Professional Documents
Culture Documents
TPItL10 CtLv10 Com EN
TPItL10 CtLv10 Com EN
2
L
)
S I nd
ard EN
615
08
( Sta
Configuration Dimensions
Numbering of the 22.7(*)
130.4
Easy programming on front face with a micro-console or with the terminals:
PC software SuperVISION (ARDETEM) or MCvision (SFERE) connectors A/B/C 1234
119.9
Voltage presence Led
Programming with the Micro-console ON (green) or major error
indication (red)
This minaturised micro-console connected on the front face of the A B C
instruments allows: Relay 1 Location of the upper connectors
- the visualisation of the measure and the status of the analog and Relay 2
relay outputs,
- the visualisation and the modification of the programming,
µconsole
108.5
Dimensions
Self-extinguishing case of black UL 94VO ABS. Coding
Mounting in switchbox: latching on symmetrical DIN rail.
Rack version: consult.
Plug-off connectors for screwed connectings Types:
Dimensions: 22.5x75x120 mm ARDETEM reference: TPItL10
with µconsole: 26.5x80x130 mm SFERE reference: µCtL10
To allow the inserting of the µconsole: mount Type TPI/µC tL10 AR
the instruments vertically (horizontal DIN rail)
leaving a 5mm space between each.
Operating T°: -5° to 50°C Outputs:
Storage T°: -20 to 70°C A analog I/U isolated
R 2 change-over relays
22.7 5 22.7 3 26.5 1 Power supply:
♦ according to the directive EMC 2004/108/CE.. 20 to 270 VAC and 20 to 300 Vdc
Compliance with standards:
Power draw : 3.5 W max. 6 VA max.
IEC 61000-6-4 on emissions, IEC 61000-6-2 immunity Dielectric withstanding : 2 kV-50Hz-1min.
(industrial environment)
Order example: For a converter with universal input + analog output +
IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-6 (level 3)
2 relays, request the reference TPItL10/µCtL10 AR
Sensitiveness < ±1% of the measure range
CA CO2016/31 - A 12/16 - Any data in this documentation may be modified without prior notice.
MR Measure range Thermal drift <150ppm /°C
Outputs
Features related to the
Code
Types of
Features
safety
OUTPUTS
Current
active/ Current: Direct or reversed 0-4-20mA
A 1 analog Load impedance ≤ Lr 600Ω
passive Type of the instrument B
Voltage: Direct or reversed 0-10V
Voltage Load impedance ≥ Lr 5000Ω SIL (safety integrity level) 2
Typical response time: 500 ms (for a variation from 0 to 90 % of SFF (safe failure fraction) 93%
the input signal)
Add 50 ms for the response time on the analog output
Only the output 4-20mA and the relays can be used in a safety
system.
Galvanic partition:
2kV-50Hz-1min. between supply, input, analog output, relay
outputs
y o u r r e p r e s e n t a t i ve
Route de Brindas
Parc d’activité d’Arbora N°2
69510 SOUCIEU EN JARREST
- FRANCE -
e-mail : info@ardetem.com Tél. : 33 (0)4 72 31 31 30
http : //www.ardetem.com Fax. : 33 (0)4 72 31 31 31