves are designed to be soft soldered. Apply heat with the flame directed
away from the center of the valve body. Excessive heat can harm the Teflon seats.
Solder valves only in the fully open position.
3. UNION END VALVES: Remove the union nut from valve and place onto pipe.
Solder the tailpiece onto pipe, thread union nut onto valve body and lightly torque.
OPERATION
The valve is marked showing proper rotation direction for “ON” and “OFF” positions.
Rotation is clockwise for “OFF” and counterclockwise for “ON”.
MAINTENANCE
Normal stem packing wear can be compensated for by tightening the packing gland
screw clockwise. If all of the adjustment to the packing gland screw has been made,
remove the lever and packing gland nut and add one or two replacement bearings on
top of the old packing. Reassemble the lever and packing gland nut.
CAUTION: Do not disassemble Valve while under pressure nor with entrapped
hazardous fluids therein.
1. Close valve.
2. Remove retainer from body center section by turning counterclockwise
3. 1/4” thru 1” valves only; pry out the top seat being careful not to damage the ball. 1-
1/4” thru 3” valves; the top seat will come out with the retainer.
4. Push ball out of body with finger.
5. Remove packing gland nut by turning counterclockwise and push stem down into
body to remove.
6. Remove all seats and seals. To facilitate removal of the stem packing, cut with
knife.
7. Replace all seats and seals as furnished in the Service Kit. Inspect the ball and
stem for excessive wear or damage and replace if necessary.
8. Reverse the above procedure to reassemble using a sealant on the retainer threads
equivalent to Loctite Hydraulic Sealant. NOTE: VALVES IN OXYGEN SERVICE
CAN ONLY BE SEALED WITH AN OXYGEN COMPATIBLE THREAD SEALANT.
Union End Valves cannot be easily field repaired, therefore it is recommended that the
main valve section be replaced.
NOTE: ALWAYS TEST VALVE AND SYSTEM BEFORE PUTTING THE SYSTEM
INTO SERVICE.
Bronze Valves: WARNING: This product is made from Bronze Alloys which contain
lead; a chemical known to the State of California to cause cancer and birth defects and
other reproductive harm.
General 2-PC. BALL VALVE
Identification
Installation
Install FS-200 or FS-400 Series units in piping system using standard pipe fitting procedures. Be careful to keep
sealing compound out of the unit. Be sure to observe direction of flow - marked “IN” and “OUT” on housing. See
chart below for port and wrench hex. sizes.
Unless otherwise specified, standard FS-200 and FS-400 units are factory-calibrated with water. FS-200 and
FS-200 Adjustable units are installed horizontally, in line, with lead wires up. FS-400 and FS-400 Adjustable units are
installed vertically; lead wires up, as shown. 150 micron filtration is suggested for use with all units.
Wetted Materials
Housing Bronze
Shuttle Delrin
Spring 316 Stainless Steel
O-Ring Viton
Other Wetted Parts Ceramic
Pressure Rating, Max.
Operating 400 PSI @ 100°F (+37.8°C)
Proof 800 PSI @ 100°F (+37.8°C)
Operating Temperature -20°F to +180°F (-29°C to +82.2°C)
Repeatability 1% Maximum Deviation
Set Point Accuracy ±10%
Set Point Differential 15% Maximum
Switch* SPDT, 20 VA
Inlet/Outlet Ports 3/4" NPT
Electrical Termination No. 18 AWG, 24" L.,
Polymeric Lead Wires
This product is suitable for Class I and Class II applications only, per the requirements of standard EN60730
and any additional specific requirements for a particular application or medium being sensed. Class I
compliance of metal bodied units requires a ground connection between the metal body and the earthing
system of the installation. Class I compliance of plastic bodied units in contact with a conductive medium
requires that the medium be effectively earthed so as to provide an earthed barrier between the unit and
accessible areas. For Class III compliance, a supply at safety extra-low voltage (SELV) must be provided.
Please consult the Factory for compliance information on specific part numbers.
Electrical Data
Switch Ratings - Maximum Resistive Load
Dimensions (FS-400 Series)
1-7/16"
HEX 1/2" NPT
3-27/32"
1-3/8"
1-3/8"
FS-200 Series
1" NPT and 1-1/2" NPT Ports 2" NPT and 3" NPT Ports
PRESSURE DROP (PSID)
Note
Note: Tests conducted with units in horizontal position (lead wires up) with water at +70°F (21°C).
FS-400 Series
PRESSURE DROP (PSID)
Note
Note: Tests conducted with units in vertical position (lead wires up) with water at +70°F (21°C).
Electrical Connection . . . Flow Setting Adjustment . . .
Lead wires and 1/2" NPT or junction box with 1/2" NPT. (FS-200/400Adjustable and FS-400 Units.)
Bonnet
Nut Adjustment Screw with Slot in Min.
Flow Position. (Same for FS-200
Shuttle Adjustable and FS-400 Adjustable
Assembly Units.
Disc
Retainer Ring "A"
Retainer Flow
Ring "B" Switch
FS-200/400 Series
(Fixed & Adjustable)
Important Points!
Product must be maintained and installed in strict accordance with Life expectancy of switch contacts varies with applications.
the National Electrical Code and GEMS technical brochure and Contact GEMS if life cycle testing is required.
instruction bulletin. Failure to observe this warning could result in
serious injuries or damages. Ambient temperature changes do affect switch set points, since
the specific gravity of a liquid can vary with temperature.
An appropriate explosion-proof enclosure or intrinsically safe
interface device must be used for hazardous area applications Flow switches have been designed to resist shock and vibration;
involving such things as (but not limited to) ignitable mixtures, however, shock and vibration should be minimized.
combustible dust and flammable materials.
Liquid media containing particulate and/or debris should be filtered
Pressure and temperature limitations shown on individual catalog to ensure proper operation of GEMS products.
pages and drawings for the specified flow switches must not be
exceeded. These pressures and temperatures take into consider- Electrical entries and mounting points may require liquid/vapor
ation possible system surge pressures/temperatures and their sealing if located in an enclosed tank.
frequencies.
Flow switches must not be field repaired.
Selection of materials for compatibility with the media is critical to
the life and operation of GEMS flow switches. Take care in the Physical damage sustained by the product may render it unser-
proper selection of materials of construction; particularly wetted viceable.
materials.
P/N 45523
Rev. N
V24 Nelson Enclosures & Controls V24
Type GUB Junction Boxes & Instrument Enclosures
Use: Applicable Third Party Standards:
To pull or splice wires and/or to mount and UL Standard: 886
enclose electrical devices in hazardous Suitable for wet locations.
locations. ANSI C33.84 and C33.27
ASTM A-153-73 Class A
Features: Fed. Spec: W-C 586C
• O-Ring gasket provided to seal out Mil. Spec: 100 and 130
moisture, dust, oil, dirt, etc. for interior and CSA Standard C22.2, No. 30
exterior locations
• Mounting lugs provided on all enclosures. Third Party Certification:
• Tapered threads (NPT) on conduit entries Series GUB, NGUB, GUBDC
and union hubs Type GUB
UL Listed: E-30513, E-85310
• Large cover opening for easy access Series GUBSW, NGUBSW Cast Iron Box with Aluminum Cover
• Ground kit available (See Page V28) UL Listed: E-113735, E-103220 Type NGUB-A
Cast Aluminum Box and Cover
GUBSW, NGUBSW-A: Series GUB, NGUB, GUBDC
• Meter-instrument housing. CSA Certified: 43437, LR20945
• Large diameter site window cover permits Series GUBSW, NGUBNWN
maximum visibility of enclosed device. CSA Certified 43437
Finishes:
• Hot dip galvanized on cast iron.
• Gray epoxy powder coat on aluminum
Dimensional Data:
See Page V26-27
Ordering Numbers:
See Page V25-29
Catalog Number
Seal Distance (In.)(1)
Standard Cover Site Window Cover Inside Dimensions (inches) Maximum Mounting Group Group
Aluminum Iron Aluminum Iron Width Height Depth Conduit Plate Size B C
(1) For Groups B and C, all conduits must be sealed within specified distance of enclosure.
Long 2 2 -- -- -- -- -- -- -- -- 2 2 -- -- -- -- -- -- -- --
NGUB443A Short 2 2 -- -- -- -- -- -- -- -- 2 2 -- -- -- -- -- -- -- --
Long 2 2 -- -- -- -- -- -- -- -- 2 2 -- -- -- -- -- -- -- --
GUB-443 Short 2 2 -- -- -- -- -- -- -- -- 2 2 -- -- -- -- -- -- -- --
Long 3 2 -- -- -- -- -- -- -- -- 2 2 1 1 1 1 -- -- -- --
NGUB555A Short 3 2 -- -- -- -- -- -- -- -- 2 2 1 1 1 1 -- -- -- --
NGUB664A Long 3 3 2 2 2 1 1▲ -- -- -- 3 3 2 2 1 1 1▲ -- -- --
GUB-664 Short 3 3 2 2 2 1 1▲ -- -- -- 3 3 2 2 1 1 1▲ -- -- --
Long 5 4 4 3 3 2 -- -- -- -- 5 4 3 3 2 2 -- -- -- --
NGUB976A Short 4 3 3 2 2 2 -- -- -- -- 4 3 2 2 2 1 -- -- -- --
Long 5 5 4 3 3 2 -- -- -- -- 5 4 3 3 2 2 -- -- -- --
NGUB984A Short 5 4 3 3 2 2 -- -- -- -- 4 4 3 2 2 2 -- -- -- --
Long 5 5 4 3 3 2 2▲ -- -- -- 5 4 3 3 2 2 2▲ -- -- --
GUB-984 Short 5 4 3 3 2 2 2▲ -- -- -- 4 4 3 2 2 2 1▲ -- -- --
Long 6◆ 5◆ 4 3 3 2 -- -- -- -- 5◆ 4◆ 3 3 2 2 -- -- -- --
NGUB1093A Short 5◆ 4◆ 4 3 3 2 -- -- -- -- 5◆ 4◆ 3 2 2 2 -- -- -- --
Long 6◆ 5◆ 4 3 3 2 -- -- -- -- 5◆ 4◆ 3 3 2 2 -- -- -- --
GUB-1093 Short 5◆ 4◆ 4 3 3 2 -- -- -- -- 5◆ 4◆ 3 3 2 2 -- -- -- --
NGUB10105A Long 6◆ 5◆ 5 4 3 3 2 2 1 -- 6◆ 5◆ 3 3 3 2 2 2 1 --
GUB-10105 Short 6◆ 5◆ 5 4 3 3 2 2 1 -- 6◆ 5◆ 3 3 3 2 2 2 1 --
Long 6◆ 5◆ 4 3 3 2 2 2 -- -- 5◆ 4◆ 3 3 2 2 2 1 -- --
NGUB1016A Short 6◆ 5◆ 4 3 3 2 2 2 -- -- 5◆ 4◆ 3 3 2 2 2 1 -- --
Long 6◆ 5◆ 4 3 2 2 2 2 1 1 5◆ 4◆ 3 3 2 2 2 1 1 1
NGUB10108A Short 6◆ 5◆ 4 3 3 2 2 2 1 1 5◆ 4◆ 3 3 3 2 2 1 1 1
Long 7◆ 6◆ 5 4 4 3 2 2 2 1 6◆ 5◆ 4 3 3 3 2 2 2 1
NGUB12128A Short 7◆ 6◆ 5 4 4 3 2 2 2 1 6◆ 5◆ 4 3 3 3 2 2 2 1
Long 7◆ 6◆ 5 4 4 3 2 2 2 1 6◆ 5◆ 4 3 3 2 2 2 2 1
NGUB121212A Short 7◆ 6◆ 5 4 4 3 2 2 2 1 6◆ 5◆ 4 3 3 2 2 2 2 1
STANDARD COVER
NGUB443A GUB-443 55⁄16 55⁄16 53⁄16 49⁄16 61⁄4 37⁄8 3⁄8 2 33⁄4 213⁄16 33⁄4 3⁄4 4 45⁄8 4 3 7
⁄16 7
⁄16
NGUB555A -- 61⁄4 61⁄4 615⁄16 61⁄4 71⁄2 5 3⁄8 2 41⁄4 41⁄16 41⁄4 15⁄16 41⁄2 51⁄4 51⁄2 45⁄8 7
⁄16 3
⁄8
NGUB664A GUB-664 7 7 61⁄2 511⁄16 81⁄8 53⁄4 3⁄8 2 51⁄2 33⁄4 51⁄2 7⁄8 515⁄16 61⁄2 5 4 7
⁄16 7
⁄16
NGUB976A -- 101⁄4 81⁄2 87⁄16 77⁄16 93⁄4 9 3⁄8 4 81⁄4 415⁄16 61⁄2 13⁄16 7 73⁄4 63⁄8 51⁄2 1
⁄2 7
⁄16
NGUB984A GUB-984 10 9 65⁄8 57⁄8 101⁄8 81⁄2 3⁄8 2 81⁄2 313⁄16 71⁄2 15⁄16 715⁄16 85⁄8 51⁄16 41⁄16 7
⁄16
7
16 ⁄
NGUB1093A GUB-1093 10 9 67⁄16 511⁄16 12 91⁄4 3⁄8 4 87⁄8 37⁄16 71⁄2 15⁄16 815⁄16 93⁄4 45⁄8 35⁄8 11
16⁄ 11
16 ⁄
NGUB10105A GUB-10105 12 12 83⁄4 77⁄8 135⁄8 10 7⁄8 4 93⁄4 413⁄16 93⁄4 11⁄4 97⁄8 11 61⁄2 53⁄16 11
16⁄ 11
16 ⁄
NGUB10106A -- 115⁄8 115⁄8 93⁄8 77⁄8 13 10 7⁄8 4 87⁄8 411⁄16 87⁄8 13⁄8 91⁄4 101⁄4 69⁄16 51⁄2 3
⁄4
11
16 ⁄
NGUB10108A -- 115⁄8 115⁄8 113⁄8 97⁄8 13 10 7
⁄8 4 87⁄8 611⁄16 87⁄8 13⁄8 91⁄4 101⁄4 89⁄16 71⁄2 3
⁄4 11
⁄16
NGUB12128A -- 135⁄8 135⁄8 113⁄4 97⁄8 15 10 7
⁄8 4 107⁄8 611⁄16 107⁄8 13⁄8 111⁄4 121⁄4 89⁄16 71⁄2 3
⁄4 11
⁄16
NGUB121212A -- 135⁄8 135⁄8 153⁄4 137⁄8 15 10 7
⁄8 4 103⁄4 1011⁄16 103⁄4 13⁄8 111⁄4 121⁄4 129⁄16 111⁄2 3
⁄4 11
⁄1
ADJUSTABLE
POSITIONING
SECTION VIEW
CONDUIT SPACE
(DOME NOT SHOWN FOR CLARITY)
DOME COVER STYLE
Dimensions in Inches
Refer to Catalog No. Maximum Mounting Mounting
Catalog Number on Page V93 Overall Conduit Plate Seal Distance (In)(1) Plate
Aluminum Iron for Dimensions Height C Size Size Group B Group C Adjustment*
*Optional mounting plate is adjustable. It may be located in center of cover or toward either side of dome cover.
(1) For Groups B and C, all conduits must be sealed within specified distance of enclosures.
Options:
GUB boxes can be ordered with drilled and Examples Standard or Custom:
tapped conduit entries or union hubs subject STANDARD
to the parameters of Table 3. 1 Box: GUB-984
2 Arrangement: 12
To Order: 3 Required: One 1⁄2” drilled and tapped entry
1 Select box from appropriate catalog page. at “a”; no entry at “b”; one 1” union hub at
2 Determine standard conduit arrangement “c”; two 3⁄4” drilled and tapped entries at “d”
from Table 1 or use the custom GUB drilling and “e”.
template on the following page. 4 Symbols: Substitute symbols for entry
3 Verify the size of GUB selected using sizes in clockwise order around box starting
TABLE 2
Table 3 for conduit entries or union hubs with location “a”. Drilled and
required. Trade Size Tapped Conduit Union
4 Select the corresponding symbol from Completed Example: GUB-984-12-10Y22 (inches) Entry Symbol Hub Symbol
Table 2 for the conduit entries or union hubs
needed. CUSTOM ⁄2
1
1 W
1 Box: GUB-10105 ⁄4
3
2 X
5 Mounting lugs (when provided) are on the 1 3 Y
left & right side of box, relative to 2 Arrangement : Photocopy template on 11⁄4 4 R
illustrations in Table 1. page V31 and mark-up with all dimensions
6 All threaded entries will be centered and for conduit entries. 11⁄2 5 S
3 Required: All conduit entries and options 2 6 T
evenly spaced on the box wall(s). 21⁄2 7 U
located on templates. 3 8 V
4 Symbols: Label the template with
appropriate symbols conduit entry 31⁄2 9 WD
locations. 4 10 XE
None 0 O
TABLE 1 STANDARD CONDUIT ARRANGEMENT
TABLE 3 RECOMMENDED SPACING AND LOCATION OF CONDUIT Allows for Bushing Clearance
⁄2
1
35⁄8 33⁄8 3 25⁄8 23⁄8 2 17⁄8 13⁄4 15⁄8 11⁄2
⁄4
3
33⁄4 31⁄2 31⁄8 23⁄4 21⁄2 21⁄8 2 17⁄8 13⁄4
1 4 35⁄8 31⁄4 3 25⁄8 23⁄8 21⁄4 2
11⁄4 41⁄8 37⁄8 31⁄2 31⁄8 27⁄8 21⁄2 2⁄ 3
8
2 ⁄8
7
31⁄8 33⁄8 35⁄8 4 43⁄8 45⁄8 1 ⁄4
1
⁄2
1 3
⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4
Minimum Space Between Centers of Conduits (inches)
Minimum spacing from sides and Minimum Space from Sides and Back (inches)
back. For drilled and tapped conduit
entries and union hubs. Conduit Trade Size 1
⁄2 3
⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4
Conduit Dimensions and Enclosure Threading Requirements (All dimensions are in Inches):
Conduit Size ⁄2
1
⁄4
3
1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 5 6
Actual O.D. 0.840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.563 6.625
Nominal O.D. 27
⁄32 11⁄16 111⁄32 111⁄16 129⁄32 23⁄8 27⁄8 31⁄2 4 41⁄2 59⁄16 65⁄8
Actual I.D. 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 3.548 4.026 5.047 6.065
Nominal I.D. 5
⁄8 27
⁄32 11⁄16 13⁄8 15⁄8 21⁄16 215⁄32 31⁄16 39⁄16 41⁄32 51⁄16 61⁄16
Conduit to Staggered
Conduit Conduit Size Conduit Conduit Size
Conduit Size ⁄2
1
⁄4
3
1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 Seals/Unions Size ⁄2
1
⁄4
3
1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4
⁄2
1
15⁄8 13⁄4 17⁄8 2 21⁄8 23⁄8 25⁄8 3 31⁄4 31⁄2 ⁄2
1
17⁄8 2 21⁄4 21⁄2 25⁄8 27⁄8 31⁄4 37⁄8 4 41⁄4
⁄4
3
-- 17⁄8 2 21⁄8 21⁄4 21⁄2 23⁄4 31⁄8 33⁄8 35⁄8 ⁄4
3
-- 21⁄8 23⁄8 21⁄2 23⁄4 3 33⁄8 4 41⁄8 43⁄8
1 -- -- 21⁄8 21⁄4 23⁄8 25⁄8 27⁄8 31⁄4 31⁄2 33⁄4 1 -- -- 21⁄2 25⁄8 27⁄8 31⁄8 31⁄2 41⁄8 41⁄4 41⁄2
11⁄4 -- -- -- 21⁄2 25⁄8 27⁄8 31⁄8 33⁄8 35⁄8 37⁄8 11⁄4 -- -- -- 27⁄8 31⁄4 33⁄8 33⁄4 43⁄8 41⁄2 43⁄4
11⁄2 -- -- -- -- 23⁄4 3 31⁄4 31⁄2 33⁄4 4 11⁄2 -- -- -- -- 35⁄8 31⁄2 37⁄8 41⁄2 45⁄8 47⁄8
2 -- -- -- -- -- 31⁄8 33⁄8 33⁄4 4 41⁄4 2 -- -- -- -- -- 35⁄8 4 45⁄8 43⁄4 5
21⁄2 -- -- -- -- -- -- 35⁄8 4 41⁄4 41⁄2 21⁄2 -- -- -- -- -- -- 41⁄4 47⁄8 5 51⁄4
3 -- -- -- -- -- -- -- 41⁄4 41⁄2 43⁄4 3 -- -- -- -- -- -- -- 51⁄4 51⁄2 53⁄4
1
⁄2 2 21⁄4 23⁄8 25⁄8 23⁄4 3 33⁄8 4 41⁄8 43⁄8 1
⁄2 15⁄8 13⁄4 17⁄8 21⁄4 21⁄2 23⁄4 31⁄8 33⁄8 33⁄4 4
3
⁄4 -- 23⁄8 21⁄2 23⁄4 3 31⁄4 35⁄8 41⁄4 43⁄8 45⁄8 3
⁄4 -- 17⁄8 2 23⁄8 21⁄2 27⁄8 31⁄8 31⁄2 37⁄8 41⁄8
1 -- -- 25⁄8 27⁄8 31⁄8 33⁄8 33⁄4 43⁄8 41⁄2 43⁄4 1 -- -- 21⁄8 21⁄2 23⁄4 31⁄8 33⁄8 33⁄4 4 43⁄8
11⁄4 -- -- -- 31⁄8 33⁄8 35⁄8 4 45⁄8 43⁄4 5 11⁄4 -- -- -- 27⁄8 31⁄8 33⁄8 33⁄4 41⁄8 43⁄8 45⁄8
11⁄2 -- -- -- -- 31⁄2 33⁄4 41⁄8 43⁄4 47⁄8 51⁄8 11⁄2 -- -- -- -- 31⁄4 35⁄8 37⁄8 41⁄4 41⁄2 47⁄8
2 -- -- -- -- -- 4 43⁄8 5 51⁄8 53⁄8 2 -- -- -- -- -- 4 41⁄4 45⁄8 47⁄8 51⁄4
21⁄2 -- -- -- -- -- -- 45⁄8 51⁄4 53⁄8 55⁄8 21⁄2 -- -- -- -- -- -- 41⁄2 47⁄8 51⁄8 51⁄2
3 -- -- -- -- -- -- -- 53⁄8 57⁄8 61⁄8 3 -- -- -- -- -- -- -- 51⁄4 51⁄2 57⁄8
70-600 SERIES
70-900 SERIES
76-600 SERIES
NOTE: THIS IS A DIVERSION VALVE, open port pressure must exceed closed port
pressure.
1. Piping connections to be soldered into these valves should be cut square and then
cleaned with an appropriate cleaner or flux.
2. These valves are designed to be soft soldered. Apply heat with the flame directed
AWAY from the center of the valve body. Excessive heat can harm the TFE seats
and packing. SOLDERING TEMPERATURE NOT TO EXCEED 500ºF. Adjust
packing after joints are cool.
OPERATION
The valve levers are marked showing proper flow direction in respect to lever position at
extreme end of lever travel.
MAINTENANCE
Normal stem packing wear can be compensated for by tightening the packing gland
screw clockwise. If all of the adjustment to the packing gland screw has been made,
remove the lever and packing gland screw and add one or two replacement bearings on
top of the old packing. Reassemble the lever and packing gland screw.
CAUTION: Do not disassemble Valve while under pressure nor with entrapped
hazardous fluids therein.
1. Remove Valve from system. Turn Valve lever to position shown on exploded view.
(Clockwise)
2. Remove retainer by turning counterclockwise.
3. Remove top seat.
4. Push ball out of body with finger.
5. Remove lever nut by turning counterclockwise. Lever assembly can then be lifted
off stem.
6. Remove packing gland screw by turning counterclockwise and push stem down into
body to remove.
7. Remove all seats and seals. To facilitate removal of the stem packing, cut with
knife.
8. Replace all seats and seals as furnished in the Service Kit. Inspect the ball and
stem for excessive wear or damage and replace if necessary.
9. Reverse the above procedure to reassemble. Make certain to install the lever, ball,
and stem in the position shown in the exploded view. Use Loctite Hydraulic Sealant
or equal on the retainer threads.
NOTE: Always test Valve and system before putting the system into service.
A. RETAINER
B. BODY SEAL (1-1/4” – 2” SIZES)
C. SEAT
D. BALL
E. STEM
F. BEARING
G. BODY
H. PACKING
I. GLAND SCREW
J. LEVER / GRIP ASSEMBLY
K. WASHER (1-1/2” – 2” S.S. ONLY)
L. LEVER NUT
Catalog HY14-2502/US Check Valves
Technical Information Series C
General Description
Series “C” check valves permit free flow in one direc-
tion, and dependable shut-off in the reverse direction.
Operation
When pressure going through the valve is increased to
the cracking level, the valve opens. When the pressure
is reduced to below the cracking level, the valve closes.
Features
• Stainless steel poppets standard.
• Soft seal poppets are available.
• Triangular retainers guide the poppets, and hold the
spring firmly in place even under high velocity and shock.
Specifications
150 10.5
C1020: 57 LPM (15 GPM)
Pressure Drop
2020,
125 8.6
C1200: 95 LPM (25 GPM) 2000
C1220: 95 LPM (25 GPM) 100 6.9
C1600: 151 LPM (40 GPM) 2420,
C1620: 151 LPM (40 GPM) 75 5.2 2400
C2000: 265 LPM (70 GPM) 3220,
50 3.5 3200
C2020: 265 LPM (70 GPM)
C2400: 379 LPM (100 GPM)
25 1.7
C2420: 379 LPM (100 GPM)
C3200: 569 LPM (150 GPM) 0
LPM 94.6 189.3 283.9 378.5 473.1 567.8
C3220: 569 LPM (150 GPM) 0
GPM 25 50 75 100 125 150
Poppets Soft seal poppet is standard for Flow
200 through 800/1020 size.
For cracking pressures > 15 PSI,
solid metal poppets are standard
2502-F9.p65, dd
Ordering Information
C
Options Series C Size Material Cracking Pressure Seal Design
(nominal) Compound Series
NOTE:
Not required
when ordering.
200 * 800*† 1600 * 2400 Code Description Code Description Code Description
400 *† 820 1620 2420
600 *† 1020 2000 3200 B Brass Omit Standard Omit Nitrile (Standard)
620 1200 * 2020 3220 S Steel 0.4 Bar (5 PSI) V Fluorocarbon
1220 SS * Stainless Steel 65 4.5 Bar (65 PSI)
* Sizes available in Brass
Series C Brass Valves can be Other cracking pressures available
† Sizes available in Stainless Steel
used for both air and oil service.
* Available in 400, 600 and 800
sizes.
Code Description Model Weight Model Weight Model Weight Model Weight
Omit NPTF/SAE Number kg (lbs.) Number kg (lbs.) Number kg (lbs.) Number kg (lbs.)
C200 0.0 (0.1) C820 0.3 (0.7) C1600 1.5 (3.3) C2400 3.8 (8.4)
8 BSPT C400 0.2 (0.4) C1020 0.6 (1.3) C1620 1.5 (3.3) C2420 3.8 (8.4)
9 BSPP C600 0.2 (0.5) C1200 0.9 (2.0) C2000 2.8 (6.2) C3200 7.0 (15.4)
C620 0.2 (0.5) C1220 0.9 (2.0) C2020 2.8 (6.2) C3220 7.0 (15.4)
C800 0.6 (1.3)
Dimensions
Inch equivalents for millimeter dimensions are shown in (**)
Free
Flow
A
D (Both Ends) B
C Sq.
Model
Number A B C D
C200 1/8–27 NPTF 50.8 (2.00) 16.0 (0.63) 7.9. (0.31)
C400 1/4–18 NPTF 66.8 (2.63) 20.6 (0.81) 10.4 (0.41)
C420 7/16–20 UNF #4 SAE 68.3 (2.69) 20.6 (0.81) 10.4 (0.41)
C600 3/8–18 NPTF 69.9 (2.75) 25.4 (1.00) 12.7 (0.50)
C620 9/16–18 UNF #6 SAE 79.2 (3.12) 25.4 (1.00) 12.7 (0.50)
C800 1/2–14 NPTF 87.4 (3.44) 31.8 (1.25) 16.0 (0.63)
C820 3/4–16 UNF #8 SAE 88.9 (3.50) 28.4 (1.12) 14.2 (0.56)
C1020 7/8–14 UNF #10 SAE 101.6 (4.00) 31.8 (1.25) 15.7 (0.62)
C1200 3/4–14 NPTF 98.6 (3.88) 38.1 (1.50) 19.1 (0.75)
C1220 1 1/6–12 UN #12 SAE 117.3 (4.62) 38.1 (1.50) 19.1 (0.75)
C1600 1–11 1/2 NPTF 127.0 (5.00) 44.5 (1.75) 22.4 (0.88)
C1620 1 5/16–12 UN #16 SAE 142.7 (5.62) 57.2 (2.25) 28.4 (1.12)
C2000 1 1/4–11 1/2 NPTF 143.0 (5.63) 57.2 (2.25) 28.7 (1.13)
C2020 1 5/8–12 UN #20 SAE 165.1 (6.50) 69.9 (2.75) 35.1 (1.38)
C2400 1 1/2–11 1/2 NPTF 143.0 (5.63) 69.9 (2.75) 35.1 (1.38)
C2420 1 7/8–12 UN #24 SAE 184.2 (7.25) 76.2 (3.00) 38.1 (1.50)
C3200 2–11 1/2 NPTF 165.1 (6.50) 88.9 (3.50) 44.5 (1.75)
C3220 2 1/2–12 UN #32 SAE 228.6 (9.00) 101.6 (4.00) 50.8 (2.00)
2502-F9.p65, dd
49.25
TO R. F. 3x 1.00 - 11.5 NPT
.88 CASE DRAIN (PLUGGED)
29.88
4x O 2.19 THRU HOLES
26.25
OIL LEVEL SIGHT GLASS 2x O .562 PILOT HOLES
(FAR SIDE ) FOR #10 TAPER PINS.
DIAGONALLY OPPOSITE FEET
.75 - 14 NPT OIL INLET
11.50 11.50 SUPPLY OIL AT 1 - 1.5 GPM
OIL LEVEL 1.75 SEE NOTE 1
SIGHT GLASS 14.75 14.75 11.00 11.00
46.75 15.00
4x O .75-14 NPT LEAKPATHS
.75 - 14 NPT OIL INLET TO SHOW LEAKAGE 30.00
SUPPLY OIL AT 5.5 - 6 GPM 4x 1.00-8 UNC JACKING TAPS IN THE EVENT OF
SEE NOTE 1 MECH. SEAL FAILURE.
UNLESS OTHERWISE SPECIFIED Warren Pumps LLC
2.50-8 NPT OIL OUTLET DIMENSIONS ARE IN INCHES Warren 82 Bridges Ave
(PLUGGED) BOTH SIDES D R Landry 05-24-05 PO Box 969
NOTES : TOLERANCES APPROVED DATE A Member of the COLFAX PUMP GROUP Warren, MA 01083.0969
CUSTOMER : SOLAR TURBINES INCORPORATED ON OVERALL DIM'S
MABANK REFURBISH CENTER TITLE
1. CUSTOMER TO USE MOBIL SHC 629 OIL THRU 12.00 ±.13 CHECKED RD 05-23-05 OUTLINE DRAWING
OVER 12 THRU 36 ±.19
IN GEAR HOUSING AND FRONT HEAD. OVER 36 THRU 72 ±.25 FOR #4550 FSXB SCREW PUMP
CUST. ORDER No. : MB0500755 DRAWN drt 05-20-05
OVER 72.00 ±.38
WARREN ORDER No. : IP55836XA
2. PUMP BEARING RTD SETPOINTS ; SIZE CAGE CODE ESWBS DRAWING NO. REV
EQUIP. No. : 1012779-76761 THIRD ANGLE PROJECTION
ALARM = 195°F NO. OF UNITS: ( 6 ) SIX C 63857 C-3558 A
SHUT - DOWN = 210°F
SCALE: MASS (WEIGHT) 12,500 LBS ( EST) SHEET 1 OF 1
(This page intentionally left blank)