Professional Documents
Culture Documents
Using the S7800A1142 Keyboard Display (standard on Fig. 1. The valve proving system.
RM7800L1087) the following features can be set up:
MV1—Wired to terminal 9. It is located in the most upstream
• Post Purge time—Up to 60 minutes—Device shipped position of the main gas valve train.
with 15 seconds Post purge.
VPS—Valve Proving Switch: Setpoint at 1/2 of Main Valve
• Valve Proving features including: inlet pressure.
— VPS test time
— When (Never, Before, After, Split or Both) MV2—Wired to terminal 21. It is the main valve located
• See S7800A1142 Instructions (65-0288). Series 5 can closest to the burner.
be programmed for Modbus communication. The PII—Pre-Ignition Interlock (or Proof of Closure Switch) for
At commissioning time, the Valve Proving System may be terminal 20 can be installed on MV1, MV2, or as a series
scheduled to occur at one of five different times: connection through both valves.
• Never—Device default as received—Valve proving Appendix B lists many wiring options for single and dual fuel
does not occur. along with the Valve Proving options.
• Before—Valve proving before run concurrent with Pre-Purge.
• After—Valve proving occurs after the Run state, before
the device goes to Standby (Concurrent with Post-
SPECIFICATIONS
Purge, if selected.)
Electrical Ratings, see Table 3:
• Both—Valve proving occurs at both times Before and Voltage and Frequency:
After, noted above. RM78xx—120 Vac (+10/-15%), 50 or 60 Hz (±10%).
• Split—The main valve 2 (MV2) (high pressure) seat test EC78xx—220–240 Vac (+10/-15%), 50 or 60 Hz (±10%).
is performed at the Before time and the main valve 1 Power Dissipation: RM7800/RM7840/EC7840L: 10W
(MV1) (low pressure) seat test is performed during the maximum in the Run mode.
After time.
SIL3
Capable 66-1162-05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Maximum Total Connected Load: 2000 VA. 3. Installer must be a trained, experienced, flame
safeguard service technician.
Fusing: 15A maximum, Type SC or equivalent Fast Blow. 4. After installation is complete, check out the product
operation as provided in these instructions.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C).
WARNING
Fire or Explosion Hazard.
Humidity: 85% relative humidity continuous, noncondensing.
Can cause property damage, severe injury,
Vibration: 0.5G environment.
or death.
SIL 3 Capable: To prevent possible hazardous burner operation, verify
RM7800/RM7840E, G, L, M are now SIL 3 Capable in a prop- safety requirements each time a control is installed on
erly desgined Safety Instrumented system. See form num- a burner.
ber 65-0312 for Certificate Agreement.
Approvals: RM7800L/40G,L:
Underwriters Laboratories Inc. Listed: File No. MP268,
WARNING
Electrical Shock Hazard.
Guide No. MCCZ.
Can cause serious injury or death.
Canadian Standards Association Certified: LR9S329-3.
Disconnect the power supply before beginning
Factory Mutual Approved: Report No. 1V9A0.AF.
installation. More than one power supply disconnect
Swiss Re (formerly IRI): Acceptable.
may be required.
Federal Communications Commission, Part 15,
Class B—Emissions.
IMPORTANT
Approvals: EC7840L:
1. Wiring connections for the relay modules are unique;
Factory Mutual Approved: Report No.1V9A0.AF.
therefore, refer to Figs. 3, 4, 6, 7, or Appendix B for
Swiss Re (formerly IRI): Acceptable.
proper subbase wiring.
Federal Communications Commission, Part 15,
2. Wiring must comply with all applicable codes,
Class B—Emissions.
ordinances and regulations.
This document provides installation and static checkout 3. Wiring must comply with NEC Class 1 (Line Voltage)
instructions. Other applicable publications are: wiring.
4. Loads connected to the RM7800L/40G,L, EC7840L
Publication must not exceed those listed on the RM7800L/40G,L,
No. Product EC7840L label or the Specifications, see Table 3.
5. Limits and interlocks must be rated to simultaneously
65-0084 Q7800A,B 22-Terminal Wiring Subbase carry and break current to the ignition transformer,
Product Data pilot valve, and main fuel valve(s).
65-0288 S7800A1142 Keyboard Display Module 6. All external timers must be listed or component
Product Data recognized by authorities who have jurisdiction for
65-0091 S7810A Data ControlBus™ Module Product the specific purpose for which they are used.
Data 7. For on-off gas-fired systems, some authorities who
have jurisdiction prohibit the wiring of any limit or
65-0095 S7820 Remote Reset Module Product Data
operating contacts in series between the flame
65-0097 221729C Dust Cover Installation safeguard control and the main fuel valve(s).
Instructions 8. Two Flame Detectors can be connected in parallel with
65-0101 S7830 Expanded Annunciator Product Data the exception of Infrared Flame Detectors (C7015,
65-0109 R7824, R7847, R7848, R7849, R7851, C7915), Ultraviolet (C7927, C7961), or Visible
R7852, R7861, R7886 Flame Amplifiers for (C7962).
the 7800 SERIES Product Data 9. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used
65-0131 221818A Extension Cable Assembly in accordance with the instructions, may cause
Product Data interference to radio communications. It has been
65-0229 7800 SERIES Relay Modules Checkout and tested and found to comply with the limits for a
Troubleshooting Product Data Class B computing device of Part 15 of FCC rules
65-0249 S7810M ModBus Module which are designed to provide reasonable protection
against such interference when operated in a
commercial environment. Operation of this
INSTALLATION equipment in a residential area may cause
interference; in which case, the users at their own
When Installing this Product... expense may be required to take whatever
measures are required to correct this interference.
1. Read these instructions carefully. Failure to follow them 10.This digital apparatus does not exceed the Class B
could damage the product or cause a hazardous limits for radio noise for digital apparatus set out in
condition. the Radio Interference Regulations of the Canadian
2. Check the ratings given in the instructions and marked Department of Communications.
on the product to make sure the product is suitable for
the application.
66-1162—05 2
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Location 5.
6.
Recommended wire size and type: see Table 1.
Recommended grounding practices: see Table 2.
2.
Appendix B.
For proper remote wiring of the Keyboard Display
Final Wiring Check
Module, through a 203541 5-wire Connector, refer to 1. Check the power supply circuit. The voltage and fre-
the Specifications for the Keyboard Display Module quency tolerance must match those of the
(65-0288), Data ControlBus Module™ (65-0091) or RM7800L/40G,L, EC7840L. A separate power supply
Extension Cable Assembly (65-0131). circuit may be required for the RM7800/RM7840/
3. Disconnect the power supply from the main disconnect EC7840L. Add the required disconnect means and
before beginning installation to prevent electrical shock overload protection.
and equipment damage. More than one disconnect may 2. Check all wiring circuits and complete the Static
be required. Checkout, see Table 9, before installing the
4. All wiring must comply with all applicable electrical RM7800L/40G,L, EC7840L on the subbase.
codes, ordinances and regulations. Wiring, where 3. Install all electrical connectors.
required, must comply with NEC, Class 1 (Line Voltage) 4. Restore power to the panel.
wiring.
3 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
L1 (HOT) L2
INTERNAL
4 L2
ELECTRONICS
ALARM
3
3K
BLOWER
5
6K
DEMAND
LOW FIRE
LIMITS CONTROLLER 18
SWITCH
6
17 HIGH FIRE
DEMAND (VALVE 19
SWITCH
AIR FLOW PROVING)
SWITCH PILOT
7 8 VALVE
VALVE PROVING SWITCH 1K 4K
MAIN
16 9
VALVE 1
2K
20 10 IGNITION
5K 2K
PRE-IGNITION INTERLOCK
21 1
7K
HIGH FIRE
12
COMMON
13
MODULATE
INTERNAL RELAY OPTO FEEDBACK
15
FIELD WIRING
INTERNAL WIRING LOW FIRE
14
Fig. 2. Internal block diagram of the RM7800L/40L, EC7840L (See Figs. 3, 4, 6 or 7 for individual detailed wiring
instructions).
66-1162—05 4
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
2. Use wide straps or brackets to provide minimum length, maximum surface area
ground conductors. If a leadwire must be used, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the ground path are free of
nonconductive coatings and protected against corrosion on mating surfaces.
Signal ground (KDM, Data ControlBus Use the shield of the signal wire to ground the device to the signal ground terminals
Module™ [3(c)] of each device. Connect the shield at both ends of the chain to earth ground.
a
The relay module must have an earth ground providing a connection between the subbase and the control panel or the
equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event of an
internal short circuit. The relay module requires a low impedance ground connection to the equipment frame, which, in turn,
requires a low impedance connection to earth ground.
b
2000 VA maximum connected load to relay module assembly.
c
See Tables 4 and 5.
d 220/240 Vac to 120 Vac, 10 VA (minimum) stepdown transformer (not provided) must be used to drive the shutter.
5 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
66-1162—05 6
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
SERIES 90
FIRING RATE SERIES 90
Q7800 MOTOR CONTROLLER
HIGH FIRE
G 12 B B
FOR DIRECT SPARK IGNITION (OIL
OR GAS)
COMMON
L2 13 R R
IGNITION
10 TRANSFORMER
LINE VOLTAGE LOW FIRE
3 14 W W
ALARM
8 L2
MODULATE
4 (L1) 15
9 2ND STAGE
FUEL VALVE
BURNER MOTOR (OPTIONAL)
(BLOWER) 5 16
BURNER 6 17
CONTROLLER/LIMITS
2
7 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
RM7800/RM7840L/EC7840L
INITIATE PREPURGE PREPURGE PFEP
(INITIAL HOLD HOLD 10 SEC.
POWERUP 00 DRIVE TO 00 TIMED 00 DRIVE TO 00(4 SEC. IF 10 1 20 25 00 15
ONLY) STANDBY HIGH FIRE PREPURGE LOW FIRE JR1 CLIPPED MFEP RUN POSTPURGE STANDBY
POWER POWER POWER POWER POWER POWER POWER POWER POWER POWER
LED PILOT PILOT PILOT PILOT PILOT
DISPLAY
FLAME FLAME FLAME FLAME FLAME
MAIN MAIN MAIN MAIN MAIN
ALARM ALARM ALARM ALARM ALARM
10 IGN. 5 SEC.
10 SEC. IGN./PILOT 8
15 SEC. PILOT 21
MAIN VALVE 9
OPERATING
LIMITS AND BURNER CONTROLLER CLOSED L1 TO 6
CONTROLS
AND
INTERLOCKS INTERLOCK. CHECK LOCKOUT INTERLOCKS CLOSED 6 TO 7 IC
FLAME
SAFE START CHECK FLAME PROVING SSC
SIGNAL
SWITCHING 13 TO 15
13 TO 12 13 TO 14 13 TO 14
FIRING
RATE MOTOR ACTION
MOTOR
Fig. 3. Typical wiring subbase and sequence for RM7800L/40L, EC7840L without enabled Valve Proving.
66-1162—05 8
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
SERIES 90
FIRING RATE SERIES 90
Q7800 MOTOR CONTROLLER
HIGH FIRE
G 12 B B
FOR DIRECT SPARK IGNITION (OIL
OR GAS)
COMMON
L2 13 R R
IGNITION
10 TRANSFORMER
LOW FIRE
LINE VOLTAGE 3 14 W W
ALARM 9 MAIN VALVE 1
L2
MODULATE
4 (L1) 15
21 MAIN VALVE 2
LIMITS
6 17
BURNER CONTROL
2
LOCKOUT INTERLOCKS LOW FIRE
(INC. AIR FLOW SWITCH) 7 18
START SWITCH
1 120V, 50/60 Hz (EC7840L 220-240 VAC) POWER SUPPLY.
10 SEC. INTERRUPTED 8 HIGH FIRE PROVIDE DISCONNECT MEANS AND OVERLOAD
PILOT/IGNITION 19
PURGE SWITCH PROTECTION AS REQUIRED.
9 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
RM7800/RM7840L/EC7840L
INITIATE PREPURGE PREPURGE PFEP
(INITIAL HOLD HOLD 10 SEC.
POWERUP 00 DRIVE TO 00 TIMED 00 DRIVE TO 00(4 SEC. IF 10 3 20 25 00 15
ONLY) STANDBY HIGH FIRE PREPURGE LOW FIRE JR1 CLIPPED MFEP RUN POSTPURGE STANDBY
POWER POWER POWER POWER POWER POWER POWER POWER POWER POWER
LED PILOT PILOT PILOT PILOT PILOT
DISPLAY
FLAME FLAME FLAME FLAME FLAME
MAIN MAIN MAIN MAIN MAIN
ALARM ALARM ALARM ALARM ALARM
10 IGN. 5 SEC.
10 SEC. IGN./PILOT 8 2
MV2 21 1
MAIN VALVE 9
FLAME
SAFE START CHECK FLAME PROVING SSC
SIGNAL
SWITCHING 13 TO 15
13 TO 12 13 TO 14 13 TO 14
FIRING
RATE MOTOR ACTION
MOTOR
1 MV2 IS MAIN VALVE CLOSEST TO THE BURNER. 3 RM7840L1091 HAS A FOUR SECOND MFEP.
Fig. 4. Wiring subbase and sequence for RM7800L/40L, EC7840L with Valve Proving feature enabled.
66-1162—05 10
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
BEFORE
HF T19 FINISH
CLOSED 5 3
PURGE
4 SEC. 3 SEC. TEST TIME 4 SEC. 3 SEC. TEST TIME IGNITION TRIALS
CONTROLLER L1-17
AIRFLOW 17-7
MV2 (21)
MV1 (9)
VPS (16) 1 VPS (16) 2
PII (20) PII (20) PII (20)
POST FINISH POST
AFTER PURGE 4
PURGE
RUN 4 SEC. 3 SEC. TEST TIME 4 SEC. 3 SEC. TEST TIME STANDBY
CONTROLLER L1-17
L1-7
MV2 (21) MV1 (9)
VPS (16) 1 VPS (16) 2
PII (20) PII (20)
HF T19 FINISH POST
CLOSED POST PURGE PURGE
SPLIT 3 4
4 SEC. 3 SEC. TEST TIME BURNER RUN TIME 4 SEC. 3 SEC. TEST TIME STANDBY
CONTROLLER L1-17
LOCKOUT INTERLOCKS L1-7
MV1 (9) MV2 (21)
VPS (16) 2 VPS (16) 1
PII (20) PII (20)
1 LOCKOUT IF ON, MV1 LEAKING (LOW PRESSURE TEST). 3 TEST IS RUN CONCURRENT WITH PRE PURGE TIME.
2 LOCKOUT IF OFF, MV2 LEAKING (HIGH PRESSURE TEST). 4 TEST IS RUN CONCURRENT WITH POSTPURGE, IF POSTPURGE TIME IS ENABLED.
Fig. 5. RM7800L/40G,L and EC7840L Relay Module operation, Valve Proving test options.
11 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
SERIES 90
FIRING RATE SERIES 90
Q7800 MOTOR CONTROLLER
HIGH FIRE
G 12 B B
COMMON
L2 13 R R
LOW FIRE
120V ALARM 3 14 W W
MODULATE
4 (L1) 15
RM7840G
INITIATE PREPURGE PFEP
(INITIAL HOLD 10 SEC.
POWERUP 00 TIMED 00 DRIVE TO 00(4 SEC. IF 10 20 25 00 15
ONLY) STANDBY PREPURGE LOW FIRE JR1 CLIPPED MFEP RUN POSTPURGE STANDBY
POWER POWER POWER POWER POWER POWER POWER POWER POWER
LED PILOT PILOT PILOT PILOT PILOT
DISPLAY
FLAME FLAME FLAME FLAME FLAME
MAIN MAIN MAIN MAIN MAIN
ALARM ALARM ALARM ALARM ALARM
10 IGN. 5 SEC.
10 SEC. IGN./PILOT 8
1 21
MAIN VALVE 9
RM7840G SWITCHING 13 TO 15
13 TO 12 13 TO 14 13 TO 14
FIRING
RATE MOTOR ACTION
MOTOR
M24169B
1 15/30 SEC. INTERRUPTED/INTERMITTENT PILOT VALVE
Fig. 6. Typical wiring subbase and sequence for RM7840G without Valve Proving enabled.
66-1162—05 12
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
SERIES 90
FIRING RATE SERIES 90
Q7800 MOTOR CONTROLLER
HIGH FIRE
G 12 B B
FOR DIRECT SPARK IGNITION (OIL
OR GAS)
COMMON
L2 13 R R
IGNITION
10 TRANSFORMER
LOW FIRE
120V ALARM 3 14 W W
L2
9 MV1
MODULATE
4 (L1) 15
21 MV2
BURNER MOTOR VALVE PROVING 4
(BLOWER) 5 16 SWITCH 2
RECYCLE LIMITS
6 17
BURNER CONTROLLER
3
F 22
FLAME DETECTOR
L1
(HOT)
3 1
L2
MASTER M24095
SWITCH
13 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
RM7840G
INITIATE PREPURGE PFEP
(INITIAL HOLD 10 SEC.
POWERUP 00 TIMED 00 DRIVE TO 00(4 SEC. IF 10 20 25 00 15
ONLY) STANDBY PREPURGE LOW FIRE JR1 CLIPPED MFEP RUN POSTPURGE STANDBY
POWER POWER POWER POWER POWER POWER POWER POWER POWER
LED PILOT PILOT PILOT PILOT PILOT
DISPLAY
FLAME FLAME FLAME FLAME FLAME
MAIN MAIN MAIN MAIN MAIN
ALARM ALARM ALARM ALARM ALARM
10 IGN. 5 SEC.
10 SEC. IGN./PILOT 8 1
MAIN VALVE 2 21 2
MAIN VALVE 1 9
RM7840G SWITCHING 13 TO 15
13 TO 12 13 TO 14 13 TO 14
FIRING
RATE MOTOR ACTION
MOTOR
M24096B
1 JR3 REMOVED FOR PILOT SEQUENCE 2 MV2 IS MAIN VALVE CLOSEST TO THE BURNER
Fig. 7. Typical wiring subbase and sequence for RM7840G with Valve Proving enabled.
66-1162—05 14
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
WIRING
SUBBASE
RUN/TEST
SWITCH HONEYWELL
RELAY
MODULE
CONFIGURATION
JUMPERS
PURGE
TIMER
SEQUENCE
STATUS
LED PANEL
POWER
RESET
PILOT
BUTTON
FLAME
MAIN
ALARM
KEYBOARD CAPTIVE
RESET
DISPLAY MOUNTING
MODULE SCREW
(STANDARD ON
RM7800E,G,L,M)
BURNER CONTRO
L FLAME
AMPLIFIER
SCROLL
MODE
- SAVE -
M16353
The Valve Proving System feature provides a systematic way After—Valve Proving occurs after the Run state before the
of testing the valve seat integrity to assure the valves are in internal Safety Relay dropout state and concurrent with
the closed state whenever the sequence of operation requires Post Purge (if configured).
them to be closed. It is designed to detect a leak greater than
0.1% of the burner input capacity. For example, a 10 million Both—Valve proving occurs at both times Before and After
Btu/hr natural gas-fueled burner would have a fuel input noted above.
capacity of approximately 1,000 ft3/hr. A leak rate greater than
0.1% of 1,000 ft3/hr or 1 ft3/hr in either valve will be detected Split—The downstream seat (high pressure) test is per-
with the Valve Proving System. Smaller leaks will not be formed at the Before time and the upstream seat (low
detected. pressure) test is performed during the After time.
At commissioning time, the Valve Proving System may be The Valve Proving items programmed are:
scheduled to occur at one of five different times: Never,
Before, After, Both, and Split. 1. Specify when to perform Valve Proving. Demand input
to terminal 17 actually enables the function of Valve
Never—Device default as received: in this case Valve Proving.
Proving does not occur. 2. Specify the time duration of the test (calculated from
Appendix A).
15 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Typical Valve Proving System C. Thereafter, the VPS is monitored for the duration of the
valve proving test time and, if it turns on, then a lockout
Function occurs. (Because the gas pressure has increased due to a
Valve proving consists of monitoring the pressure in the space leaky upstream valve.) (Low pressure test.)
between two shutoff valves, MV1 (upstream) and MV2
(downstream). The valve proving function, identified by letters D. MV1 is commanded to be open while MV2 remains
A through F, operates as follows: closed, to pressurize the space. After 4 seconds, MV1 is
commanded closed again.
The tolerance on all valve proving timing values is ±10%.
E. This is followed by a three second delay, during which
The following are steps performed during valve proving tests. the valve proving pressure switch (VPS) is ignored.
This section is for background information and does not define
the exact behavioral requirements. F. Thereafter, the VPS is monitored for the duration of the
valve proving test time and, if it turns off, then a lockout
A. MV2 is commanded to be open while MV1 remains occurs. (Because the gas pressure has decreased due to a
closed; to depressurize the space. After 4 seconds, MV2 is leaky downstream valve.) (High pressure test.)
commanded closed again.
B. This is followed by a three second delay during which Pressure Switches for Valve Proving
the valve proving pressure switch (VPS) is ignored. System
The Valve Proving System requires a pressure switch to be
installed to monitor the pressure in the internal space between
the two shutoff valves. Recommended pressure switches are
the following Honeywell non-manual reset models:
66-1162—05 16
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
System operation requires the Valve Proving function setup NOTE: This screen sets up when to do the Valve Proving Test.
and demand input must be connected to terminal 17.
8. Use the up/down arrows to select from Never, Before,
NOTE: The S7800A1142 Keyboard Display is NOT supplied After, Both, or Split, then press ENTER.
on RM7840G,L or EC7840L device.
NOTE: Use Never (as shipped) on initial startup so gas line
When the RM7800L/40G,L, EC7840L is installed and purging and System Checkout can be performed.
powered, “STANDBY” will be shown on the first line of the Then come back to set final operation configuration.
display. Be sure to conduct final VPS System checkout when
Setup is complete.
1. Scroll down until the “Setup” is displayed in the second
line. (Setup is only available when the control is in
Standby or Lockout state.)
=Save changes
=Restart
STANDBY
Setup BACK
Edit: - + ENTER
BACK M22665B
Edit: - + ENTER
Fig. 13. Save Changes screen.
M22662B
9. Use the down arrow to save changes. After pressing the
Fig. 9. STANDBY/Setup screen. down arrow, “Getting Data” is displayed.
2. Enter the Setup submenu by pressing the far right key on the
display. Note that the second line now reads “BC Password”.
SETUP: ValveProve SU
±VP Time: 00:00
STANDBY SU
± BC Password: 00 BACK
Edit: - + ENTER
BACK M22666B
Edit: - + ENTER
Fig. 14. Valve Prove time screen.
M22663B
This screen sets up how long the RM7800L/40G,L, EC7840L
Fig. 10. Password screen. will conduct the Valve Proving Test for a given time. VP TIme:
3. Use the +/- buttons to enter the first number—7. 00:00 is shown.
4. Use the far right key to shift over one space. 10. Enter the appropriate Valve Proving test time from the
5. Use the +/- buttons to enter the second number—8. worksheet in the appendix.
6. Press Enter (left/right arrow simultaneously).
Use the (+) button to increase time and the (-) button to
decrease. Time changes:
a. 0 to 60 seconds in 1-second intervals.
=Select b. 60 to 600 seconds in 10-second intervals.
=Restart c. 10 to 60 minutes in 1-minute intervals.
BACK
Press ENTER when correct time is displayed.
Edit: - + ENTER
M22764B
=Save changes
Fig. 11. Select/Restart screen. =Restart
7. To get to the next screen, press the down arrow. “Get-
ting Data” will be displayed, then the following screen. BACK
Edit: - + ENTER
M22665B
SETUP: ValveProve SU
± VP When: BEFORE Fig. 15. Save Changes screen.
BACK
Edit: - + ENTER
M22664B
17 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
=Select CONFIRM:ValvProve SC
=Restart ±VP When: BEFORE ?
BACK BACK
Edit: - + ENTER Edit: - + ENTER
M22764B M22670B
Fig. 16. Select/Restart screen. Fig. 19. Confirmation Acknowledgement screen. (The
11. Press down arrow to select. Valve Proving Test location is shown.)
12. “Getting Data” will be momentarily displayed, followed
by the screen shown in Fig. 12. 16. Press ENTER.
BACK M22671B
Edit: - + ENTER
Fig. 20. Confirmation Correct screen.
M22668
BACK BACK
Edit: - + ENTER Edit: - + ENTER
M22665B M22671B
Fig. 18. Save Changes screen. Fig. 22. Confirm Correct screen.
15. Use the down arrow to save changes. “Getting Data” is 19. Use the down arrow to confirm correct.
displayed momentarily. “Getting Data” will be displayed.
The following steps are to confirm your selections.
The following steps are used to confirm your selection.
66-1162—05 18
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
19 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
66-1162—05 20
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
d. Flame must be proven by the end of the ten-second a. Terminal 9 and 21 are energized when the presence
PFEP (four-seconds if JR1 is clipped). If flame is not of flame is verified at the end of a 10- second Pilot
proven by the end of the PFEP, a safety shutdown Flame Establishing Period (PFEP) (four seconds if
occurs. JR1 is clipped).
2. Main Flame Establishing Period (MFEP): b. Terminal 8 is turned off 10 seconds after Terminal 9
a. Terminal 9 is energized when the presence of flame and 21 are energized. (4 seconds for
is verified at the end of a 10-second Pilot Flame RM7840L1091)
Establishing Period (PFEP) (four seconds if JR1 is c. The RM7800L/40G, L, EC7840L releases to modu-
clipped). lation (RUN) 15-seconds terminal 9 and 21 are
b. Terminal 8 is turned off 10 seconds after Terminal 9 energized if flame is present.
is energized. (4 seconds for RM7840L1091)
c. Terminal 21 action: Ignition Trials—Valve Proving with DSI
(1) RM7800/40L, EC7840L - turned off15-seconds
after Terminal 9 is energized. System
(2) The RM7840G: 1. Demand connected to Terminal 17:
(a) Not turned off, (intermittent pilot) — JR2 Intact on RM7800L/40L, EC7840L
(b)Turns off 15-seconds after Terminal 9 is ener- — JR3 Intact on RM7840G
gized (if configuration jumper 2 removed); a. Ignition, Main Valve 1 and Main Valve 2, Terminals
(c)Turns off 30-seconds after Terminal 9 is ener- 10, 9, and 21 turn on together.
gized (if configuration jumper 2 removed and b. Flame must be proven at the end of the 4 second
terminal 5 is jumpered to terminal 19). Main Flame Establishing Time.
d. The RM78XX releases to modulation (RUN) 15-sec- c. Ignition, Terminal 10 is turned off. System now in
onds (30 seconds for RM7840G with terminal 5 to 19 Run.
jumpered) after terminal 9 is energized if flame is d. If Flame is not proven, safety lockout occurs.
present.
Run
Valve Proving Ignition Trials (demand on 1. A ten-second stabilization period occurs at the
terminal 17) -Pilot Lighted System (Not VP beginning of the RUN period.
2. The firing rate motor releases to modulation.
DSI). (Configuration jumper 2 on RM7800L/ 3. The RM7800L/40G,L, EC7840L is now in RUN and
40L, EC7840L or Jumper 3 on RM7840G remains in RUN until the controller input, terminal 6,
MUST be removed). opens (terminal 17, on VP applications), indicating that
the demand is satisfied or a limit opened.
1. Pilot Flame Establishing Period (PFEP):
a. With the firing rate motor at the low fire position
(Low Fire Start Switch-terminal 18 enabled): Postpurge
b. Terminals 8, 10, are energized. The RM7800L/40G,L, EC7840L provides a programmable
(default is 15 seconds) POSTPURGE following the
NOTE: Low Fire Start Switch-terminal 18 enabled completion of the RUN period. The blower motor output is
must remain closed until the RM7800L/40G, L, powered to drive all products of combustion and any
EC7840L releases to modulation - or a safety unburned fuel from the combustion chamber. It also supplies
shutdown will occur. combustion air to burn fuel being purged from the fuel line
downstream of the fuel shutoff valve.
The Pre-Ignition Interlock input is ignored
throughout the Ignition Trial state. 1. The main fuel valve and intermittent pilot valve,
Terminals 9 and 21, are de-energized and the firing rate
c. After five seconds, the ignition, terminal 10, is de- motor is commanded to the low fire position to begin the
energized for early spark termination. POSTPURGE period.
d. Flame must be proven by the end of the ten-second 2. The Pre-Ignition Interlock closes within the first five
PFEP (four-seconds if JR1 is clipped). If flame is not seconds after the demand opens.
proven by the end of the PFEP, a safety shutdown 3. If Valve Proving option—After, Split or Both have been
occurs. selected, then the Valve Proving test will be conducted
2. Main Flame Establishing Period (MFEP): concurrent with Postpurge. If Postpurge timing remains
after the Valve Proving test is completed, the Postpurge
timing will complete before the RM7800/40G,L,
EC7840L go into standby.
21 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
66-1162—05 22
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
STATIC CHECKOUT
WARNING
After checking all wiring, perform this checkout before Explosion and Electrical Shock Hazard.
installing the RM7800L/40G,L, EC7840L on the subbase. Can cause serious injury, death or equipment
These tests verify the Q7800 Wiring Subbase is wired damage.
correctly, and the external controllers, limits, interlocks, 1. Close all manual fuel shutoff valve(s) before starting
actuators, valves, transformers, motors and other devices are these tests.
operating properly. 2. Use extreme care while testing the system. Line
voltage is present on most terminal connections
when power is on.
3. Open the master switch before installing or
removing a jumper on the subbase.
4. Before continuing to the next test, be sure to
remove test jumper(s) used in the previous test.
5. Replace all limits and interlocks that are not
operating properly. Do not bypass limits and
interlocks.
23 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
5. For each test, open the master switch and install the
CAUTION jumper wire(s) between the subbase wiring terminals
listed in the Test Jumpers column.
Equipment Damage Hazard. 6. Close the master switch before observing operation.
Improper testing can damage equipment. 7. Read the voltage between the subbase wiring terminals
Internal surge protectors can break down and conduct listed in the Voltmeter column.
a current, causing the RM7800L/40G,L, EC7840L to 8. If there is no voltage or the operation is abnormal, check
fail the dielectric test or possibly destroy the internal the circuits and external devices as described in the last
lightning and high current protection. Do not perform a column.
dielectric test with the RM7800L/40G,L, EC7840L 9. Check all wiring for correct connections, tight terminal
installed. screws, correct wire, and proper wiring techniques.
Replace all damaged or incorrectly sized wires.
Equipment Recommended 10. Replace faulty controllers, limits, interlocks, actuators,
valves, transformers, motors and other devices as
1. Voltmeter (1M ohm/volt minimum sensitivity) set on the required.
0-300 Vac scale. 11. Make sure normal operation is obtained for each
2. Two jumper wires; no. 14 wire, insulated, 12 inches required test before continuing the checkout.
(304.8 mm) long with insulated alligator clips at both 12. After completing each test, be sure to remove the test
ends. jumper(s).
3. Ammeter can be used to verify valve loads connected to
the wiring subbase.
WARNING
General Instructions Explosion Hazard.
1. Perform all applicable tests listed in Static Checkout, Can cause serious injury or death.
Table 8, in the order listed. Make sure all manual fuel shutoff valves are closed
2. Make sure all manual fuel shutoff valve(s) are closed. before performing static checkout.
3. Perform only those tests designated for the specific
RM7800L/40G,L, EC7840L model being tested.
4. Raise the setpoint of the operating controller to simulate
a call for heat.
66-1162—05 24
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
25 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
TROUBLESHOOTING slow blinks identify the units portion of the fault code (two slow
blinks is 2). Three fast blinks followed by two slow blinks
would be fault code 32. (See Table 10 for Blink Fault Code
Troubleshooting can be accomplished by using the S7800 list.)
Keyboard Display Module (KDM) or a blinking POWER LED.
The LED code repeats as long as the fault exists. To clear the
The POWER LED provides fault identification when the relay fault, press the RESET button.
module locks out on an alarm. Fault identification is a series of
fast and slow blinking LED lights. The fast blinks identify the Use Table 10 to identify fault code numbers, possible system
tens portion of the fault code (three fast blinks is 30), while the failure and recommended troubleshooting procedures.
Code 2-3 Flame signal value is 1. Make sure the flame detector and flame amplifier are compatible.
*Flame Signal too high to be valid. 2. Remove the flame amplifier and inspect its connections. Reset the flame
Overrange* amplifier.
3. Reset and sequence the relay module.
4. Check the flame detector sighting position; reset and recycle. Measure flame
strength. Verify that it meets specifications. If not, refer to the flame detector
and/or flame amplifier checkout procedures in the installation instructions.
5. If the code reappears, replace the flame amplifier and/or the flame detector.
6. If the fault persists, replace the relay module.
Code 3-1 Running or Lockout 1. Check wiring; correct any errors.
*Running/ Interlock fault during 2. Inspect the fan; make sure there is no air intake blockage and that it is supply-
Interlock Switch Pre-Purge. ing air.
Problem* 3. Make sure the Lockout Interlock switches are functioning properly and the
contacts are free from contaminants.
4. Reset and sequence the relay module to Pre-Purge (place the TEST/RUN
Switch in the TEST position, if available). Measure the voltage between
terminal 7 and G (ground); line voltage should be present. Switch TEST/RUN
back to RUN.
5. If steps 1 through 4 are correct and the fault persists, replace the relay module.
66-1162—05 26
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
27 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
66-1162—05 28
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
APPENDIX A
Valve Proving Test
The Valve Proving System feature offers a systematic way of 3. Use appropriate Results column items to fill in the Valve
testing the valve seat integrity to assure the valves are indeed in Train Volume Formula and the Calculation of Valve
the closed position when the system is off-line, in STANDBY. Proving Test Time.
4. Round up the time to the nearest second.
5. The test time calculated is the time you will enter into
WARNING the VPS Setup.
Explosion Hazard.
Can cause severe injury, death or property damage. Calculation of Valve Train Volume
Leaking gas valves can result in fire or explosion. The X = V1 + V2 + (A X L/144)
Valve Proving System is designed to detect such
leaks. A valve proving test time that is too short may
allow unacceptable leaks to go undetected. Use the Calculation of Valve Proving Test
procedure in Appendix A to select sufficient valve test
times to detect any unacceptable leak. Time
Test Time = 187,000 x (P x X)/C
The following steps are to determine the test time for the relay
module to verify the valve seats are not leaking at a rate of Table 11. Valve Proving Test Time Symbols
greater than/equal to 0.1% of the burner capacity. and Descriptions.
Fig. 29 shows a typical valve train. The legend identifies Symbol Unit Description
information that will be used to fill out the worksheet that
appears at the end of this appendix. X ft 3 Volume between the two valves to be
tested.
1. Identify items of your system and fill in the “Information” V1 Volume of upstream valve outlet cavity.
ft3
portion of the worksheet.
2. Go to the Lookup Tables noted (13, 14 or 15) to get the V2 ft3 Volume of downstream valve inlet cavity.
results for your system.
L ft Length of pipe between valves.
IMPORTANT D npt Pipe Size—used to define A
The Tables show information on Honeywell Valves
only. Contact other valve manufacturers to obtain A in.2 Pipe Cross Section Area (from Table 15)
data on their specific valves. Test Seconds Minimum VPS test period.
Time
V1 V2
P psi Gas inlet pressure to upstream valve.
VP C ft 3/hr Burner Capacity.
D SW.
P
NOTE: V1 is the outlet cavity of the upstream valve and V2
INLET OUTLET
is the inlet cavity of the downstream valve.
L
C NOTE: 10 seconds is the minimum test time allowed. If your
X calculations are less than 10 seconds, enter 10
LEGEND seconds.
V1 UPSTREAM VALVE
V2 DOWNSTREAM VALVE For Example:
D PIPE DIAMETER (IN INCHES.) USED TO DETERMINE A;
ARE FOUND IN TABLE III We have a 2.5 MBTU burner with 2 psi valve train inlet
L PIPE LENGTH (IN FEET)
P VALVE INLET PRESSURE (PSIG)
pressure. The upstream valve is a proof-of-closure V5044 with
C BURNER MAX. FIRING (CFH) a solenoid V4295 valve downstream. We have a 2 in. NPT
X CALCULATED TEST VALVE TRAIN VOLUME M22778 pipe, 1-3/4 ft long, between the valves.
Fig. 28. Typical valve train layout.
29 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
66-1162—05 30
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
31 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Column 2 lists the figure letter that shows the connections for that option. The figure letters refer to the figures on pages 30–32.
Column 3 refers to the fuel changeover switch and how many connections or poles that would be required.
66-1162—05 32
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
A. NO VP/SINGLE FUEL: L2 T7
M24098A
OP.
OIL
LIMITS CONTROL
INTERLOCKS
L1 T6 T8 T8
PV
T21 T21 PV
T17 1 1
INTERLOCKS
T9
T7 GAS MV
MV
T9
1 RM7840G - CLIP JR2 L2
B. NO VP/SINGLE FUEL M24099A
OIL MV
OP. L2
LIMITS CONTROL 1 RM7840G CLIP JR2
L1 T6 T8
F. NO VP/DUAL FUEL: GAS 10 SECOND MFEP, OIL 15 SECOND MFEP
M24123
T17 T21 1
INTERLOCKS
T9 OP.
T7 LIMITS CONTROL
MV
L2 L1 T6
1 RM7840G - CONNECT DIRECTLY TO TERMINAL 21.
M24120
C. NO VP/SINGLE FUEL: DSI GAS IF EA IS USED THEN
INTERLOCKS GAS/OIL SWITCHING IS
ALSO NEEDED HERE.
OP.
LIMITS CONTROL
L1 T6 T7
IF EA IS USED THEN
GAS
GAS/OIL SWITCHING IS
INTERLOCKS OIL
ALSO NEEDED HERE.
INTERLOCKS
T8
T7 PV
T21
1
OIL INTERLOCKS
GAS MV
T9
T8
PV OIL MV
T21
L2
1 RM7840G CLIP JR2.
GAS MV
T9
G. NO VP/DUAL FUEL: GAS 15 SECOND MFEP, OIL 10 SECOND MFEP
M24124A
OIL MV
L2 OP.
LIMITS CONTROL
D. NO VP/DUAL FUEL: BOTH 10 SECOND MFEP M24121A
L1 T6
OP. GAS IF EA IS USED THEN
LIMITS CONTROL
INTERLOCKS GAS/OIL SWITCHING IS
L1 T6 ALSO NEEDED HERE.
IF EA IS USED THEN
GAS
GAS/OIL SWITCHING IS
INTERLOCKS T7
ALSO NEEDED HERE.
T7
OIL
INTERLOCKS
OIL INTERLOCKS
T8 PV
1
T8 T21
1 PV
T21
GAS MV
T9
GAS MV
T9
OIL MV
OIL MV L2
L2 RM7840G: A SEPARATE POLE NEEDED TO CONNECT OIL MV TO
1
RM7840G CLIP JR2 TERMINAL 21.
1
H. NO VP/DUAL FUEL: GAS 10 SECOND MFEP, OIL DSI
M24122A M24125A
E. NO VP/DUAL FUEL: 15 SECOND MFEP
33 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
OP. OP.
LIMITS CONTROL LIMITS CONTROL
L1 T6 T6
L1
GAS IF EA IS USED THEN IF EA IS USED THEN
GAS
INTERLOCKS GAS/OIL SWITCHING IS GAS/OIL SWITCHING IS
INTERLOCKS
ALSO NEEDED HERE. ALSO NEEDED HERE.
T7 T7
OIL T8
OIL
INTERLOCKS INTERLOCKS
1 T21
T8 PV GAS MV
T9
T21
OIL MV
GAS MV L2
T9
1 RM7840: NO JUMPER - SWITCH FUEL OFF TERMINAL 21.
OIL OP.
INTERLOCKS LIMITS CONTROL
L1 T6 T8
T8 PV
T17
1
INTERLOCKS T21
T21
T7 MV2
GAS MV
T9 WHEN JR2 IS INTACT THEN GAS
T9
DSI IS ENABLED WHENEVER A
JR2 INTACT MV1
VALVE PROVING DEMAND IS
OIL MV PRESENT ON T17. L2
L2 RM7840G IS JR3 INTACT.
1 RM7840G: REQUIRES SEPARATE POLE TO CONNECT GAS MV TO N. VP/GAS ONLY DSI M24131A
TERMINAL 21.
J. NO VP/DUAL FUEL: GAS DSI, OIL 10 SECOND MFEP M24127A OP.
LIMITS CONTROL GAS
T17
OP. L1
LIMITS CONTROL T6
OIL
L1 T6 IF EA IS USED THEN
GAS
GAS IF EA IS USED THEN INTERLOCKS GAS/OIL SWITCHING IS
INTERLOCKS GAS/OIL SWITCHING IS ALSO NEEDED HERE.
ALSO NEEDED HERE.
OIL T7
T7 INTERLOCKS
T8
OIL
PV
INTERLOCKS
T21
T8 PV GAS MV2
66-1162—05 34
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING
OP. OP.
LIMITS CONTROL GAS LIMITS CONTROL GAS
T17 T17
L1 L1
T6
T6 OIL
OIL IF EA IS USED THEN
IF EA IS USED THEN GAS GAS/OIL SWITCHING IS
GAS
INTERLOCKS ALSO NEEDED HERE.
INTERLOCKS GAS/OIL SWITCHING IS
ALSO NEEDED HERE.
OIL
T7
INTERLOCKS
OIL T7
INTERLOCKS
THE SOFTWARE DOES
NOT ENERGIZE T8 T8
T8 WHEN GAS IS PV
SELECTED AND T21
PV
JUMPER 2 (JUMPER 3
T21 ON RM7840G) IS INTACT
1 TO INDICATE GAS DSI GAS MV2
FOR A VALVE PROVING
GAS MV2
SYSTEM.
GAS MV1
T9
GAS MV1
T9 JR2 INTACT OIL MV
L2
JR2 CLIPPED R. VALVE PROVING: GAS DSI, OIL 10 SECOND MFEP M24134A
OIL MV
L2 OP.
1 RM7840G: CLIP JR2 AND JR3. LIMITS CONTROL GAS
T17
P. VALVE PROVING/DUAL FUEL: GAS 10 SECOND MFEP, OIL 15 SECOND MFEP L1
T6
M24133B OIL
IF EA IS USED THEN
OP. GAS GAS/OIL SWITCHING IS
LIMITS CONTROL GAS INTERLOCKS ALSO NEEDED HERE.
T17
L1
T6 OIL
T7
OIL INTERLOCKS
GAS IF EA IS USED THEN
INTERLOCKS GAS/OIL SWITCHING IS THE SOFTWARE DOES
ALSO NEEDED HERE. NOT ENERGIZE T8 T8
WHEN GAS IS PV
SELECTED AND T21
OIL T7 JUMPER 2 (JUMPER 3
INTERLOCKS ON RM7840G) IS INTACT 2
GAS MV2
TO INDICATE GAS DSI
FOR A VALVE PROVING
T8 SYSTEM.
PV GAS MV1
T9
JR2 INTACT
OIL MV
L2
T21
1 2 RM7840G: CLIP JR2.
GAS MV2
S. VALVE PROVING/DUAL FUEL: GAS DSI, OIL 15 SECOND MFEP. M24135A
OIL
T7
THE SOFTWARE DOES INTERLOCKS
NOT ENERGIZE T8 T8
WHEN GAS IS
SELECTED AND T21
JUMPER 2 (JUMPER 3
ON RM7840G) IS INTACT
1 GAS MV2
TO INDICATE GAS DSI
FOR A VALVE PROVING
SYSTEM.
GAS MV1
T9
JR2 INTACT
OIL MV
L2
1 RM7840G: CONNECT OIL VALVE DIRECTLY TO TERMINAL 21
SIDE OF FUEL SWITCH - DO NOT USE THE JUMPER.
T. VALVE PROVING/DUAL FUEL: DSI FOR GAS AND OIL M24136A
35 66-1162—05
RM7800L1087; RM7840G1022,L1075,L1091; EC7840L1014 RELAY MODULES WITH VALVE PROVING