You are on page 1of 5

Location = Odiongan, Romblon

Temperatures English SI

Windy Outdoor to 0 ºF 0.00 °C LEGENDS:


Windy Indoor ti 0 ºF 0.00 °C - Input Data For leakage:
Sum. Outdoor todb 82 ºF 27.50 °C - Constant Data
towb 82 ºF 27.50 °C
Sp. Hum. #VALUE! Lbw/Lba MISCELLANEOUS FILES:
Rel. Hum. #VALUE! %
Sum. Indoor tidb 66 ºF 19.00 °C Psychrometric Chart - ASHRAE.PDF
tiwb 61 ºF 16.00 °C
Sp. Hum. #VALUE! Lbw/Lba where:
Rel. Hum. #VALUE! % U- Heat Transmission Coefficient
Daily Range DR 0 ºF 0.00 °C Qc - Cooling Load
Sens. Heat Ratio SHR 0.7 Qh - Heating Load
CLTD - Cooling Load Temperature Difference
Floor Area Aflr 1614.74 sq. ft. 150.091482 sq. m. SC - Shading Coefficient
Avg. Height CeilHt 9.843 ft. 3.00091463 m GLF - Gain Load Factor
Elevation Elev 31.8 ft 9.70 m
Latitude Lat 12.4047 ºN
Building Leakage 2 Tight = 1 Medium=2 Loose =3

Zone 1 Other source of data

Windows U (4) SC (4) GLF (5) Area (sf) qc (Btu/h) qh(Btu/h)


North 0 0 0.000 0 0.00 0.00
NE 0.55 0.36 18.217 364.2864 6636.1 0.0
East 0 0 0.000 0 0.00 0.00
SE 0.55 0.36 18.217 75.57 1376.6 0.0
South 0 0 0.000 0 0.00 0.00
SW 0.55 0.36 18.217 131.7632 2400.3 0.0
West 0 0 0.000 0 0.00 0.00
NW 0.55 0.36 18.217 40.466 737.2 0.0
Horz. 0 0 0.000 0.0 0.0

Walls U CLTD (6)


North 0 18.3 0 0.00 0.00
NE 0.49 24.3 231.231 2753.3 0.0
East 0 28.3 0 0.00 0.00
SE 0.49 26.3 200.879 2588.7 0.0
South 0 21.3 0 0.00 0.00
SW 0.49 26.3 352.66 4544.7 0.0
West 0 28.3 0 0.00 0.00
NW 0.49 24.3 282.4821 3363.5 0.0

Doors U CLTD (6)


North 0 18.3 0 0.0 0.0
NE 0 24.3 0 0.0 0.0
East 0 28.3 0 0.00 0.00
SE 0.25 26.3 46.5 305.7 0.0 For Infiltration :
South 0 21.3 0 0.0 0.0 ACH = (k)(NL)
SW 0 26.3 0 0.0 0.0 Where:
West 0 28.3 0 0.00 0.00 k = 1.44 s/hr.m)(0.0073 min/hr.ft
NW 0 24.3 0 0.0 0.0 NL = 1000(ELA/Floor area) (No. of story) from ASTM E779 (2003)
ELA (Effictive leakage area)
Roof/Ceiling U CLTD (6) NL (Normalized leakage) ASHRAE (Standard 119, 1998)
Roof 1 0.033 52.3 1614.7442 2786.89 0.00
Roof 2 0.0 0.0 For summer indoor:
tiwb - 16 degree celsius is the average temperature used for indoor AC (Thermal comfort)
Partition U CLTD (6)
(To Unc. Space) 19.18 0.0 0.0 For heat transmission coefficient (Wall):
Material Thickness Density (lb/cu.ft) Weight (lb/sq.ft) Resistance ®
Crawl Space U CLTD (6) Air film 0.25
(or floor garage) 19.18 0.0 0.0 Cement plaster 0.5 116 4.8 0.1
CHB 6 64 32 0.91
Slab R (ins) UP CLTD (7) Perimeter Cement plaster 0.5 116 4.8 0.1
0.5 1614.744 0.00 Still air 0.68
TOTAL 7 296 41.6 2.04
Infiltration ACH Vol cfm
Windy 0 0 0 0.00 U = 1/R
Summer 0.42 15893.9 111 0.00 U= 0.49019608

People Btu/h-per Number


230 15 3450.00

Internal (AVG) Btu/h Watts


Kitchen/Laundry 0 0.00
Other (in watts) 300 1023.60

Sensible
Cool Subtotal 31966.72
Heat Subtotal 0.00
Clg.Fac Htg.Fac
Duct 0 0 0.00 0.00

Sensible
Cool Total 31966.72
Heat Total 0.00

Net Total
Cooling Hp 17.95
Heating Hp 0.00

Residential Heating and Cooling Load Calculation - 2001 ASHRAE Fundamentals


Handbook
(Implemented by Dr. Steve Kavanaugh)
Insulation Cooling Gains Heating Losses
Duct Location (hr-ft-F/Btu) Supply Return Supply<120 FSupply>120 F Return
Outdoors, open to well vented None 0.25 0.15 0.25 0.3 0.15
space, uninsulated, R2 0.15 0.08 0.15 0.2 0.08
unconditioned space R4 0.1 0.06 0.1 0.15 0.06
R6 0.05 0.03 0.05 0.1 0.03

Ducts located in enclosed, None 0.2 0.12 0.2 0.25 0.12


insulated, unconditioned, R2 0.1 0.06 0.1 0.15 0.06
unvented spaces R4 0.05 0.03 0.05 0.1 0.03
R6 0.03 0 0.03 0.05 0

None 0.1 0 0.1 0.15 0


Ducts located in return air R2 0.05 0 0.05 0.1 0
ceiling plenum R4 0.03 0 0.03 0.08 0
R6 0 0 0 0.03 0

None 0.1 0.06 0.1 0.15 0.06


Ducts buried in or under R2 0.05 0.03 0.05 0.1 0.03
concrete slab R4 0.03 0 0.03 0.08 0
R6 0 0 0 0.03 0

Ducts in conditioned space or 0 0 0 0 0


stubbed up in space, short run Any 0 0 0 0 0

Cooling Heating Factors


Factor
Table 5 - Shading Coefficients and U-Factors for Residential Windows

Drapes, Venetian Blind,


or Translucent Roller Opaque Roller
None Shade Shade
Glass Type SC U SC U SC U
Single 1.00 1.04 0.50 0.81 0.38 0.81
Double 0.88 0.61 0.45 0.55 0.36 0.55
Heat Absorbing 0.58 0.45 0.37 0.44 0.33 0.44
Triple 0.80 0.44 0.44 0.40 0.36 0.40

Source: ASHRAE Manual - 2001 Fundamentals, The American Society of Heating,


Refrigeration and Air Conditioning Engineers
Notes
1
2
3
4
5
6
7
Weather and climatic information available Table 1A & 1B, Chp. 27, 2001 ASHRAE Fundamental Handbook.
SHR = Sensible Load/Total Load Use: 0.65 for Tropic, 0.70 Humid, 0.75 Avg., 0.80 Dry, 0.85 Arid
Values curve fit fromTables 7 & 8, Chp. 28, 2001 ASHRAE Fundamental Handbook.
See Table 5, Chp. 28, 2001 ASHRAE Fundamental Handbook (reproduced ona another worksheet).
Values curve fit from Table 3, Chp. 28, 2001 ASHRAE Fundamental Handbook.
Values curve fit from Table 1, Chp. 28, 2001 ASHRAE Fundamental Handbook.
See Table 16, Chp. 28, 2001 ASHRAE Fundamental Handbook.