Professional Documents
Culture Documents
PRODUCT BROCHURE
—
P C S 10 0 AVC- 4 0 | 1 5 0 k VA TO 3 6 0 0 k VA
—
PCS100 Static Frequency Converter
125 kVA to 10 MVA
PCS100 Static Frequency Converters are commonly used to
interconnect 50 Hz and 60 Hz systems.
—
01 PCS100 SFC diagram
ABB’s PCS100 Static Frequency Converter allows How it works
the interconnection of grid systems with varying The system is constructed of multiple power
frequencies, offering the ideal solution for shore electronic modules and functions by converting
to ship, plant relocation and testing facility the input AC power through a sine-wave rectifier
applications. to a DC link, and then through an AC sine-wave
inverter to produce a clean, full sine-wave output
User benefits at the new frequency and voltage.
– Minimize operating and maintenance costs
– High reliability provides maximum power The PCS100 SFC is extremely flexible in terms of
availability paralleling with other voltage sources, either
– Keeps equipment running through utility generators or multiple SFC units. Parallel load
voltage sags and frequency variation sharing is achieved using frequency and voltage
– N+1 modular redundancy for mission critical droop profiles programmed into the converter.
applications This allows the converters to share power with
– Lowest total cost of ownership other systems without the need for any
– Minimal spares required additional communication signals.
– Easy paralleling to other voltage sources using
droop Starting the SFC into the live bus is greatly
simplified due to the automatic output
Key product features synchronization feature. This enables a full
– High efficiency power conversion seamless transfer from generator supply to SFC
– Clean sinewave output voltage supply on the output bus. If the output bus is
– Unity power factor, sinewave, active rectifier dead when the SFC is given a start command it
design will ramp up the voltage over one second,
– Built-in module redundancy without providing a soft energizing of the output.
interruption of operation
– Fully isolated AC connection using an output
Utility voltage DC bus voltage Load voltage
transformer
– Wide range of voltages available; 50 Hz and
60 Hz
– Small footprint design
– Touch screen colour graphic display (GDM)
– Internal web server and Modbus TCP allows PCS100 SFC
remote monitoring Graphic Ethernet
Display
– Output cable voltage drop compensation module
Control
Master
– Seamless generator change over standard module I/O
(synchronization) CAN
– Generator emulation and load sharing Power modules bus
Output isolation
transformer
—
RectifierI nverter
01
P C S 1 0 0 S F C S TAT I C F R E Q U E N C Y C O N V E R T E R 3
—
Complete grid interconnection
Typical applications
Providing highly reliable clean and efficient frequency conversion.
Visit: www.abb.com/ups
2UCD301089-P_l