Professional Documents
Culture Documents
Abstract A load sharing control based on the frequency and information such as output frequency and current of other
voltage droop concept for parallel operation of two three-phase systems [3-51. However, the control interconnection lines
Uninterruplible Power Supply (UPS) systems with no control restrict the location of the paralleled systems, cause noise
interconnection lines is presented in this paper. First of all, due disturbance, and hinder the isolation and redundancy of
to the use of active power and reactive power as control
variables, the characteristics of output powers according to
multi-inverter systems.
amplitude and phase differences between output voltages of two To operate independently each UPS system in this paper,
UPS systems are analyzed. Secondly, simulation results with the load sharing control is adapted to the frequency and
different line impedance are demonstrated the feasibility of the voltage droop method except for the variation of output
wireless load sharing control. Finally, experiments are presented power per every sampling time. The output frequency and
to verify the theoretical discussion with two three-phase 2OkVA voltage droops as function of the active and reactive power
UPS systems employed TMS320C32, a kind of real time digital respectively, and each UPS system has no control
signal processor (DSP). interconnection lines except for the power lines.
I
2 . 1 A E = O & q=o
-A
- 2e 2 ) - A E . e-JP
the complex powers A$M and A.$m under the
z' * ( 2 + -z) ( 2 + 7 z*
) amplitude difference AE are derived as follows:
ZL z,
(3)
S2 =vL.i;
527
28-2
Note that the line impedance is dominantly resistive. 2.4 Line Impedance Imbalance
However, the source impedance of the inverter is highly
inductive. Thus the total impedance of the system becomes The line impedance imbalance considerably impacts the
almost purely inductive. output power sharing. To get the characteristics of the power
Consequently, if the reactive power of an UPS system sharing under the line impedance imbalance, we set the line
increases, its amplitude must be decreased for compensating resistance = 0.01[ Q ] and the line inductance = 0.0001[H] of
the reactive power imbalance between two UPS systems. the UPSl, and change the line resistance = 0.01 0.5[Q] -
-
and the line inductance = 0.0001 O.OOS[H] of the UPS2.
2.3AEm=O&p f 0 As can be seen Fig. 2, the output power is very sensitive to
the line impedance imbalance. Therefore, we can know that a
To know the relationship between the phase difference and proper control is required for compensating the imbalance.
the output power, if there is only the phase difference rp and
the amplitude difference AE = O in Eq. (3) and (4), the
complex powers Sl,+, and S2,+, will be obtained as
follows:
5
a
(a) (b)
Fig. 2. Complex Powers of (a) UPSl and (b) UPS2 Under Line Impedance
Imbalance
528
28-2
3.2 Output Power Calculation The control algorithm of the reactive power is as follows:
529
28-2
Q and AQ in Eq. (21). Due to the droop characteristics, in In Fig. 7, the simulation waveforms of the load voltage and
case that the reactive powers of two UPS systems are current, and the output currents for the steady state are
different while parallel operation, the two output voltages illustrated. It can be observed from Fig. 7 that equal current
will drop to such values that both systems will be operating distribution can be achieved regardless of line impedance
in a lower voltage eliminating the reactive power imbalance. imbalance, Z2 is twice as much as Z1.
The Kq2 .AQ term in Eq. (21) is added to the
conventional droop method. It is to minimize the output
voltage drop for the steady state, and to get a fast transient
response.
The droop method is simple to implement. However, in
this case a trade-off must be made between accuracy of
reactive power sharing and output voltage quality. The higher
the reactive power coefficients K q l and K q 2 the better
accuracy of the reactive power sharing. However, higher the
coefficierrts mean a reduction in output voltage quality, As a
result, the coefficients should be decided so that the output
voltage can be within a permission range.
4. SimuRation
IOW
om
F-&J-jj load
4oDD
Z , = 0.1 + j0.038 [a], Z , = 0.2 + j0.075 [Q] , Z,o,,,, = 13 + j9.7 [Q] Fig. 8. The Simulation Results of Active PowersP, and P2 , Reactive Powers
Fig. 6. Configurationof the Simulated System Q, and Qz,and Output Currents il and i2 with the Step Load Variation
530
28-2
In Fig. 9, the simulation results for two parallel UPS Fig. 12 shows the experimental results of the active powers
systems of different power ratings are shown. The power and the output currents when a pure resistant load changes
coefficients K~ and K of each system are set differently. from no load to 7.2[kW], and then to 14.4[kW]. It can be
4
observed from Fig. 12 that a fast transient response and an
As can be seen from Fig. 9, the active and reactive power equivalent active power sharing like the simulation results in
sharing can be controlled by the power coefficients. Fig. 8.
From the simulation results above, the validity of the
Fig. 13 illustrates the experimental results of the active and
control algorithm is proved reactive power when both a resistant load 7.2[kW] and a
reactant load 5.4[kVar] are connected, and disconnected to
the two UPS systems. The transient response of the reactive
power sharing is not so fast. However, totally the error of the
power sharing is within 5 percentages at steady state.
The experiment results above also show the validity of the
control algorithm like those of the simulation.
Fig. 9. The Simulation Results of Active Powers Ip and Zp, and Reactive
Powers Q,and Q2 in Case that the Power Coefficients of Each U P S System
Set Differently
5. Experimental Results
Two UPS systems have been designed and implemented. (2OOV/div, SNdiv, 5msldiv)
The parameters of each system are listed below: Fig. IO. The Experimental Waveforms of Load Voltage V L , Load Current iL ,
and Output Currents il and i2 with No Load
Each system capacity: 20[kVA]
Switching frequency: 5.16[kHz]
DC Link voltage: 265[V]
Output voltage: 3 4 38O[V] / 22O[V], 60[Hz]
LC filters: 400[ p F], 250[ p HI
53 1
28-2
7. References
I I I I I
(2kW/div, 2kVar/div, Is/div)
Fig. 13. The Experimental Results of Active Power 4 and Pz , and Reactive
Power Q, and Q2 when Load is Connected and Disconnected
6. Conclusion
532