You are on page 1of 28

OPGW and ADSS Fiber Cable

For Overhead Transmission Lines


PRYSMIAN GROUP
VISION, MISSION, VALUES

Vision
The Prysmian Group believes
in the effective, efficient
and sustainable supply
of Energy and Information
as a primary driver
in the development
of communities

Mission
The Prysmian Group provides
its customers worldwide
with superior cable solutions
based on pioneering technology
and consistent excellence in
execution, ultimately delivering
sustainable growth and profit.

Values
Excellence
Every day we relentlessly purse
excellence in all we do

Understanding
We listen closely to our customers
to really understand their needs

Integrity
We uphold the highest standards
of integrity in our actions

Prysmian Group

Market, innovation and technology leader in the global cables industry.

Prysmian Group is world leader in the energy and telecom cables and systems industry. With more than 130 years of
experience, sales in excess of 8 billion dollars in 2016, over 19,000 employees in 50 countries and 88 production sites,
the Group offers the widest possible range of products, services, technology and know-how for every type of industry
thanks to an extensive commercial presence and 17 R&D centers in Europe, the United States, South America and
China, with more than 500 qualified R&D professionals.

Prysmian is a public company, listed on the Italian Stock Exchange in the FTSE MIB index.
Table of Contents

Introduction.................................................. 4-5

PureCore™ OPGW............................................6-7

CladCore™ OPGW............................................ 8-9

StrandCore™ OPGW...................................... 10-11

EzSpan ADSS...............................................12-19

Long Span ADSS.........................................20-25

OPGW & ADSS Ordering Guide.....................26-27


Linking the Future
As the worldwide leader in the energy and telecom cable industries, Prysmian Group
believes in the effective, efficient and sustainable supply of energy and information as a
primary driver in the development of communities.

With this in mind, we provide major global organizations in many industries with best-
in-class cable solutions, based on state-of-the-art technology. Through two renowned
commercial brands – Prysmian and Draka – based in almost 100 countries, we’re
constantly close to our customers, enabling them to further develop the world’s energy
and telecoms infrastructures, and achieve sustainable, profitable growth.

Introducing fiber optic systems for


Overhead Transmission Lines
Overhead optical fiber cable systems have become a key factor in
telecommunication networks used by operators and power utilities.
Due to the fact that minimal civil works are required and the rights of way have already been
established, it is possible to minimize costs and, most importantly, the time required to begin
network operation.

Prysmian offers its customers a broad range of fiber optic cables for
overhead cable networks:
Optical Ground Wire (OPGW)
Composite optical ground wire system for installation on high voltage electric lines.

All Dielectric Cable (ADSS)


Self-supporting optical cable for all types of lines:
transport electrical lines, distribution electrical lines, railways lines, etc.

4
The main advantages of Prysmian’s solutions include the following:
High reliability and proven experience ISO 9001 and TL9000
We have installed over 200,000km (124,000 The Prysmian brand has always been a
miles) of OPGW since 1983 in more than 100 guarantee for the supply of products and
countries in all five continents. services based on common worldwide quality
standards. Prysmian has a built-in multi-step
Manufacturing capabilities quality assurance program, which covers the
Prysmian has a growing production capacity entire production process from cable design and
of more than 25,000km of OPGW cables per raw materials purchasing, to final inspection and
year in three different continents; Europe, testing documentation.
America and Asia.
Full range of technologies
OHSAS 18001 and ISO 14001 Because we own all of the required technology,
Prysmian Group is involved in implementing we provide every customer with the most
management and production processes which appropriate and relevant technical solution for
help improve environmental sustainability any single project. Prysmian Group never has a
and safety at work, in accordance with the pre-determined answer to a challenge – instead,
guidelines of its HSE policy. we always recommend the best solution on a
case-by-case basis.

5
PureCore™ OPGW
Aluminum Central Tube Cable

Optical Power Ground Wire for


Transmission Applications
Overview Features and Benefits
Prysmian’s PureCore™ OPGW cables are typically custom- Extruded Aluminum Core Tube
designed to best match the optical, electrical, mechanical,
quality and cost requirements of each individual project. - Superior combination of crush and kink resistance
This includes optimizing diameter, weight, breaking strength - Core tube can safely and easily be routed to
and short circuit capacity. However, some “REFERENCE closures without armor
DESIGNS” are presented here. The core consists of optical
- Easy access to optical core
fibers contained in one or more loose buffer tubes allowing
the fibers to be free from strain even at high operating loads. Superior Corrosion Resistance
In areas where there is high contamination or close proximity - No exposed stainless steel to induce corrosion of
to the ocean, Prysmian recommends a grease coating on the aluminum elements
outer armor layer.
- Meets IEEE construction guidelines for use in
high corrosion sites
Product Snapshot
Superior Electrical Performance
Applications Prysmian’s PureCore™ OPGW provides
- Aluminum core tube substantially increases
increased conductivity without sacrificing
conductor cross-section
tensile performance, lightning resistance
or limiting fiber count. It is best suited Superior Lightning Resistance
to applications with moderate to high - Fewer aluminum alloy wires are needed to meet
electrical, tensile and/or fiber count electrical specs
requirements.
- More/heavier duty ACS wires can be used
Construction Single or double armor layers,
- AA wires can be completely replaced with ACS in
Options Single or multiple buffer tubes
some applications
within the core tube,
Right or left-hand stranding lay High Performance Even in High Fiber Counts
(on single armor) - All fibers are housed in the core tube
Fiber Count Up to 288 fibers in buffer tubes - A core tube is available in a wide range of inside
Fiber Types Standard Single Mode (G.652.D), Bend- diameters
Insensitive Single Mode (G.657), and NZDSF - Armor wires are not replaced with fiber tubes in
high count designs
Performance Meets or exceeds IEEE-1138-2009, tested in
accordance with relevant EIA-455 FOTPs - Electrical and mechanical properties can be
for fiber optic cables maintained
Other Versions StrandCore™, CladCore™
Registered ISO 9001, ISO 14001, TL 9000,
Supplier and OHS AS 18001

6
PureCore™ OPGW
Optical ground wires with capacity up to 96 optical fibers

Aluminum Alloy Armor Wire


Aluminum-Clad Steel Armor Wire
Extruded Aluminum Core Tube
Optical Fiber
Gel-Filled Buffer Tube
Heat Barrier Tape

Fault Total Conductor


Fiber Count OPGW Reference Current Current Overall Diameter Weight RBS SAG 10
(max) (kA)2sec Inches2 mm2 Inches mm lbs/ft kg/m lbs kg Chart #

12 OPGW 18A46 (7546) 41 0.1232 79.5 0.466 11.8 0.308 0.458 16226 7360 1-1421
12 OPGW 18B34 (7521) 51 0.1232 79.5 0.466 11.8 0.228 0.340 10362 4700 1-1439
12 OPGW 28C56 (7520) 56 0.1468 94.7 0.506 12.8 0.374 0.556 20349 9230 1-1442
12 OPGW 28D43 (7562) 70 0.1468 94.7 0.506 12.8 0.288 0.428 13735 6230 1-917
24 OPGW 34D55 (7522) 68 0.1500 96.5 0.529 13.4 0.367 0.546 18409 8350 1-1450
24 OPGW 34D43 (7772) 81 0.1500 96.5 0.529 13.4 0.287 0.427 12147 5510 1-1439
24 OPGW 40E61 (7557) 81 0.1650 106.6 0.553 14.0 0.410 0.611 21142 9590 1-1453
24 OPGW 40F46 (7523) 98 0.1650 106.6 0.553 14.0 0.311 0.463 13558 6150 1-1438
36 OPGW 45F62 (7524) 95 0.1765 113.9 0.571 14.5 0.415 0.617 20569 9330 1-1461
36 OPGW 45G49 (7525) 110 0.1765 113.9 0.571 14.5 0.327 0.486 13801 6260 1-1438
36 OPGW 54H73 (7526) 118 0.2018 130.2 0.608 15.4 0.487 0.725 24846 11270 1-1457
36 OPGW 54J57 (7527) 141 0.2018 130.2 0.608 15.4 0.381 0.567 16667 7560 1-1439
48 OPGW 64K78 (7540) 151 0.2227 143.7 0.647 16.4 0.519 0.773 25111 11390 1-1461
48 OPGW 64K64 (7541) 172 0.2227 143.7 0.647 16.4 0.425 0.641 18056 8190 1-1439
48 OPGW 83N105 (7543) 239 0.2878 185.7 0.722 18.3 0.707 1.052 35054 15900 1-1453
48 OPGW 83P80 (7552) 292 0.2878 185.7 0.722 18.3 0.537 0.799 22531 10220 1-1438
72 OPGW 67K78 (7995) 154 0.2229 143.8 0.657 16.7 0.531 0.784 25573 11600 1-1461
72 OPGW 67K63 (7996) 177 0.2229 143.8 0.657 16.7 0.426 0.630 17747 8050 1-1438
72 OPGW 73L88 (7999) 182 0.2446 157.8 0.681 17.3 0.595 0.879 29784 13510 1-1450
72 OPGW 73M70 (7997) 212 0.2446 157.8 0.681 17.3 0.476 0.704 20624 9355 1-1439
96 OPGW 62J72 (8000) 138 0.2080 134.2 0.638 16.2 0.489 0.723 23192 10520 1-1166
96 OPGW 62J57 (8001) 159 0.2080 134.2 0.638 16.2 0.384 0.568 15079 6840 1-1441
96 OPGW 84N104 (7994) 230 0.2818 181.8 0.724 18.4 0.701 1.036 35163 15950 1-1453
96 OPGW 84P81 (7632) 277 0.2818 181.8 0.724 18.4 0.547 0.808 23545 10680 1-1439

Cable Characteristics Temperature Range


- Optical unit composed of 1 to 4 tubes -40° F to +176° F (-40° C to +80° C)
- Armor Lay direction: left (S) or right (Z)
Routine Tests
100% of optical fibers are measured by OTDR technique before leaving factory.
Installation Procedure
Prysmian recommends installing the cable described in this specification following the latest
version of our “Installation Procedures for OPGW Fiber Optic Cable” reference SIG-07-PE-PA-013.

7
CladCore™ OPGW
Aluminum Clad Stainless Steel Central Tube Cable

Optical Power Ground Wire for


Transmission Applications
Overview Features and Benefits
Prysmian’s CladCore™ OPGW cables are typically custom-
designed to best match the optical, electrical, mechanical, Aluminum-Clad Stainless Steel Core Tube
quality and cost requirements of each individual project. - High crush resistance in a small form-factor
This includes optimizing diameter, weight, breaking strength
and short circuit capacity. However, some “REFERENCE Superior Corrosion Resistance
DESIGNS” are presented here. The core consists of optical
fibers contained in a welded stainless steel tube, which is - Dissimilar metals are prevented from reacting
overclad with Aluminum. Where there is high contamination with one another
or close proximity to the ocean, Prysmian recommends a - Provides performance similar to stainless
grease coating on the outer armor layer. steel central tube, without the risk of galvanic
corrosion
Product Snapshot - Meets IEEE construction guidelines for use in
Prysmian’s CladCore™ OPGW provides high corrosion sites
Applications
a compact design without sacrificing
corrosion resistance. It is best suited to Enhanced Electrical Performance
applications with moderate to low span and - Use of aluminum alloy wires can be decreased
electrical requirements. - Replacement with ACS wires improves lightning
Construction Single or double armor layers, right or left- resistance
Options hand stranding lays (on single armor)
Compact Design
Fiber Count Up to 48 fibers in a stainless steel tube
- Reduced weight
Fiber Types Standard Single Mode (G.652.D), Bend-
Insensitive Single Mode (G.657), and NZDSF - Increased flexibility
- Smaller minimum bend radius
Performance Meets or exceeds IEEE-1138-2009, tested in
accordance with relevant EIA-455 FOTPs for - Easier to handle and install
fiber optic cables - Lower wind and ice loads put less load on
Other Versions StrandCore™, PureCore™ structures

Registered ISO 9001, ISO 14001, TL 9000,


Supplier and OHS AS 18001

8
CladCore™ OPGW
Aluminum Clad Stainless Steel Central Tube Cable

Aluminum-Clad Steel Armor Wire

Aluminum Over-Cladding

Gel-Filled Stainless Steel Tube

Optical Fibers

Aluminum Allow Armor Wire

REFERENCE DESIGNS
Fault
Fiber Count OPGW Reference Current Total Conductor Area Overall Diameter Weight RBS
(max) (kA)2sec Inches2 mm2 Inches mm lbs/ft kg/m lbs kg

48 OPGW 18B47 (8190) 43 0.124 80.52 0.465 11.80 0.314 0.467 16626 7541
48 OPGW 18B35 (8319) 54 0.124 80.52 0.465 11.80 0.238 0.354 10755 4878
48 OPGW 20B47 (8392) 53 0.132 85.40 0.472 12.00 0.316 0.470 16089 7298
48 OPGW 20C36 (8393) 63 0.132 85.40 0.472 12.00 0.244 0.364 10523 4773
48 OPGW 26C53 (8364) 63 0.146 94.10 0.496 12.60 0.355 0.529 18454 8371
48 OPGW 26D42 (8390) 75 0.146 94.10 0.496 12.60 0.279 0.416 12584 5708
48 OPGW 28C57 (8261) 58 0.147 94.90 0.504 12.80 0.381 0.568 20749 9408
48 OPGW 28D44 (8391) 74 0.147 94.90 0.504 12.80 0.295 0.441 14144 6416
48 OPGW 34E61 (8394) 75 0.165 106.60 0.528 13.40 0.410 0.611 21831 9903
48 OPGW 34F46 (8395) 94 0.165 106.60 0.528 13.40 0.310 0.461 14092 6392

Cable Characteristics Temperature Range


- Optical unit composed of a stainless steel -40° F to +185° F (-40° C to +85° C)
tube embedded in an aluminium tube.
- Armor Lay direction: left (S) or right (Z)
Routine Tests
100% of optical fibers are measured by OTDR technique before leaving factory.
Installation Procedure
Prysmian recommends installing the cable described in this specification following the latest
version of our “Installation Procedures for OPGW Fiber Optic Cable” reference SIG-07-PE-PA-013.

9
StrandCore™ OPGW
Stranded Tube Cable

Optical Power Ground Wire for


Transmission Applications
Overview Features and Benefits
Prysmian’s StrandCore™ OPGW cables are typically custom
designed to best match the optical, electrical, mechanical, Stranded Stainless Steel Tube
quality and cost requirements of each individual project. - Wire strands are replaced with fiber-filled
This includes optimizing diameter, weight, breaking strength stainless steel tubes
and short circuit capacity. However, some “REFERENCE
DESIGNS” are presented here. Fibers are contained in one or - Fiber tubes are helically stranded alongside the
more stranded stainless steel tubes, allowing the fibers to wires
be free from strain even at highest designed operating load. - Fiber strain margin is increased relative to core
tube designs
Product Snapshot - Loaded sag can be increased without inducing
fiber strain
Applications Prysmian’s StrandCore™ OPGW
allows cable elongation and sag to be
Compact Design
increased without inducing fiber strain.
It is best suited for applications with - Reduced weight
modest electrical requirements. Because - Increased flexibility
StrandCore™ OPGW contains exposed
elements made of both stainless steel - Smaller minimum bend radius
and aluminum, it should not be used in - Easier to handle and install
high corrosion areas.
- Lower wind and ice loads put less load on
Construction Aluminum-Alloy and aluminum-clad armor structures
Options wires.
Fiber Count Up to 96 fibers in buffer tubes
Fiber Types Standard Single Mode (G.652.D), Bend-
Insensitive Single Mode (G.657), and NZDSF
Performance Meets or exceeds IEEE-1138-2009, tested in
accordance with relevant EIA-455 FOTPs for
fiber optic cables
Other Versions CladCore™, PureCore™
Registered ISO 9001, ISO 14001, TL 9000,
Supplier and OHS AS 18001

10
StrandCore™ OPGW
Stranded Tube Cable

Aluminum-Clad Steel Armor Wire


Aluminum Alloy Wire
Aluminum-Clad Steel
Optical Fibers
Stainless Steel Tube
Aluminum Alloy Wire

REFERENCE DESIGNS
Fault
Fiber Count OPGW Reference Current Total Conductor Area Overall Diameter Weight RBS SAG 10
(max) (kA)2sec Inches2 mm2 Inches mm lbs/ft kg/m lbs kg Chart #

24 20A42Ds (7978) 41 0.1233 79.53 0.472 12.0 0.282 0.417 14947 6780 1-1461
36 20A37Ds (7979) 41 0.1180 76.12 0.472 12.0 0.251 0.370 12269 5565 1-350
24 41G47Ds (7975) 96 0.1764 113.81 0.555 14.1 0.320 0.473 15621 7086 1-1438
24 46H47Ds (7976) 116 0.1896 122.32 0.575 14.6 0.321 0.474 14782 6705 1-430
96 60J62Ds (7977) 137 0.2140 138.05 0.630 16.0 0.420 0.620 20091 9113 1-1170
96 64J67Ds (7980) 152 0.2254 145.45 0.646 16.4 0.452 0.668 22191 10066 1-917
96 70K71Ds (7981) 177 0.2412 155.63 0.669 17.0 0.478 0.706 23303 10570 1-917

Cable Characteristics Temperature Range


- Optical unit composed of 1 to 3 stranded -40° F to +185° F (-40° C to +85° C)
stainless steel tubes.
- Armor Lay direction: left (S) or right (Z)
Routine Tests
100% of optical fibers are measured by OTDR technique before leaving factory.
Installation Procedure
Prysmian recommends installing the cable described in this specification following the latest
version of our “Installation Procedures for OPGW Fiber Optic Cable” reference SIG-07-PE-PA-013.

11
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

All-Dielectric Self-Support (ADSS) easy entry fiber cable


for up to 1200' (365m) spans typical in distribution

Overview Features and Benefits


Prysmian’s ezSPAN® ADSS provides reliable self-support
performance for up to 1200 feet (365 meters). Each ezSPAN® Easy Cable Entry and Preparation
ADSS cable is custom engineered for each application based
- 12 fibers per tube construction up to 144 fiber
on its full weather load, ensuring safe, reliable lifetime
designs allow easy termination and mid-span
performance. Flexible buffer tubes enable ease of mid-entry,
fiber access
preparation and routing in splice closures. These cables
uniquely combine flexible buffer tubes and swellable water- - Flexible buffer tubes and single jacket option
blocking to make ezSPAN the easiest ADSS cables to prep enhance mid-entry
and access. - Ripcord speeds cable entry and outer jacket
removal
Product Snapshot - Swellable binders speed cable preparation
Applications Self-supporting aerial deployment for
communications & power transmission. Flexible Routing and Termination
- Flexible buffer tubes simplify routing, storage
Constructions All-dielectric round - typical span lengths and prep
up to 1,200' (305m), single and dual jacket.
- Available with G657.A1 and G657.A2 bend-
insensitive single-mode fiber
Fiber Count 12 to 144 fibers in color coded buffer tubes.
Versatile Installation and Use
Fiber Types Single-mode / bend-insensitive / NZDSF /
multimode / hybrid - Tailored designs span distances up to 1200’
(305m) without interrupting power
Standards IEEE 1222-2011, ANSI / ICEA 640, IEC, - Easy mid-entry is ideal for FTTx distribution
RUS 7 CFR 1755 (RUS LISTED), applications
Telecordia GR- 20
- Matching pole attachment hardware (dead-ends,
Long Span ADSS suspension clamps)
Other Versions

ISO 9001, ISO 14001, TL 9000, Reliable Lifetime Performance


Registered
Supplier and OHSAS 18001 - Custom engineered for operation under full load
- Guaranteed standards-based performance

RUS
LISTED

12
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

Aramid Strength Yarns


Inner Jacket Polyethylene (optional)
Central Strength Member
Water Blocking Material
Gel-Filled Buffer Tube Containing up to 12 Fibers
Ripcord

PLP ATTACHMENT HARDWARE CONSIDERATIONS


- Dead-ends indicated are Limited & Medium Tension dead-ends. The Limited Tension dead-end is designed for a
maximum long-term tension of 1000 lbs and short-term tension of 2500 lbs. The Medium Tension dead-end is
designed for 2000 lbs for long-term tensions and 4000 lbs for short-term loads. Semi-high or High Tension dead-
ends should be used for higher tension ratings.
- Limited Tension dead ends are limited to a maximum span length of 600 feet.
- C1E1 designates thimble clevis and extension link (recommended).
- Aluminum Suspension is designed for in-line support with a maximum angle change of 20° and a maximum span
of 600 feet.
- Spans of > 600 to 1200 feet require reinforcing rods (SSR).
- The “S” designates anchor shackle and eye-nut (recommended).
- Vibration dampers may be required.
- Aluminum support is designed for in-line support with a maximum angle change of 20° and a maximum span of
600 feet.

INSTALLATION SPECIFICATIONS
Minimum Bend Radius
With load: 20x cable diameter
No load: 10x cable diameter
Temperature Range
Shipping and Storage -40° F to +167° F (-40° C to +75° C)
Installation -22° F to +140° F (-30° C to +60° C)
Operation -40° F to +158° F (-40° C to +70° C)

Maximum Stringing Tension: 600 lbs

13
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

NESC Light Loading ezSPAN Single Jacket


PLP Attachment Hardware Part #
Maximum
Cable Outside Rated Cable Al Suspension Al Suspension
Span Distance Diameter Load Initial Sag w/o SSR Al Suspension Spans
(ft) (in) (MRCL) (lbs) (%) Cable Part Numbers Dead End (<600 ft) with SSR <600 ft

6-30 Fibers (6 fibers per tube)


up to 430 0.393 465 1.5 F-ADSS0465-06-HB-XXX 2872000C1E1 4450198S — 4450098
12-60 Fibers (12 fibers per tube)
up to 328 0.398 415 1.5 F-ADSS0415-12-HB-XXX 2872000C1E1 4450198S – 4450098
12-72 Fibers
up to 328 0.420 495 1.5 F-ADSS0495-12-HB-XXX 2872001C1E1 4450198S – 4450098
up to 600 0.482 1025 1.5 F-ADES1025-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
700 0.482 1025 1.5 F-ADES1025-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
800 0.483 1075 1.5 F-ADES1075-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
900 0.486 1205 1.5 F-ADES1205-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
1000 0.489 1345 1.5 F-ADES1345-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
1100 0.491 1475 1.5 F-ADES1475-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
1200 0.494 1615 1.5 F-ADES1615-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
84-96 Fibers
up to 600 0.567 1025 1.5 F-ADES1025-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
700 0.568 1115 1.5 F-ADES1115-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
800 0.571 1255 1.5 F-ADES1255-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
900 0.574 1435 1.5 F-ADES1435-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
1000 0.577 1615 1.5 F-ADES1615-12-HB-XXX 2872102C1E1 4450202S 4470202S 4450102
1100 0.580 1795 1.5 F-ADES1795-12-HB-XXX 2872103C1E1 4450202S 4470202S 4450102
1200 0.582 1925 1.5 F-ADES1925-12-HB-XXX 2872103C1E1 4450202S 4470202S 4450102
108-144 Fibers
up to 400 0.733 1025 1.5 F-ADES1025-12-HB-XXX 2872010C1E1 4450204S 4470204S 4450104
500 0.734 1075 1.5 F-ADES1075-12-HB-XXX 2872010C1E1 4450204S 4470204S 4450104
600 0.737 1295 1.5 F-ADES1295-12-HB-XXX 2872010C1E1 4450204S 4470204S 4450104
700 0.740 1525 1.5 F-ADES1525-12-HB-XXX 2872107C1E1 4450204S 4470205S 4450104
800 0.742 1705 1.5 F-ADES1705-12-HB-XXX 2872107C1E1 4450204S 4470205S 4450104
900 0.745 1925 1.5 F-ADES1925-12-HB-XXX 2872107C1E1 4450204S 4470205S 4450104
1000 0.748 2155 1.5 F-ADES2125-12-HB-XXX 2872107C1E1 4450204S 4470205S 4450104

14
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

NESC Medium Loading ezSPAN Single Jacket


PLP Attachment Hardware Part #
Maximum
Cable Outside Rated Cable Al Suspension Al Suspension
Span Distance Diameter Load Initial Sag w/o SSR Al Suspension Spans
(ft) (in) (MRCL) (lbs) (%) Cable Part Numbers Dead End (<600 ft) with SSR <600 ft

6-30 Fibers (6 fibers per tube)


280 0.393 465 1.5 F-ADSS0465-06-HB-XXX 287500TE 4450198S — 4450098
12-72 Fibers
up to 500 0.482 1025 1.5 F-ADES1025-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
600 0.484 1115 1.5 F-ADES1115-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
700 0.488 1295 1.5 F-ADES1295-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
800 0.492 1525 1.5 F-ADES1525-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
900 0.496 1705 1.5 F-ADES1705-12-HB-XXX 2872100C1E1 4450200S 4470200S 4450100
84-96 Fibers
up to 500 0.567 1025 1.5 F-ADES1025-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
600 0.571 1255 1.5 F-ADES1255-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
700 0.575 1475 1.5 F-ADES1475-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
800 0.578 1705 1.5 F-ADES1705-12-HB-XXX 2872103C1E1 4450202S 4470202S 4450102
900 0.582 1885 1.5 F-ADES1885-12-HB-XXX 2872103C1E1 4450202S 4470202S 4450102
108-144 Fibers
up to 400 0.733 1025 1.5 F-ADES1025-12-HB-XXX 2872010C1E1 4450204S 4470204S 4450104
500 0.737 1295 1.5 F-ADES1295-12-HB-XXX 2872010C1E1 4450204S 4470204S 4450104
600 0.740 1565 1.5 F-ADES1565-12-HB-XXX 2872011C1E1 4450204S 4470205S 4450104
700 0.744 1835 1.5 F-ADES1835-12-HB-XXX 2872107C1E1 4450204S 4470205S 4450104
800 0.747 2105 1.5 F-ADES2105-12-HB-XXX 2872107C1E1 4450204S 4470205S 4450104
900 0.751 2375 1.5 F-ADES2375-12-HB-XXX 2872107C1E1 4450205S 4470205S 4450105

15
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

NESC Heavy Loading ezSPAN Single Jacket


PLP Attachment Hardware Part #
Maximum
Cable Outside Rated Cable Al Suspension Al Suspension
Span Distance Diameter Load Initial Sag w/o SSR Al Suspension Spans
(ft) (in) (MRCL) (lbs) (%) Cable Part Numbers Dead End (<600 ft) with SSR <600 ft

6-30 Fibers (6 fibers per tube)


165 0.393 465 1.5 F-ADSS0465-06-HB-XXX 287500TE 4450198S — 4450098
12-72 Fibers
up to 330 0.482 1025 1.5 F-ADES1025-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
350 0.483 1075 1.5 F-ADES1075-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
400 0.487 1255 1.5 F-ADES1255-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
450 0.490 1385 1.5 F-ADES1385-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
500 0.492 1525 1.5 F-ADES1525-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
550 0.496 1705 1.5 F-ADES1705-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
600 0.500 1885 1.5 F-ADES1885-12-HB-XXX 2872004C1E1 4450200S 4470200S 4450100
700 0.506 2195 1.5 F-ADES2195-12-HB-XXX 2872100C1E1 4450200S 4470201S 4450100
84-96 Fibers
up to 310 0.567 1025 1.5 F-ADES1025-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
350 0.569 1165 1.5 F-ADES1165-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
400 0.572 1345 1.5 F-ADES1345-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
450 0.575 1525 1.5 F-ADES1525-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
500 0.578 1705 1.5 F-ADES1705-12-HB-XXX 2872007C1E1 4450202S 4470202S 4450102
550 0.582 1885 1.5 F-ADES1885-12-HB-XXX 2872007C1E1 4450202S 4470202S 4450102
600 0.584 2015 1.5 F-ADES2015-12-HB-XXX 2872007C1E1 4450202S 4470202S 4450102
700 0.590 2375 1.5 F-ADES2375-12-HB-XXX 2872103C1E1 4450202S 4470202S 4450102
108-144 Fibers
up to 250 0.733 1025 1.5 F-ADES1025-12-HB-XXX 2872010C1E1 4450204S 4470204S 4450104
300 0.736 1205 1.5 F-ADES1205-12-HB-XXX 2872010C1E1 4450204S 4470204S 4450104
350 0.738 1385 1.5 F-ADES1385-12-HB-XXX 2872010C1E1 4450204S 4470205S 4450104
400 0.741 1615 1.5 F-ADES1615-12-HB-XXX 2872011C1E1 4450204S 4470205S 4450104
450 0.743 1795 1.5 F-ADES1795-12-HB-XXX 2872011C1E1 4450204S 4470205S 4450104
500 0.746 1975 1.5 F-ADES1975-12-HB-XXX 2872011C1E1 4450204S 4470205S 4450104
550 0.748 2195 1.5 F-ADES2195-12-HB-XXX 2872011C1E1 4450204S 4470205S 4450104
600 0.751 2375 1.5 F-ADES2375-12-HB-XXX 2872011C1E1 4450205S 4470205S 4450105

16
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

NESC Light Loading ezSPAN Double Jacket


PLP Attachment Hardware Part #
Maximum
Cable Outside Rated Cable Al Suspension Al Suspension
Span Distance Diameter Load Initial Sag w/o SSR Al Suspension Spans
(ft) (in) (MRCL) (lbs) (%) Cable Part Numbers Dead End (<600 ft) with SSR <600 ft

12-72 Fibers
up to 600 0.533 1031 1.5 F-ADED1031-12-HB-XXX 2872005C1E1 4450201S 4470201S 4450101
700 0.534 1071 1.5 F-ADED1071-12-HB-XXX 2872101C1E1 4450201S 4470201S 4450101
800 0.537 1211 1.5 F-ADED1211-12-HB-XXX 2872101C1E1 4450201S 4470201S 4450101
900 0.540 1391 1.5 F-ADED1391-12-HB-XXX 2872101C1E1 4450201S 4470201S 4450101
1000 0.542 1521 1.5 F-ADED1521-12-HB-XXX 2872101C1E1 4450201S 4470201S 4450101
1100 0.546 1701 1.5 F-ADED1701-12-HB-XXX 2872102C1E1 4450201S 4470201S 4450101
1200 0.549 1881 1.5 F-ADED1881-12-HB-XXX 2872102C1E1 4450201S 4470201S 4450101
1300 0.552 2021 1.5 F-ADED2021-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
1400 0.555 2201 1.5 F-ADED2201-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
1500 0.558 2381 1.5 F-ADED2381-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
1600 0.561 2561 1.5 F-ADED2561-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
84-96 Fibers
up to 575 0.618 1031 1.5 F-ADED1031-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
600 0.619 1071 1.5 F-ADED1071-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
700 0.622 1251 1.5 F-ADED1251-12-HB-XXX 2872104C1E1 4450202S 4470202S 4450102
800 0.625 1431 1.5 F-ADED1431-12-HB-XXX 2872104C1E1 4450202S 4470202S 4450102
900 0.628 1661 1.5 F-ADED1661-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
1000 0.631 1841 1.5 F-ADED1841-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
1100 0.634 2021 1.5 F-ADED2021-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
1200 0.636 2201 1.5 F-ADED2201-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
1300 0.640 2421 1.5 F-ADED2421-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
1400 0.643 2621 1.5 F-ADED2621-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
108-144 Fibers
up to 425 0.785 1031 1.5 F-ADED1031-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
500 0.787 1211 1.5 F-ADED1211-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
600 0.791 1481 1.5 F-ADED1481-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
700 0.793 1701 1.5 F-ADED1701-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105
800 0.796 1971 1.5 F-ADED1971-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105
900 0.799 2201 1.5 F-ADED2201-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105
1000 0.802 2471 1.5 F-ADED2471-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105
1100 0.806 2751 1.5 F-ADED2751-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105

17
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

NESC Medium Loading ezSPAN Double Jacket


PLP Attachment Hardware Part #
Maximum
Cable Outside Rated Cable Al Suspension Al Suspension
Span Distance Diameter Load Initial Sag w/o SSR Al Suspension Spans
(ft) (in) (MRCL) (lbs) (%) Cable Part Numbers Dead End (<600 ft) with SSR <600 ft

12-72 Fibers
up to 500 0.533 1031 1.5 F-ADED1031-12-HB-XXX 2872005C1E1 4450201S 4470201S 4450101
600 0.537 1211 1.5 F-ADED1211-12-HB-XXX 2872005C1E1 4450201S 4470201S 4450101
700 0.541 1431 1.5 F-ADED1431-12-HB-XXX 2872101C1E1 4450201S 4470201S 4450101
800 0.545 1661 1.5 F-ADED1661-12-HB-XXX 2872102C1E1 4450201S 4470201S 4450101
900 0.549 1881 1.5 F-ADED1881-12-HB-XXX 2872102C1E1 4450201S 4470201S 4450101
1000 0.553 2111 1.5 F-ADED2111-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
1100 0.556 2291 1.5 F-ADED2291-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
84-96 Fibers
up to 450 0.618 1031 1.5 F-ADED1031-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
500 0.620 1161 1.5 F-ADED1161-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
600 0.624 1391 1.5 F-ADED1391-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
700 0.627 1611 1.5 F-ADED1611-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
800 0.631 1841 1.5 F-ADED1841-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
900 0.635 2111 1.5 F-ADED2111-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
1000 0.638 2331 1.5 F-ADED2331-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
1100 0.643 2621 1.5 F-ADED2621-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
108-144 Fibers
up to 350 0.785 1031 1.5 F-ADED1031-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
400 0.787 1161 1.5 F-ADED1161-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
500 0.790 1431 1.5 F-ADED1431-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
600 0.794 1751 1.5 F-ADED1751-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
700 0.797 2021 1.5 F-ADED2021-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105
800 0.801 2331 1.5 F-ADED2331-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105
900 0.804 2621 1.5 F-ADED2621-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105

18
ezSPAN® ADSS
All-Dielectric Self-Supporting Loose Tube Cable

NESC Heavy Loading ezSPAN Double Jacket


PLP Attachment Hardware Part #
Maximum
Cable Outside Rated Cable Al Suspension Al Suspension
Span Distance Diameter Load Initial Sag w/o SSR Al Suspension Spans
(ft) (in) (MRCL) (lbs) (%) Cable Part Numbers Dead End (<600 ft) with SSR <600 ft

12-72 Fibers
up to 300 0.533 1031 1.5 F-ADED1031-12-HB-XXX 2872005C1E1 4450201S 4470201S 4450101
350 0.536 1161 1.5 F-ADED1161-12-HB-XXX 2872005C1E1 4450201S 4470201S 4450101
400 0.539 1341 1.5 F-ADED1341-12-HB-XXX 2872005C1E1 4450201S 4470201S 4450101
450 0.542 1481 1.5 F-ADED1481-12-HB-XXX 2872005C1E1 4450201S 4470201S 4450101
500 0.545 1661 1.5 F-ADED1661-12-HB-XXX 2872006C1E1 4450201S 4470201S 4450101
550 0.548 1841 1.5 F-ADED1841-12-HB-XXX 2872006C1E1 4450201S 4470201S 4450101
600 0.552 2021 1.5 F-ADED2021-12-HB-XXX 2872006C1E1 4450201S 4470202S 4450101
650 0.555 2201 1.5 F-ADED2201-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
700 0.558 2381 1.5 F-ADED2381-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
750 0.560 2511 1.5 F-ADED2511-12-HB-XXX 2872102C1E1 4450201S 4470202S 4450101
84-96 Fibers
up to 290 0.618 1031 1.5 F-ADED1031-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
300 0.619 1171 1.5 F-ADED1171-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
350 0.622 1251 1.5 F-ADED1251-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
400 0.625 1431 1.5 F-ADED1431-12-HB-XXX 2872008C1E1 4450202S 4470202S 4450102
450 0.627 1611 1.5 F-ADED1611-12-HB-XXX 2872008C1E1 4450203S 4470203S 4450103
500 0.631 1841 1.5 F-ADED1841-12-HB-XXX 2872008C1E1 4450203S 4470203S 4450103
550 0.634 2021 1.5 F-ADED2021-12-HB-XXX 2872008C1E1 4450203S 4470203S 4450103
600 0.636 2201 1.5 F-ADED2201-12-HB-XXX 2872008C1E1 4450203S 4470203S 4450103
650 0.639 2381 1.5 F-ADED2381-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
700 0.642 2561 1.5 F-ADED2561-12-HB-XXX 2872104C1E1 4450203S 4470203S 4450103
108-144 Fibers
up to 240 0.785 1031 1.5 F-ADED1031-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
250 0.786 1071 1.5 F-ADED1071-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
300 0.788 1301 1.5 F-ADED1301-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
350 0.791 1521 1.5 F-ADED1521-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
400 0.794 1751 1.5 F-ADED1751-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
450 0.796 1931 1.5 F-ADED1931-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
500 0.798 2157 1.5 F-ADED2157-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
550 0.801 2381 1.5 F-ADED2381-12-HB-XXX 2872012C1E1 4450205S 4470205S 4450105
600 0.804 2621 1.5 F-ADED2621-12-HB-XXX 2872108C1E1 4450205S 4470205S 4450105

19
Long Span ADSS
All-Dielectric Self-Supporting Loose Tube Cable

All-Dielectric Self-Support (ADSS) fiber cable for up


to 2600' (800m) spans common in transmission

Overview Features and Benefits


Prysmian’s Long Span ADSS version provides reliable
self-support performance for up to 2,600 feet (800 meters). Proven Long Span Installation & Use
Each Long Span ADSS cable is custom engineered for
optimum placement on utility towers and to operate under - Tailored designs span distances up to 2,600'
full weather load, ensuring safe reliable lifetime performance. (800m) without interrupting power
For installation on high-voltage lines up to 275 kV, an optional - Higher count designs utilize 24 fiber per tube to
track-resistant jacket prevents dry-band arcing damage. reduce diameter and environmental loading
Available up to 288 fibers, cables greater than 72 fibers
utilize a 24 fiber per tube design to reduce environmental Easy Cable Entry & Preparation
load (12 fibers per tube design is also available for fiber - Ripcord speeds cable entry & outer jacket removal
counts of 84-144).
- Swellable binders speed cable preparation
Product Snapshot - Available bend-insensitive single-mode fiber

Applications Self-supporting aerial deployment for - 2.6 mm tube with 12 fibers per tube; 3.0 mm tube
communications & power transmission space with 24 fibers per tube (with two 12 fiber binder
groups)
Constructions All-dielectric round - typical span lengths up to
2,600’ (800m), single and dual jacket, and track Reliable Lifetime Performance
resistant - Custom engineered for operation under full load
- Available with zero fiber strain at the maximum
Fiber Count 12 to 288 fibers in color-coded buffer tubes rated cable load (MRCL) or with a SafeStrain
design limiting fiber strain to 0.20%
Fiber Types Single-mode /bend-insensitive/ NZDSF /
multimode / hybrid - Guaranteed standards-based performance

Options Track resistant jacket, SafeStrain or ZeroStrain


designs

Standards IEEE 1222-2011, ANSI / ICEA 640, RUS 7 CFR 1755


(RUS LISTED), Telecordia GR-20, IEC 60794-4-20

Other Versions ezSPAN ADSS

Registered ISO 9001, ISO 14001, TL 9000,


Supplier and OHSAS 18001

RUS
LISTED

20
Long Span ADSS
All-Dielectric Self-Supporting Loose Tube Cable

HDPE Outer Jacket


Aramid Strength Yarns
Inner Jacket Polyethylene (optional)
Central Strength Member
Water Blocking Tube
Gel-Filled Buffer Tube Material
Ripcord

PLP ATTACHMENT HARDWARE CONSIDERATIONS


- Dead-ends indicated are Limited & Medium Tension dead-ends. The Limited Tension dead-end is designed for a
maximum long-term tension of 1000 lbs and short-term tension of 2500 lbs. The Medium Tension dead-end is
designed for 2000 lbs for long-term tensions and 4000 lbs for short-term loads. Semi-high or High Tension dead-
ends should be used for higher tension ratings.
- Limited Tension dead ends are limited to a maximum span length of 600 feet.
- C1E1 designates thimble clevis and extension link (recommended).
- Aluminum Suspension is designed for in-line support with a maximum angle change of 20° and a maximum span
of 600 feet.
- Spans of > 600 to 1200 feet require reinforcing rods (SSR).
- The “S” designates anchor shackle and eye-nut (recommended).
- Vibration dampers may be required.
- Aluminum support is designed for in-line support with a maximum angle change of 20° and a maximum span of
600 feet.

INSTALLATION SPECIFICATIONS
Minimum Bend Radius
With load: 20x cable diameter
No load: 10x cable diameter
Temperature Range
Shipping and Storage -40° F to +167° F (-40° C to +75° C)
Installation -22° F to +140° F (-30° C to +60° C)
Operation -40° F to +158° F (-40° C to +70° C)

21
Long Span ADSS
All-Dielectric Self-Supporting Loose Tube Cable
Single HDPE Jacket (without track resistance) SafeStrain Design | ADLS
NESC Light Load
6-72 fibers: ezSPAN ADSS design is recommended

Maximum Al
Span Installation
Rate Cable Cable O.D. Installation Al Support Suspension Al Suspension
Distance Cable Part Number Load Dead End
Load (in) Sag <600 ft Span w/o SSR with SSR
(ft) (lbf)
(MRCL) (lbf) (<600 ft)

84 to 144 Fibers
up to 600 ADLS1025-24-HB-XXX 1025 0.492 491 1.5 2872004C1E1 4450100 4450200S 4470200S
700 ADLS1025-24-HB-XXX 1025 0.492 491 1.5 2872100C1E1 4450100 4450200S 4470200S
800 ADLS1115-24-HB-XXX 1115 0.494 565 1.5 2872100C1E1 4450100 4450200S 4470200S
900 ADLS1295-24-HB-XXX 1295 0.498 644 1.5 2872100C1E1 4450100 4450200S 4470200S
156 to 216 Fibers
up to 500 ADLS1025-24-HB-XXX 1025 0.616 500 1.5 2872008C1E1 4450102 4450202S 4470202S
600 ADLS1115-24-HB-XXX 1115 0.618 603 1.5 2872008C1E1 4450102 4450202S 4470202S
700 ADLS1295-24-HB-XXX 1295 0.621 709 1.5 2872104C1E1 4450102 4450202S 4470202S
800 ADLS1475-24-HB-XXX 1475 0.624 818 1.5 2872104C1E1 4450102 4450202S 4470202S
900 ADLS1655-24-HB-XXX 1655 0.626 928 1.5 2872104C1E1 4450103 4450203S 4470203S
1000 ADLS1835-24-HB-XXX 1835 0.629 1040 1.5 2872104C1E1 4450103 4450203S 4470203S
228 to 288 Fibers
up to 450 ADLS1025-24-HB-XXX 1025 0.743 608 1.5 2872011C1E1 4450104 4450204S 4470205S
500 ADLS1155-24-HB-XXX 1155 0.745 678 1.5 2872011C1E1 4450104 4450204S 4470205S
600 ADLS1385-24-HB-XXX 1385 0.748 820 1.5 2872011C1E1 4450105 4450204S 4470205S
700 ADLS1605-24-HB-XXX 1605 0.751 965 1.5 2872107C1E1 4450105 4450205S 4470205S
800 ADLS1835-24-HB-XXX 1835 0.754 1111 1.5 2872107C1E1 4450105 4450205S 4470205S
900 ADLS2105-24-HB-XXX 2105 0.757 1262 1.5 2872107C1E1 4450105 4450205S 4470205S
1000 ADLS2325-24-HB-XXX 2325 0.760 1413 1.5 2872107C1E1 4450105 4450205S 4470205S

For longer span applications, contact Prysmian for specific cable designs

22
Long Span ADSS
All-Dielectric Self-Supporting Loose Tube Cable
Single HDPE Jacket (without track resistance) SafeStrain Design | ADLS
NESC Medium Load
6-72 fibers: ezSPAN ADSS design is recommended

Maximum Al
Span Installation
Rate Cable Cable O.D. Installation Al Support Suspension Al Suspension
Distance Cable Part Number Load Dead End
Load (in) Sag <600 ft Span w/o SSR with SSR
(ft) (lbf)
(MRCL) (lbf) (<600 ft)

84 to 144 Fibers
up to 500 ADLS1025-24-HB-XXX 1025 0.492 351 1.5 2872004C1E1 4450100 4450200S 4470200S
600 ADLS1155-24-HB-XXX 1155 0.495 425 1.5 2872004C1E1 4450100 4450200S 4470200S
700 ADLS1385-24-HB-XXX 1385 0.500 505 1.5 2872100C1E1 4450100 4450200S 4470200S
800 ADLS1565-24-HB-XXX 1565 0.503 584 1.5 2872100C1E1 4450100 4450200S 4470201S
900 ADLS1785-24-HB-XXX 1785 0.508 668 1.5 2872100C1E1 4450100 4450200S 4470201S
1000 ADLS2015-24-HB-XXX 2015 0.513 754 1.5 2872101C1E1 4450100 4450200S 4470201S
156 to 216 Fibers
up to 400 ADLS1025-24-HB-XXX 1025 0.616 400 1.5 2872008C1E1 4450102 4450202S 4470202S
500 ADLS1155-24-HB-XXX 1155 0.619 503 1.5 2872008C1E1 4450102 4450202S 4470202S
600 ADLS1385-24-HB-XXX 1385 0.622 611 1.5 2872008C1E1 4450102 4450202S 4470202S
700 ADLS1655-24-HB-XXX 1655 0.626 722 1.5 2872104C1E1 4450103 4450203S 4470203S
800 ADLS1875-24-HB-XXX 1875 0.630 834 1.5 2872104C1E1 4450103 4450203S 4470203S
900 ADLS2105-24-HB-XXX 2105 0.634 948 1.5 2872104C1E1 4450103 4450203S 4470203S
1000 ADLS2375-24-HB-XXX 2375 0.638 1067 1.5 2872104C1E1 4450103 4450203S 4470203S
228 to 288 Fibers
up to 375 ADLS1025-24-HB-XXX 1025 0.743 506 1.5 2872011C1E1 4450104 4450204S 4470205S
400 ADLS1115-24-HB-XXX 1115 0.745 542 1.5 2872011C1E1 4450104 4450204S 4470205S
500 ADLS1385-24-HB-XXX 1385 0.748 684 1.5 2872011C1E1 4450105 4450204S 4470205S
600 ADLS1655-24-HB-XXX 1655 0.752 828 1.5 2872011C1E1 4450105 4450205S 4470205S
700 ADLS1925-24-HB-XXX 1925 0.755 975 1.5 2872107C1E1 4450105 4450205S 4470205S
800 ADLS2235-24-HB-XXX 2235 0.759 1127 1.5 2872107C1E1 4450105 4450205S 4470205S
900 ADLS2505-24-HB-XXX 2505 0.762 1279 1.5 2872107C1E1 4450105 4450205S 4470205S

For longer span applications, contact Prysmian for specific cable designs

23
Long Span ADSS
All-Dielectric Self-Supporting Loose Tube Cable
Single HDPE Jacket (without track resistance) SafeStrain Design | ADLS
NESC Heavy Load
6-72 fibers: ezSPAN ADSS design is recommended

Maximum Al
Span Installation
Rate Cable Cable O.D. Installation Al Support Suspension Al Suspension
Distance Cable Part Number Load Dead End
Load (in) Sag <600 ft Span w/o SSR with SSR
(ft) (lbf)
(MRCL) (lbf) (<600 ft)

84 to 144 Fibers
up to 300 ADLS1025-12-HB-XXX 1025 0.492 210 1.5 2872004C1E1 4450100 4450200S 4470200S
400 ADLS1295-24-HB-XXX 1295 0.498 286 1.5 2872004C1E1 4450100 4450200S 4470200S
500 ADLS1605-24-HB-XXX 1605 0.504 266 1.5 2872004C1E1 4450100 4450200S 4470201S
600 ADLS1925-24-HB-XXX 1925 0.511 450 1.5 2872005C1E1 4450100 4450200S 4470201S
700 ADLS2285-24-HB-XXX 2285 0.518 538 1.5 2872100C1E1 4450100 4450200S 4470201S
800 ADLS2615-24-HB-XXX 2615 0.525 630 1.5 2872101C1E1 4450100 4450200S 4470201S
156 to 216 Fibers
up to 200 ADLS1025-24-HB-XXX 1025 0.616 200 1.5 2872008C1E1 4450102 4450202S 4470202S
300 ADLS1115-24-HB-XXX 1115 0.618 301 1.5 2872008C1E1 4450102 4450202S 4470202S
400 ADLS1475-24-HB-XXX 1475 0.624 409 1.5 2872008C1E1 4450102 4450202S 4470202S
500 ADLS1835-24-HB-XXX 1835 0.629 520 1.5 2872008C1E1 4450103 4450203S 4470203S
600 ADLS2195-24-HB-XXX 2195 0.635 635 1.5 2872008C1E1 4450103 4450203S 4470203S
700 ADLS2555-24-HB-XXX 2555 0.641 753 1.5 2872104C1E1 4450103 4450203S 4470203S
228 to 288 Fibers
up to 250 ADLS1025-24-HB-XXX 1025 0.743 338 1.5 2872011C1E1 4450104 4450204S 4470205S
300 ADLS1245-24-HB-XXX 1245 0.746 408 1.5 2872011C1E1 4450104 4450204S 4470205S
400 ADLS1655-24-HB-XXX 1655 0.752 552 1.5 2872011C1E1 4450105 4450205S 4470205S
500 ADLS2105-24-HB-XXX 2105 0.757 701 1.5 2872011C1E1 4450105 4450205S 4470205S
600 ADLS2505-24-HB-XXX 2505 0.762 853 1.5 2872011C1E1 4450105 4450205S 4470205S

For longer span applications, contact Prysmian for specific cable designs

24
Long Span ADSS
All-Dielectric Self-Supporting Loose Tube Cable
Dual HDPE Jacket (without track resistance) SafeStrain Design | ADLD
NESC Heavy, 1% Sag NESC Medium, 1% Sag NESC Light, 1% Sag
Span
Fiber Count Diameter Weight Diameter Weight Diameter Weight
ft (m)
inches (mm) lb/kft (kg/km) inches (mm) lb/kft (kg/km) inches (mm) lb/kft (kg/km)

2 - 72 200 (61) 0.53 (13.4) 97 (144) 0.52 (13.3) 95 (142) 0.52 (13.3) 95 (142)
400 (122) 0.55 (13.9) 103 (153) 0.53 (13.5) 98 (146) 0.53 (13.4) 97 (144)
600 (183) 0.57 (14.4) 109 (162) 0.55 (13.9) 103 (153) 0.54 (13.6) 99 (148)
800 (244) 0.60 (15.3) 122 (182) 0.56 (14.2) 106 (158) 0.55 (13.9) 103 (153)
1000 (305) 0.64 (16.2) 135 (201) 0.57 (14.5) 111 (165) 0.56 (14.1) 106 (157)
1200 (366) 0.67 (17.0) 147 (218) 0.60 (15.3) 122 (182) 0.57 (14.4) 110 (163)
1600 (488) – – 0.65 (16.5) 140 (208) 0.62 (15.7) 127 (189)
2000 (610) – – 0.69 (17.6) 157 (234) 0.65 (16.6) 141 (210)
84 - 144 200 (61) 0.57 (14.6) 114 (169) 0.57 (14.6) 114 (169) 0.57 (14.6) 114 (169)
400 (122) 0.59 (15.1) 120 (179) 0.58 (14.8) 116 (172) 0.58 (14.6) 114 (170)
600 (183) 0.61 (15.5) 127 (188) 0.59 (15.1) 120 (179) 0.59 (14.9) 117 (175)
800 (244) 0.65 (16.5) 141 (210) 0.60 (15.4) 124 (184) 0.60 (15.1) 121 (180)
1000 (305) 0.68 (17.3) 154 (229) 0.62 (15.8) 130 (193) 0.60 (15.4) 124 (184)
1200 (366) 0.71 (17.9) 164 (244) 0.65 (16.5) 141 (210) 0.62 (15.7) 129 (192)
1600 (488) 0.77 (19.6) 192 (286) 0.70 (17.8) 161 (240) 0.67 (16.9) 147 (219)
2000 (610) – – 0.74 (18.8) 179 (267) 0.71 (17.9) 164 (244)
156 - 216 200 (61) 0.70 (17.8) 157 (234) 0.70 (17.8) 156 (233) 0.70 (17.8) 156 (233)
400 (122) 0.72 (18.3) 165 (245) 0.71 (18.0) 160 (238) 0.70 (17.9) 159 (236)
600 (183) 0.75 (19.0) 178 (265) 0.72 (18.3) 166 (247) 0.72 (18.2) 163 (243)
800 (244) 0.77 (19.6) 189 (281) 0.73 (18.6) 171 (254) 0.73 (18.4) 168 (250)
1000 (305) 0.80 (20.4) 202 (301) 0.76 (19.3) 182 (272) 0.74 (18.7) 172 (255)
1200 (366) 0.83 (21.0) 215 (319) 0.78 (19.9) 193 (288) 0.76 (19.4) 184 (274)
1600 (488) – – 0.83 (21.0) 215 (319) 0.80 (20.4) 202 (301)
2000 (610) – – 0.87 (22.0) 235 (349) 0.84 (21.3) 220 (327)
240 - 288 200 (61) 0.83 (21.1) 207 (308) 0.83 (21.0) 205 (305) 0.83 (21.0) 205 (305)
400 (122) 0.85 (21.5) 216 (321) 0.84 (21.3) 211 (313) 0.83 (21.2) 209 (311)
600 (183) 0.87 (22.2) 229 (340) 0.85 (21.6) 218 (324) 0.84 (21.5) 215 (319)
800 (244) 0.90 (22.9) 244 (363) 0.87 (22.2) 229 (340) 0.86 (21.7) 220 (327)
1000 (305) 0.93 (23.5) 257 (382) 0.89 (22.6) 238 (354) 0.88 (22.3) 232 (345)
1200 (366) 0.95 (24.2) 272 (404) 0.91 (23.2) 249 (371) 0.90 (22.8) 242 (360)
1600 (488) – – 0.96 (24.3) 274 (408) 0.94 (23.8) 264 (393)
2000 (610) – – – – 0.97 (24.7) 284 (422)

For zero strain and rack resistant Jacket options, Contact your Prysmian representative or for information about designs with alternative span
requirements or cable diameters. Cable diameters and weights may vary depending on specific span design requirements.

25
ADSS / OPGW Worksheet
Customer Name: ______________________________________ Project Name:_________________________________________________
Installation Location (City & State):____________________________________________________________________________________
Fiber Type(s): (if the cable will include more than one fiber type, please indicate the fiber sequence)
Number of Fibers __________ Single Mode (ITU G652.D )__________ ITU G655 NZDSF __________
Attenuation (dB/km): _______@ 1310 nm, _______@ 1383 nm, _______@ 1550 nm

ADSS Information:
Maximum Span Length (ft): _______ Installation Sag: _______% (i.e. 1.5%)
Maximum Weather Loading Conditions: NESC Light ______ Medium ______ or Heavy ______; or Defined by NESC map ______
Or User Defined: Radial Ice _______, Wind Speed (mph) _______, Other ___________________________________________________
Maximum Fiber Strain: SafeStrain (0.2% - Default) _______ ZeroStrain _______ Other (please specify) ___________________
Number of Jackets: Single Jacket _______ Dual Jacket _______
Line Voltage: None _______ Distribution _______ Transmission (if yes, specify the Line Voltage) ________________________
Standard print in: ft _______ meters _______ or other ________________________________________________________________
Special Requirements (OD, MRCL, etc): ________________________________________________________________________________

OPGW Cable Design Information:


Cable Construction: Aluminum Tube _____ Aluminum-Clad SS tube _____ Stranded SS Tube _____ Central SS Tube _____

The minimum information needed for design/quotation is in the Required Information section.
Additional information may be provided at the customer’s discretion.

OPGW 1 OPGW 2 OPGW 3


End User Cable Reference (optional)
Required Information
Total Length (feet)
Fiber Count by Type
Rated Tensile Strength - RTS (lbs)*
Onset of Fiber Strain†
Short Circuit Capacity (kA2s)
Optional Specifications
Maximum Span Length*
Installed Sag*
Loading Conditions (wind in mph)*
(radial ice in inches)
Max Loaded Sag
Cable Diameter (inch)
Cable Weight (lb/ft)
Single or Double Layer Armor
Outer Layer Lay Direction (default=LH)
Minimum Armor Wire OD
Initial/Final Short Circuit Temp (F)
Short Circuit Duration (s)

* Max Span Length, Installed Sag and Loading Conditions can be provided in lieu of RTS
† Fiber Strain limits are critical to fiber reliability and cable cost. Please contact Prysmian Group if you would like assistance with the specification of this parameter.

26
NOTES
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________
_________________________________________________________________

27
Prysmian Group

LINKING the FUTURE

Prysmian Group
2512 Penny Road | Claremont, NC 28610 | +1-800-669-0808 | +1-800-879-9862 | website: na.prysmiangroup.com/telecom

You might also like